heated flame ionization detector module - spartan controls/media/resources... · instruction manual...

118
Instruction Manual 748414-B February 2002 http://www.processanalytic.com Model NGA 2000 HFID Heated Flame Ionization Detector Module

Upload: others

Post on 27-Feb-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

http://www.processanalytic.com

Model NGA 2000 HFIDHeated Flame Ionization Detector Module

Page 2: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Emerson Process ManagementRosemount Analytical Inc.Process Analytic Division1201 N. Main St.Orrville, OH 44667-0901T (330) 682-9010F (330) 684-4434e-mail: [email protected]://www.processanalytic.com

ESSENTIAL INSTRUCTIONSREAD THIS PAGE BEFORE PROCEEDING!

Rosemount Analytical designs, manufactures and tests its products to meet many national andinternational standards. Because these instruments are sophisticated technical products, youMUST properly install, use, and maintain them to ensure they continue to operate within theirnormal specifications. The following instructions MUST be adhered to and integrated into yoursafety program when installing, using, and maintaining Rosemount Analytical products. Failure tofollow the proper instructions may cause any one of the following situations to occur: Loss of life;personal injury; property damage; damage to this instrument; and warranty invalidation.

• Read all instructions prior to installing, operating, and servicing the product.

• If you do not understand any of the instructions, contact your Rosemount Analytical repre-sentative for clarification.

• Follow all warnings, cautions, and instructions marked on and supplied with the product.

• Inform and educate your personnel in the proper installation, operation, and mainte-nance of the product.

• Install your equipment as specified in the Installation Instructions of the appropriate In-struction Manual and per applicable local and national codes. Connect all products to theproper electrical and pressure sources.

• To ensure proper performance, use qualified personnel to install, operate, update, program,and maintain the product.

• When replacement parts are required, ensure that qualified people use replacement partsspecified by Rosemount. Unauthorized parts and procedures can affect the product’s per-formance, place the safe operation of your process at risk, and VOID YOUR WARRANTY.Look-alike substitutions may result in fire, electrical hazards, or improper operation.

• Ensure that all equipment doors are closed and protective covers are in place, exceptwhen maintenance is being performed by qualified persons, to prevent electrical shockand personal injury.

The information contained in this document is subject to change without notice.

Teflon is a Registered Trademark of E.I. duPont de Nemours and Co., Inc.Kynar is a Registered Trademark of Atochem North America, Inc.SNOOP is a registered trademark of NUPRO Co.

Page 3: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Contents i

Model NGA 2000 HFID

TABLE OF CONTENTS

PREFACE...........................................................................................................................................1Definitions ...........................................................................................................................................1Safety Summary .................................................................................................................................2General Precautions For Handling And Storing High Pressure Gas Cylinders .................................5Documentation....................................................................................................................................6Compliances .......................................................................................................................................6Glossary of Terms ............................................................................................................................7

1.0 DESCRIPTION AND SPECIFICATIONS..............................................................................1-11-1 Overview................................................................................................................................1-11-2 Typical Applications...............................................................................................................1-11-3 Safety Gas Features..............................................................................................................1-11-4 Theory of Technology............................................................................................................1-11-5 Specifications ........................................................................................................................1-4

a. General ...........................................................................................................................1-4b. Physical...........................................................................................................................1-4c. Gas Requirements ..........................................................................................................1-5d. Gas Connections.............................................................................................................1-6

2.0 INSTALLATION ....................................................................................................................2-12-1 Unpacking..............................................................................................................................2-12-2 Assembly ...............................................................................................................................2-12-3 Location .................................................................................................................................2-12-4 Gases ....................................................................................................................................2-1

a. Overview .........................................................................................................................2-1b. Pneumatic Connections ..................................................................................................2-3c. Specifications ..................................................................................................................2-3

2-5 Leak Test ...............................................................................................................................2-42-6 Electrical Connections ...........................................................................................................2-62-7 Installation Considerations Checklist.....................................................................................2-9

3.0 OPERATION .........................................................................................................................3-13-1 Overview................................................................................................................................3-13-2 Startup Procedure .................................................................................................................3-13-3 Binding...................................................................................................................................3-33-4 Calibration..............................................................................................................................3-43-5 Routine Operation .................................................................................................................3-53-6 Safety System........................................................................................................................3-5

4.0 MAINTENANCE AND SERVICE ..........................................................................................4-14-1 Overview................................................................................................................................4-14-2 Oven ......................................................................................................................................4-3

a. Removal ..........................................................................................................................4-3b. Disassembly....................................................................................................................4-4

4-3 Burner ....................................................................................................................................4-6a. Temperature Sensor .......................................................................................................4-6b. RTD Detector ..................................................................................................................4-6c. Igniter ..............................................................................................................................4-6d. Flameout Sensor.............................................................................................................4-6

Page 4: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

ii Contents Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

4-4 Burner Internal Components .................................................................................................4-8a. Disassembly of Burner/Thermal Block............................................................................4-8b. Replacing Burner Jets.....................................................................................................4-9c. Burner Jet Installation .....................................................................................................4-11

4-5 Thermal Block........................................................................................................................4-12a. Sample RTD....................................................................................................................4-12b. Cartridge Heater..............................................................................................................4-13c. Thermostat ......................................................................................................................4-13d. Sample Capillary .............................................................................................................4-13

4-6 Electronics Assembly ............................................................................................................4-14a. Printed Circuit Boards .....................................................................................................4-15b. Case Temperature Sensor..............................................................................................4-16c. Case Pressure Purge Switch ..........................................................................................4-17d. Preamp Assembly ...........................................................................................................4-18

4-7 Fan Assembly........................................................................................................................4-194-8 Flow Controller ......................................................................................................................4-204-9 DC Power Supply Module .....................................................................................................4-224-10 Front Panel Components.......................................................................................................4-23

a. LON/Power Module.........................................................................................................4-25b. LED Indicator Assembly..................................................................................................4-25c. Manual Ignite Toggle Switch...........................................................................................4-25d. Burner Air Sensor............................................................................................................4-25e. Fuel Sensor.....................................................................................................................4-25f. Burner Air and Fuel Regulators ......................................................................................4-25g. Purge Air Regulator ........................................................................................................4-26h. Purge Air Flow Switch and Diffuser ................................................................................4-26i. Burner Air Solenoid Valve...............................................................................................4-26j. Air Ignite Restrictor..........................................................................................................4-26

4-11 Rear Panel Components .......................................................................................................4-27a. Fuel In 2-Way Solenoid Valve.........................................................................................4-28b. Burner Air In Filter ...........................................................................................................4-28c. Heated Bypass Sample Out and Heated Sample In Restrictors ....................................4-28d. Regulated Air In Check Valve .........................................................................................4-28

5.0 TROUBLESHOOTING..........................................................................................................5-15-1 Troubleshooting Checklist .....................................................................................................5-1

a. Safety System.................................................................................................................5-1b. Ignition.............................................................................................................................5-1c. Drift..................................................................................................................................5-2d. Noise ...............................................................................................................................5-2

6.0 REPLACEMENT PARTS......................................................................................................6-16-1 Matrix .....................................................................................................................................6-16-2 General ..................................................................................................................................6-26-3 Pneumatics ............................................................................................................................6-26-4 Oven Components.................................................................................................................6-3

7.0 RETURN OF MATERIAL......................................................................................................7-17-1 Return Of Material .................................................................................................................7-17-2 Customer Service ..................................................................................................................7-17-3 Training..................................................................................................................................7-1

8.0 APPENDIX A - MENU DISPLAYS........................................................................................8-1

Page 5: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Contents iii

Model NGA 2000 HFID

LIST OF ILLUSTRATIONS

Figure 1-1. Flame Ionization Detection Technology ...........................................................................1-2Figure 1-2. Heated Flame Ionization Detector Analyzer Module - Top View....................................1-3Figure 2-1. Back Panel Connections ..................................................................................................2-2Figure 2-2. Flow Diagram....................................................................................................................2-5Figure 2-3. Front Panel Electrical Connections ..................................................................................2-6Figure 2-4. Front Panel Connections, Controls and Indicators...........................................................2-6Figure 2-5. HFID Outline and Mounting Dimensions ..........................................................................2-7Figure 2-6. HFID Wiring Diagram........................................................................................................2-8Figure 3-1. Typical Curves of Module Response vs. Pressure Setting on Fuel Pressure Regulator ..3-7Figure 3-2. Typical Curves of Module Response vs. Pressure Setting on Air Pressure Regulator.....3-7Figure 3-3. Front Panel Torque Sequence ..........................................................................................3-8Figure 4-1. Removal of Cover and Insulation Shield ...........................................................................4-1Figure 4-2. Locations of Major Assemblies of the HFID ......................................................................4-2Figure 4-3. Removal of Oven from Chassis.........................................................................................4-3Figure 4-4. Oven Assembly..................................................................................................................4-5Figure 4-5. Burner - Sensor, Flameout Detector, RTD Detector and Ignitor .......................................4-7Figure 4-6. Burner/Thermal Block Disassembly ..................................................................................4-8Figure 4-7. Burner Disassembly...........................................................................................................4-9Figure 4-8. Burner Jets ........................................................................................................................4-10Figure 4-9. Thermal Block – Sample RTD, Cartridge Heater and Thermostat....................................4-12Figure 4-10. Thermal Block Assembly .................................................................................................4-13Figure 4-11. Removing Electronics Assembly from Chassis ...............................................................4-14Figure 4-12. Electronics Assembly – Exploded View...........................................................................4-15Figure 4-13. Case Sensor Installation..................................................................................................4-16Figure 4-14. Case Pressure Purge Switch Installation ........................................................................4-17Figure 4-15. Preamp Assembly Installation .........................................................................................4-18Figure 4-16. Fan Assembly Installation................................................................................................4-19Figure 4-17. Flow Controller Replacement ..........................................................................................4-20Figure 4-18. Flow Controller Assembly................................................................................................4-21Figure 4-19. DC Power Supply Module Replacement .........................................................................4-22Figure 4-20. Front Panel – Exploded View ..........................................................................................4-23Figure 4-21. Accessing Front Panel Components ...............................................................................4-24Figure 4-22. Rear Panel Components .................................................................................................4-27

LIST OF TABLES

Table 3-1. HFID Analyzer Module Alarms ..................................................................................... 3-8

Page 6: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

iv Contents Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

Page 7: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Preface P-1

Model NGA 2000 HFID

PREFACE

The purpose of this manual is to provide information concerning the components, functions,installation and maintenance of the NGA 2000 HFID and the System Accessories of the NGA2000 System.

Some sections may describe equipment not used in your configuration. The user shouldbecome thoroughly familiar with the operation of this module before operating it. Read thisinstruction manual completely.

DEFINITIONS

The following definitions apply to DANGERS, WARNINGS, CAUTIONS and NOTES foundthroughout this publication.

DANGER .

Highlights the presence of a hazard which will cause severe personal injury, death, or sub-stantial property damage if the warning is ignored.

WARNING .

Highlights an operation or maintenance procedure, practice, condition, statement, etc. If notstrictly observed, could result in injury, death, or long-term health hazards of personnel.

CAUTION.

Highlights an operation or maintenance procedure, practice, condition, statement, etc. If notstrictly observed, could result in damage to or destruction of equipment, or loss of effective-ness.

NOTEHighlights an essential operating procedure, condition or statement.

Page 8: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

P-2 Preface Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

SAFETY SUMMARY

If this equipment is used in a manner not specified in these instructions, protective systems may beimpaired.

AUTHORIZED PERSONNEL

To avoid explosion, loss of life, personal injury and damage to this equipment and on-siteproperty, all personnel authorized to install, operate and service the this equipment should bethoroughly familiar with and strictly follow the instructions in this manual. SAVE THESE IN-STRUCTIONS.

DANGER.

ELECTRICAL SHOCK HAZARDOperate this equipment only when covers are secured. Servicing requires access to live partswhich can cause death or serious injury. Refer servicing to qualified personnel. For safetyand proper performance, this module must be connected to a properly grounded three-wiresource of electrical power.

WARNING .

POSSIBLE EXPLOSION HAZARDThis equipment is used in the analysis of sample gases which may be flammable, and theburner fuel used in the ionization process is flammable. A continuous dilution purge systemis factory-installed (in accordance with Standard ANSI/NFPA 496-1993, Chapter 6, and it mustbe functional at all times during operation. Do not disable this purge system.

WARNING.

FLAMMABLE SAMPLESThe internal compartment of the oven is vented to the main enclosure by the top and bottomvents. DO NOT RESTRICT THOSE VENTS.

Consult the factory if flammable samples will be measured.

Page 9: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Preface P-3

Model NGA 2000 HFID

WARNING.

HIGH TEMPERATURE

This equipment is used in the analysis of sample gases at temperatures of up to 250 C. All compo-nents and material in contact with the sample, the oven and the burner can reach this temperaturelevel.

Operate this equipment only when covers are secured. Servicing requires access to "hot" partswhich can cause serious injury. Refer servicing to qualified personnel.

NOTEThis Analyzer Module is completely leak-tested at the factory for gas leakage. The user is responsi-ble for testing for leakage at the inlet and outlet fittings on the rear panel (with a test procedure cho-sen by the user). The user is also responsible for leak-testing periodically and if any internalpneumatic components are adjusted or replaced. See leak test instructions in Section 2-5.

WARNING.

PARTS INTEGRITYTampering with or unauthorized substitution of components may adversely affect safety of thisproduct. Use only factory-approved components for repair.

CAUTION.

PURGE AIR REQUIREMENTThis Analyzer Module must be used in conjunction with a device (Control Module or PC Interface)that can actively monitor network variables related to pressure or flow of the continuous dilutionpurge, or the front panel LEDs of the Analyzer Module, as installed, must be visible. The purpose ofthis requirement is to maintain adherence to ANSI/NFPA 496 standard which assures the continuedviability of the purge system. Under no circumstances should any pressure or flow indicator beconnected to the PURGE AIR OUT outlet of the Analyzer Module because this may affect the sealingperformance of the module.

CAUTION.

PRESSURIZED GASThis module requires calibration with a known standard gas. See General Precautions for Handlingand Storing High Pressure Gas Cylinders, page P-5.

Page 10: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

P-4 Preface Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

WARNING.

POSSIBLE EXPLOSION HAZARDEnsure that all gas connections are made as labeled and are leak free. Improper gas connectionscould result in explosion or death.

CAUTION.

OVER-VOLTAGE SPIKINGIf this analyzer module is used with a non-Rosemount Analytical power supply, adding RosemountAnalytical PN 903341 Current Protector in series with the 24V positive power line will prevent over-voltage spiking and resultant fuse blowing when powering up the instrument.

CAUTION .

PRESSURIZED ENCLOSUREThis enclosure shall not be opened unless the area is known to be free of flammable materials orunless all devices within have been de-energized.

Area classification for the protected enclosure:

Nonclassified.

Pressurization: Type Z

Temperature Identification Number: T4A

Power shall not be restored after enclosure has been opened (or loss of purge) until enclosure hasbeen purged for a minimum of 6 (six) minutes at the minimum pressure of 689 hPa (10 psig).

Page 11: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Preface P-5

Model NGA 2000 HFID

GENERAL PRECAUTIONS FOR HANDLING AND STORINGHIGH PRESSURE GAS CYLINDERS

Edited from selected paragraphs of the Compressed Gas Association's "Handbook of Com-pressed Gases" published in 1981

Compressed Gas Association1235 Jefferson Davis HighwayArlington, Virginia 22202

Used by Permission

1. Never drop cylinders or permit them to strike each other violently.

2. Cylinders may be stored in the open, but in such cases, should be protected against extremes ofweather and, to prevent rusting, from the dampness of the ground. Cylinders should be stored in theshade when located in areas where extreme temperatures are prevalent.

3. The valve protection cap should be left on each cylinder until it has been secured against a wall orbench, or placed in a cylinder stand, and is ready to be used.

4. Avoid dragging, rolling, or sliding cylinders, even for a short distance; they should be moved by usinga suitable hand-truck.

5. Never tamper with safety devices in valves or cylinders.

6. Do not store full and empty cylinders together. Serious suckback can occur when an empty cylinderis attached to a pressurized system.

7. No part of cylinder should be subjected to a temperature higher than 125°F (52°C). A flame shouldnever be permitted to come in contact with any part of a compressed gas cylinder.

8. Do not place cylinders where they may become part of an electric circuit. When electric arc welding,precautions must be taken to prevent striking an arc against the cylinder.

Page 12: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

P-6 Preface Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

NAMUR

97-C219

N96

DOCUMENTATION

The following NGA 2000 HFID instruction materials are available. Contact Customer Service Center orthe local representative to order.

748414 Instruction Manual (this document)

COMPLIANCES

This product may carry approvals from several certifying agencies, including Factory Mutual and the Cana-dian Standards Association (which is also an OSHA accredited, Nationally Recognized Testing Labora-tory), for use in non-hazardous, indoor locations.

Rosemount Analytical Inc. has satisfied all obligations from the European Legislation to harmonize theproduct requirements in Europe.

This product complies with the standard level of NAMUR EMC. Recommendation (May 1993).

This product satisfies all obligations of all relevant standards of the EMC framework in Australia and NewZealand.

®

NRTL /CAPPROVED

FM

Page 13: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Preface P-7

Model NGA 2000 HFID

GLOSSARY OF TERMS

Analyzer ModuleThe module that contains all sensor/detector components for development of a Primary Variable signal; in-cludes all signal conditioning and temperature control circuitry.

BackplaneThe interconnect circuit board which the Controller Board, Power Supply, Analyzer Module power and net-work cables, I/O Modules and Expansion Modules plug into.

Control ModuleThe Operator Interface plus the Controller Board.

Controller BoardThe computer board that serves as the Network Manager and operates the Display and Keypad.

Distribution AssemblyThe Backplane and the card cages that hold I/O and Expansion Modules.

Expansion ModuleA circuit board that plugs into the Backplane from the front of the Platform and performs special featuresnot related to I/O functions.

I/O ModuleA circuit board that plugs into the Backplane from the rear of the Platform. Has a connector terminal forcommunication with external data acquisition devices and provides an input/output function.

Operator InterfaceThe Display and Keyboard.

PlatformAny workable collection of the following: Controller Board, Power Supply, Distribution Assembly, Enclosureand Operator Interface.

Power SupplyAny of a variety of components that provides conditioned power to other NGA 2000 components, from thePower Supply Board that plugs into the front of the Backplane in a stand-alone instrument to several largerones that can power larger collections of modules and components.

Primary VariableThe measured species concentration value from an Analyzer Module.

Secondary VariableData placed on the network by a module regarding current status, e.g., sample flow, source voltage andother diagnostic information.

Page 14: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

P-8 Preface Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

SoftkeysThe five function softkeys located below the front panel display; they assume the function displayed directlyabove each on the display, a function dictated by software.

SystemAny collection of Analyzer Module(s), Platform(s), I/O Module(s) and Expansion Module(s).

Page 15: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-1

Model NGA 2000 HFID

SECTION 1DESCRIPTION AND SPECIFICATIONS

1-1 OVERVIEW

This manual describes the Heated Flame Ioni-zation Detector (HFID) Analyzer Module ofRosemount Analytical's NGA 2000 Series ofgas analysis components. See Figure 1-1 andFigure 1-2.

The HFID Analyzer Module is designed to con-tinuously determine the concentration of hydro-carbons in a flowing gaseous mixture at auser-selectable temperature setpoint between93°C and 204°C (200°F and 400°F). The con-centration is expressed in ppm or percent ofvolume.

The entire HFID Analyzer Module is designedas a stand-alone module, with gas connectionsmade from the rear. All electronics relative tosample detection and conditioning are includedin this module.

1-2 TYPICAL APPLICATIONS

The monitoring of atmospheric air for low-levelhydrocarbon contaminants and determining thehydrocarbon content of exhaust emissions frominternal combustion engines are examples oftypical applications for the HFID Analyzer Mod-ule.

1-3 SAFETY GAS FEATURES

The HFID Analyzer Module is designed with afactory-installed continuous dilution purge sys-tem in accordance with standard ANSI/NFPA496 - 1993, Chapter 6. Front-panel LEDs indi-cate that the burner flame is lit and that thepurge system is enabled. In addition, fuel gas isautomatically shut off when a flame-out condi-tion occurs or the safety system is disabled.

The purge system is enabled only if there isproper purge gas flow in, purge gas pressure,and internal case pressure, and after five timesthe case volume has been exchanged.

All tubing ahead of the burner is rigid metal-lic tubing assembled with ferrule/nut typecompression fittings. However, should aninternal fuel leak occur, a worst-case leakwould be dissipated below 25% of the LELof hydrogen through the combination of aninlet fuel flow restrictor and purge gas flow.

This module is designed to use 40%H2/60% He fuel at a maximum inlet pres-sure of 3446 hPa-gauge (50 psig).

A standard HFID Analyzer Module is onlyequipped to analyze a non-flammable sam-ple, below 100% of the LEL.

WARNING

POSSIBLE EXPLOSION HAZARDProtection against explosion dependsupon a special fuel flow restrictor in thefuel inlet fitting. Do not remove fuel inletrestrictor. Do not use 100% hydrogenfuel. Replace only with a factory sup-plied fitting.

1-4 THEORY OF TECHNOLOGY

This Analyzer Module uses the flame ioni-zation method of detection. The sensor is aburner in which a regulated flow of samplegas passes through a flame sustained byregulated flows of a fuel gas (a hydro-gen/diluent mixture) and air.

Within the flame, the hydrocarbon compo-nents of the sample stream undergo a com-plex ionization that produces electrons andpositive ions. Polarized electrodes collectthese ions, causing current to flow throughan electronic measuring circuit.

The ionization current is proportional to therate at which carbon atoms enter theburner, and is therefore a measure of the

Page 16: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

1-2 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

concentration of hydrocarbons in the sample.This measure of concentration is placed on the

network, where it can be shown on a dataacquisition device.

Figure 1-1. Flame Ionization Detection TechnologyC

PositiveCarbonIons

Signal Conditioning

Negative IonCollection Plate

Sample

Air

Fuel

+90V

Page 17: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-3

Model NGA 2000 HFID

Detector(Burner)

Purge Air Outlet

Preamp Board(In Shield)

Fuel ShutoffSolenoid Valve

Gas Lines(See Figure 2-2)

Computer Board

Sensor Board

Safety Board

Burner Air & Fuel Regulators(Stacked Vertically)

Case Pressure Switch

Oven

Air Circulation Fan

Case Heater

Sample FlowController

Purge AirFlow Switch

DC-DC Module

Burner AirSolenoid Valve

Network & Power Module

Power Supply Board

Purge AirRegulator

Figure 1-2. Heated Flame Ionization Detector Analyzer Module - Top View

Page 18: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

1-4 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

1-5 SPECIFICATIONS

a. GeneralMeasurement Species ....................Total hydrocarbonsRanges (H2/He Fuel)

Low range.............................. 0 to 10 ppm, CH4, through 0 to 1%, CH4 at an oven setpoint be-tween 113°C and 191°C

High range ............................. 0 to 50 ppm, CH4, through 0 to <5%, CH4 at an oven setpoint be-tween 113°C and 191°C

Analysis Temperature .....................Adjustable from 200oF to 400oF (93oC to 204oC), maintained within±11oF (±6oC) from the setpoint.

Repeatability ....................................≤1% of fullscale for successive identical samples, at a constanttemperature, sample flow and fuel, burner air, regulated air andsample pressures

Min. Detectable Level......................0.10 ppm, CH4

Noise ................................................≤1% of fullscale, peak to peakLinearity............................................≤±1% of fullscale, ≤±2% of data point (must be above the minimum

detectable level)Response Time ...............................≤1.5 sec., 0% to 90% of fullscaleDrift

Zero ....................................... ≤ ±1% of fullscale/24 hours at constant temperature, sample flow,hydrocarbon concentration of supply gases, andfuel, burner air, regulated air and sample pres-sures.

Span...................................... ≤ ±1% of fullscale/24 hours at constant temperature, sample flow,hydrocarbon concentration of supply gases, andfuel, burner air, regulated air and sample pres-sures.

Effect of Temperature.................... ≤±2% of fullscale for any ambient temperature change of 10oC andrate of change less than 10oC/hr.

Operating Temperature ................. 59°F to 95°F (15°C to 35°C)Power Requirements.......................+24 VDC ±5%, 120 W max. direct to Analyzer Module

Ripple and Noise: <100 mV ppLine and Load Regulations: <1%

b. PhysicalCase Classification ........................ General purpose for installation in weather-protected areaMaximum Separation .................... 1600m (1 mile) from Analyzer Module to PlatformMaterials in Contact With Sample . Stainless steel and glass-filled TeflonDimensions.................................... See Outline and Mounting Dimensions, Figure 2-5Weight ........................................... 15.9 kg (35 lbs.)Mounting........................................ Horizontally, custom-installed in a panel

Page 19: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-5

Model NGA 2000 HFID

c. Gas RequirementsSample .......................................... Non-flammable, below 100% of LEL

Flow rate ................................ 1.0 to 2.5 L/min.Supply pressure..................... 345 to 620 hPa-gauge (5 to 9 psig)Temperature .......................... 110oC to 230oC (230oF to 446oF), <20oC variance/24 hours, <10oC

variance/hr.Particulates ............................ filtered to <2 micronsDewpoint................................ <15oC below the setpoint

Regulated Air................................. Instrument air or nitrogenFlow rate ................................ 2 to 4 L/min.THC ....................................... ≤2 ppm, CH4Supply pressure..................... 689 to 1723 hPa-gauge (10 to 25 psig)Particulates ............................ filtered to <2 microns

Purge Air:....................................... Instrument air, nitrogen or other nonflammable gas (refer toANSI/NFPA 496 for the requirements for the Protective Gas Sys-tem)

Flow rate: .............................. 16 to 18 L/min.Supply pressure:.................... 689 to 1378 hPa-gauge (10 to 20 psig)

Fuel Gas ........................................ Premixed 40% hydrogen and 60% heliumFlow rate ................................ 80 to 100 ml/minTHC ....................................... ≤0.5 ppm, CH4Supply pressure..................... 3101 to 3446 hPa-gauge (45 to 50 psig)

WARNING

EXPLOSION HAZARDDo not use pure hydrogen fuel. An explosion resulting in severe personal injury or death could oc-cur.

Burner Air ...................................... Zero-grade airFlow rate ................................ 350 to 400 mL/min.THC ....................................... ≤1 ppm, CH4Supply pressure..................... 1723 to 3446 hPa-gauge (25 to 50 psig)

Page 20: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

1-6 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

d. Gas ConnectionsSample In ...................................... 1/4" O.D. tube fitting, stainless steelRegulated Air In ...............................1/4" O.D. tube fitting, brassBurner Air In .....................................1/4" O.D. tube fitting, brassFuel In...............................................1/4" O.D. tube fitting, stainless steelPurge Air In ......................................3/8" O.D. tube fitting, brassPurge Air Out....................................3/8" O.D. tube fitting, brassBypass Out.......................................1/4" O.D. tube fitting, stainless steelBurner Exhaust Out: ...................... 3/8" O.D. tube connection, stainless steel (must slope downward

6o min. from horizontal)

Burner Exhaust, Bypass Out and Purge Air Out to be vented to atmospheric pressure and tonon-classified location in accordance with ANSI/NFPA-496 guidelines.

Pressure Relief Valve ......................See Caution Below

CAUTION

PRESSURE RELIEF VALVENo connection shall be made to this fitting. If this caution is ignored, damage to the case sealscould occur, and the instrument will not operate properly.

WARNING

HIGH TEMPERATUREThe Sample In, Bypass Out, and Burner Exhaust Out connections can reach temperatures of up to250°C (480°F). Severe burns could result from touching these connections.

See the Preface section of the Platform Components manual for specifications regarding Platform-relatedcomponents and the Preface of the I/O Module manual for specifications regarding I/O (e.g., relay outputs).

Page 21: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 2-1

Model NGA 2000 HFID

SECTION 2INSTALLATION

2-1 UNPACKING

If the HFID Analyzer Module is received as aseparate unit, carefully examine the shippingcarton and contents for signs of damage. Im-mediately notify the shipping carrier if the cartonor contents is damaged. Retain the carton andpacking material until all components associ-ated with the Analyzer Module are operational.

2-2 ASSEMBLY

If the Analyzer Module requires assembly withother components, do so at this time.

Connect the network cable to either the NET-WORK 1 or NETWORK 2 connection on theAnalyzer Module. Connect the power cable tothe Analyzer Module front panel and an electri-cal +24VDC power supply.

2-3 LOCATION

Install the Analyzer Module in a clean,weather-proofed, non-hazardous, vibration-freelocation free from extreme temperature varia-tions. For best results, install the Analyzer Mod-ule near the sample stream to minimize sampletransport time.

WARNING

INSTALLATION RESTRICTIONSFor safety, the Analyzer Module should beinstalled in a non-confined, ventilated space.Do not block any of the rear panel outlets asthey are part of the safety system.

Operating ambient temperature is 15°C to35°C, limited to temperature changes of lessthan 10°C/hr. Acceptable dew point range isless than 95% relative humidity, but not in ex-cess of 45°C wet bulb temperature.

The cylinders of fuel, air, and calibrationgas(es) and the source of purge and regu-lated air should be located in an area ofrelatively constant ambient temperature.

2-4 GASES

a. Overview

During normal operation, the AnalyzerModule requires fuel and air to maintain theburner flame as well as suitable standardgases for calibration and instrument air forpurge requirements. In addition, instrumentair for regulated air in is required to controlthe sample pressure at the sample capillary.Criteria for selection of these gases follow inSection 2-4c.

After initial startup or after startup followinga prolonged shutdown, the analyzer maydisplay baseline drift for a considerable pe-riod of time, particularly on the most sensi-tive range. Commonly, the drift is caused bysmall amounts of hydrocarbons in the innerwalls of the tubing in both the internal flowsystem and the external gas supply system.Drift results from any factor influencing theequilibrium of these absorbed hydrocar-bons, such as temperature or pressure.

Note that this type of drift occurs only whenthe flame is burning. If drift occurs when theflame is extinguished, the electronic circuitryis at fault. To minimize drift, use clean fueland air, keep the analyzer clean, and locatethe gas cylinders in an area of relativelyconstant ambient temperature.

The cylinders supplying all gases eachshould be equipped with a clean, hydrocar-bon-free, two-stage regulator and a shutoffvalve.

All new external gas tubing (except forPURGE IN/OUT and SAMPLE BYPASS) isstrongly recommended, preferably pre-cleaned, stainless steel, gas chromato-

Page 22: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

2-2 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

graph-grade tubing. Thoroughly clean beforeuse (if a hydrocarbon-based cleaning solventsuch as acetone is used, purge tubing with drynitrogen or helium for several minutes beforeusing.)

Gas line connections are compression fittings.Do not use pipe thread tape.

Since the oxidation of hydrogen is accompaniedby the formation of water vapor, the Exhausttubing always should be slanted downward atleast 6 degrees from horizontal. Otherwise,water may accumulate in the line, causing backpressure and noisy readings, or may back up in

the line and flood the burner. Depending onthe percent of water vapor in the sample,the sample bypass out connection mayhave condensation. Proper drainage maybe required.

If the sample is toxic or noxious, or is to bereclaimed, connect the Bypass outlet to asuitable disposal system. Do not use anydevice that may cause back pressure in theline.

Purge air and burner air should be suppliedfrom separate sources.

Figure 2-1. Back Panel Connections

Danger d'electrocution, d'explosion ou d'emanation de gaztoxique. Se refere aux details inscrits surla face du module.

PURGEAIR IN

PURGEAIR OUT

PRESSURERELIEFVALVE

BURNERAIR IN

HEATEDSAMPLE IN

VENT TO SAFE AREASLOPE DOWNWARD 6°MINIMUM

FUELINBURNER

EXHAUSTOUT

REGULATED

MAXIMUMINPUTPRESSURE

HEATEDSAMPLEBYPASS OUT

Possible electric shock, explosion or toxic gas hazard. See front of module

ATTENTION

FUEL: 50 psig(3445 hPa)BURNER AIR: 50 psig (3445 hPa)SAMPLE: 8 psig (551 hPa)PURGE AIR: 20 psig (1378 hPa)REG AIR: 25 psig (1722 hPa)

ATTENTION

WARNING

WARNING

CHAUD !

!

!

HOT !

Page 23: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 2-3

Model NGA 2000 HFID

b. Pneumatic Connections

WARNING

HIGH TEMPERATURESThe Sample In, Sample Bypass Out, andBurner Exhaust Out gases and fittings canreach temperatures of up to 250°C. Makeconnections to these fittings when the ovenheater is disabled or the module is powereddown.

(See Figure 2-1) Connect inlet and outletlines for sample, burner fuel and air, ex-haust, bypass, regulated air, and purge toappropriately labeled fittings on the rearpanel. All connections are 1/4-inch fer-rule-type compression fittings except thePURGE AIR IN and OUT connections,which are 3/8-inch compression fittings. TheBurner Exhaust is a 3/8-inch connection.

It is recommended that no connection bemade to the PURGE AIR OUT port. If, how-ever, the analyzer's location requires inter-connection with a venting system, the 3/8"O.D. line should be kept as short as possi-ble, and no longer than four feet.

CAUTION

POSSIBLE INSTRUMENT DAMAGENo connection should be made to thePRESSURE RELIEF VALVE fitting. Doing somay cause damage to the instrument.

CAUTION

PURGE AIR REQUIREMENTSThe front panel LEDs of the Analyzer Mod-ule, as installed, are not visible, the usershould provide an indicator for the safetysystem as per ANSI/NFPA 496 standards.

c. Specifications

Fuel GasStandard analysis usually requiresmixed fuel, i.e., 40% ±2%) hydrogenand 60% helium. H2/He mixed fuel isrecommended over H2/N2 fuel becauseof better linearity in concentration out-put. Such blends are supplied by manygas vendors specifically for this use,with a guaranteed maximum total hy-drocarbon content of 0.5 ppm, meas-ured as methane. This specificationshould be used when obtaining thesemixtures.

NOTEThe fuel restrictor is marked with ared dot, and the sample capillary ismarked with a red or green dot formixed fuel applications.

Burner AirIn order to ensure a low backgroundsignal, burner air should contain lessthan 1 ppm maximum total hydrocarboncontent. An alternate source for burnerair and zero gas (see CALIBRATIONGASES below) is a combination dia-phragm pump and heated palladiumcatalyst. This process continuously re-moves moderate amounts of hydrocar-bons and carbon monoxide fromambient air.

Purge AirInstrument quality air or nitrogen is re-quired for the safety purge system.

Regulated AirInstrument quality air or nitrogen is re-quired. The air should contain less than2 ppm maximum total hydrocarboncontent.

Calibration GasesCalibration method and gases dependon the operating range, and the desiredmeasurement accuracy. In all methods,zero and span gases are used, and are

Page 24: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

2-4 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

introduced through the sample inlet at therear of the module.

Zero Gas - Analysis is affected by thebackground gas of the sample. Therefore, itis recommended to use zero gas with asclose to the background composition of thesample as possible. Normally less than 0.5THC as CH4 is sufficient.

Span Gas - Span gas consists of a speci-fied concentration of methane or other hy-drocarbon in a background gas such asnitrogen. Analysis is affected by the back-ground gas of the sample. Therefore, spangas containing the same background gas asthe sample is recommended. Then, thebackground effect is canceled out.

Sample GasSample gas should be nonflammable (be-low 100% of the sample's LEL). For highsensitivity applications requiring backgroundgas compensation, contact the factory.

Flow RateRequired sample flow rate is 1.0 L/min. to2.5 L/min. for a supply pressure between 5and 9 psig. Flow rate for purge gas shouldbe 16 to 18 L/min. Flow rate for regulatedair should be 2 to 4 L/min.

Pressure/FiltrationSample Pressure at the SAMPLE inletshould be within the range of 345 to 620hPa-gauge (5 to 9 psig, 7.0 psig nominal),and internally, should be between 206.7and 275.6 hPa-gauge (3.0 and 4.0 psig).

Burner Fuel Pressure should be: 3101 to3450 hPa-gauge (45 to 50 psig) for cylinderregulator, 1723 hPa-gauge (25 psig) nomi-nal for internal pressure.

Burner Air Pressure should be : 1725to 3450 hPa-gauge (25 to 50 psig) forcylinder regulator, 1035 hPa-gauge (15psig) nominal for internal pressure.

Regulated Air Pressure should be 689to 1725 hPa-gauge (10 to 25 psig) forcylinder regulator.

Purge Air Pressure should be 689 to1380 hPa-gauge (10 to 20 psig).

Nominal Internal Case Pressure isabout 0.5 to 1.0 inch of water, and thepressure relief valve is set at 1/3 psig(nominal).

CAUTION

OVER PRESSURE DAMAGENoncompliance with these specifica-tions, particularly those concerningpurge air, could cause over-pressuredamage to the module.

NOTEThe sample gas and regulated airshould be filtered for particulatesdown to 2 microns to prevent theplugging of pneumatic components.

2-5 LEAK TEST

The analyzer module is completely leaktested at the factory. The user is responsi-ble for testing for leakage at the inlet andoutlet fittings on the rear panel. The user isalso responsible for internal leak testing pe-riodically and if any internal pneumaticcomponents are adjusted or replaced (witha test procedure chosen by the user).

Page 25: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 2-5

Model NGA 2000 HFID

DIFFUSER

BULKHEADREDUCER1/4T - 1/8TBRASS

FILTERBULKHEAD1/4T - 1/4TBRASS

TUBING 1/8 ODCOPPER

MANIFOLD,SAMPLE

SAMPLECAPILLARY

SENSOR,SAMPLETEMPERATURE

BULKHEAD1/4T - 1/8TSS

RESTRICTOR,BYPASS

RUN TEE1/4T - 1/4FPTBRASS

PORT CONNECTOR1/4 TUBING 1/4 OD

VITON

PURGEPRESSURESENSOR

AB

PLUG1/4NPT

BULKHEAD3/8T BRASS

PURGEAIR IN

REDUCER3/8T - 1/4TBRASS

ELBOW1/4T - 1/4NPTBRASS

SWITCH,PURGEFLOW

REGULATOR,PURGE AIR

PLUG1/8NPT

ADAPTER1/4T - 1/8NPTBRASS

ELBOWPURGE AIRRESTRICTORBRASS

TUBING 1/4 ODVITON

REGULATEDAIR IN

CHECKVALVE1/3 PSIG

ELBOW1/4T - 1/4FPTBRASS

AIRRESTRICTOR

FUEL RESTRICTOR1/8T - 1/8T

ELBOW1/8T - 1/8MPTBRASS

TUBING 1/8 ODCOPPER

INOUT

GA

INOUT

RUN TEE1/8T - 1/8MPTBRASS

ELBOW1/8T - 1/8TBRASS

TUBING 1/8 ODCOPPER

AIR IGNITERESTRICTOR

SENSOR,BURNER AIRPRESSURE0 - 30 PSIG

TUBING 1/8 ODSS

TUBING 1/8 ODCOPPER

PRESSUREREGULATOR,BURNER AIR0 - 60 PSIG

REGULATOR,FUELPRESSURE0 - 30 PSIG

INOUT

GA

SENSOR,FUEL

PRESSURE0 - 30 PSIG

BURNERDETECTOR

ELBOW1/4T - 1/4MPTBRASS

PRESSURE SENSOR,REGULATED AIR0 - 15 PSIG

FIXED FLOWCONTROLLER,REGULATED AIR

RUN TEE1/4T - 1/4MPTBRASS

TUBING 1/4 ODCOPPER

UNION1/4T BRASS

TUBING 1/4 ODCOPPER

CONNECTOR1/16T - 1/8NPTSS

PRESSURESWITCH

SOLENOIDVALVE

OUT

BULKHEADRESTRICTOR1/4T - 1/4TSS

TUBING 1/8 ODSS

PRESSURERELIEFVALVE

HEATEDSAMPLE

IN

SAMPLEBYPASS

OUT

BURNEREXHAUST BURNER

AIR INPURGE

AIR OUTFUEL

INBULKHEAD3/8T - 1/4MPTBRASS

BULKHEADCONNECTOR1/4T - 1/8NPTSS

FUELRESTRICTOR

MALECONNECTOR1/8T - 1/8NPTSS

Figure 2-2. Flow Diagram

Page 26: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

2-6 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

2-6 ELECTRICAL CONNECTIONS

Two electrical connections are required on theAnalyzer Module: POWER and NETWORK(See Figure 2-3 and Figure 2-4). On the Ana-lyzer Module, two NETWORK connectors areavailable, either of which is appropriate for: 1)interconnection with the control module or 2)"daisy-chaining" with other NGA 2000 compo-nents. Connect Analyzer Module POWER to anexternal +24 VDC power source with a voltagetolerance of ±5% and a minimum power ratingof 120 watts.

Figure 2-3. Front Panel Electrical Connections

Figure 2-4. Front Panel Connections, Controls and Indicators

HFIDPOSSIBLEEXPLOSION HAZARDHydrogen fuel gas is used in this instrument.Do not remove fuel restrictor or operate atgreater than 50 psig. An explosion resultingin severe personal injury or deathcouldoccur.

DANGER D′EXPLOSION

POSSIBLEEXPLOSION HAZARDDo not operate flammablesample without followinginstructions in the Manual.An explosion resulting insevere personal injury ordeath could occur.

Ne pas utiliser l′echantilloninflammable avant d′avoir prisconnaissance des instructionscontenues dans le manuel. Lenon respect de ces instructionspeut entrainer une explosionprovoquant des blessure gravesou mortelles.

FUEL

BURNERAIR

250 V

POWER

OVENHEAT

FLAMEON

PURGEAIR

IGNITE

FUELOVERRIDE

24V1 +2 -3 GND

LON1

LON2

WARNING

ATTENTIONCet instrument contient du gaz hydrogene. Neretirez pas le limitateur d′decombustible, et n′operez pas au plus de 50psigCes conditions peuvent provoquer une explosion

WARNING

T 6A

!

!

!

! ATTENTIONDANGER

���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������

NETWORK1

NETWORK2

FUSE

POWER

Page 27: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 2-7

Model NGA 2000 HFID

6.0[152]

.7[18]

1.9[48]

6.8[174]

8.2[208]

.6[15]

2.8[71]

4.3[110]

1.1[28]

2.0[51]

3.6[91]

1.1[28]

FRONT VIEW

1.4[34]

22.5[571]

.3[7]

.7[17]

.2[6]

.25[6] DIA

SIDE VIEW

2.4[60]

3.0[75]

1.0[25]

3.1[78]3.3

[83]3.2[81]

1.4[35]

.9[23]

2.0[52]

1.1[27]

4.0[103]

4.2[107]

5.4[137]

7.2[183]

REAR VIEW

Dimensions:

INCHES[MM]

Figure 2-5. HFID Outline and Mounting Dimensions

Page 28: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

2-8 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

HAR

NES

S, G

LOW

PLU

G

J3

P3

J4P4J5P5

J6P6

J1

P1

J2

P2

J3

P3

P7

J7

COMPUTERANALYSIS

BOARD

J1 P1

CAB

LE A

SSEM

BLY,

FLAT

30

CO

ND

MTGSTUD

GNDSTRAP

POWERRESISTOR

SEN

SOR

ASS

EMBL

Y,R

EF T

EMP

CAB

LE A

SSEM

BLY,

OVE

N H

EATE

R

SEN

SOR

ASS

EMBL

Y,FL

AME

OU

T

SAM

PLE

RTDOVEN

RTD

P4 J

4

P18

J18

P17

J17

P5 J

5

P3 J

3

CAB

LE A

SSEM

BLY,

FLA

T 24

CO

ND

P4

J4

P5

J5P10

J10 J7 P7J1

1P1

1J8 P8

J2 P2J6

P6

J9

P9

J3

P3

P1 J1

RED BL

KR

ED BLK

BRN

RED

OR

NYE

LG

RN

BLU

POWERSUPPLYBOARD

+ - + - + -

FUEL

SO

L.

OVE

N H

EATE

R

AIR

POW

ER

OVEN

HEAT

FLAM

EON

PURG

E AI

R

HAR

NES

S

CAB

LE A

SSEM

BLY,

SEN

SOR

BD

TO

HAR

NES

SP1

0

J10

SENSORBOARD

J14

P15

J15

P16

J16

P13

J13

P11

J11

NC

SEN

SOR

,C

ASE

TEM

P

J14

P14

CAB

LE A

SSY,

PRES

SUR

ESW

ITC

H

SAFETYBOARD

CAB

LE A

SSEM

BLY,

FLA

T 20

CO

ND

CAB

LE A

SSEM

BLY,

FLAT

16

CO

ND

J4

P4

P21

23

45

67

8

CAB

LE A

SSEM

BLY,

FLA

T 3

CO

ND

P16

J16

P15

J15

2-W

AY S

OLE

NO

IDFU

EL IN

3-W

AY S

OLE

NO

IDAI

R

CAB

LE A

SSEM

BLY,

FLAT

10

CO

ND

HEA

TER

THER

MO

STAT

FAN

ASS

EMBL

Y

PWRMOD

J1J1

J6

J5+1

0VR

EF

POWERMODULE

ASSEMBLY

J2

P3 J3R

TN

JP1

J4

HARNESS,CHASSIS

J11

P11

J10

P10

J12

P12

SENSOR,AIR

PRESSURE

SENSOR,FUEL

PRESSURE

SENSOR,SAMPLE

PRESSURE

J10

P10

J9

P9

J7

P7

J8

P8

J12

P12

NC

CABLEASSEMBLY,IGNITOR

J1 P1

PREAMPBOARD

CHASSISGND

SHIE

LD

E3

R37

R38

CAB

LE A

SSEM

BLY,

TH

ERM

AL F

USE

CAB

LE A

SSEM

BLY,

CAT

HO

DE

DETECTORBLOCKASSEMBLY

THER

MAL

OVE

N S

AMPL

ESW

ITC

H

R

TD

R

TD

OVE

NH

EATE

R

CAT

HO

DE

ANO

DE

CAB

LE A

SSEM

BLY,

AN

OD

E

POLVOL

GR

Y

PUR

EI E2

SHIE

LD

J1

P1

J2

FLO

WSW

ITC

H

CASEPRESSSWITCH

FLOWSW

FLOWSW

P1

J1

P2

J2

CABLE ASSEMBLY,FLAT 3 COND

RED BL

K

GR

N

LON/POWERMODULE

P5

J5 E2 2

4VO

LTE1

RTN

E3

LED

IND

ICAT

OR

ASSE

MBL

Y

SWITCHASSEMBLY,MANUALIGNITE

J6

Figure 2-6. HFID Wiring Diagram

Page 29: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 2-9

Model NGA 2000 HFID

2-7 INSTALLATION CONSIDERATIONS CHECK-LIST

Verify the following:

• The Analyzer’s location shouldbe:

Clean

A well ventilated area

weatherproofed

Non-hazardous

Vibration-free

Have stable ambient temperature

• The gas cylinders should beequipped with a clean, hydrocar-bon free two stage regulator andshut off valve.

• All external tubing, regulators,valves, pumps, fittings, etc. areclean.

• The correct fuel type is beingused.

• The THC content of the supplygases are compatible with theanalysis range.

• The calibration backgroundgases are similar to the sample.

• The purge air out, burner ex-haust, and bypass are vented toatmospheric pressure. The pres-sure should be constant.

• The burner exhaust tube must beslanted down a minimum of 6degrees from horizontal.

• The bypass line connection mustbe slanted down a minimum of 6degrees from horizontal fordrainage of water condensation.

• If required, thermal insulationaround the bypass fitting to pre-vent condensation in the bypassrestrictor.

• If required, thermal insulation forthe sample inlet connection tominimize the cold spot.

• The heated line is at the correcttemperature.

• The sample, zero, and spangases are at the correct tem-perature.

• The heated line to have overtemperature protection.

• The sample, bypass, and burnerexhaust tubing material musthandle high temperature andhave thermal insulation to protectfrom burns.

• The purge air out tubing to be3/8 inch and less than 4 feet inlength.

• All external gas connectionshave been leak checked.

• The dead volume for externalsample and fuel lines have beenminimized.

• The stainless steel tubing usedfor the fuel and sample lines isclean.

Page 30: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

2-10 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

Page 31: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Operation 3-1

Model NGA 2000 HFID

SECTION 3OPERATION

3-1 OVERVIEW

Prior to initial startup, the user should leak testthe module as outlined in Section 2.

For the remainder of this section, AnalyzerModule interconnection with a control moduleor some interfacing component will be as-sumed operational.

3-2 STARTUP PROCEDURE

WARNING

PRESSURIZED ENCLOSUREThis enclosure shall not be opened unlessthe area is known to be free of flammablematerials or unless all devices within havebeen de-energized.

Area classification for the protected enclo-sure:

Non-Classified.

Pressurization: Type Z

Temperature Identification Number: T4A

Power shall not be restored after enclo-sure has been opened (or loss of purge)until enclosure has been purged for aminimum of 6 minutes at the minimumpressure of 689 hPa (10 psig). For safety,the Analyzer Module should be installed ina non-confined, ventilated space. Do notblock any of the rear panel outlets as theyare part of the safety system.

1. Connect supply gases and outlets to/frommodule.

2. Turn ON the purge gas only. Perform aleak check. Wait a minimum of 6 min-utes.

3. Connect the LON cable(s) and the+24VDC power cable.

4. Turn power ON.

5. Check the 4 LEDs. The power green LEDshould be illuminated. The Oven amberLED should be blinking or on. The otherLEDs should be OFF.

6. Allow the network to initialize.

7. If the user's system contains only oneAnalyzer Module, all system components,the Controller Board and the network"self-install" (bind together) during initialstartup. If the system contains more thanone Analyzer Module, the startup se-quence will interrogate the network to lo-cate and identify all components on thenetwork. The user will have to bind ap-propriate combinations of componentsafter the startup sequence. (See Section3-3.)

8. Check the general health of the analyzerby reviewing the status of the Self Tests.All “Pass” conditions should be obtained.

These test results can be found by se-lecting the following from the Main Menu:Technical Level Configuration, DiagnosticMenus, Analyzer Module Diagnostics,Self Test. All tested parameters shouldindicate "Pass."

Descriptions of the tests performed follow:

• EEPROM test - Checks the EEPROMon the Analysis Computer PCB.

• EPROM test - Checks the EPROMon the Analysis Computer PCB.

• RAM test - Checks the RAM on theAnalysis Computer PCB.

Page 32: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

3-2 Operation Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

• Power supply test - Verifies that allinternal DC voltages are within therequired tolerances.

• Network test - Checks the internalnetwork interface.

• 20 bit ADC test - Checks the 20-bitADC on the Analysis Computer PCBby sending a DC signal through thePreamp PCB and reading the signalback with the 20-bit ADC.

• 12 bit ADC test - Checks the 12-bitADC on the Analysis Computer PCBby sending a DC signal and readingthe signal back with the 12-bit ADC.

• Power Supply PCB test - Checksthe presence of the Power SupplyPCB by activating the 3-way air sole-noid.

• Safety PCB test - Checks the pres-ence of the Safety PCB by sending acommand and reading it back.

• Case temperature test - Comparesthe temperature read between thePreamp temperature sensor and thecase temperature sensor. They mustbe within 10°C of each other. This testsometimes fails if the case is opened.The sensor in the Preamp will takelonger to cool off since it is in an en-closure. Re-running the self-test afterthermal equilibrium will produce apositive result if the sensors areworking properly.

• Oven/Sample Temperature test -Compares the temperature read be-tween the sample temperature sensorand the oven temperature sensor.They must be within 50°C of eachother.

The self-test can be repeated at any timeby activating the TEST softkey in the SelfTest Results menu.

9. Set the desired oven setpoint in the rangeof 93°C to 204°C (200°F to 400°F).

10. Wait for the Purge Air green LED to illu-minate.

11. Introduce the remaining supply gases.Perform leak check. (See Section 1-5Specifications)

12. Set and verify the internal gas pressures.

InternalPressureRegulator

Typical OperatingPressures

Burner Air 965 to 1103 hPa-gauge(14 to 16 psig)

Fuel 1516 to 1723 hPa-gauge(22 to 25 psig)

Sample(non-adjustable)

206 to 290 hPa-gauge(3.0 to 4.0 psig)

Purge air of the following specificationsmust be present:

Flow: 16 to 18 L/min.

Supply Pressure: 689 to 1378 hPa-gauge (10 to 20 psig)

Noncompliance could cause damage tothe module. At the very least, the mod-ule's safety system, which requires acertain volume of purge air flowingthrough the case before allowing burnerignition, will not allow the instrument tooperate. The lowest purge airflow/pressure setting possible duringburner operation is preferable. Thus, theuser should set the external purge airpressure initially at 689 hPa-gauge (10psig). Check the Miscellaneous ControlParameters screen under Technical Di-agnostics, and note whether the PurgeGas (switch) variable is "ON." If it is"OFF," increase purge air supply by69 hPa-gauge (1 psig), and recheck thePurge Gas variable until it reads "ON."DO NOT EXCEED 1378 hPa-GAUGE (20PSIG). If the maximum setting is reached,

Page 33: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Operation 3-3

Model NGA 2000 HFID

and the Purge Gas variable does not read"ON," contact factory. If the safety systemis initiated successfully (Purge Gas vari-able is "ON"), continue with the remainderof the startup procedure.

NOTEDo not restrict the PURGE OUT portand the pressure relief valve. Theymust be vented to atmospheric pres-sure.

13. Manual or Auto-ignite the flame. TheFlame-On green LED should be illumi-nated.

Two methods of burner ignition are possi-ble: auto-ignition and manual ignition.(Note: The burner is easier to ignite whenthe oven has reached the desired setpointtemperature.)

Auto-ignition provides fuel override andthree attempted ignitions (default setting),if necessary.

Before ignition and operation, Fuel Flowmust be set to ON in "Light Flame" displayscreen under Basic Controls and oventemperature must be at least 85°C.

The manual ignition switch on the Ana-lyzer Module front panel must be ma-nipulated in the following ways:

• Press up and hold for one minute.This opens burner fuel and air sole-noids.

• Press down to ignite burner glow plugfor up to 10 seconds.

• Repeat as necessary (if fuel and airsources are farther away than 10 feet,several more attempts may be neces-sary).

• If the flame has been lit, but the flametemperature increases slowly, per-form the following steps:

After igniting flame, releaseswitch for 2 seconds

Press switch down for2 seconds

Repeat release switch andpress down steps asnecessary.

14. Allow the case and oven to warm up, ap-proximately 1 to 2 hours.

15. Verify that all 4 LEDs are illuminated.

16. Note the four LEDs on the front panel ofthe Analyzer Module. They provide nec-essary information for either ignition pro-cedure. The LEDs, when illuminated,denote the following information:

• Green - unit powered on

• Amber - continuous illumination im-plies oven has reached operatingtemp. Within ±6°C of setpoint

• Green - Flame on

• Green - purge air system intact (it hasfilled five volumes of the module inte-rior)

17. Check and re-adjust the internal pres-sures if required.

The unit is ready for operation.

3-3 BINDING

To achieve full coordination between AnalyzerModules and associated I/O Modules, theuser must bind those components together inthe System Set Up portion of the TechnicalConfiguration Menu in software.

Page 34: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

3-4 Operation Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

3-4 CALIBRATION

Calibration gas setup is as follows:

1. Set oven temperature setpoint.

2. Apply regulated air at a pressure between10 and 25 psig.

3. Allow case, oven, and sample tempera-tures to stabilize.

4. Supply heated zero gas to sample inlet.Adjust external flow controller or throttlevalve so that the sample inlet pressure isbetween 5 and 9 psig., 7 nominal.

5. Supply heated span gas to sample input.Repeat adjustment described in step 3.The reading of the sample pressure,oven, and sample temperatures should bethe same as that used during the adjust-ment of the zero gas.

See Section 2-4c for a description of themethod for choosing calibration zero and spangases.

To calibrate the Analyzer Module, introducezero gas into the SAMPLE INLET, and do thefollowing:

1. If more than one Analyzer Module is func-tional and the split Run Mode display isshown, press the DISPLAY softkey untilthe desired Analyzer's Run Mode displayis acquired.

2. Press the MENUS softkey to enter theMain Menu.

3. Verify the fuel type in the MiscellaneousControl Parameters menu (under theTechnical Configuration menu structure,select the following from the Main Menu:Diagnostic menus, Analyzer Module Di-agnostics and then Miscellaneous ControlParameters).

4. Verify the capillary type in the AnalyzerManufacturing Data menu (under theTechnical Configuration menu structure,select the following from the Main Menu:

Technical Level Configuration, ServiceMenus, Manufacturing Data, AnalyzerModule Data).

5. In the Calibration Gas List menu (from theMain Menu, select Expert Controls andSetup, Analyzer Module Setup, then Cali-bration Gas List), enter necessary data,including the Operational Sample Pres-sure and the Calibration Gas HC Re-sponse Factor. Common HC factors are:methane (CH4), 1.0, ethane (C2H6), 1.90,propane (C3H8), 3.00. These factors arenot used to compensate the reading, butare used to select the proper preampsense resistor.

6. Press HOME to re-enter the Main Menu,enter the Basic Controls menu, select de-sired range, introduce zero gas and allowits response to stabilize, press the ZEROsoftkey to enter the Analyzer Zero menu,press ZERO again and wait.

7. Press the SPAN softkey to enter theAnalyzer Span menu, introduce span gasand allow its response to stabilize, pressSPAN again and wait.

8. Repeat steps 6 and 7.

9. Press the HOME softkey to re-enter theMain Menu.

10. Press DISPLAY softkey for the Run Modedisplay.

If the user is unable to calibrate the AnalyzerModule (i.e., when ZERO or SPAN is initiated,nothing happens), several possible solutionspresent themselves. One solution relates tothe use of an incorrect gas for zeroing orspanning (e.g., using a high concentration gasto zero or a zero gas to span the AnalyzerModule). Simply recalibrating with the appro-priate gas(es) will not correct the problem be-cause the ZERO OFFSET or SPAN FACTORhas been set to an extreme value in the proc-ess.

To remedy the problem, do the following:

Page 35: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Operation 3-5

Model NGA 2000 HFID

1. Verify that correct zero and span calibra-tion gases are being used properly. If so,attempt to recalibrate according to in-structions at the beginning of Section 3-4,ensuring that the oven, sample and casetemperatures and displayed measure-ment reading are stable before initiatingthe calibration routine. If incorrect gaseswere used in the initial, failed calibration,skip to Step 2.

2. Make the following selections from theMain Menu: Expert Controls and Setup,Analyzer Module Setup, then CalibrationParameters. Disable Calibration Adjust-ment Limits.

3. Recalibrate the analyzer module accord-ing to instructions at the beginning of sec-tion 3.4, ensuring that oven, sample, andcase temperatures and displayed meas-urement reading are stable before initiat-ing the calibration routine.

4. Enable Calibration Adjustment Limits inthe Calibration Parameters menu.

NOTEIf the range selections straddle 725 ppm,CH4, the zero and span calibration for eachrange must be done separately.

3-5 ROUTINE OPERATION

After case, oven, and sample temperaturestabilization, calibration, and binding, proceedas follows:

Supply heated sample gas to SAMPLE IN-LET. Adjust external flow controller or throttlevalve so that the sample inlet pressure is be-tween 5 and 9 psig, 7 psig nominal. Thereading on the SAMPLE pressure gauge andsample and oven temperatures should be thesame as that used during adjustment of thezero and span calibration gas control.

Adjust the Range Number setting. The Ana-lyzer Module will now automatically and con-tinuously output the measured hydrocarboncontent of the sample. Output is in terms ofthe particular hydrocarbon present in the spangas. Note that readings obtained during op-

eration depend on the concentration of totalhydrocarbons in the sample.

If maximum sensitivity is required from theHFID Analyzer Module, use an optimum com-bination of settings on the FUEL, and AIRpressure regulators. Settings must be deter-mined experimentally, but the curves in Fig-ures 3-1 and 3-2 may be used as guides.

The Analyzer Module will not allow the user toincrease the upper limit of a range beyond the"maximum range" software setting. To changethe "maximum range" value, select the fol-lowing from the Main Menu: Technical Con-figuration Menu, Service Menus,Manufacturing Data, and Analyzer ModuleData. Select Maximum Range, and use thearrow keys to scroll the indicated value. Thesame applies for Minimum Range settings.

During shutdown, always turn off fuel gas first,then the air and sample gases. The flame canalso be turned off by setting Ignition SystemEnable to "Off" in the Light Flame menu (un-der Basic Controls). Subsequently, rememberto set Ignition System Enable to "On" beforeattempting to ignite the flame.

After initial startup, or startup following a pro-longed shutdown, the Analyzer Module re-quires about one day's continuous operationto stabilize. For several days afterwards, cali-brate daily. The frequency of subsequent cali-brations can be reduced as experiencedictates, consistent with the accuracy re-quirements of the particular application.

3-6 SAFETY SYSTEM

The HFID Analyzer Module safety system willnot allow ignition or continuous burner func-tion unless the following conditions are pres-ent:

• The internal purge gas pressure is at least380 hPa - gauge (5.5 psig). (Monitor dis-play message, Purge Gas Pressure inPhysical Measurements menu, for propersetting.)

• Flow rate for purge air in is at least16 L/min. and case pressure is greater

Page 36: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

3-6 Operation Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

than 0.5 inches of water. (Monitor displaymessage, Purge Gas (ON) in Miscellane-ous Control Parameters menu for correctstate. Proper sealing hardware must beused in order to obtain the required purgeair in flow rate and case pressure).

• Five case volumes of purge air have beenachieved and the three above conditionsare present. The time duration to achievea safe system is a minimum of 6 min. Theelapsed time can be monitored in theTechnical Startup Analyzer menu. (Moni-tor the Purge Air Green LED (ON), Purge

Control Status (ON), or Purge Air Alarmfor indication of the state of the safetysystem.)

As stated above, proper sealing hardware iscrucial to the successful operation of thesafety system. Therefore, a specific torquesequence (shown in Figure 3-3) must be fol-lowed when the front panel of the module isbeing reinstalled after removal. All front andrear panel screws must be installed.

NOTEDo not over-torque rear panel screws.

Page 37: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Operation 3-7

Model NGA 2000 HFID

Figure 3-1. Typical Curves of Module Response vs. Pressure Setting on Fuel Pressure Regulator

Figure 3-2. Typical Curves of Module Response vs. Pressure Setting on Air Pressure Regulator

0

0.2

0.4

0.6

0.8

1.0

RESPONSE(100 ppm CH4 fullscale)

SAMPLE: 100 ppm CH4 in N2 at 3.5 psig (241 hPa)

0 5344

10688

151032

201376

251726

302064

psighPaFUEL PRESSURE

AIR: 30 psig (2064 hPa)AIR: 20 psig (1376 hPa)

AIR: 10 psig (688 hPa)

0

0.2

0.4

0.6

0.8

1.0

RESPONSE(100 ppm CH4 fullscale)

SAMPLE: 100 ppm CH4 in N2 at 3.5 psig (241 hPa)

0 5344

10688

151032

201376

251726

302064

psighPaAIR PRESSURE

FUEL: 30 psig (2064 hPa) H2

FUEL: 25 psig (1726 hPa) H2

FUEL: 20 psig (1376 hPa) H2

Page 38: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

3-8 Operation Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

6 1 4

23 5

Torque Sequence:Screw #1, 4 to 5 turnsScrew #2, 4 to 5 turnsScrew #3, 4 to 5 turnsScrew #4, 4 to 5 turnsScrew #5, 4 to 5 turnsScrew #6, 4 to 5 turns

Repeat torque sequence untilall screws are tight.

The gasket must fill in betweenthe front panel plate and the en-closure.

DISPLAY MESSAGE DESCRIPTION TYPEAIR FET FID Air FET current WARNINGAIR PRESS FID Air Pressure WARNINGBAIR FLOW Burner Air Flow WARNINGBAROMETER System Barometer WARNINGBFUEL FLOW Burner Fuel Flow WARNINGBLOCK FET Heater current WARNINGCASE TEMP Case Temperature WARNINGCRUDE NOISE Calculated Noise WARNINGCURRENTRNGHI Current, High Range WARNINGCURRENTRNGLO Current, Low Range WARNINGCURRENTSFAC Current Range WARNINGFLAME TEMP Flame Temperature WARNINGFUEL PRES Fuel Pressure WARNINGLIN ERROR Linearizer Error WARNINGN15 VOLTS Power Supply -15V WARNINGP10 VOLTS Power Supply +10V REF WARNINGP15 VOLTS Power Supply +15V WARNINGPOL VOLTS Polarizing Volts WARNINGSAMP PRES Sample Pressure WARNINGCALRESULT Calibration Error FAILUREPURGE AIR FID Purge Air FAILURESW ERROR Software Error FAILURE

Table 3-1. HFID Analyzer Module Alarms

Figure 3-3. Front Panel Torque Sequence

Page 39: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-1

Model NGA 2000 HFID

Cover

Insulation Shield

SecuringScrew (4)

Cover/Rear Panel Secur-ing Screws (6)

ATTENTION

PURGEAIR OUT

WARNING

WARNING

ATTENTION

BURNERAIR IN

REGULATEDAIR IN

PURGEAIR IN

HEATEDSAMPLEBYPASS

HEATEDSAMPLE IN

BURNEREXHAUSTOUT

FUELIN

PRESSURERELIEFVALVE

Front Panel SecuringScrews (6)

SECTION 4 MAINTENANCE AND SERVICE

WARNING

QUALIFIED PERSONNELThis equipment should not be adjusted orrepaired by anyone except properly quali-fied service personnel.

4-1 OVERVIEW

This section contains instructions and proce-dures for troubleshooting and maintaining theHFID analyzer module. To access the inter-nal components of the analyzer module, per-form the following:

1. Remove power to the unit; shut off gasesand disconnect lines. Allow module tocool.

2. Refer to Figure 4-1. Remove the sixscrews securing the front panel, then thesix screws securing the cover to the rearpanel. Slide cover towards rear panel toremove. Loosen four screws securing in-ner insulation shield to base, lift up to re-move.

Figure 4-2 illustrates the locations of majorcomponents of the HFID.

Figure 4-1. Removal of Cover and Insulation Shield

Page 40: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-2 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

Oven Assembly659551

Fan Assembly657414

Rear Panel Assembly656954

Fixed Flow Controller Assembly657434

Front Panel Assembly656949

Electronics Assembly656943

DC Power Supply Mod-ule Assembly657413

Figure 4-2. Locations of Major Assemblies of the HFID

Page 41: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-3

Model NGA 2000 HFID

Oven Assembly659551

4-2 OVEN

Though the oven can be replaced as a com-plete unit, all internal components are field re-placeable.

a. Removal

Refer to Figure 4-3, disconnect the oven'sthree gas lines and seven electrical ca-bles, noting location of mating connectorsfor re-installation.

NOTEDO NOT remove the fittings from thegas lines on the detector.

Remove the two hex nuts securing theoven to the chassis and the twoscrews securing oven to the rearpanel. Lift oven assembly from ana-lyzer.

Figure 4-3. Removal of Oven from Chassis

Page 42: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-4 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

b. Disassembly

1. Refer to Figure 4-4A. Remove thefour retaining screws on the ovencover, remove cover.

2. Remove the two screws and one nutsecuring the outer oven front panelto the outer oven, remove frontpanel.

3. Remove the nuts and ferrules fromsample in and sample bypass out.

CAUTION

PREAMP CONNECTORSThe electrical preamp connectors are frag-ile, handle with care to avoid breaking sol-der connection.

4. Refer to Figure 4-4B. Remove thetwo nuts and washers from the elec-trical preamp connectors on the inneroven front panel. Do not unsolderthese connections.

5. Unscrew the three screws from innerfront panel and remove it.

6. Refer to Figure 4-4C. Remove thetwo hex nuts securing the burner tothe bottom of the inner oven.

7. Disconnect the sample input andoutput bypass fittings.

8. Lift the burner/thermal block up andout, while disconnecting exhaust.

Reverse procedure for installation.

Page 43: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-5

Model NGA 2000 HFID

Figure 4-4. Oven Assembly

A B

C

Inner Oven FrontPanel 657352

Preamp connectornut, washer (typ 2)

Exhaust

Oven Cover 657105 (withinsulation 657346)

Nuts and Fer-rules (2 ea.)

Inner Oven Retain-ing Screw (2) andWasher (2)

Inner Oven

Heater/CableAssembly 659643

Jam Nuts659550

Heated Bridge659555

Spring, HeatedBridge 904294

Burner657359

Insulating Washers073737

Outer Oven

Outer Oven Front Panel657356

For clarity, outer oven not shown in Figures B and C.

Page 44: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-6 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

4-3 BURNER

This section covers burner components whichcan be replaced without removal of oven fromthe chassis.

a. Temperature Sensor

1. Refer to Figure 4-4A. Remove thefour screws on the oven cover, re-move cover.

2. Refer to Figure 4-5. Remove theburner cap retainer.

3. Disconnect the temperature sensorwiring connector, note location.

4. Remove the temperature sensor.

5. Insert replacement sensor.

NOTE The leads of the temperature sensormust be leading away and down fromthe sensor to enable proper fit ofburner cap retainer.

6. Install the burner cap retainer. U-slotmust be located above temperaturesensor.

7. Re-attach wiring connector.

8. Install oven cover.

b. RTD Detector

1. Refer to Figure 4-4A. Remove thefour screws on the oven cover, re-move cover.

2. Refer to Figure 4-5. Loosen the setscrew securing RTD detector.

3. Disconnect RTD detector wiring con-nector, note location.

4. Gently grasp RTD detector wires andpull out of hole.

5. Insert replacement RTD detector intohole, snug down set screw.

6. Re-attach wiring connector.

7. Install oven cover.

c. Igniter

1. Refer to Figure 4-4A. Remove thefour screws on the oven cover, re-move cover.

2. Refer to Figure 4-5. Disconnect theigniter wiring connector, note location.

3. Using an open-end wrench, unscrewthe igniter assembly from the burner.Verify that o-ring is also removed.

4. Install replacement igniter and new o-ring. Using open-end wrench, snugdown. Do not over-tighten!

5. Re-attach wiring connector.

6. Install oven cover

d. Flameout Sensor

1. Refer to Figure 4-4A. Remove thefour screws on the oven cover, re-move cover.

2. Refer to Figure 4-5. Disconnect theflameout detector wiring connector,note location.

3. Lift up the burner cap until flameoutsensor is accessible. Using an open-end wrench, unscrew the flameoutdetector from the burner. Verify thato-ring is also removed.

4. Install replacement flameout detectorand new o-ring. Using open-endwrench, snug down. Do not over-tighten!

5. Re-attach wiring connector.

6. Install oven cover.

Page 45: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-7

Model NGA 2000 HFID

Set ScrewM3X0.5 x 10mm903125

RTD Detector657063

Igniter Assembly657205

O-Ring903736

O-Ring903737

Flameout Sensor657199

Temperature Sensor657468

Retainer, Burner Cap

The components shown can be replaced without removing burner/thermal block from oven.Oven not shown for clarity.Thermal block shown in phantom for clarity.

Burner Cap

Figure 4-5. Burner - Sensor, Flameout Detector, RTD Detector and Igniter

Page 46: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-8 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

4-4 BURNER INTERNAL COMPONENTS

WARNING

BURNER CONTAMINATIONDo not handle internal parts of the burnerwith bare hands. All tools used for main-tenance must be free of contaminates.

a. Disassembly of Burner/Thermal Block

1. Remove oven from analyzer moduleper Section 4-2a.

2. Remove burner/thermal block fromoven per Section 4-2b.

3. Refer to Figure 4-6. Disconnect sam-ple capillary nut at base of burner.

4. Remove screw securing thermal blockto burner.

5. Carefully pull burner away from ther-mal block.

Figure 4-6. Burner/Thermal Block Disassembly

Sample capillary

Sample capillaryinput

Burner

Thermal Block

Page 47: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-9

Model NGA 2000 HFID

Burner Cap

Burner CapRetainer

Gasket656931

Burner Base Burner Base

CombustionChamber

A B

O-Ring904373

b. Replacing Burner Jets

Disassemble the burner only if contami-nants are evident. Combustion productsor other contaminates which accumulateinside the burner may form electricalleakage paths between the collector andthe burner contact, resulting in noisyreadings.

If the analyzer module is to be operated atthe highest sensitivity, traces of suchcontaminates can cause erroneous read-ings. For best performance, replace theburner jet follows:

WARNING

BURNER CONTAMINATIONDo not handle internal parts of the burnerwith bare hands. All tools used for main-tenance must be free of contaminates.

1. Remove oven from analyzer moduleper Section 4-2a.

2. Remove burner/thermal block fromoven per Section 4-2b.

3. Remove thermal block from burnerper Section 4-4a.

4. Refer to Figure 4-7A. Removescrews (2) holding burner cap re-tainer, remove retainer.

5. Holding burner base, lift burner capoff of assembly, set aside, removegasket.

6. Refer to Figure 4-7B. Holding burnerbase, lift combustion chamber off, setaside.

Figure 4-7. Burner Disassembly

Page 48: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-10 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

Air Baffle (Ref)102260See Below

Sample Jet657005

Gasket102256

Jet Assembly657012

Gasket102273

Nut, Jet657016

Air Baffle

≈ .06Position with tab overthe air hole(approximately 1/16” tothe right).

End bent to raise it above the tab adistance equal to the height of the tab.

7. Refer to Figure 4-8. Lift air baffle outof burner base.

8. Remove the sample jet and gasketfrom the bottom of the burner base.

9. Remove the jet nut. Grasp jet as-sembly and lift out (along with uppergasket) of burner base. Removebottom gasket.

Figure 4-8. Burner Jets

Page 49: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-11

Model NGA 2000 HFID

c. Burner Jet Installation

WARNING

BURNER CONTAMINATIONDo not handle internal parts of the burnerwith bare hands. All tools used for main-tenance must be free of contaminates.

1. Install new lower gasket, jet assemblyand upper gasket into burner base,finger-tight jet nut.

2. Install new sample jet (with gasket)and tighten.

3. Tighten jet nut.

4. Install air baffle per Figure 4-8.

NOTEIncorrect installation of air baffle willcause ignition failure.

5. See Figure 4-7B. Insert new o-ringinto burner base.

6. Set combustion chamber into burnerbase being careful not to move airbaffle.

7. See Figure 4-7A. Insert new gasketon combustion chamber, installburner cap and burner cap retainer,torque screws to 6 inch lbs.

Page 50: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-12 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

Sample RTD657061

Cartridge Heater659643

Thermostat657065

4-5 THERMAL BLOCK

The sample RTD can be replaced with thethermal block attached to burner and mountedin oven. The cartridge heater and thermostatare also replaceable with thermal block se-cured to burner, but must be removed fromthe oven.

a. Sample RTD

1. Refer to Figure 4-4A. Remove thefour screws securing the oven cover,remove cover.

2. Disconnect the sample RTD wiringconnector, note location.

3. Refer to Figure 4-9. Remove the twoscrews securing the sample RTD, pullsample RTD out.

4. Install replacement sample RTD, se-cure with screws.

5. Attach sample RTD wiring connector.

6. Re-attach oven cover.

Figure 4-9. Thermal Block – Sample RTD, Cartridge Heater and Thermostat

Page 51: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-13

Model NGA 2000 HFID

b. Cartridge Heater

1. Remove oven from analyzer moduleper Section 4-2a.

2. Remove burner/thermal block fromoven per Section 4-2b.

3. Refer to Figure 4-9. Loosen retainingset screw, pull out cartridge heater.

4. Install replacement cartridge heater,snug down set screw.

5. Install burner/thermal block into oven.

6. Install oven into analyzer module.

c. Thermostat

1. Remove oven from analyzer moduleper Section 4-2a

2. Remove burner/thermal block fromoven per Section 4-2b.

3. Refer to Figure 4-9. Remove the tworetaining screws, pull thermostat out.

4. Install replacement thermostat, attachwith the two retaining screws.

5. Install burner/thermal block into oven.

6. Install oven into analyzer module.

d. Sample Capillary

1. Remove oven from analyzer moduleper Section 4-2a

2. Remove burner/thermal block fromoven per Section 4-2b.

3. Remove burner from thermal blockper Section 4-4a

4. Refer to Figure 4-10. Remove thetwo screws securing the capillarycover to thermal block, remove cover.

5. Remove capillary nut, remove capil-lary.

6. Install replacement capillary.

7. Insert capillary into thermal block.The capillary may require bending tofit.

8. Install cover.

Figure 4-10. Thermal Block Assembly

Capillary

Cover

Page 52: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-14 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

4-6 ELECTRONICS ASSEMBLY

The electronics assembly must be removedfrom the chassis if replacement of any of thefollowing components is necessary:

Power Supply BoardSafety BoardComputer Analysis BoardPreamp Assembly

Sensor BoardCase Temperature SensorCase Pressure Switch

1. Remove the hex nut and screw asshown in Figure 4-11.

2. Lay electronics assembly on bench,do not disconnect cables or tubing.

Figure 4-11. Removing Electronics Assembly from Chassis

Electronics Assembly656943

Hex Nut

Screw

Page 53: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-15

Model NGA 2000 HFID

Figure 4-12. Electronics Assembly – Exploded View

a. Printed Circuit Boards

When replacing a circuit board, the fol-lowing procedure is recommended:

Per Section 4-6, remove securing hard-ware from electronics assembly and layon bench.

Remove securing hardware from printedcircuit board to be replaced, do not dis-connect cable(s).

One at a time, remove the wiring con-nectors and attach to replacement board.

Mount replacement board to electronicsassembly.

Safety Board657499

Sensor Board657060

Computer Analysis Board659149

Preamp Assembly656945

Case Pressure PurgeSwitch 903690

Power Supply Board655764

Case Temperature Sensor656026

Page 54: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-16 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

b. Case Temperature Sensor

1. Per Section 4-6, remove securinghardware from electronics assemblyand lay on bench.

2. Disconnect case temperature sensorcable.

3. Remove screw securing cable clampholder to signal board.

4. Remove case temperature sensorfrom cable clamp holder.

5. Per Figure 4-13 insert replacementcase temperature sensor into cableclamp holder.

6. Re-assemble to signal board mount-ing screw.

Figure 4-13. Case Sensor Installation

Center sen-sor in cable

clamp

Page 55: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-17

Model NGA 2000 HFID

c. Case Pressure Purge Switch

1. Per Section 4-6, remove securinghardware from electronics assemblyand lay on bench.

2. Disconnect the two electrical termi-nals, note location.

3. Disconnect tube at pressure switch.

4. Remove mounting screws (2) andwashers (2).

5. Reverse procedure for installation ofreplacement switch.

Figure 4-14. Case Pressure Purge Switch Installation

The bracket does not have to be removed from the electronics assembly for thisprocedure.

Case Pressure PurgeSwitch 903690

Page 56: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-18 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

d. Preamp Assembly

1. Per Section 4-6, remove securinghardware from electronics assemblyand lay on bench.

2. Disconnect and note location of ca-bles.

3. Remove the two screws and washersfrom the top bracket and slide thepreamp assembly out.

4. Remove the lower bracket from thepreamp assembly and install on re-placement preamp assembly.

5. Slide replacement preamp assemblyinto top bracket and secure withmounting hardware.

6. Re-connect cables.

Figure 4-15. Preamp Assembly Installation

Bottom Bracket

Top Bracket

Preamp Assembly656945

Page 57: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-19

Model NGA 2000 HFID

4-7 FAN ASSEMBLY

1. Disconnect and note location of cables.

2. Remove the two hex nuts securing the fanto the chassis, lift fan assembly out.

Figure 4-16. Fan Assembly Installation

Fan Assembly657414

Page 58: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-20 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

4-8 FLOW CONTROLLER

1. Disconnect the all tubing and wiring con-nectors, note locations.

2. Remove the four hex nuts securing theflow controller assembly to the analyzermodule chassis.

Figure 4-17. Flow Controller Replacement

Flow Controller Assembly657434

Page 59: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-21

Model NGA 2000 HFID

Figure 4-18. Flow Controller Assembly

Remove and discard bracket supplied with regulator, assembly as shown.

Sample Sensor656418

Regulator 250 psi023382

FLOW

Regulated Air In

Regulated Air Out

Remove red capafter installation

Page 60: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-22 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

4-9 DC POWER SUPPLY MODULE

Disconnect and note location of all wiring toDC power supply module.

Remove the two hex nuts securing module tochassis, remove module.

Figure 4-19. DC Power Supply Module Replacement

DC Power Supply Module

Page 61: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-23

Model NGA 2000 HFID

LED Indicator Assembly657029

Purge Air FlowSwitch 656533

Burner Air Regulator902832

Burner Air Sensor656443

Air Ignite Restrictor655794

Manual IgniteToggle Switch657053

Purge Air Regulator871672

Burner Air Solenoid Valve656219

Fuel Regulator902832

Fuel Sensor656444

Air Measurement Re-strictor 656888

O-Ring011167

Toggle Switch Seal898980

O-Ring010177

O-Rings008025

Diffuser657548

LON/Power Module656560

Connectorfitting

Regulator Mounting Nut

Regulator Mounting Bracket

Plugs

Male AdapterFitting

Sensor Fittings657412

4-10 FRONT PANEL COMPONENTS

The following components are mounted to thefront panel:

• LON/Power Module• Manual Ignite Toggle Switch

• LED Indicator Assembly• Purge Air Regulator• Purge Air Flow Switch• Burner Air Solenoid Valve• Burner Air Regulator• Fuel Regulator• Burner Air Sensor• Fuel Sensor• Air Ignite Restrictor• Air Measurement Restrictor

Figure 4-20. Front Panel – Exploded View

Page 62: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-24 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

Replacing Front Panel Components1. To access components, remove the

four front panel mounting screws (twoon front, one on each side).

2. Remove the burner air regulator andfuel regulator mounting nuts.

3. Remove the purge air regulatormounting bracket screws.

The front panel can now be pulled awayfrom the chassis.

NOTEThe wiring from front panel compo-nents is still connected. Do not dis-connect unless replacing thatcomponent.

Figure 4-21. Accessing Front Panel Components

Front panel mounting screw(opposite side also)

Front panelmounting screws

Page 63: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-25

Model NGA 2000 HFID

a. LON/Power Module

1. Disconnect wiring connectors, notelocations.

2. Refer to Figure 4-20. From the out-side of the front panel, remove thetwo mounting screws.

3. Install replacement module in reverseorder.

b. LED Indicator Assembly

1. Disconnect wiring connector, note lo-cation.

2. Refer to Figure 4-20. From the insideof the front panel, remove the two hexnuts securing LED indicator assemblyto front panel. Remove indicator as-sembly and o-rings (four).

3. Inspect o-rings for damage, replace ifnecessary. Install o-rings on re-placement indicator assembly, mountassembly on mounting studs with hexnuts.

4. Re-connect wiring connector.

c. Manual Ignite Toggle Switch

1. Disconnect wiring connector, note lo-cation.

2. Refer to Figure 4-20. From the out-side of the front panel, remove thetoggle switch seal.

3. Pull the switch and o-ring out from in-side the front panel.

4. Inspect o-ring for damage, replace ifnecessary. Install o-ring on replace-ment switch, insert through frontpanel from the inside.

5. Install switch seal.

6. Re-connect wiring connector.

d. Burner Air Sensor

1. Disconnect wiring connector, note lo-cation.

2. Using an open-end wrench to hold thesensor fitting while using anotheropen-end wrench to remove the sen-sor.

3. Replace the Teflon pipe thread tapeon the treads of the sensor fitting.

4. Install sensor onto sensor fitting.

5. Re-connect wiring connector.

e. Fuel Sensor

1. Disconnect wiring connector, note lo-cation.

2. Using an open-end wrench to hold thesensor fitting while using anotheropen-end wrench to remove the sen-sor.

3. Replace the Teflon pipe thread tapeon the treads of the sensor fitting.

4. Install sensor onto sensor fitting.

5. Re-connect wiring connector.

f. Burner Air and Fuel Regulators

1. Disconnect the two tubes and thesensor fitting on the rear of the regu-lator, note locations.

2. Replace the Teflon pipe thread tapeon the threads of the sensor fitting.

3. Remove the regulator and o-ring.

4. The replacement regulator comeswith two panel mounting nuts, removeboth and discard one of them.

Page 64: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-26 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

5. Inspect o-ring for damage, replace ifnecessary. Install o-ring onto regu-lator threaded shaft.

6. Insert regulator into front panel, se-cure with mounting nut.

7. Pre-attach the three tubes.

g. Purge Air Regulator

1. Remove the regulator mounting nut,remove mounting bracket.

2. Loosen nut on tee fitting attached topurge air flow switch.

3. Disconnect tube at elbow, removeregulator.

4. Remove the two plugs, elbow andmale adapter fittings from the regula-tor.

5. Replace the Teflon pipe thread tapeon the two plugs, the elbow and themale adapter and install into replace-ment regulator.

6. Connect tube to elbow, insert maleadapter into tee fitting.

7. Install mounting bracket onto regula-tor, hand snug mounting nut.

8. Attach mounting bracket to frontpanel, tighten regulator mounting nut.

h. Purge Air Flow Switch and Diffuser

1. Unscrew flow switch from tee fitting.

2. Replace Teflon pipe thread tape ontee fitting.

3. Remove diffuser from flow switch andinstall into replacement flow switch.

4. Install replacement flow switch.

5. Install purge switch onto tee fitting.

6. Re-connect tubes.

i. Burner Air Solenoid Valve

1. Disconnect the tube at the top elbowfitting.

2. Disconnect the tube at the tee fitting,remove valve analyzer module.

3. Holding the air ignite restrictor, un-screw the solenoid valve.

4. On the solenoid valve, remove theconnector fitting.

5. Replace the Teflon pipe thread tapeon the elbow, connector and restric-tor.

6. Verify replacement solenoid valvewires (flat side of body) are exiting onthe same side as the COM port asshown in Figure 4-20. If not, use anopen-end wrench to hold the N.O. hexport while rotating body.

7. Install air ignite restrictor into N.C.port.

8. Install elbow into COM port and con-nector fitting into N.O. port.

9. Re-connect tubes.

j. Air Ignite Restrictor

1. On the burner air solenoid valve:

a. Disconnect the tube at the top el-bow fitting.

b. Disconnect tube at tee fitting.c. Lift solenoid valve from analyzer

module.d. Disconnect tube going to air ignite

restrictor.e. Remove restrictor from solenoid

valve.2. Add Teflon pipe thread tape to re-

placement restrictor, install intosolenoid.

3. Re-connect tubes to restrictor, elbowand tee fitting.

Page 65: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-27

Model NGA 2000 HFID

4-11 REAR PANEL COMPONENTS

The following components are mounted to therear panel:

• Fuel In 2-Way Solenoid Valve

• Regulated Air In Check Valve• Burner Air In Filter• Heated Sample Bypass Out Restric-

tor• Heated Sample In Restrictor

Figure 4-22. Rear Panel Components

VIEW FROM OUTSIDE ANALYZER MODULE

VIEW FROM INSIDE ANALYZER MODULE

Check Valve, Regulated Air In903728

Solenoid Valve, Fuel In656218

Filter, Burner Air In017154

Restrictor, Heated SampleBypass Out – 10 Micron619615

Restrictor, HeatedSample In – 40 Micron619616

Page 66: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

4-28 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

a. Fuel In 2-Way Solenoid Valve

1. Disconnect wiring solenoid valve wir-ing connector, note location.

2. Inside the analyzer module, discon-nect the tube going to the connectoron the “out” port of the solenoid valve.

3. On the rear of the analyzer module atthe fuel in port:

a. Disconnect the fuel in tube.

b. Remove nuts and washers.

c. Remove solenoid valve fromanalyzer module

4. Remove the fittings from the solenoidvalve and replace the Teflon pipethread tape.

5. Verify that body of replacement sole-noid valve is oriented as shown inFigure 4-22. If not, rotate till wires arein-line with “out” port.

6. Install fittings into replacement sole-noid valve, re-install in analyzer mod-ule.

b. Burner Air In Filter

1. Leaving the bulkhead fitting securedto the rear panel, remove the tubes,nuts and ferrules from the fitting.

2. Insert a clean, rigid piece of tube orrod (smaller than .25 inch diameter)

into the bulkhead fitting to force outthe filter disc.

3. Install the replacement filter in thesame manner, through the rear of thebulkhead fitting.

4. Re-connect tubes.

c. Heated Bypass Sample Out and HeatedSample In Restrictors

1. On the outside of the rear panel, dis-connect tube and remove nut.

2. Insert a small spade screwdriver intothe bulkhead and remove the restric-tor.

3. Install in reverse order.

d. Regulated Air In Check Valve

1. Disconnect tube at elbow.

2. Remove check valve from femaleconnector.

3. Remove elbow from check valve.

4. Add Teflon pipe thread tape to checkvalve threads.

5. Install elbow onto check valve.

6. Install check valve into female con-nector, verifying orientation of elbowfitting as shown in Figure 4-22.

Page 67: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Troubleshooting 5-1

Model NGA 2000 HFID

SECTION 5TROUBLESHOOTING

5-1 TROUBLESHOOTING CHECKLIST

a. Safety System

1. Verify purge supply pressure at bulk-head is between 10 and 20 psig.

2. Check case for leaks.

3. Check burner for leaks.

4. Verify purge pressure sensor tubeconnection.

5. Verify purge out port is vented to at-mospheric pressure.

6. Verify Safety PCB connector J2 isattached.

7. Check for a +24V power glitch.

8. Verify that there is no large vibrationshock.

9. Check for external leak in purge line.

10. Verify case pressure is greater than0.5” of water.

11. Check case for over-pressurization.

12. Verify the purge flow/pressure switchharness is routed away from the sole-noid valves.

13. Verify the purge timer is counting.

14. Verify purge timer jumper is correctlyinstalled.

15. Verify Internal purge pressure isgreater than 5.5 psig.

16. Verify the purge gas switch has beenactivated.

b. Ignition

1. Verify that the fuel pressure/flow iscorrect.

2. Verify that the burner air pres-sure/flow is correct.

3. Verify that the igniter is generatingenough heat.

4. Verify the burner exhaust is vented toatmosphere.

5. Verify safety system has been acti-vated.

6. Verify the manual switch is operatingcorrectly.

7. Verify auto-ignite parameters areproperly set.

8. Verify burner is properly sealed.

9. Verify quality of air supply is good.

10. Verify quality of fuel supply is good.

11. Check burner tip for damage.

12. Check air and fuel restrictor for cor-rect flow.

13. Check burner tip alignment.

14. Verify burner cone is tight.

15. Check burner air and fuel lines forleaks.

16. Verify oven temperature is greaterthan 85°C.

17. Verify the reference thermistor is100K ohm ±15% at 25°C.

Page 68: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

5-2 Troubleshooting Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

18. Verify that there is +10VDC to thereference thermistor.

c. Drift

1. Verify that the sample, burner air, andfuel supply pressures are constant.

2. Check that the tubing, regulators,pumps, fittings, and valves are cleanof hydrocarbons.

3. Verify that the oxygen level in theburner air and sample are constant.

4. Verify the THC level is correct for theburner air and fuel supply.

5. Check that the ambient temperatureis changing <10°C per hour.

6. Verify the burner is clean.

7. Verify temperature of the sample gas,case, burner, and oven has stabilized.

8. Verify the Preamp PCB is clean.

9. Verify atmospheric pressure at burnerexhaust is constant.

10. Verify purge gas pressure is constant.

11. Verify burner has been on and stabi-lized.

12. Check for gas leaks.

d. Noise

1. Check that the burner exhaust is freefrom water condensation.

2. Verify connection to the collector iscorrect.

3. Verify connection to the polarizingvoltage is correct.

4. Check the ambient temperature ischanging <10°C per hour.

5. Verify the +24VDC is clean andgrounded properly.

6. Verify there are no strong magneticfields near.

7. Check for excessive vibration.

8. Verify burner exhaust is vented to aconstant atmospheric pressure.

9. Verify bypass line is vented to a con-stant atmospheric pressure.

10. Verify purge out port vented to a con-stant atmospheric pressure.

11. Verify the collector wires are routedaway from the heater.

12. Verify the collector wires are cleanand not damaged.

Page 69: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Replacement Parts 6-1

Model NGA 2000 HFID

SECTION 6REPLACEMENT PARTS

WARNINGPARTS INTEGRITY

Tampering with or unauthorized substitution of components may adversely affect safety of this product.Use only factory-approved components for repair.

6-1 MATRIX

Each analyzer is configured per the customer sales order. Below is the HFID sales matrix which lists thevarious configurations available.

To identify the configuration of an analyzer, locate the analyzer name-rating plate. The 12-position salesmatrix identifier number appears on the analyzer name-rating plate.

HFID Heated Flame Ionization Detection Analyzer Module

Code Software Version01 Standard02 2.3 Version Software99 Special

Code Configuration IdentifierA1 Mixed Fuel, 4 Selectable Ranges: 0-10 to 0-10,000 ppm CH4A2 Mixed Fuel, 4 Selectable Ranges: 0-100 to 0-10,000 ppm CH4H1 Mixed Fuel, 4 Selectable Ranges: 0-100 ppm to 0-5% CH499 Special Calibrated Ranges

Code Cable Selection00 NoneA1 Standard (3 ft LON and Pwr AM to Platform)B1 System (10 ft LON and Pwr AM to 30A PS)

Code Special Requirements00 NoneG1 Customer Option99 Special

HFID 01 A1 A1 00 Example

Page 70: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

6-2 Replacement Parts Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

6-2 GENERAL

813344 Fuse, 6A903107 Fuse, Thermal Cutoff 72° (2 Required - Safety and Power Supply PCB’s)657029 LED Indicator Assembly656560 LON/Power Module657413 DC Power Supply Module657053 Manual Ignite Switch Assembly657414 Fan Assembly656943 Electronics Assembly

659149 Computer Board656945 Preamp Assembly657499 Safety Board655764 Power Supply Board657060 Sensor Board656026 Case Temperature Sensor

6-3 PNEUMATICS

017154 Filter, .25 DIA x .06 -.09 THK 50-100 Microns (Burner Air)902832 Regulator 0 - 60 PSI (Fuel and Burner Air)657434 Fixed Flow Controller Assembly

023382 Regulator 250 psi656418 Sample Sensor

871672 Purge Air Regulator655794 Air Ignite Restrictor656888 Air Measurement Restrictor656443 Burner Air Sensor656444 Fuel Sensor656418 Flow Control Sample Pressure Sensor656219 Burner Air 3-Way Solenoid Valve656218 Fuel In Solenoid Valve903690 Case Pressure Purge Switch656533 Purge Air Flow Switch903728 Regulated Air In Check Valve903647 Case Pressure Relief Valve

Page 71: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Replacement Parts 6-3

Model NGA 2000 HFID

6-4 OVEN COMPONENTS

659551 Oven Assembly657359 Burner Assembly

657205 Igniter Assembly903736 O-Ring (Igniter Assembly)657063 RTD Detector903125 Set Screw M3X0.5 x 10mm (RTD Detector)657468 Temperature Sensor657199 Flameout Sensor903737 O-Ring (Flameout Sensor)656931 Gasket904373 O-Ring102260 Air Baffle657016 Jet Nut102273 Gasket657012 Jet Assembly102256 Gasket657005 Sample Jet

659614 Thermal Block Assembly657486 Capillary, Mixed Fuel (Lo) 9.7 cc/min @ 3.5 psig657550 Capillary, Mixed Fuel (Hi) 2.5 cc/min @ 3.5 psig657061 Sample RTD659618 Heated Bypass Sample Out Restrictor Assembly – 10 Microns

659615 Restrictor, Heated Bypass Sample Out – 10 Microns659619 Heated Sample In Restrictor Assembly – 40 Microns

659616 Restrictor, Heated Sample In – 40 Microns657065 Thermostat 450°F659643 Cartridge Heater

Page 72: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

6-4 Replacement Parts Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

Page 73: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Return of Material 7-1

Model NGA 2000 HFID

SECTION 7RETURN OF MATERIAL

7-1 RETURN OF MATERIALIf factory repair of defective equipment is re-quired, proceed as follows:1. Secure a return authorization from a

Rosemount Analytical Inc. Sales Office orRepresentative before returning theequipment. Equipment must be returnedwith complete identification in accordancewith Rosemount instructions or it will notbe accepted.Rosemount CSC will provide the shippingaddress for your instrument.In no event will Rosemount be responsi-ble for equipment returned without properauthorization and identification.

2. Carefully pack the defective unit in asturdy box with sufficient shock absorbingmaterial to ensure no additional damageoccurs during shipping.

3. In a cover letter, describe completely:• The symptoms that determined the

equipment is faulty.• The environment in which the equip-

ment was operating (housing,weather, vibration, dust, etc.).

• Site from where the equipment wasremoved.

• Whether warranty or non-warrantyservice is expected.

• Complete shipping instructions for thereturn of the equipment.

4. Enclose a cover letter and purchase orderand ship the defective equipment ac-cording to instructions provided in theRosemount Return Authorization, prepaid,to the address provided by RosemountCSC.

Rosemount Analytical Inc.Process Analytical DivisionCustomer Service Center

1-800-433-6076

If warranty service is expected, the defectiveunit will be carefully inspected and tested atthe factory. If the failure was due to the condi-

tions listed in the standard Rosemount war-ranty, the defective unit will be repaired orreplaced at Rosemount’s option, and an oper-ating unit will be returned to the customer inaccordance with the shipping instructions fur-nished in the cover letter.For equipment no longer under warranty, theequipment will be repaired at the factory andreturned as directed by the purchase orderand shipping instructions.

7-2 CUSTOMER SERVICEFor order administration, replacement Parts,application assistance, on-site or factory re-pair, service or maintenance contract informa-tion, contact:

Rosemount Analytical Inc.Process Analytical DivisionCustomer Service Center

1-800-433-6076

7-3 TRAININGA comprehensive Factory Training Program ofoperator and service classes is available. Fora copy of the Current Operator and ServiceTraining Schedule contact the TechnicalServices Department at:

Rosemount Analytical Inc.Phone: 1-714-986-7600FAX: 1-714-577-8006

Page 74: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

7-2 Return of Material Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

Page 75: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-1

Model NGA 2000 HFID

SECTION 8APPENDIX A - MENU DISPLAYS

Menu: 0 ANALOP

Menu: 1 ANALSET

MENU: 2 FLOCHEK

Page 76: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-2 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 3 FLOCHEKI1

MENU: 4 ACALSET

MENU: 5 APARLST

Page 77: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-3

Model NGA 2000 HFID

MENU: 6 ANALSETI1

MENU: 7 CALLIST

MENU: 8 CALLISTI1

Page 78: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-4 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 9 ACALSETI1

MENU: 10 APARLSTI1

MENU: 11 AMMAN

Page 79: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-5

Model NGA 2000 HFID

MENU: 12 AMMANI1

MENU: 13 AMSVC

MENU: 14 AMSVCI1

Page 80: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-6 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 15 ADIAG

MENU: 16 AMPWR

MENU: 17 AM1V

Page 81: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-7

Model NGA 2000 HFID

MENU: 18 AMTEMP

MENU: 19 AMMISC

MENU: 20 AMTREND

Page 82: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-8 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 21 ADIAGI1

MENU: 22 RANGESETAM

MENU: 23 RANGESSETI1

Page 83: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-9

Model NGA 2000 HFID

MENU: 24 LINRANGE1

MENU: 25 LINRANGE2

MENU: 26 LINRANGE3

Page 84: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-10 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 27 LINRANGE4

MENU: 28 LINRANGE0

MENU: 29 AMPWRI1

Page 85: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-11

Model NGA 2000 HFID

MENU: 30 FLOCHEK1I1

MENU: 31 FILTER

MENU: 32 AM1VI1

Page 86: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-12 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 33 AMTEMPI1

MENU: 34 AM2VA

MENU: 35 PLIMITSA

Page 87: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-13

Model NGA 2000 HFID

MENU: 36 TLIMITSA

MENU: 37 AMMISCI1

MENU: 38 ANALSIMPLE

Page 88: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-14 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 39 FILTERI1

MENU: 40 LINRANGE0I1

MENU: 41 PLIMITSAI1

Page 89: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-15

Model NGA 2000 HFID

MENU: 42 CALFACTORS

MENU: 43 R1FACTORS

MENU: 44 RN2FACTORS

Page 90: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-16 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 45 RN3FACTORS

MENU: 46 RN4FACTORS

MENU: 47 AMHELPINDEX

Page 91: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-17

Model NGA 2000 HFID

MENU: 48 LINRANGE1I1

MENU: 49 CALFACTORSI1

MENU: 50 APARLST2

Page 92: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-18 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 51 APARLST4

MENU: 52 APARLST5

MENU: 53 APARLST6

Page 93: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-19

Model NGA 2000 HFID

MENU: 54 IGNITION

MENU: 55 LISTNOTES

MENU: 56 LIGHTFLAMEI1

Page 94: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-20 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 57 AUTOFLAMEI1

MENU: 58 DISPLAY

MENU: 59 MPARMS

Page 95: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-21

Model NGA 2000 HFID

MENU: 60 AMTOPINFO

MENU: 61 ANALSET2

MENU: 62 MPARMSI1

Page 96: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-22 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 63 TLIMITSAI1

MENU: 64 IGNITIONI1

MENU: 65 SELFTEST

Page 97: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-23

Model NGA 2000 HFID

MENU: 66 AMHELPINDEX2

MENU: 67 SOFT_DIAG

MENU: 68 CALI1

Page 98: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-24 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 69 AM2VC

MENU: 70 AM2VD

MENU: 71 OVENTEMP

Page 99: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-25

Model NGA 2000 HFID

MENU: 72 LINFUNCT

MENU: 73 POLYSETUP

MENU: 74 MIDPOINT1

Page 100: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-26 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 75 POLYGAS1

MENU: 76 POLYSETI1

MENU: 77 POLYGAS2

Page 101: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-27

Model NGA 2000 HFID

MENU: 78 POLYGAS3

MENU: 79 POLYGAS4

MENU: 80 POLYGAS5

Page 102: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-28 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 81 POLYGAS6

MENU: 82 POLYGAS7

MENU: 83 POLYGAS8

Page 103: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-29

Model NGA 2000 HFID

MENU: 84 POLYGAS9

MENU: 85 POLYGAS0

MENU: 86 MIDPOINT2

Page 104: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-30 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 87 MIDPOINT3

MENU: 88 MIDPOINT4

MENU: 89 LIGHTFLAME

Page 105: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-31

Model NGA 2000 HFID

MENU: 90 EXP_CAL

MENU: 91 ZEROI2

MENU: 92 EXP_CAL_DAT

Page 106: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-32 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 93 EXP_CAL_DATI

MENU: 94 UNITS

MENU: 95 UNITSI1

Page 107: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-33

Model NGA 2000 HFID

MENU: 96 POLYSETI2

MENU: 97 POLYSETI3

MENU: 98 RESET

Page 108: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-34 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 99 STORE

MENU: 100 ANALOPI1A

MENU: 101 RFHIST1A

Page 109: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-35

Model NGA 2000 HFID

MENU: 102 RFACTORSIA

MENU: 103 RFHIST2A

MENU: 104 RFHIST3A

Page 110: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-36 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 105 RFHIST4A

MENU: 106 SW_DIAGI1

MENU: 107 TWEAKI1

Page 111: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-37

Model NGA 2000 HFID

MENU: 108 ANALSETI3

MENU: 109 STOREDPVA

MENU: 110 ZEROI2A

Page 112: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-38 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 111 ZEROI1A

MENU: 112 ZERO_NOW2

MENU: 113 SPAN_NOW2

Page 113: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-39

Model NGA 2000 HFID

MENU: 114 AMMISC2

MENU: 115 MPARMS2

MENU: 116 AUTOFLAME

Page 114: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-40 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

MENU: 117 REBOOT

MENU: 118 ABOUT

MENU: 119 ABOUT1

Page 115: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-B

February 2002

Rosemount Analytical Inc. A Division of Emerson Process Management Appendix A – Menu Displays 8-41

Model NGA 2000 HFID

MENU: 120 ALARM1

MENU: 121 MANDATA

Page 116: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

8-42 Appendix A –Menu Displays Rosemount Analytical Inc. A Division of Emerson Process Management

Model NGA 2000 HFID

Page 117: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

WARRANTY

Goods and part(s) (excluding consumables) manufactured by Seller are warranted to be free fromdefects in workmanship and material under normal use and service for a period of twelve (12)months from the date of shipment by Seller. Consumables, glass electrodes, membranes, liquidjunctions, electrolyte, o-rings, etc., are warranted to be free from defects in workmanship andmaterial under normal use and service for a period of ninety (90) days from date of shipment bySeller. Goods, part(s) and consumables proven by Seller to be defective in workmanship and/ormaterial shall be replaced or repaired, free of charge, F.O.B. Seller's factory provided that thegoods, part(s) or consumables are returned to Seller's designated factory, transportation chargesprepaid, within the twelve (12) month period of warranty in the case of goods and part(s), and inthe case of consumables, within the ninety (90) day period of warranty. This warranty shall be ineffect for replacement or repaired goods, part(s) and the remaining portion of the ninety (90) daywarranty in the case of consumables. A defect in goods, part(s) and consumables of the com-mercial unit shall not operate to condemn such commercial unit when such goods, part(s) andconsumables are capable of being renewed, repaired or replaced.

The Seller shall not be liable to the Buyer, or to any other person, for the loss or damage directlyor indirectly, arising from the use of the equipment or goods, from breach of any warranty, or fromany other cause. All other warranties, expressed or implied are hereby excluded.

IN CONSIDERATION OF THE HEREIN STATED PURCHASE PRICE OF THE GOODS,SELLER GRANTS ONLY THE ABOVE STATED EXPRESS WARRANTY. NO OTHER WAR-RANTIES ARE GRANTED INCLUDING, BUT NOT LIMITED TO, EXPRESS AND IMPLIEDWARRANTIES OR MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

Limitations of Remedy. SELLER SHALL NOT BE LIABLE FOR DAMAGES CAUSED BY DE-LAY IN PERFORMANCE. THE SOLE AND EXCLUSIVE REMEDY FOR BREACH OF WAR-RANTY SHALL BE LIMITED TO REPAIR OR REPLACEMENT UNDER THE STANDARDWARRANTY CLAUSE. IN NO CASE, REGARDLESS OF THE FORM OF THE CAUSE OF AC-TION, SHALL SELLER'S LIABILITY EXCEED THE PRICE TO BUYER OF THE SPECIFICGOODS MANUFACTURED BY SELLER GIVING RISE TO THE CAUSE OF ACTION. BUYERAGREES THAT IN NO EVENT SHALL SELLER'S LIABILITY EXTEND TO INCLUDE INCIDEN-TAL OR CONSEQUENTIAL DAMAGES. CONSEQUENTIAL DAMAGES SHALL INCLUDE, BUTARE NOT LIMITED TO, LOSS OF ANTICIPATED PROFITS, LOSS OF USE, LOSS OF REVE-NUE, COST OF CAPITAL AND DAMAGE OR LOSS OF OTHER PROPERTY OR EQUIPMENT.IN NO EVENT SHALL SELLER BE OBLIGATED TO INDEMNIFY BUYER IN ANY MANNERNOR SHALL SELLER BE LIABLE FOR PROPERTY DAMAGE AND/OR THIRD PARTY CLAIMSCOVERED BY UMBRELLA INSURANCE AND/OR INDEMNITY COVERAGE PROVIDED TOBUYER, ITS ASSIGNS, AND EACH SUCCESSOR INTEREST TO THE GOODS PROVIDEDHEREUNDER.

Force Majeure. Seller shall not be liable for failure to perform due to labor strikes or acts beyondSeller's direct control.

Page 118: Heated Flame Ionization Detector Module - Spartan Controls/media/resources... · Instruction Manual 748414-B February 2002 Rosemount Analytical Inc. A Division of Emerson Process

Instruction Manual748414-BFebruary 2002

© Rosemount Analytical Inc. 2001

Emerson Process ManagementRosemount Analytical Inc.Process Analytic Division1201 N. Main St.Orrville, OH 44667-0901T (330) 682-9010F (330) 684-4434E [email protected]

ASIA - PACIFICFisher-RosemountSingapore Private Ltd.1 Pandan CrescentSingapore 128461Republic of SingaporeT 65-777-8211F 65-777-0947http://www.processanalytic.com

Fisher-Rosemount GmbH & Co.Industriestrasse 163594 HasselrothGermanyT 49-6055-884 0F 49-6055-884209

EUROPE, MIDDLE EAST, AFRICAFisher-Rosemount Ltd.Heath PlaceBognor RegisWest Sussex PO22 9SHEnglandT 44-1243-863121F 44-1243-845354

LATIN AMERICAFisher - RosemountAv. das Americas3333 sala 1004Rio de Janeiro, RJBrazil 22631-003T 55-21-2431-1882

Model NGA 2000 HFID