Submittal Data Sheet Package CV System Heating and Air Conditioning ® Form: 036-22241-001 Rev A (602) Supersedes: Nothing

Upload: phungthu

Post on 06-Feb-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

Submittal Data

Sheet Package

CV System

Heating and Air Conditioning

®

Form: 036-22241-001 Rev A (602)Supersedes: Nothing

Page 2: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

�������������� �����

Form: 036-22267-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

����������The Meridian CV control system is designed to con-trol up to 30 single zone, constant volume HVACunits. For systems with more than 30 single zoneconstant volume units, the CV-EX control system isavailable which will allow 60 single zone units on thesystem, and 30 more with each CV-EX Loop Expan-sion Kit. Up to two CV-EX Loop Expansion Kits canbe added for a total system maximum of 120 singlezone constant volume units being controlled on thesystem. Each CV controller on the CV system oper-ates stand alone and shares common data, such asoutside air temperature, over a communicationsnetwork.

The System Manager is a central operators interfaceto all controllers on the network. All system vari-ables, setpoints, and values can be viewed andmodified from one convenient location. Menu drivenprogramming using English language descriptors,make the Meridian CV easy to set up and operate.

The System Manager is password protected to pre-vent unauthorized access to the control system.

The CommLink interface provides an intelligent, highspeed computer/modem interface to the CV system.A computer and/or Remote Link can be connectedfor on site or remote monitoring (not required for thesystem to operate). MeridianView, a Windows™based software program, provides a user friendly,full function program for system set up, status, callout alarm capability, and trend logging.

���� ����������

• All control devices are 24 VAC and can be pow-ered from common or individual transformers.

• CommLink - 24 VAC (Plug-in transformer in-cluded)

• Communications - RS-485/9600 Baud - DaisyChain Configuration - Twisted Pair/Shieldedwire

������������� ��

Page 3: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

�������������� �����

Form: 036-22268-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

������������� �����������Project: ___________________________________________________________________

�� ������

Part No Description Quantity

2ZCV004702124OE720

CV System PackageFor Systems with up to 30 Single Zone Units.Includes: System Manager, Single Loop CommLink II, Outside Air Temperature Sensor,Installation Manual, and Wiring Diagram.

2ZMC004702424OE724

CV-C System PackageFor Systems using up to 30 CV-C Controllers. Includes: CommLink II, Outside AirTemperature Sensor, Installation Manual, and Wiring Diagram.

�� ��������

2ZRC0047000224OE746 Fahrenheit2ZRC0047001324OE746 Celsius

CV Controller Package *One Required per Single Zone Unit for All CV or CV-EX Systems.Includes: CV Controller with Backplate, Supply Air Temperature Sensor.

2ZRC0047000324OE747 Fahrenheit

2ZRC0047003024OE747 Celsius

CV-C Controller Package *CV-C is a Configurable Controller that Allows for User Configurable Inputs and Outputs.Also Allows for the Addition of a Relay Expansion Board for Additional Heating and/orCooling Staging Capabilities.Includes: CV-C Controller with Backplate, Supply Air Temperature Sensor.

Note: Set-up, Programming and Monitoring of CV-C Requires the Use of a Computerand Meridian View Software. See Page 13 for Meridian View Software Information andPricing. The CV-C Controller Does Not Communicate with a System Manager.

2ZRE0047001024OE351

CV-C Relay Expansion BoardProvides 8 Additional Relays for Heating and/or Cooling Staging Capabilities. Connectswith Modular Cable to CV-C Controller. Used with CV-C Controller Only.Includes: Relay Expansion Board with Snaptrack, 1 Ft. Long Modular Cable.

� �����

2ZTS004704024OE210

2ZTO004704024OE211

2ZTA004704124OE212

2ZTB004704124OE213

Room Sensor – Plain

Room Sensor with Override

Room Sensor with Setpoint Adjust

Room Sensor with Override and Setpoint Adjust

Note: Set-up, Programming and Monitoring of All Add-On Devices and CV-C Requires the Use of a Computer andMeridianView Software.

Page 4: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

�������������� ������

Form: 036-22269-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

���������The Meridian 2ZRC0247000224 and the2ZRC0247000424 CV Controllers are usedfor controlling a constant volume HVACunit. The 2ZRC0247000224 is the Fahren-heit version and the 2ZRC0247000424 isthe Celsius version of the controller. TheCV Controller operates stand-alone andshares common data, such as outside airtemperature, over a network. A SystemManager is connected to the CV Controllerto provide a central operators interface toall CV Controllers on the network. A Me-ridian CV system provides an excellent al-ternative to installing multiple programma-ble thermostats to control constant volumeHVAC units. CV Controllers are designedwith room temperature, room setpoint ad-just, outside air temperature, discharge airtemperature and auxiliary alarm inputs.Relay outputs provided are; fan (continuousor cycling), four stages of heating/cooling(user configurable) and economizer control(0-10VDC output, full modulating). An in-ternal seven day schedule function is alsobuilt in to each CV Controller.

���� The CV Controller is provided with an inte-gral backplate for mounting inside of acontrol enclosure. It is recommended thatthe CV Controller is mounted in the HVACunit control enclosure, or in a control enclo-sure in the building equipment room. An optional factory control enclosure for the CV Controller is available.

���������������

��������������

����� ������

Technical Data 2ZRC0247000224 & 2ZRC0247000424 CV Controller

Power 24 Volt AC Weight 1.5 lb.Power Consumption 20 VA Maximum Network Connection RS-485Operating Temp 10°F(12ºC) to 149°F(65ºC) Protocol HSI Open Protocol Token PassingOperating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud

Inputs: Outputs:Room Temperature Type III-10kohm sensor Fan Relay - (2 Amp @ 24 VAC)Room Setpoint Adjust Slide potentiometer Heating/Cooling Stage 1 Relay - (2 Amp @ 24 VAC)Outside Air Temperature Type III-10kohm sensor Heating/Cooling Stage 2 Relay - (2 Amp @ 24 VAC)(1 required per system) Heating/Cooling Stage 3 Relay - (2 Amp @ 24 VAC)Discharge Temperature Type III-10kohm sensor Heating/Cooling Stage 4 Relay - (2 Amp @ 24 VAC)Generic Alarm Binary Contact Economizer Analog Output 0-10 VDCYork reserves the right to change specifications without notice

Three Year Warranty

6.2“

6.6“7.3“

6.7“ 1.1“

Page 5: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

�������������� ������

Form: 036-22270-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

���������The 2ZSM004702924 System ManagerSystem Interface provides a direct link toenable the system operator to view thestatus and to adjust the setpoints of anycontroller on the Meridian Plus, CV or CV-EX system communications loop. TheSystem Manager is housed in an attrac-tive beige colored plastic enclosure withwhite and green accents. The SystemManager is equipped with a four line by20 character backlighted display paneland a 20 key membrane keypad for dataselection and entry. All keypad operationsare simple and straight forward, utilizingnon-cryptic plain English language mes-sages. Menu driven programming allowsfor easy setup and operation without theneed for specialized training. The SystemManager also has three integral LED’s foruser notification of system communica-tion, alarm condition and override initia-tions. Protection from unauthorized usersis provided by the System Manager’s in-tegral multi-level passcode authorizationprogramming.

���� The System Manager is designed for wallmounting. It is recommended that theSystem Manager be mounted at ap-proximately eye level to allow for ease ofprogramming and reading of the display.The System Manager is typically mountedin the building manager or superinten-dent’s office or in an equipment room.The attractive enclosure is quite suitablefor mounting in any location or with mostdecor.

�������������

��� ��������

��� ����������

Clear Window

Area

6

5

4

DEC

7MIN

US

0

CLEAR9

8

1

3

2

MENU

Overr

ide

Com

munic

ation

ENTER

ESC

Ala

rm

System

Manager

-

Merid

ianPlus

05/17/0

003:3

8PMW

ED

OCCUPIED

NOALARM

S

Heating and Air Conditio

ning

®

1.90

9.00

6.25

MembraneKeypad

Four Line by 20 CharacterBacklighted Display

Technical Data ������������� System ManagerSystem Interface

Power 24 Volt AC Display 4 Line by 20 Character Backlighted LCDPower Consumption 25 VA Maximum Network Connection RS-485Operating Temp 10°F(12ºC) to 149°F(65ºC) Protocol HSI Open Protocol Token PassingOperating Humidity 90% RH Non-Condensing Color Beige w/ Green and White AccentsKeypad 20 Key Membrane Type Communications RS-485 - 9600 BaudYork reserves the right to change specifications without notice

Three Year Warranty

Page 6: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

�������������� ������

Form: 036-22271-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

���������The York Meridian 2ZCP004703124CommLink II Communications Interfaceallows user access to any controller in theMeridian system. It is configurable forsingle loop or multiple loop applicationsby a simple jumper switch setting on thecircuit board. The CommLink II comespackaged in an attractive beige coloredplastic enclosure. The CommLink II ispowered by a small wall mounted plug-intransformer that is included. Locally, anoptional on-site computer may be con-nected to the CommLink II for direct ac-cess to system control parameters. Re-mote access is obtained via an optionalRemote Link (modem) which is con-nected with the CommLink II Communi-cation Interface. With the Remote Linkinstalled, the CommLink II may be config-ured to call a number, if an alarm condi-tion occurs. With the Remote Link optioninstalled the system could be dialed andmonitored from a remote location by aPC. Computer and modem cables (6ftlong) are provided with the CommLink II.

���� If an on-site computer is to be used fordirect connection and monitoring of thesystem, the CommLink II should be lo-cated near the computer terminal tomonitor the system. If no on-site com-puter is to be used, locate the CommLinkII near the phone line jack for ease ofconnection to a the Remote Link (mo-dem). If for any reason you use cables ofgreater length than those provided withthe CommLink II (6 ft. long) be sure thecables that connect the CommLink II tothe modem and the CommLink II to theon-site computer do not exceed twenty-five feet in length.

������������

���� �����

����� ��� �����������

Com

mLin

kII

Com

mLin

kII

LO

OP

STA

TUS

CO

MP

SD

LN

K

1.50

7.005.25

COMPUTER

MODEM(DTE)

(DCE)

SERIAL #

POWER

485LOOPT

GR

24 G

N

Heating and Air Conditioning

®

Technical Data 2ZCP004703124CommLink II Communication Interface

Power 24 Volt AC Computer Connection RS-232Plug-in Transformer 110V to 24V (Included) Network Connection RS-485Power Consumption 14 VA Maximum Protocol HSI Open Protocol Token PassingOperating Temperature 10°F(-12°C) to 149°F (65°C) Physical Connections (2) 9 Pin/DB9 MaleOperating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 BaudYork reserves the right to change specifications without notice

Three Year Warranty

���� ����

��� ����

Page 7: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

�������������� �����

Form: 036-22272-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

Technical Data 2ZRC004700524 & 2ZRC004700624 CV-C ControllerPower 24 Volt AC Weight 1.5 lb.Power Consumption 12 VA Maximum Network Connection RS-485

Operating Temp 10°F(12ºC) to 149°F(65ºC) Protocol HSI Open Protocol Token PassingOperating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud

Inputs: Outputs:Quantity Available Types Quantity Available Types

Type III-10kohm Sensor Binary

0-10 VDC Sensor0-5 VDC Sensor

5 Onboard Relays (2 Amp @ 24 VAC)N.O. Contacts with Suppressors

4-20mA Sensor Analog

6

Binary Contact Closure1 Modular Phone Jack For Optional

Airflow or SP Sensor

2 0-10 Volt DC Out

York reserves the right to change specifications without notice Three Year Warranty

Relay OutputsOnly Relay Output #1 (Fan On/Off Only) has a specific functionthat cannot be changed. All other outputs are user configurablein one of the following modes:

• 0 - Not Used (Nothing connected to this output )• 1 - Heating Stage• 2 - Cooling Stage• 3 - Humidifier Enable• 4 - De-Humidifier Enable• 5 - Scheduled Relay from Internal Schedule• 6 - Scheduled Relay from External Schedule (Only 1

Available!)

There are a total of 12 relays that can be configured. Four arefound on the Controller itself (R2 - R5) and the remaining eight(R6 - R13) are found on the Optional Relay Expansion Board thatcan be connected to the PJ2 expansion input.

MountingThe CV-C Controller is provided with an integral backplate formounting inside of a control enclosure. An optional factory controlenclosure for the CV-C Controller is available.

Analog OutputsThere are two Analog Outputs available on this con-troller. They are both user configurable as follows:

• 0 - Not Used (Nothing connected to this out-put)

• 1 - Economizer (Requires either Supply Air orMixed Air Sensor)

• 2 - Relief Fan VFD Signal (Requires ReliefPressure Sensor)

• 3 - Chilled Water Valve (Requires SupplySensor)

• 4 - Hot Water Valve (Requires Supply Sensor)• 5 - Humidification/De-Humidification (Re-

quires Humidity Sensor)

DescriptionThe 2ZRC004700524 & 2ZRC004700624 CV-C Con-troller is a configurable controller that allows for userconfigurable controller inputs and outputs. The2ZRC004700524 CV-C Controller is the Fahrenheitversion and the 2ZRC004700624 is the Celsius ver-sion. CV-C Controllers also have provisions formounting a Relay Expansion Board to provide addi-tional heating or cooling staging capability.Analog InputsOnly Analog Input #1 (Space Temp Sensor Only) andAnalog Input #6 (Airflow Sensor Only) have a specificfunction that cannot be changed. All other inputs areuser configurable in one of the following modes:

• 0 - Not Used( Nothing connected to this input )

• 1 - Slide Offset (Requires Flush Mount WallSensor with this Option)

• 2 - Supply Air Temperature• 3 - Return Air Temperature• 4 - Mixed Air Temperature• 5 - Outdoor Air Temperature (Will broadcast

to ALL other controllers)• 6 - Humidity Sensor (4-20 ma scaling)• 7 - Humidity Sensor (0-5 VDC scaling)• 8 - CO² Sensor (4-20 ma scaling)• 9 - CO² Sensor (0-5 VDC scaling)• 10 - Relief Pressure Sensor (Requires 0-5

VDC ±0.3" WG Sensor)• 11 - Dirty Filter Contact (Normally Open)• 12 - Alarm Contact (Normally Open)• 13 - Alarm Contact (Normally Closed)• 14 - Fan Status Contact (Normally Open)

��������������������������

�� �����������

EXPANSION

SENSOR

PRESSURE

GND

7

AIN

AOUT2

AOUT1

AIN

GND

GND

5

AIN

AIN

AIN

4

3

2

T'STAT

24VAC

NETWORK

16

TOKEN

32

8

4

GND

AIN

1

12V

INPUTS

R

SHLD

T

COMM

1

2

YS101718

TUC5R PLUS

CO

M1

-3

R4

CO

M4

-5

R4

R3

R2

R1

6.2“

6.6“7.3“

6.7“ 1.1“

Page 8: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

�������������� ������

Form: 036-22273-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

���������The Meridian 2ZRE0047001024 - 8 RelayOutput Modular Expansion Board is usedin conjunction with the CV-C ControllerBoard to allow for additional stages ofheating and cooling. The Relay Expan-sion Board provides 8 relay outputs forpilot duty switching control.

The Relay Expansion Board connects tothe CV-C Controller by means of amodular cable provided with the RelayOutput Expansion Board. Quick ConnectTerminals for connection of 24VAC powerare provided on the Relay Output Expan-sion Board for field wiring to a 24VACpower source. Quick connect terminalsare also provided for connection of fieldwiring to the relay outputs.

The relay outputs are N.O. contacts withtwo common terminals. All outputs andthe relay common are electrically isolatedfrom all other circuitry on the board. Allrelay outputs are supplied with transientsuppression devices across each set ofcontacts to reduce EMI and arcing. Therelay output contacts are rated for pilotduty control of a maximum of 2 Amps @24 VAC or 24 VDC.

���� The Meridian Relay Output ExpansionBoard is supplied mounted on a plasticSnap Track channel. The Snap Trackchannel has two mounting holes whichare used to field mount the board with theprovided screws. The board should bemounted in close proximity to the CVCController board to allow for connection ofthe modular cable,

��������������

��� �������

��� ������� ��

Technical Data 2ZRE0047001024 – 8 Relay OutputExpansion Board

Operating Power 24VAC Power Consumption 20 VA MaximumOperating Temp 10°F to 149°F Operating Humidity 90% RH Non-CondensingCommunications Integral I2 C Chip Weight 0.25 lb.

Outputs:Relay Qty. 8 – Electrically Isolated Relay Contact Rating 2 Amp @ 24 VACYork reserves the right to change specifications without notice

3 Year Warranty

EXPANSION PORT

24VAC

IN OUT

COM

PO

WE

R

U4

U5

U3

U1

RELAY 1

RELAY 2

RELAY 3

ADDRESS

RELAY 4

RELAY 5

RELAY 6

RELAY 7

RELAY 8

N.O

.C

ON

TA

CT

SR

EL

AY

CO

MM

ON

S9

,10

7.0

0"

4.00"

Snap Track

Relay Board

Page 9: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

�������������� ������

Form: 036-22274-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

���������The patented design of the York Meridian RoomSensor provides accurate sensing of the roomtemperature. Its design allows for flush wallmounting yet rejects the influence of surface andinternal wall temperatures. The Room Sensor’sattractive styling and off white casing color make itsuitable for most building decors. If interior deco-ration requires, the Zone Sensor casing can alsobe painted or wall papered without affecting thesensor's performance. Room Sensors are avail-able in 4 different configurations:

• 2ZTS004704024 - Sensor Plain• 2ZTO004704024 - Sensor with Setpoint

Adjustment• 2ZTA004704124 - Sensor with Override• 2ZTB004704124 - Sensor with Setpoint

Adjustment and Override

The Room Sensor Plain and Room Sensor withOverride, require (2) wires to be connected fromthe controller to the sensor. The Room Sensorwith setpoint adjustment and Zone Sensor withSetpoint and Override options, require 3 wires beconnected to the sensor. Twisted cable is rec-ommended for wiring of all Room Sensors. Wiringshould not be run in conduit with other AC linevoltage wiring, or with any conductors carryinghighly inductive loads. Most applications do notrequire shielding.

���� The Room Sensors are designed to be mounted on a vertical, 2” x 4” electrical box recessed in the wall. If the wallcannot be penetrated, a plastic surface mount box such as those made by Wiremold, may be used to mount thesensor to the wall surface.

�����������������������������

����������������������������

��������

TechnicalData

2ZTS004704024, 2ZTO004704024, 2ZTA004704124,2ZTB004704124 Room Sensors

Sensor Element Type III Thermistor 10k ohm @ 77º F

Mounting Designed to be Flush Mounted to Wallusing Vertical 2” x 4” Handy Box (by others)

Accuracy ±0.4º F between 30º F to 150º F Line Loss 0.25º F max. error, using 22 AWG wire at 1000 ft.Range -30º F to 150º F Weight 4 oz.York reserves the right to change specifications without notice

Three Year Warranty

OE210 OE211 OE212 OE213

Room Sensor - Plain Room SensorWith Override

Room SensorWith Setpoint Adjust

Room SensorWith Setpoint Adjust

& Overide

O O

A A

O O

R R

L L

M M

E E

E E

C C

W W

R R

R R

OVR OVR

0.25“

TMP

GND

AUXOUT

2.7

5“

2.00“

Wall Cut-Out DimensionsWhen Sensor Is To BeMounted WithoutHandy Box (By Others)

2.75“

3.2

5“

4.5

0“

2.5

0"

0.88“

O

A

O

R

L

M

E

E

C

W

R

R

Page 10: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

Duct Temperature Sensor - 2ZDS0047002242ZDS004700124 &

Mounting Plate

Gasket

Adhesive Backed Drill GuideMounting Template

Mounting Plate

4.0"

3/4"

1/4" Hex Head Sheet Metal Screws

ThreadTogether

Duct Work

Drill 5/16" Hole In Ductwork For Probe

Leads Are Non-polarized.Butt Splice Leads To 24 GaugeWire Minimum. Connect LeadsTo "Analog In" And "Ground"At Controller.

Notes:

1.)All Wiring To Be In Accordance WithLocal And National Electrical CodesAnd Specifications.

Temperature Sensor Resistance/Voltage Chart

Temp Resistance* Voltage

F Ohms @ Input*-10.............93333........4.620-5...............80531........4.5500...............69822........4.4745...............60552........4.39010..............52500........4.29715..............45902........4.20020..............40147........4.09525..............35165........3.98230..............30805........3.86235..............27140........3.73740..............23874........3.605

Temp Resistance* Voltage

F Ohms @ Input*�

45..............21094........3.47050..............18655........3.33052..............17799........3.27554..............16956........3.21756..............16164........3.16058..............15385........3.10060..............14681........3.04262..............14014........2.98564..............13382........2.92766..............12758........2.86768..............12191........2.810

Temp Resistance* Voltage

F Ohms @ Input*�

69..............11906 ........2.78070..............11652 ........2.75271..............11379 ........2.72272..............11136 ........2.69573..............10878........2.66574..............10625........2.63575..............10398........2.60776..............10158........2.57078..............9711 ..........2.52080..............9302..........2.46582..............8893..........2.407

Temp Resistance* Voltage

F Ohms @ Input*84..............8514..........2.35286..............8153..........2.29788..............7805..........2.24290..............7472..........2.18795..............6716..........2.055100............6047..........1.927105............5453..........1.805110 ............4923..........1.687115 ............4449..........1.575120............4030..........1.469

125............3656..........1.369

*Chart Notes:1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).

2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts.Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltageis above 5.08 VDC, the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.

The Duct Sensor Is Used For Sensing SupplyOr Return Air Temperatures. Location Of TheSensors Is Very Important In Order To ObtainAccurate Temperature Readings. TheFollowing Recommendations Should BeFollowed:

When Used As A Supply Air Sensor TheSensor Should Be Mounted In The Supply AirDuct As Close To The HVAC Unit As PossibleAnd Upstream Of The Bypass Damper (IfUsed) For Best Results. For Best Accuracy,Apply Insulation On The Outside Of TheDuctwork Over The Sensor. This Will HelpThermal Gradients From Affecting The Sensor.

Supply Air

Return AirWhen Used As A Return Air Sensor TheSensor Should Be Mounted In The Return AirDuct As Close To The HVAC Unit As PossibleAnd Upstream Of The Bypass Damper (IfUsed) For Best Results. For Best Accuracy,Apply Insulation On The Outside Of TheDuctwork Over The Sensor. This Will HelpThermal Gradients From Affecting The Sensor.

See The Systems Installation And OperationManual For Other Design Considerations AndRecommendations Regarding DuctTemperature Sensor Location.

Caution!

FILENAME

JOB NAME

DESCRIPTION:

6" & 12" Duct Sensor

2ZDS004700124 & 2ZDS004700224

DATE DRAWN:

PAGE

1 of 1

B. CREWSDRAWN BY:

11-1/2" ( )2ZDS004700224

5-1/2" ( )2ZDS004700124

036-22275-001-A-0602.CDR

06/28/02

Form: 036-22275-001 Rev. A (0602) Supersedes: Nothing

Page 11: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

4.)All Wiring To Be In Accordance WithLocal And National Electrical CodesAnd Specifications.

3.)Gasket Must Be Installed Under CoverPlate To Provide Raintight Seal.Rainwater Can Damage Sensor!

Temperature Sensor Resistance/Voltage Chart

Temp Resistance* Voltage

F Ohms @ Input*-10.............93333........4.620-5...............80531........4.5500...............69822........4.4745...............60552........4.39010..............52500........4.29715..............45902........4.20020..............40147........4.09525..............35165........3.98230..............30805........3.86235..............27140........3.73740..............23874........3.605

Temp Resistance* Voltage

F Ohms @ Input*�

45..............21094........3.47050..............18655........3.33052..............17799........3.27554..............16956........3.21756..............16164........3.16058..............15385........3.10060..............14681........3.04262..............14014........2.98564..............13382........2.92766..............12758........2.86768..............12191........2.810

Temp Resistance* Voltage

F Ohms @ Input*�

69..............11906 ........2.78070..............11652 ........2.75271..............11379 ........2.72272..............11136 ........2.69573..............10878........2.66574..............10625........2.63575..............10398........2.60776..............10158........2.57078..............9711 ..........2.52080..............9302..........2.46582..............8893..........2.407

Temp Resistance* Voltage

F Ohms @ Input*84..............8514..........2.35286..............8153..........2.29788..............7805..........2.24290..............7472..........2.18795..............6716..........2.055100............6047..........1.927105............5453..........1.805110 ............4923..........1.687115 ............4449..........1.575120............4030..........1.469

2.)Unused Conduit Opening(s) MustHave Closure Plugs Installed And MustBe Coated with Sealing Compound ToProvide Raintight Seal. Water CanDamage Sensor!

1.)The Outside Air Sensor Must BeMounted In A Vertical Position AsShown (Sensor Tube PointingDown).

Sensor Must Be LocatedWhere It Will Not Be Affected ByDirect Sunlight Or Heat ProducingEquipment. If Possible Mount UnderRoof Eave Or Similar ProtectedLocation. If Sensor Is Not LocatedAs Specified, Erroneous Outside AirTemperature Readings Will Result.

Water Must Not BeAllowed To Stand In SensorTube. Rainwater Will DamageSensor.

*Chart Notes:1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).

2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DCvolts. Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. Ifthe voltage is above 5.08 VDC, then the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor orwiring is shorted.

Outside Air Sensor - OE250Y

Notes:

Closure PlugCAUTION!See Note 2

Gasketed CoverCAUTION!See Note3

CoverMountingScrew - Typ.

Mounting Tab& Screw - Typ.

0.21" Dia. x 0.73Lg. Slot - Typ.

4.5

0”

2.2

5”

3.00”

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

Outside Air Temperature Sensor1

JOB NAME

2ZOT004704424

Front View Side View Back View

Closure PlugCAUTION!See Note 2

Sensor TubeCAUTION!See Note 1

Mounting Tab& Screws - Typ.

Correct

Incorrect

Incorrect

See Note #1

Sensor MountingPostion

2.70”

1.1

3”

2.30”

3.0

0”

036-22276-001-A-0602.CDR

06/28/02

Form: 036-22276-000 Rev. A (0602) Supersedes: Nothing

Page 12: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

�������������� �����

Form: 036-22277-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

Project: ___________________________ Location _____________________________

Stages of Cooling: ____ Stages of Heat ___ Gas Electric Economizer Yes No

Modem Installed: Yes No Phone No. ________________

���������

UnitAddress

Unit Description or Location Sensor Type Notes

1 S SO SA SOA

2 S SO SA SOA

3 S SO SA SOA

4 S SO SA SOA

5 S SO SA SOA

6 S SO SA SOA

7 S SO SA SOA

8 S SO SA SOA

9 S SO SA SOA

10 S SO SA SOA

11 S SO SA SOA

12 S SO SA SOA

13 S SO SA SOA

14 S SO SA SOA

15 S SO SA SOA

16 S SO SA SOA

17 S SO SA SOA

18 S SO SA SOA

19 S SO SA SOA

20 S SO SA SOA

21 S SO SA SOA

22 S SO SA SOA

23 S SO SA SOA

24 S SO SA SOA

25 S SO SA SOA

26 S SO SA SOA

27 S SO SA SOA

28 S SO SA SOA

29 S SO SA SOA

30 S SO SA SOA

[S=Sensor] [SO=Sensor w/ Override] [SA=Sensor w/ Setpoint adjust] [SOA=Sensor w/ Override & Setpoint adjust]

Page 13: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

Form

: 036

-222

78-0

01 R

ev. A

(06

02)

Supe

rsed

es: N

othi

ngP

age

1 of

1

����������

���

�������

����� ���

����

��Jo

b N

ame:

������������������

Lo

cati

on

:___

____

____

____

____

____

____

__

Sch

edu

ling

Set

po

ints

Co

ntr

olle

r

Ad

dre

ss

Co

ntr

olle

r

Des

crip

tio

n

Are

a S

erve

dB

y C

V C

on

tro

ller

Sta

rt T

ime

Sto

p T

ime

Co

olin

gH

eati

ng

1C

V C

on

tro

ller

2C

V C

on

tro

ller

3C

V C

on

tro

ller

4C

V C

on

tro

ller

5C

V C

on

tro

ller

6C

V C

on

tro

ller

7C

V C

on

tro

ller

8C

V C

on

tro

ller

9C

V C

on

tro

ller

10C

V C

on

tro

ller

11C

V C

on

tro

ller

12C

V C

on

tro

ller

13C

V C

on

tro

ller

14C

V C

on

tro

ller

15C

V C

on

tro

ller

16C

V C

on

tro

ller

17C

V C

on

tro

ller

18C

V C

on

tro

ller

19C

V C

on

tro

ller

20C

V C

on

tro

ller

21C

V C

on

tro

ller

22C

V C

on

tro

ller

23C

V C

on

tro

ller

24C

V C

on

tro

ller

25C

V C

on

tro

ller

26C

V C

on

tro

ller

27C

V C

on

tro

ller

28C

V C

on

tro

ller

29C

V C

on

tro

ller

30C

V C

on

tro

ller

Page 14: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

Computer(Optional)

CommLink IISingle Loop

Interface

#30#1

RS-4859600 Baud

SupplyAir

Sensor

RS-485Local Loop RS-485

Local LoopEconomizer

(Actuator By Others)

Generic AlarmDirty Filter Alarm Shown

Room Sensorwith Optional

Override & Adj.

F

Typical CV Controller Wiring

* Only One Outside Air Sensor

110/24 VAC

110/9 VAC

Local Loop

Power Pak(14 VA@24VAC)

Power Pak

Typical Local Loop Wiring2 Conductor Twisted Pair With Shield(Belden #82760 Or Equivalent)

*Outside AirSensor

Loop #1

24VAC(20 VA)

24VAC(20 VA)

24VAC

24VAC(20 VA)

CVControllers

System Manager

Notes:

1.)24 VAC Must Be ConnectedSo That All Ground WiresRemain Common.

RELAY

OUTPUT

COM

1-3

OUT

OUT1

2

COM4-5

OUT

OUT

OUT

3

4

5

24VAC

GNDPWR

COMM

T

SHLD

LD4

REC.

12V

AIN1

2

3

4

5

GND

GND

AOUT

AIN

AIN

AIN

AIN

4-5

OUT

COMM

TEST

32K

8K

RAM EPROM

ADDRESS ADD

PRESSURE

SENSOR

485

COMM

R

YS101564

EW

DO

G

0-5

VD

C

0-1

VD

C

CPU

RELAY

OUTPUT

COM

1-3

OUT

OUT1

2

COM4-5

OUT

OUT

OUT

3

4

5

24VAC

GNDPWR

COMM

T

SHLD

LD4

REC.

12V

AIN1

2

3

4

5

GND

GND

AOUT

AIN

AIN

AIN

AIN

4-5

OUT

COMM

TEST

32K

8K

RAM EPROM

ADDRESS ADD

PRESSURE

SENSOR

485

COMM

R

YS101564

EW

DO

G

0-5

VD

C

0-1

VD

C

CPU

RELAY

OUTPUT

COM

1-3

OUT

OUT1

2

COM4-5

OUT

OUT

OUT

3

4

5

24VAC

GNDPWR

COMM

T

SHLD

LD4

REC.

12V

AIN1

2

3

4

5

GND

GND

AOUT

AIN

AIN

AIN

AIN

4-5

OUT

COMM

TEST

32K

8K

RAM EPROM

ADDRESS ADD

PRESSURE

SENSOR

485

COMM

R

YS101564

EW

DO

G

0-5

VD

C

0-1

VD

C

CPU

CO

MM

LINK

II

CO

MM

LINK

II

L

C

M

M

O

O

O

O

M

D

P

PE

3.)The Local Loop May Have Up To 30CV Controllers Connected To It.

5.)For Individual Component Wiring SeeSpecific Component Wiring Diagram.

6.)It Is Recommended That All CVControllers Address Switches AreSet Before Installation To TheirRespective Constant Volume Units. FILENAME

JOB NAME

DATE: 06/28/02 B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

Meridian CV

System Wiring Diagram

See Drawing Filename: MCVSYW3.CDR for CV Controller Wiring Details

SeeFor

Commlink WiringDetails

Drawing Filename:MCVSYW4.CDR

SeeFor System Manager Wiring Details

Drawing Filename: MCVSYW2.CDR

1

2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes and Specifications.

4.)All Communication Wiring To Be 18Ga. Minimum, 2 Conductor TwistedPair With Shield. Belden #82760 OrEquivalent.

Remote Link(Optional)

Remote

Link

C

O

N

T

R

O

L

S

C

O

N

T

R

O

L

S

SIG

DE

T

RD

Y

SN

D

RE

C

PW

R

24VAC(25 VA)

Clear Window

Area

6

5

4

DEC

7MIN

US

0

CLEAR9

8

1

3

2

MENU

Overr

ide

Com

munic

ation

ENTER

ESC

Ala

rm

System

Manager

-

Heating and Air Conditio

ning

®

Form: 035-18954-000 Rev. A (0602) Supersedes: Nothing

035-18954-000-A-0602.CDR

Page 15: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

Notes:

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

System Manager Wiring2

JOB NAME1.)24 VAC Must Be Connected So

That All Ground Wires RemainCommon.

2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes And Specifications.

3.) All Communication Wiring To Be2 Conductor Twisted Pair WithShield. Use Belden #82760 OrEquivalent.

035-18955-000-A-0602.CDR

Meridian CV

The Ideal Recommended Location For The System Manager Is As TheFirst Device On The Local Loop. The System Manager May Be Connected To TheLocal Loop At Any Point On The Local Loop.

System Manager

654

DEC

7

MINUS0 CLEAR

98

1 32 MENU

Override

Communication

ENTER

ESC

Alarm

To MiniLink, Or Next DeviceOn Local Loop

Line Voltage

See Note 1

See Note 324VAC

GND

Required VA For TransformerSystem Manager = 25VA Max.

MADE IN

THE USA

EP

RO

M

1000uF10v

YS101806 REV. 1

DSPY1

UNIVERSAL SMART DISP. UNIT

SYSTEM MANAGER

SERIAL # :

U13SERIAL #

1000uF10v

C9

470uF50v

D2

PC

B8

0C

55

2-5

-16

WP

44

28

60

=2

/5

DfD

97

22

V7

Y

PH

ILIP

S

CX

13

LD8

CX

9

SS0017

vx.xx 1234

V62C518256L-70P

U9

U8

LD7

RN

1

LD6

U7

CX7

74

HC

57

3

LD5

LD4

74HC573

CX

8

RN2

X2

CX

4

470uF50v

TB

2

GN

D

24

VA

C

R1

0

75176

RS-485

COMM

U12

CX

12

RA

M

SC1

T

TB

1

SH

LD

C7

C11

L1

C4

R

D6

85

83

U6

CX6C3

D3

24

C1

28

U5

R7

VAR1

D4

PJ1

R3

U1

74HC259

LD3

LD2

LD1

R2

R1

EW

DO

G

PH

ILIP

S

U3

U2

CX

1

82B715CX5

CX

3

U3

DSPY1

R5

D1

R6

MC

34

06

4A

C6

R11

99

36 C

8

R9

U10

U11

R8

R12

C5

74

HC

92

3

CX10

P1

R4

RV1

C2

C1

X1

06/28/02

Form: 035-18955-000 Rev. A (0602) Supersedes: Nothing

Page 16: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

Notes:

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

Wx or Yx (Htg or Clg Stage x)

Wx or Yx (Htg or Clg Stage x)

Wx or Yx (Htg or Clg Stage x)

Wx or Yx (Htg or Clg Stage x)

G (Fan-On/Off)

R (24VAC)

Constant VolumeUnit Connections

CV Controller

R

SH

T

R

SH

T

R

SH

T

R

SH

T

All Comm Loop Wiring IsStraight Thru

Required VA For TransformerEach CV Controller = 20VA Max.

24VAC

24VAC

GND

GND

Mount In HVACUnit Supply

Air Duct

Auxiliary AlarmInput

Switch SuppliedBy Others

DischargeAir Temp.Sensor

AOUT

GND

GND

AIN5

AIN1

AIN2

AIN3

AIN4

12V

GND

AUX

TMP

NORMAL

OVR

RELO

C

REMR

O

AW

COMM

REC.

LD4

T

R

SHLD

GND

24VAC

PWR

COMM

TEST

16

8421

RELAYOUTPUTS

COM4-5

OUT1

OUT2

OUT3

OUT4

OUT5

COM1-3

Caution!CV Controllers Must Have Address Switches SetBetween 1 And 30 ( Up To 30 Units Per Local Loop ).

Room Sensor

Diagnostic Blink Code LED

RAM

EPROM

Local LoopRS-485

9600 Baud

Connect ToNext Controller

And/OrMiniLink On

Address Switch Shown IsSet For Address 1

Address Switch Shown IsSet For Address 13

ControllerAddress Switch

This Switch Must BeIn The ON PositionAs Shown

These Switches Should BeIn The OFF PositionAs Shown

Note:The Power To The CV Controller Must Be RemovedAnd Reconnected After Changing The AddressSwitch Settings In Order For Any Changes To TakeEffect.

Caution:Disconnect All Communication Loop WiringFrom The CV Controller Before Removing PowerFrom The CV Controller. Reconnect Power AndThen Reconnect Communication Loop Wiring.

ADDRESS ADD

ADDRESS ADD

ADDRESSADD

ADDRESSADD

The Address For Each ControllerMust Be Unique To The Other Controllers

On The Local Loop

Connection ToAUX Terminal is ReqdOnly When SensorIs Specified WithSlide Adjust Option

JOB NAME1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.

2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes And Specifications.

3.)All Communication Wiring To Be2 Conductor Twisted Pair WithShield. Use Belden #82760 OrEquivalent. 3

EconomizerActuator

(Belimo Shown)Consult Factory ForOther ManufacturersWiring Connections

Note:Up To 4 Stages Of Heating Or Cooling Or AnyCombination Of Each Is Allowed And ProgrammableVia The System Manager or ZoneView Software. If TheUnit Has Heat, Heating Stages Must Be Connected ToThe First Outputs in Consecutive Order And CoolingStages To The Remaining Outputs In Consecutive Order.

Outside AirTemp. Sensor(See Note 4)

4.)Only One Outside Air Sensor IsRequired Per System. It May BeConnected To Any CV Controller Or OnThe System. If A Wetbulb ModuleController Is Used The OA Sensor MustBe Connected To The Wetbulb Module.

CV Controller Wiring

Meridian CV

Y 3

+ 2

COM 1

035-18956-000-A-0602.CDR

06/28/02

Form: 035-18956-000 Rev. A (0602) Supersedes: Nothing

Page 17: Heating and Air Conditioning Submittal Data Sheet · PDF file2ZRC0047000224 OE746 Fahrenheit 2ZRC0047001324 OE746 Celsius ... Room Setpoint Adjust Slide potentiometer Heating/Cooling

Commlink II Communications Interface

(Jumper Set For Multiple Loop)

Caution: Use The “Molded Cable” ToConnect To The Computer (DCE) Connector.This Cable Is Only To Be Used To ConnectFrom The CommLink (DTE) Connection ToThe Modem (When Used).

Do Not

Caution:Disconnect All Communication Loop WiringFrom The CommLink Before Removing PowerFrom The CommLink. Reconnect Power And ThenReconnect Communication Loop Wiring.

Use 25 Pin Or 9 Pin Connector AsRequired By Available Serial (COM) Port

JOB NAME

Caution: Use The “25 Pin Or 9 Pin Cable” ToConnect To The Modem (DTE) Connector.. ThisCable Is Only To Be Used To Connect From TheCommLink (DCE) Connection To The Computer

Serial Port (COM) Connection.

Do Not

(When Used) Note:Place Jumper BetweenPins 1 & 2 for MultipleLoop Applications &Between Pins 2 & 3 forSingle Loop ApplicationsSee Note 4.

COMM DRIVER CHIP( U1 )PIN 1

MULTI

SINGLE

12

3

CommLink Jumper Switch SettingsNotes:

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

CommLink II Wiring4

R

SH

T

R

SH

T

R

SH

T

R

SH

T

All Communication LoopWiring Is Straight Through

Connect To First Zone

Network LoopRS-485

19200 Baud

Required VA For TransformerCommLink = 14VA Max.

CommLink Is Supplied With 110/24VAC Power Supply.If Desired A Transformer (By Others)

May Be Wired To The CommLink Instead

Molded Modem Cable.Supplied With CommLink

(DTE)MODEM COMPUTER

(DCE)

GT R

POWER

4 Piece ComputerCable Kit.Supplied WithCommLink

Connect To Modem .Only

9P

inF

em

ale

9 PinFemale

25 PinFemale

9P

inF

em

ale

120/24 VacTransformer

Part # PX000015

25 PinMale

Connect Supplied RJ12 Modular Phone CableTo Supplied 9 Pin Or 25 Pin Connector As ReqdBy Your Computer Com Port Connection

1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.

2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes And Specifications.

3.)All Communication Wiring To Be2 Conductor Twisted Pair WithShield. Use Belden #82760 OrEquivalent. Meridian CV

4.)CommLink Is Shipped With TheJumper In The Multiple LoopConfiguration, So It Is NecessaryTo Move It To The Single LoopConfiguration For A CV System.

485 LOOP 24V

GND

035-18957-000-A-0602.CDR

06/28/02

Form: 035-18957-000 Rev. A (0602) Supersedes: Nothing