Submittal Data
Sheet Package
CV System
Heating and Air Conditioning
®
Form: 036-22241-001 Rev A (602)Supersedes: Nothing
�������������� �����
Form: 036-22267-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1
����������The Meridian CV control system is designed to con-trol up to 30 single zone, constant volume HVACunits. For systems with more than 30 single zoneconstant volume units, the CV-EX control system isavailable which will allow 60 single zone units on thesystem, and 30 more with each CV-EX Loop Expan-sion Kit. Up to two CV-EX Loop Expansion Kits canbe added for a total system maximum of 120 singlezone constant volume units being controlled on thesystem. Each CV controller on the CV system oper-ates stand alone and shares common data, such asoutside air temperature, over a communicationsnetwork.
The System Manager is a central operators interfaceto all controllers on the network. All system vari-ables, setpoints, and values can be viewed andmodified from one convenient location. Menu drivenprogramming using English language descriptors,make the Meridian CV easy to set up and operate.
The System Manager is password protected to pre-vent unauthorized access to the control system.
The CommLink interface provides an intelligent, highspeed computer/modem interface to the CV system.A computer and/or Remote Link can be connectedfor on site or remote monitoring (not required for thesystem to operate). MeridianView, a Windows™based software program, provides a user friendly,full function program for system set up, status, callout alarm capability, and trend logging.
���� ����������
• All control devices are 24 VAC and can be pow-ered from common or individual transformers.
• CommLink - 24 VAC (Plug-in transformer in-cluded)
• Communications - RS-485/9600 Baud - DaisyChain Configuration - Twisted Pair/Shieldedwire
������������� ��
�������������� �����
Form: 036-22268-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1
������������� �����������Project: ___________________________________________________________________
�� ������
Part No Description Quantity
2ZCV004702124OE720
CV System PackageFor Systems with up to 30 Single Zone Units.Includes: System Manager, Single Loop CommLink II, Outside Air Temperature Sensor,Installation Manual, and Wiring Diagram.
2ZMC004702424OE724
CV-C System PackageFor Systems using up to 30 CV-C Controllers. Includes: CommLink II, Outside AirTemperature Sensor, Installation Manual, and Wiring Diagram.
�� ��������
2ZRC0047000224OE746 Fahrenheit2ZRC0047001324OE746 Celsius
CV Controller Package *One Required per Single Zone Unit for All CV or CV-EX Systems.Includes: CV Controller with Backplate, Supply Air Temperature Sensor.
2ZRC0047000324OE747 Fahrenheit
2ZRC0047003024OE747 Celsius
CV-C Controller Package *CV-C is a Configurable Controller that Allows for User Configurable Inputs and Outputs.Also Allows for the Addition of a Relay Expansion Board for Additional Heating and/orCooling Staging Capabilities.Includes: CV-C Controller with Backplate, Supply Air Temperature Sensor.
Note: Set-up, Programming and Monitoring of CV-C Requires the Use of a Computerand Meridian View Software. See Page 13 for Meridian View Software Information andPricing. The CV-C Controller Does Not Communicate with a System Manager.
2ZRE0047001024OE351
CV-C Relay Expansion BoardProvides 8 Additional Relays for Heating and/or Cooling Staging Capabilities. Connectswith Modular Cable to CV-C Controller. Used with CV-C Controller Only.Includes: Relay Expansion Board with Snaptrack, 1 Ft. Long Modular Cable.
� �����
2ZTS004704024OE210
2ZTO004704024OE211
2ZTA004704124OE212
2ZTB004704124OE213
Room Sensor – Plain
Room Sensor with Override
Room Sensor with Setpoint Adjust
Room Sensor with Override and Setpoint Adjust
Note: Set-up, Programming and Monitoring of All Add-On Devices and CV-C Requires the Use of a Computer andMeridianView Software.
�������������� ������
Form: 036-22269-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1
���������The Meridian 2ZRC0247000224 and the2ZRC0247000424 CV Controllers are usedfor controlling a constant volume HVACunit. The 2ZRC0247000224 is the Fahren-heit version and the 2ZRC0247000424 isthe Celsius version of the controller. TheCV Controller operates stand-alone andshares common data, such as outside airtemperature, over a network. A SystemManager is connected to the CV Controllerto provide a central operators interface toall CV Controllers on the network. A Me-ridian CV system provides an excellent al-ternative to installing multiple programma-ble thermostats to control constant volumeHVAC units. CV Controllers are designedwith room temperature, room setpoint ad-just, outside air temperature, discharge airtemperature and auxiliary alarm inputs.Relay outputs provided are; fan (continuousor cycling), four stages of heating/cooling(user configurable) and economizer control(0-10VDC output, full modulating). An in-ternal seven day schedule function is alsobuilt in to each CV Controller.
���� The CV Controller is provided with an inte-gral backplate for mounting inside of acontrol enclosure. It is recommended thatthe CV Controller is mounted in the HVACunit control enclosure, or in a control enclo-sure in the building equipment room. An optional factory control enclosure for the CV Controller is available.
���������������
��������������
����� ������
Technical Data 2ZRC0247000224 & 2ZRC0247000424 CV Controller
Power 24 Volt AC Weight 1.5 lb.Power Consumption 20 VA Maximum Network Connection RS-485Operating Temp 10°F(12ºC) to 149°F(65ºC) Protocol HSI Open Protocol Token PassingOperating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud
Inputs: Outputs:Room Temperature Type III-10kohm sensor Fan Relay - (2 Amp @ 24 VAC)Room Setpoint Adjust Slide potentiometer Heating/Cooling Stage 1 Relay - (2 Amp @ 24 VAC)Outside Air Temperature Type III-10kohm sensor Heating/Cooling Stage 2 Relay - (2 Amp @ 24 VAC)(1 required per system) Heating/Cooling Stage 3 Relay - (2 Amp @ 24 VAC)Discharge Temperature Type III-10kohm sensor Heating/Cooling Stage 4 Relay - (2 Amp @ 24 VAC)Generic Alarm Binary Contact Economizer Analog Output 0-10 VDCYork reserves the right to change specifications without notice
Three Year Warranty
6.2“
6.6“7.3“
6.7“ 1.1“
�������������� ������
Form: 036-22270-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1
���������The 2ZSM004702924 System ManagerSystem Interface provides a direct link toenable the system operator to view thestatus and to adjust the setpoints of anycontroller on the Meridian Plus, CV or CV-EX system communications loop. TheSystem Manager is housed in an attrac-tive beige colored plastic enclosure withwhite and green accents. The SystemManager is equipped with a four line by20 character backlighted display paneland a 20 key membrane keypad for dataselection and entry. All keypad operationsare simple and straight forward, utilizingnon-cryptic plain English language mes-sages. Menu driven programming allowsfor easy setup and operation without theneed for specialized training. The SystemManager also has three integral LED’s foruser notification of system communica-tion, alarm condition and override initia-tions. Protection from unauthorized usersis provided by the System Manager’s in-tegral multi-level passcode authorizationprogramming.
���� The System Manager is designed for wallmounting. It is recommended that theSystem Manager be mounted at ap-proximately eye level to allow for ease ofprogramming and reading of the display.The System Manager is typically mountedin the building manager or superinten-dent’s office or in an equipment room.The attractive enclosure is quite suitablefor mounting in any location or with mostdecor.
�������������
��� ��������
��� ����������
Clear Window
Area
6
5
4
DEC
7MIN
US
0
CLEAR9
8
1
3
2
MENU
Overr
ide
Com
munic
ation
ENTER
ESC
Ala
rm
System
Manager
-
Merid
ianPlus
05/17/0
003:3
8PMW
ED
OCCUPIED
NOALARM
S
Heating and Air Conditio
ning
®
1.90
9.00
6.25
MembraneKeypad
Four Line by 20 CharacterBacklighted Display
Technical Data ������������� System ManagerSystem Interface
Power 24 Volt AC Display 4 Line by 20 Character Backlighted LCDPower Consumption 25 VA Maximum Network Connection RS-485Operating Temp 10°F(12ºC) to 149°F(65ºC) Protocol HSI Open Protocol Token PassingOperating Humidity 90% RH Non-Condensing Color Beige w/ Green and White AccentsKeypad 20 Key Membrane Type Communications RS-485 - 9600 BaudYork reserves the right to change specifications without notice
Three Year Warranty
�������������� ������
Form: 036-22271-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1
���������The York Meridian 2ZCP004703124CommLink II Communications Interfaceallows user access to any controller in theMeridian system. It is configurable forsingle loop or multiple loop applicationsby a simple jumper switch setting on thecircuit board. The CommLink II comespackaged in an attractive beige coloredplastic enclosure. The CommLink II ispowered by a small wall mounted plug-intransformer that is included. Locally, anoptional on-site computer may be con-nected to the CommLink II for direct ac-cess to system control parameters. Re-mote access is obtained via an optionalRemote Link (modem) which is con-nected with the CommLink II Communi-cation Interface. With the Remote Linkinstalled, the CommLink II may be config-ured to call a number, if an alarm condi-tion occurs. With the Remote Link optioninstalled the system could be dialed andmonitored from a remote location by aPC. Computer and modem cables (6ftlong) are provided with the CommLink II.
���� If an on-site computer is to be used fordirect connection and monitoring of thesystem, the CommLink II should be lo-cated near the computer terminal tomonitor the system. If no on-site com-puter is to be used, locate the CommLinkII near the phone line jack for ease ofconnection to a the Remote Link (mo-dem). If for any reason you use cables ofgreater length than those provided withthe CommLink II (6 ft. long) be sure thecables that connect the CommLink II tothe modem and the CommLink II to theon-site computer do not exceed twenty-five feet in length.
������������
���� �����
����� ��� �����������
Com
mLin
kII
Com
mLin
kII
LO
OP
STA
TUS
CO
MP
SD
LN
K
1.50
7.005.25
COMPUTER
MODEM(DTE)
(DCE)
SERIAL #
POWER
485LOOPT
GR
24 G
N
Heating and Air Conditioning
®
Technical Data 2ZCP004703124CommLink II Communication Interface
Power 24 Volt AC Computer Connection RS-232Plug-in Transformer 110V to 24V (Included) Network Connection RS-485Power Consumption 14 VA Maximum Protocol HSI Open Protocol Token PassingOperating Temperature 10°F(-12°C) to 149°F (65°C) Physical Connections (2) 9 Pin/DB9 MaleOperating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 BaudYork reserves the right to change specifications without notice
Three Year Warranty
���� ����
��� ����
�������������� �����
Form: 036-22272-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1
Technical Data 2ZRC004700524 & 2ZRC004700624 CV-C ControllerPower 24 Volt AC Weight 1.5 lb.Power Consumption 12 VA Maximum Network Connection RS-485
Operating Temp 10°F(12ºC) to 149°F(65ºC) Protocol HSI Open Protocol Token PassingOperating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud
Inputs: Outputs:Quantity Available Types Quantity Available Types
Type III-10kohm Sensor Binary
0-10 VDC Sensor0-5 VDC Sensor
5 Onboard Relays (2 Amp @ 24 VAC)N.O. Contacts with Suppressors
4-20mA Sensor Analog
6
Binary Contact Closure1 Modular Phone Jack For Optional
Airflow or SP Sensor
2 0-10 Volt DC Out
York reserves the right to change specifications without notice Three Year Warranty
Relay OutputsOnly Relay Output #1 (Fan On/Off Only) has a specific functionthat cannot be changed. All other outputs are user configurablein one of the following modes:
• 0 - Not Used (Nothing connected to this output )• 1 - Heating Stage• 2 - Cooling Stage• 3 - Humidifier Enable• 4 - De-Humidifier Enable• 5 - Scheduled Relay from Internal Schedule• 6 - Scheduled Relay from External Schedule (Only 1
Available!)
There are a total of 12 relays that can be configured. Four arefound on the Controller itself (R2 - R5) and the remaining eight(R6 - R13) are found on the Optional Relay Expansion Board thatcan be connected to the PJ2 expansion input.
MountingThe CV-C Controller is provided with an integral backplate formounting inside of a control enclosure. An optional factory controlenclosure for the CV-C Controller is available.
Analog OutputsThere are two Analog Outputs available on this con-troller. They are both user configurable as follows:
• 0 - Not Used (Nothing connected to this out-put)
• 1 - Economizer (Requires either Supply Air orMixed Air Sensor)
• 2 - Relief Fan VFD Signal (Requires ReliefPressure Sensor)
• 3 - Chilled Water Valve (Requires SupplySensor)
• 4 - Hot Water Valve (Requires Supply Sensor)• 5 - Humidification/De-Humidification (Re-
quires Humidity Sensor)
DescriptionThe 2ZRC004700524 & 2ZRC004700624 CV-C Con-troller is a configurable controller that allows for userconfigurable controller inputs and outputs. The2ZRC004700524 CV-C Controller is the Fahrenheitversion and the 2ZRC004700624 is the Celsius ver-sion. CV-C Controllers also have provisions formounting a Relay Expansion Board to provide addi-tional heating or cooling staging capability.Analog InputsOnly Analog Input #1 (Space Temp Sensor Only) andAnalog Input #6 (Airflow Sensor Only) have a specificfunction that cannot be changed. All other inputs areuser configurable in one of the following modes:
• 0 - Not Used( Nothing connected to this input )
• 1 - Slide Offset (Requires Flush Mount WallSensor with this Option)
• 2 - Supply Air Temperature• 3 - Return Air Temperature• 4 - Mixed Air Temperature• 5 - Outdoor Air Temperature (Will broadcast
to ALL other controllers)• 6 - Humidity Sensor (4-20 ma scaling)• 7 - Humidity Sensor (0-5 VDC scaling)• 8 - CO² Sensor (4-20 ma scaling)• 9 - CO² Sensor (0-5 VDC scaling)• 10 - Relief Pressure Sensor (Requires 0-5
VDC ±0.3" WG Sensor)• 11 - Dirty Filter Contact (Normally Open)• 12 - Alarm Contact (Normally Open)• 13 - Alarm Contact (Normally Closed)• 14 - Fan Status Contact (Normally Open)
��������������������������
�� �����������
EXPANSION
SENSOR
PRESSURE
GND
7
AIN
AOUT2
AOUT1
AIN
GND
GND
5
AIN
AIN
AIN
4
3
2
T'STAT
24VAC
NETWORK
16
TOKEN
32
8
4
GND
AIN
1
12V
INPUTS
R
SHLD
T
COMM
1
2
YS101718
TUC5R PLUS
CO
M1
-3
R4
CO
M4
-5
R4
R3
R2
R1
6.2“
6.6“7.3“
6.7“ 1.1“
�������������� ������
Form: 036-22273-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1
���������The Meridian 2ZRE0047001024 - 8 RelayOutput Modular Expansion Board is usedin conjunction with the CV-C ControllerBoard to allow for additional stages ofheating and cooling. The Relay Expan-sion Board provides 8 relay outputs forpilot duty switching control.
The Relay Expansion Board connects tothe CV-C Controller by means of amodular cable provided with the RelayOutput Expansion Board. Quick ConnectTerminals for connection of 24VAC powerare provided on the Relay Output Expan-sion Board for field wiring to a 24VACpower source. Quick connect terminalsare also provided for connection of fieldwiring to the relay outputs.
The relay outputs are N.O. contacts withtwo common terminals. All outputs andthe relay common are electrically isolatedfrom all other circuitry on the board. Allrelay outputs are supplied with transientsuppression devices across each set ofcontacts to reduce EMI and arcing. Therelay output contacts are rated for pilotduty control of a maximum of 2 Amps @24 VAC or 24 VDC.
���� The Meridian Relay Output ExpansionBoard is supplied mounted on a plasticSnap Track channel. The Snap Trackchannel has two mounting holes whichare used to field mount the board with theprovided screws. The board should bemounted in close proximity to the CVCController board to allow for connection ofthe modular cable,
��������������
��� �������
��� ������� ��
Technical Data 2ZRE0047001024 – 8 Relay OutputExpansion Board
Operating Power 24VAC Power Consumption 20 VA MaximumOperating Temp 10°F to 149°F Operating Humidity 90% RH Non-CondensingCommunications Integral I2 C Chip Weight 0.25 lb.
Outputs:Relay Qty. 8 – Electrically Isolated Relay Contact Rating 2 Amp @ 24 VACYork reserves the right to change specifications without notice
3 Year Warranty
EXPANSION PORT
24VAC
IN OUT
COM
PO
WE
R
U4
U5
U3
U1
RELAY 1
RELAY 2
RELAY 3
ADDRESS
RELAY 4
RELAY 5
RELAY 6
RELAY 7
RELAY 8
N.O
.C
ON
TA
CT
SR
EL
AY
CO
MM
ON
S9
,10
7.0
0"
4.00"
Snap Track
Relay Board
�������������� ������
Form: 036-22274-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1
���������The patented design of the York Meridian RoomSensor provides accurate sensing of the roomtemperature. Its design allows for flush wallmounting yet rejects the influence of surface andinternal wall temperatures. The Room Sensor’sattractive styling and off white casing color make itsuitable for most building decors. If interior deco-ration requires, the Zone Sensor casing can alsobe painted or wall papered without affecting thesensor's performance. Room Sensors are avail-able in 4 different configurations:
• 2ZTS004704024 - Sensor Plain• 2ZTO004704024 - Sensor with Setpoint
Adjustment• 2ZTA004704124 - Sensor with Override• 2ZTB004704124 - Sensor with Setpoint
Adjustment and Override
The Room Sensor Plain and Room Sensor withOverride, require (2) wires to be connected fromthe controller to the sensor. The Room Sensorwith setpoint adjustment and Zone Sensor withSetpoint and Override options, require 3 wires beconnected to the sensor. Twisted cable is rec-ommended for wiring of all Room Sensors. Wiringshould not be run in conduit with other AC linevoltage wiring, or with any conductors carryinghighly inductive loads. Most applications do notrequire shielding.
���� The Room Sensors are designed to be mounted on a vertical, 2” x 4” electrical box recessed in the wall. If the wallcannot be penetrated, a plastic surface mount box such as those made by Wiremold, may be used to mount thesensor to the wall surface.
�����������������������������
����������������������������
��������
TechnicalData
2ZTS004704024, 2ZTO004704024, 2ZTA004704124,2ZTB004704124 Room Sensors
Sensor Element Type III Thermistor 10k ohm @ 77º F
Mounting Designed to be Flush Mounted to Wallusing Vertical 2” x 4” Handy Box (by others)
Accuracy ±0.4º F between 30º F to 150º F Line Loss 0.25º F max. error, using 22 AWG wire at 1000 ft.Range -30º F to 150º F Weight 4 oz.York reserves the right to change specifications without notice
Three Year Warranty
OE210 OE211 OE212 OE213
Room Sensor - Plain Room SensorWith Override
Room SensorWith Setpoint Adjust
Room SensorWith Setpoint Adjust
& Overide
O O
A A
O O
R R
L L
M M
E E
E E
C C
W W
R R
R R
OVR OVR
0.25“
TMP
GND
AUXOUT
2.7
5“
2.00“
Wall Cut-Out DimensionsWhen Sensor Is To BeMounted WithoutHandy Box (By Others)
2.75“
3.2
5“
4.5
0“
2.5
0"
0.88“
O
A
O
R
L
M
E
E
C
W
R
R
Duct Temperature Sensor - 2ZDS0047002242ZDS004700124 &
Mounting Plate
Gasket
Adhesive Backed Drill GuideMounting Template
Mounting Plate
4.0"
3/4"
1/4" Hex Head Sheet Metal Screws
ThreadTogether
Duct Work
Drill 5/16" Hole In Ductwork For Probe
Leads Are Non-polarized.Butt Splice Leads To 24 GaugeWire Minimum. Connect LeadsTo "Analog In" And "Ground"At Controller.
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical CodesAnd Specifications.
Temperature Sensor Resistance/Voltage Chart
Temp Resistance* Voltage
F Ohms @ Input*-10.............93333........4.620-5...............80531........4.5500...............69822........4.4745...............60552........4.39010..............52500........4.29715..............45902........4.20020..............40147........4.09525..............35165........3.98230..............30805........3.86235..............27140........3.73740..............23874........3.605
�
Temp Resistance* Voltage
F Ohms @ Input*�
45..............21094........3.47050..............18655........3.33052..............17799........3.27554..............16956........3.21756..............16164........3.16058..............15385........3.10060..............14681........3.04262..............14014........2.98564..............13382........2.92766..............12758........2.86768..............12191........2.810
Temp Resistance* Voltage
F Ohms @ Input*�
69..............11906 ........2.78070..............11652 ........2.75271..............11379 ........2.72272..............11136 ........2.69573..............10878........2.66574..............10625........2.63575..............10398........2.60776..............10158........2.57078..............9711 ..........2.52080..............9302..........2.46582..............8893..........2.407
Temp Resistance* Voltage
F Ohms @ Input*84..............8514..........2.35286..............8153..........2.29788..............7805..........2.24290..............7472..........2.18795..............6716..........2.055100............6047..........1.927105............5453..........1.805110 ............4923..........1.687115 ............4449..........1.575120............4030..........1.469
�
125............3656..........1.369
*Chart Notes:1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts.Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltageis above 5.08 VDC, the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
The Duct Sensor Is Used For Sensing SupplyOr Return Air Temperatures. Location Of TheSensors Is Very Important In Order To ObtainAccurate Temperature Readings. TheFollowing Recommendations Should BeFollowed:
When Used As A Supply Air Sensor TheSensor Should Be Mounted In The Supply AirDuct As Close To The HVAC Unit As PossibleAnd Upstream Of The Bypass Damper (IfUsed) For Best Results. For Best Accuracy,Apply Insulation On The Outside Of TheDuctwork Over The Sensor. This Will HelpThermal Gradients From Affecting The Sensor.
Supply Air
Return AirWhen Used As A Return Air Sensor TheSensor Should Be Mounted In The Return AirDuct As Close To The HVAC Unit As PossibleAnd Upstream Of The Bypass Damper (IfUsed) For Best Results. For Best Accuracy,Apply Insulation On The Outside Of TheDuctwork Over The Sensor. This Will HelpThermal Gradients From Affecting The Sensor.
See The Systems Installation And OperationManual For Other Design Considerations AndRecommendations Regarding DuctTemperature Sensor Location.
Caution!
FILENAME
JOB NAME
DESCRIPTION:
6" & 12" Duct Sensor
2ZDS004700124 & 2ZDS004700224
DATE DRAWN:
PAGE
1 of 1
B. CREWSDRAWN BY:
11-1/2" ( )2ZDS004700224
5-1/2" ( )2ZDS004700124
036-22275-001-A-0602.CDR
06/28/02
Form: 036-22275-001 Rev. A (0602) Supersedes: Nothing
4.)All Wiring To Be In Accordance WithLocal And National Electrical CodesAnd Specifications.
3.)Gasket Must Be Installed Under CoverPlate To Provide Raintight Seal.Rainwater Can Damage Sensor!
Temperature Sensor Resistance/Voltage Chart
Temp Resistance* Voltage
F Ohms @ Input*-10.............93333........4.620-5...............80531........4.5500...............69822........4.4745...............60552........4.39010..............52500........4.29715..............45902........4.20020..............40147........4.09525..............35165........3.98230..............30805........3.86235..............27140........3.73740..............23874........3.605
�
Temp Resistance* Voltage
F Ohms @ Input*�
45..............21094........3.47050..............18655........3.33052..............17799........3.27554..............16956........3.21756..............16164........3.16058..............15385........3.10060..............14681........3.04262..............14014........2.98564..............13382........2.92766..............12758........2.86768..............12191........2.810
Temp Resistance* Voltage
F Ohms @ Input*�
69..............11906 ........2.78070..............11652 ........2.75271..............11379 ........2.72272..............11136 ........2.69573..............10878........2.66574..............10625........2.63575..............10398........2.60776..............10158........2.57078..............9711 ..........2.52080..............9302..........2.46582..............8893..........2.407
Temp Resistance* Voltage
F Ohms @ Input*84..............8514..........2.35286..............8153..........2.29788..............7805..........2.24290..............7472..........2.18795..............6716..........2.055100............6047..........1.927105............5453..........1.805110 ............4923..........1.687115 ............4449..........1.575120............4030..........1.469
�
2.)Unused Conduit Opening(s) MustHave Closure Plugs Installed And MustBe Coated with Sealing Compound ToProvide Raintight Seal. Water CanDamage Sensor!
1.)The Outside Air Sensor Must BeMounted In A Vertical Position AsShown (Sensor Tube PointingDown).
Sensor Must Be LocatedWhere It Will Not Be Affected ByDirect Sunlight Or Heat ProducingEquipment. If Possible Mount UnderRoof Eave Or Similar ProtectedLocation. If Sensor Is Not LocatedAs Specified, Erroneous Outside AirTemperature Readings Will Result.
Water Must Not BeAllowed To Stand In SensorTube. Rainwater Will DamageSensor.
*Chart Notes:1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DCvolts. Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. Ifthe voltage is above 5.08 VDC, then the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor orwiring is shorted.
Outside Air Sensor - OE250Y
Notes:
Closure PlugCAUTION!See Note 2
Gasketed CoverCAUTION!See Note3
CoverMountingScrew - Typ.
Mounting Tab& Screw - Typ.
0.21" Dia. x 0.73Lg. Slot - Typ.
4.5
0”
2.2
5”
3.00”
FILENAME
DATE: B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
Outside Air Temperature Sensor1
JOB NAME
2ZOT004704424
Front View Side View Back View
Closure PlugCAUTION!See Note 2
Sensor TubeCAUTION!See Note 1
Mounting Tab& Screws - Typ.
Correct
Incorrect
Incorrect
See Note #1
Sensor MountingPostion
2.70”
1.1
3”
2.30”
3.0
0”
036-22276-001-A-0602.CDR
06/28/02
Form: 036-22276-000 Rev. A (0602) Supersedes: Nothing
�������������� �����
Form: 036-22277-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1
Project: ___________________________ Location _____________________________
Stages of Cooling: ____ Stages of Heat ___ Gas Electric Economizer Yes No
Modem Installed: Yes No Phone No. ________________
���������
UnitAddress
Unit Description or Location Sensor Type Notes
1 S SO SA SOA
2 S SO SA SOA
3 S SO SA SOA
4 S SO SA SOA
5 S SO SA SOA
6 S SO SA SOA
7 S SO SA SOA
8 S SO SA SOA
9 S SO SA SOA
10 S SO SA SOA
11 S SO SA SOA
12 S SO SA SOA
13 S SO SA SOA
14 S SO SA SOA
15 S SO SA SOA
16 S SO SA SOA
17 S SO SA SOA
18 S SO SA SOA
19 S SO SA SOA
20 S SO SA SOA
21 S SO SA SOA
22 S SO SA SOA
23 S SO SA SOA
24 S SO SA SOA
25 S SO SA SOA
26 S SO SA SOA
27 S SO SA SOA
28 S SO SA SOA
29 S SO SA SOA
30 S SO SA SOA
[S=Sensor] [SO=Sensor w/ Override] [SA=Sensor w/ Setpoint adjust] [SOA=Sensor w/ Override & Setpoint adjust]
Form
: 036
-222
78-0
01 R
ev. A
(06
02)
Supe
rsed
es: N
othi
ngP
age
1 of
1
����������
���
�������
����� ���
����
��Jo
b N
ame:
������������������
Lo
cati
on
:___
____
____
____
____
____
____
__
Sch
edu
ling
Set
po
ints
Co
ntr
olle
r
Ad
dre
ss
Co
ntr
olle
r
Des
crip
tio
n
Are
a S
erve
dB
y C
V C
on
tro
ller
Sta
rt T
ime
Sto
p T
ime
Co
olin
gH
eati
ng
1C
V C
on
tro
ller
2C
V C
on
tro
ller
3C
V C
on
tro
ller
4C
V C
on
tro
ller
5C
V C
on
tro
ller
6C
V C
on
tro
ller
7C
V C
on
tro
ller
8C
V C
on
tro
ller
9C
V C
on
tro
ller
10C
V C
on
tro
ller
11C
V C
on
tro
ller
12C
V C
on
tro
ller
13C
V C
on
tro
ller
14C
V C
on
tro
ller
15C
V C
on
tro
ller
16C
V C
on
tro
ller
17C
V C
on
tro
ller
18C
V C
on
tro
ller
19C
V C
on
tro
ller
20C
V C
on
tro
ller
21C
V C
on
tro
ller
22C
V C
on
tro
ller
23C
V C
on
tro
ller
24C
V C
on
tro
ller
25C
V C
on
tro
ller
26C
V C
on
tro
ller
27C
V C
on
tro
ller
28C
V C
on
tro
ller
29C
V C
on
tro
ller
30C
V C
on
tro
ller
Computer(Optional)
CommLink IISingle Loop
Interface
#30#1
RS-4859600 Baud
SupplyAir
Sensor
RS-485Local Loop RS-485
Local LoopEconomizer
(Actuator By Others)
Generic AlarmDirty Filter Alarm Shown
Room Sensorwith Optional
Override & Adj.
F
Typical CV Controller Wiring
* Only One Outside Air Sensor
110/24 VAC
110/9 VAC
Local Loop
Power Pak(14 VA@24VAC)
Power Pak
Typical Local Loop Wiring2 Conductor Twisted Pair With Shield(Belden #82760 Or Equivalent)
*Outside AirSensor
Loop #1
24VAC(20 VA)
24VAC(20 VA)
24VAC
24VAC(20 VA)
CVControllers
System Manager
Notes:
1.)24 VAC Must Be ConnectedSo That All Ground WiresRemain Common.
RELAY
OUTPUT
COM
1-3
OUT
OUT1
2
COM4-5
OUT
OUT
OUT
3
4
5
24VAC
GNDPWR
COMM
T
SHLD
LD4
REC.
12V
AIN1
2
3
4
5
GND
GND
AOUT
AIN
AIN
AIN
AIN
4-5
OUT
COMM
TEST
32K
8K
RAM EPROM
ADDRESS ADD
PRESSURE
SENSOR
485
COMM
R
YS101564
EW
DO
G
0-5
VD
C
0-1
VD
C
CPU
RELAY
OUTPUT
COM
1-3
OUT
OUT1
2
COM4-5
OUT
OUT
OUT
3
4
5
24VAC
GNDPWR
COMM
T
SHLD
LD4
REC.
12V
AIN1
2
3
4
5
GND
GND
AOUT
AIN
AIN
AIN
AIN
4-5
OUT
COMM
TEST
32K
8K
RAM EPROM
ADDRESS ADD
PRESSURE
SENSOR
485
COMM
R
YS101564
EW
DO
G
0-5
VD
C
0-1
VD
C
CPU
RELAY
OUTPUT
COM
1-3
OUT
OUT1
2
COM4-5
OUT
OUT
OUT
3
4
5
24VAC
GNDPWR
COMM
T
SHLD
LD4
REC.
12V
AIN1
2
3
4
5
GND
GND
AOUT
AIN
AIN
AIN
AIN
4-5
OUT
COMM
TEST
32K
8K
RAM EPROM
ADDRESS ADD
PRESSURE
SENSOR
485
COMM
R
YS101564
EW
DO
G
0-5
VD
C
0-1
VD
C
CPU
CO
MM
LINK
II
CO
MM
LINK
II
L
C
M
M
O
O
O
O
M
D
P
PE
3.)The Local Loop May Have Up To 30CV Controllers Connected To It.
5.)For Individual Component Wiring SeeSpecific Component Wiring Diagram.
6.)It Is Recommended That All CVControllers Address Switches AreSet Before Installation To TheirRespective Constant Volume Units. FILENAME
JOB NAME
DATE: 06/28/02 B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
Meridian CV
System Wiring Diagram
See Drawing Filename: MCVSYW3.CDR for CV Controller Wiring Details
SeeFor
Commlink WiringDetails
Drawing Filename:MCVSYW4.CDR
SeeFor System Manager Wiring Details
Drawing Filename: MCVSYW2.CDR
1
2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes and Specifications.
4.)All Communication Wiring To Be 18Ga. Minimum, 2 Conductor TwistedPair With Shield. Belden #82760 OrEquivalent.
Remote Link(Optional)
Remote
Link
C
O
N
T
R
O
L
S
C
O
N
T
R
O
L
S
SIG
DE
T
RD
Y
SN
D
RE
C
PW
R
24VAC(25 VA)
Clear Window
Area
6
5
4
DEC
7MIN
US
0
CLEAR9
8
1
3
2
MENU
Overr
ide
Com
munic
ation
ENTER
ESC
Ala
rm
System
Manager
-
Heating and Air Conditio
ning
®
Form: 035-18954-000 Rev. A (0602) Supersedes: Nothing
035-18954-000-A-0602.CDR
Notes:
FILENAME
DATE: B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
System Manager Wiring2
JOB NAME1.)24 VAC Must Be Connected So
That All Ground Wires RemainCommon.
2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes And Specifications.
3.) All Communication Wiring To Be2 Conductor Twisted Pair WithShield. Use Belden #82760 OrEquivalent.
035-18955-000-A-0602.CDR
Meridian CV
The Ideal Recommended Location For The System Manager Is As TheFirst Device On The Local Loop. The System Manager May Be Connected To TheLocal Loop At Any Point On The Local Loop.
System Manager
654
DEC
7
MINUS0 CLEAR
98
1 32 MENU
Override
Communication
ENTER
ESC
Alarm
To MiniLink, Or Next DeviceOn Local Loop
Line Voltage
See Note 1
See Note 324VAC
GND
Required VA For TransformerSystem Manager = 25VA Max.
MADE IN
THE USA
EP
RO
M
1000uF10v
YS101806 REV. 1
DSPY1
UNIVERSAL SMART DISP. UNIT
SYSTEM MANAGER
SERIAL # :
U13SERIAL #
1000uF10v
C9
470uF50v
D2
PC
B8
0C
55
2-5
-16
WP
44
28
60
=2
/5
DfD
97
22
V7
Y
PH
ILIP
S
CX
13
LD8
CX
9
SS0017
vx.xx 1234
V62C518256L-70P
U9
U8
LD7
RN
1
LD6
U7
CX7
74
HC
57
3
LD5
LD4
74HC573
CX
8
RN2
X2
CX
4
470uF50v
TB
2
GN
D
24
VA
C
R1
0
75176
RS-485
COMM
U12
CX
12
RA
M
SC1
T
TB
1
SH
LD
C7
C11
L1
C4
R
D6
85
83
U6
CX6C3
D3
24
C1
28
U5
R7
VAR1
D4
PJ1
R3
U1
74HC259
LD3
LD2
LD1
R2
R1
EW
DO
G
PH
ILIP
S
U3
U2
CX
1
82B715CX5
CX
3
U3
DSPY1
R5
D1
R6
MC
34
06
4A
C6
R11
99
36 C
8
R9
U10
U11
R8
R12
C5
74
HC
92
3
CX10
P1
R4
RV1
C2
C1
X1
06/28/02
Form: 035-18955-000 Rev. A (0602) Supersedes: Nothing
Notes:
FILENAME
DATE: B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
Wx or Yx (Htg or Clg Stage x)
Wx or Yx (Htg or Clg Stage x)
Wx or Yx (Htg or Clg Stage x)
Wx or Yx (Htg or Clg Stage x)
G (Fan-On/Off)
R (24VAC)
Constant VolumeUnit Connections
CV Controller
R
SH
T
R
SH
T
R
SH
T
R
SH
T
All Comm Loop Wiring IsStraight Thru
Required VA For TransformerEach CV Controller = 20VA Max.
24VAC
24VAC
GND
GND
Mount In HVACUnit Supply
Air Duct
Auxiliary AlarmInput
Switch SuppliedBy Others
DischargeAir Temp.Sensor
AOUT
GND
GND
AIN5
AIN1
AIN2
AIN3
AIN4
12V
GND
AUX
TMP
NORMAL
OVR
RELO
C
REMR
O
AW
COMM
REC.
LD4
T
R
SHLD
GND
24VAC
PWR
COMM
TEST
16
8421
RELAYOUTPUTS
COM4-5
OUT1
OUT2
OUT3
OUT4
OUT5
COM1-3
Caution!CV Controllers Must Have Address Switches SetBetween 1 And 30 ( Up To 30 Units Per Local Loop ).
Room Sensor
Diagnostic Blink Code LED
RAM
EPROM
Local LoopRS-485
9600 Baud
Connect ToNext Controller
And/OrMiniLink On
Address Switch Shown IsSet For Address 1
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
This Switch Must BeIn The ON PositionAs Shown
These Switches Should BeIn The OFF PositionAs Shown
Note:The Power To The CV Controller Must Be RemovedAnd Reconnected After Changing The AddressSwitch Settings In Order For Any Changes To TakeEffect.
Caution:Disconnect All Communication Loop WiringFrom The CV Controller Before Removing PowerFrom The CV Controller. Reconnect Power AndThen Reconnect Communication Loop Wiring.
ADDRESS ADD
ADDRESS ADD
ADDRESSADD
ADDRESSADD
The Address For Each ControllerMust Be Unique To The Other Controllers
On The Local Loop
Connection ToAUX Terminal is ReqdOnly When SensorIs Specified WithSlide Adjust Option
JOB NAME1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.
2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes And Specifications.
3.)All Communication Wiring To Be2 Conductor Twisted Pair WithShield. Use Belden #82760 OrEquivalent. 3
EconomizerActuator
(Belimo Shown)Consult Factory ForOther ManufacturersWiring Connections
Note:Up To 4 Stages Of Heating Or Cooling Or AnyCombination Of Each Is Allowed And ProgrammableVia The System Manager or ZoneView Software. If TheUnit Has Heat, Heating Stages Must Be Connected ToThe First Outputs in Consecutive Order And CoolingStages To The Remaining Outputs In Consecutive Order.
Outside AirTemp. Sensor(See Note 4)
4.)Only One Outside Air Sensor IsRequired Per System. It May BeConnected To Any CV Controller Or OnThe System. If A Wetbulb ModuleController Is Used The OA Sensor MustBe Connected To The Wetbulb Module.
CV Controller Wiring
Meridian CV
Y 3
+ 2
COM 1
035-18956-000-A-0602.CDR
06/28/02
Form: 035-18956-000 Rev. A (0602) Supersedes: Nothing
Commlink II Communications Interface
(Jumper Set For Multiple Loop)
Caution: Use The “Molded Cable” ToConnect To The Computer (DCE) Connector.This Cable Is Only To Be Used To ConnectFrom The CommLink (DTE) Connection ToThe Modem (When Used).
Do Not
Caution:Disconnect All Communication Loop WiringFrom The CommLink Before Removing PowerFrom The CommLink. Reconnect Power And ThenReconnect Communication Loop Wiring.
Use 25 Pin Or 9 Pin Connector AsRequired By Available Serial (COM) Port
JOB NAME
Caution: Use The “25 Pin Or 9 Pin Cable” ToConnect To The Modem (DTE) Connector.. ThisCable Is Only To Be Used To Connect From TheCommLink (DCE) Connection To The Computer
Serial Port (COM) Connection.
Do Not
(When Used) Note:Place Jumper BetweenPins 1 & 2 for MultipleLoop Applications &Between Pins 2 & 3 forSingle Loop ApplicationsSee Note 4.
COMM DRIVER CHIP( U1 )PIN 1
MULTI
SINGLE
12
3
CommLink Jumper Switch SettingsNotes:
FILENAME
DATE: B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
CommLink II Wiring4
R
SH
T
R
SH
T
R
SH
T
R
SH
T
All Communication LoopWiring Is Straight Through
Connect To First Zone
Network LoopRS-485
19200 Baud
Required VA For TransformerCommLink = 14VA Max.
CommLink Is Supplied With 110/24VAC Power Supply.If Desired A Transformer (By Others)
May Be Wired To The CommLink Instead
Molded Modem Cable.Supplied With CommLink
(DTE)MODEM COMPUTER
(DCE)
GT R
POWER
4 Piece ComputerCable Kit.Supplied WithCommLink
Connect To Modem .Only
9P
inF
em
ale
9 PinFemale
25 PinFemale
9P
inF
em
ale
120/24 VacTransformer
Part # PX000015
25 PinMale
Connect Supplied RJ12 Modular Phone CableTo Supplied 9 Pin Or 25 Pin Connector As ReqdBy Your Computer Com Port Connection
1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.
2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes And Specifications.
3.)All Communication Wiring To Be2 Conductor Twisted Pair WithShield. Use Belden #82760 OrEquivalent. Meridian CV
4.)CommLink Is Shipped With TheJumper In The Multiple LoopConfiguration, So It Is NecessaryTo Move It To The Single LoopConfiguration For A CV System.
485 LOOP 24V
GND
035-18957-000-A-0602.CDR
06/28/02
Form: 035-18957-000 Rev. A (0602) Supersedes: Nothing