Page 1: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AAApril 2012 Rosemount 751

4378_revAA.fm Page 1 Monday, April 2, 2012 9:16 AM

Rosemount 751 Field Signal Indicator

Step 1: Installation

Step 2: Configuration

Product Certification

Start

End

www.rosemount.com

¢00825-0100-4377J¤

Page 2: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AA

April 2012Rosemount 751

4378_revAA.fm Page 2 Monday, April 2, 2012 9:16 AM

© 2012 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.

Rosemount Inc.8200 Market BoulevardChanhassen, MN USA 55317T (US) (800) 999-9307T (Intnl) (952) 906-8888F (952) 906 8889

Emerson Process Management GmbH & Co. OHGArgelsrieder Feld 382234 WesslingGermanyT 49 (8153) 9390F49 (8153) 939172

Emerson Process Management Asia Pacific Private Limited1 Pandan CrescentSingapore 128461T (65) 6777 8211F (65) 6777 0947/65 6777 0743

Beijing Rosemount Far East Instrument Co., LimitedNo. 6 North Street, Hepingli, Dong Cheng DistrictBeijing 100013, ChinaT (86) (10) 6428 2233F (86) (10) 6422 8586

IMPORTANT NOTICEThis installation guide provides basic guidelines for Rosemount® 751 Remote Indicator. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 751 reference manual (document number 00809-0100-4378) for more instruction. This manual is also available electronically on www.rosemount.com.

WARNINGExplosions could result in death or serious injury: Installation of this indicator in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the Rosemount 751 reference manual for any restrictions associated with a safe installation.

• In an Explosion-proof/Flameproof installation, do not remove the indicator cover when power is applied to the unit.

Electrical shock can result in death or serious injury.• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause

electrical shock.

2

Page 3: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AAApril 2012

4378_revAA.fm Page 3 Monday, April 2, 2012 9:16 AM

3

Rosemount 751

STEP 1: INSTALLATION

AssemblyThe Rosemount 751 Field Signal Indicator is comprised of the componentsshown in Figure 1. The housing may contain an analog or LCD meter. Bothmeters are independent of component parts and are completelyinterchangeable. Both meters plug into the terminal screws on the housing, asshown in Figure 1.The meter subassembly contains the components shown in Figure 2.Figure 1. Rosemount 751 Exploded View

Figure 2. Meter Exploded View

Rosemount 751

Meter Exploded View

Mounting Bolt with Washer

U-Bolt for 2-inchPipe

Housing

Optional 3/4 to 1/2-inch ConduitReducing Bushing (If Required)

Optional Mounting Bracket

TappedMounting

BossLoop Protection Diode

Field Wiring TerminalsHousing O-Ring

Terminal Screws

Meter

Bushing

Foam Spacer

Housing Cover

Washer for Retaining Strap

Mounting Screw into Housing

Retaining Straps

Configuration Buttons

Mounting Screws intoMounting Plate

Terminal Screws (2)

Mounting Plate

Meter

Bushing

Foam Spacer

Page 4: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AA

April 2012

4378_revAA.fm Page 4 Monday, April 2, 2012 9:16 AM

4

Rosemount 751Wiring DiagramsUse the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in parallel, with Rosemount transmitters. Use shielded cable for best results in electrically noisy environments.It is recommended that the 751 indicator be wired in a series configuration when the 4-20 mA transmitter does not contain a test terminal. The 751 is designed so the analog or LCD meter can be removed from the housing without impacting the integrity of the 4-20 mA loop. Removal of the entire 751 device from the series configuration will disrupt the loop.Figure 3. Rosemount 751 Series Wiring Diagrams

Series Wiring Diagrams for Rosemount 3144P Temperature transmitters andRosemount 2051, 3051C, or 3051S Pressure Transmitters

Power SupplyLoad Resistor

3144P Optional Ground

Power SupplyLoad Resistor

Optional Ground2051

4–20 mA dc Input Signal for Rosemount 3144P

4–20 dc Input Signal for Rosemount 2051

Power Supply Power SupplyLoad Resistor Load Resistor

Optional GroundOptional Ground

4–20 mA dc Input Signal for Rosemount 3051C

4–20 mA dc Input Signal for Rosemount 3051S

3051C 3051S

Page 5: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AAApril 2012 Rosemount 751

4378_revAA.fm Page 5 Monday, April 2, 2012 9:16 AM

It is recommended that the 751 indicator be wired in a parallel configuration when the 4-20 mA transmitter includes a test terminal. Utilization of the test terminal is required in a parallel configuration. Connecting the 751 indicator across the positive and negative terminals of the 4-20 mA transmitter could impact the loop.A parallel configuration will allow the removal of the 751 indicator without affecting the integrity of the 4-20 mA loop. Additionally, spare 751 indicators can be added without disrupting the loop.Figure 4. Rosemount 751 Parallel Wiring Diagrams

Parallel Wiring Diagrams for Rosemount 3144P Temperature Transmitterand Rosemount 2051, 3051C or 3051S Pressure Transmitters

Power Supply

Power Supply

Power Supply

Power Supply

4–20 dc Input Signal for Rosemount 2051

4–20 mA dc Input Signal for Rosemount 3144P

3144P

Optional GroundLoad

Resistor

Optional Ground

Load Resistor

Load Resistor

Optional Ground

Optional GroundLoad

Resistor

2051

3051C 3051S

4–20 mA dc Input Signal for Rosemount 3051C

4–20 dc Input Signal for Rosemount 3051S

751 751

751 751

5

Page 6: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AA

April 2012Rosemount 751

4378_revAA.fm Page 6 Monday, April 2, 2012 9:16 AM

STEP 2: CONFIGURATION

LCD Meter ConfigurationThe 20-segment bar graph is factory calibrated and represents 4–20 mA directly, but the end points of the LCD meter are user-definable. The meter requires a current between 4 and 20 mA in order to be scaled, but the actual value of the current is not significant.

Remove the Cover

1. Unscrew and remove the transparent housing cover from the LCD meter body.

Position the Decimal Point and Select the Meter Function2. Press the left and right configuration buttons simultaneously and release them

immediately.3. To move the decimal point to the desired location, press the left configuration button.

Note that the decimal point wraps around.4. To scroll through the mode options, press the right configuration button repeatedly until

the meter displays the desired mode (See Table 2-1).

NOTEThe LCD meter time-out is approximately 16 seconds. If you do not press the configuration buttons within 16 seconds, the indicator will revert to reading the current signal.

Store the Information5. Press both configuration buttons simultaneously for two seconds. Note that the meter

displays “- -” for approximately 7.5 seconds while the information is being stored.

Set the Display Equivalent to a 4 mA Signal6. Press the left configuration button for two seconds.7. To decrease the display numbers, press the left configuration button. To increase the

numbers, press the right configuration button. Set the numbers between –999 and 1000.8. To store the information, simultaneously press both configuration buttons for two

seconds.

WARNINGExplosions can result in death or serious injury. Do not remove the instrument cover in explosive environments when the circuit is alive.

Table 1. LCD Meter Mode OptionsOptions Relationship between Input Signal and Digital Display

L in LinearLinF Linear with five-second filterSrt Square rootSrtF Square root with five-second filterSquare root function only relates to the digital display. The bar graph output remainslinear with the current signal.Square root responseThe digital display will be proportional to the square root of the input current where 4 mA = 0 and 20 mA = 1.0, scaled per the calibration procedure. The transition point from linear to square root is at 25 percent of full scale flow.Filter response operates upon “present input” and “input received in the previous fivesecond interval” in the following manner:

Display = (0.75 previous input) + (0.25 present input)This relationship is maintained provided that the previous reading minus the presentreading is less than 25 percent of full scale.

6

Page 7: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AAApril 2012 Rosemount 751

4378_revAA.fm Page 7 Monday, April 2, 2012 9:16 AM

Set the Display Equivalent to a 20 mA Signal9. Press the right configuration button for two seconds.10.To decrease the display numbers, press the left configuration button. To increase the

numbers, press the right configuration button. Set the numbers between –999 and 9999. The sum of the 4 mA point and the span must not exceed 9999.

11. To store the information, simultaneously press both configuration buttons for two seconds. The LCD meter is now configured.

Replace the Cover12.Make sure the rubber gasket is seated properly, and thread the transparent housing

cover onto the LCD meter body.

PRODUCT CERTIFICATIONS

Approved Manufacturing LocationsRosemount Inc - Chanhassen, Minnesota USAEmerson Process Management GmbH & Co - Wessling, GermanyEmerson Process Management Asia Pacific Private Limited - SingaporeEmerson Process Management India PVT LTD - Daman, India

European Directive InformationThe EC declaration of conformity can be found on page 12 - 14. The most recent revision can be found at www.rosemount.com.

Ordinary Location Certification for FM ApprovalsAs standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM Approvals, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

Electro Magnetic Compatibility (EMC)EN 61326:2006

ATEX Directive (94/9/EC)Emerson Process Management complies with the ATEX Directive.

Hazardous Locations Certifications

North American Certifications

Factory Mutual (FM) ApprovalsE5 Certificate Number: 0T2H8.AE

Standards: FM3600-1989, FM3615-1989Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II, Division 1, Groups E, F, and G. Dust-ignition Proof Class III, Division 1Indoor and outdoor use, NEMA Type 4X

I5 Certificate Number: 0T9H2.AXStandards: FM3600-1989, FM3610-1988, FM3611-1986, FM3810-1989Intrinsically safe for Class I, Division 1, Groups A, B, C, andD; Class II, Division 1, Groups E, F, and G; Class III, Division 1.Nonincendive for Class I, Division 2, Groups A, B, C, and D.

7

Page 8: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AA

April 2012Rosemount 751

4378_revAA.fm Page 8 Monday, April 2, 2012 9:16 AM

Entity Parameters:Vmax = 40 VImax = 165 mAImax = 225 mACi = 0Li = 0

SPECIAL CONDITIONS FOR SAFE USE (X): When connected per Rosemount drawing 01151-0214 (I.S.).

K5 Combination of E5 and I5NEMA enclosure type 4X

Canadian Standards Association (CSA) Approvals

Certificate Number: 1718395E6 Explosion-Proof and Dust-Ignition Proof

Standards: C22.2 No. 25-1966, C22.2 No. 30-M1986, C22.2 No. 94-M1991, C22.2 No. 142-M1987Class I, Division 1, Groups C and D;Class II, Division 1, Groups E, F, andG; Dust-Ignition Proof for Class III, Division 1; Suitable forClass III, Division 1, Groups A, B, C, and D.CSA enclosure type 4X

I6 Intrinsically safe Standards: C22.2 No. 157-1992, C22.2 No. 213-M1987, C22.2 No. 142-M1987Class I, Division 1, Groups A, B, C, and D CSA enclosure type 4X

SPECIAL CONDITIONS FOR SAFE USE (X): When connected per Rosemount drawing 00751-0068 with approved barrier system (I.S.).

C6 CSA: Explosion-Proof; Intrinsic SafeCombination of E6 and I6

International CertificationsE7 IECEx Flameproof

Certification Number: IECEx DEK 11.0082XStandards: IEC 60079-0:2007, IEC 60079-1:2007Ex d IIC T5/T6 GbT5 (-20 °C Tamb 70 °C) T6 (-20 °C Tamb 40 °C)IP 66Vmax= 60V

SPECIAL CONDITIONS FOR SAFE USE (X): Transmitters have an NPT cable entry thread; A certified flameproof thread adaptor or cable gland must be used to maintain type of protection. Contact manufacturer for flame path dimensions. Cable glands and wiring must be suitable for greater than 80 °C.

8

Page 9: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AAApril 2012 Rosemount 751

4378_revAA.fm Page 9 Monday, April 2, 2012 9:16 AM

I7 IECEx Intrinsic safety Certification Number: IECEx BAS 11.0064XStandards: IEC 60079-0:2007-10, IEC 60079-11:2006Ex ia IIC T5/T6 Ga T5 (-60 °C Tamb 80 °C)T6 (-60 °C Tamb 40 °C)IP66Entity Parameters:Ui = 60 VIi = 200 mALi = 0Ci = 0

SPECIAL CONDITIONS FOR SAFE USE (X): The enclosure is made of aluminum and finished with a protective paint finish; care should be taken to protect it from impact or abrasion when installed in a zone 0 environment.

European Certifications

E8 ATEX FlameproofCertification number: DEKRA11ATEX0240XStandards: EN60079-0:2008, EN60079-1:2009, Ex II2G Ex dIIC T5/T6 GbT5 (-60 °C Tamb 80 °C)T6 (-60 °C Tamb 40 °C)IP66Vmax = 60V

SPECIAL CONDITIONS FOR SAFE USE (X): Transmitters have an NPT cable entry thread; A certified flameproof thread adaptor or cable gland must be used to maintain type of protection. Contact manufacturer for flame path dimensions. Cable glands and wiring must be suitable for greater than 80 °C.

I8 ATEX Intrinsic SafetyCertificate number: Baseefa03ATEX0448XStandards: EN60079-0:2009, EN60079-11:2007Ex II 1 G Ex ia IIC T5/T6 GaT5 (-60 °C Tamb 80 °C)T6 (-60 °C Tamb 40 °C)IP66Input Parameters:Ui = 60 VIi = 200 mALi = 0Ci = 0

SPECIAL CONDITIONS FOR SAFE USE (X):The enclosure is made of aluminum and finished with a protective paint finish; care should be taken to protect it from impact or abrasion when installed in a zone 0 environment.

9

Page 10: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AA

April 2012Rosemount 751

4378_revAA.fm Page 10 Monday, April 2, 2012 9:16 AM

10

N1 ATEX Type NCertificate Number: Baseefa03ATEX0454Standards: EN60079-0:2009, EN60079-15:2010Ex II3G Ex na II T6 GcT6 (-40 °C Tamb 70 °C)IP66Rated Voltage = 5 V

Brazilian ApprovalsE2 Brazil INMETRO Flameproof

Certificate number: NCC 5486.09XStandards: ABNT NBR IEC 60079-0:2008, ABNT NBR IEC 60079-1:2009Ex d IIC T6 GbIP65Input parameters:Un = 12-45 VccUmax = 60 VccIn = 4-20 mAImax = 666 mA

SPECIAL CONDITIONS FOR SAFE USE (X):

Transmitters have an NPT cable entry thread; A certified flameproof thread adaptor or cable gland must be used to maintain type of protection.

I2 Brazil INMETRO Intrinsic SafetyCertificate number: NCC 7013.10XStandards: ABNT NBR IEC 60079-0:2008, ABNT NBR IEC 60079-11:2009,ABNT NBR IEC 60079-26:2008Ex ia IIC T5/T6 GaT5 (-60 ºC Tamb 80 ºC); T6 (-60 ºC Tamb 40 ºC)Input Parameters:Ui = 60 VIi = 200 mAPi= 2.4 WLi = 0Ci = 0

SPECIAL CONDITIONS FOR SAFE USE (X):The enclosure is made of aluminum and finished with a protective paint finish; care should be taken to protect it from impact or abrasion when installed in a zone 0 environment.

K2 INMETRO: Flameproof; Intrinsic SafetyCombination of E2 and I2

Chinese Approvals

E3 China (NEPSI) FlameproofCertificate number: GY071011Standards: GB3836.1-2000, GB3836.2-2000Ex ia IIC T5/T6T6 (-20 ºC Tamb 60 ºC)

Page 11: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AAApril 2012 Rosemount 751

4378_revAA.fm Page 11 Monday, April 2, 2012 9:16 AM

SPECIAL CONDITIONS FOR SAFE USE (X):

Transmitters have an NPT cable entry thread; A certified flameproof thread adaptor or cable gland must be used to maintain type of protection. Contact manufacturer for flame path dimensions. The earth connection should be connected reliably.

I3 China (NEPSI) Intrinsic SafetyCertificate number: GY091234XStandards: GB3836.1-2000, GB3836.4-2000Ex ia IIC T5/T6T5 (-60 ºC Tamb 80 ºC); T6 (-60 ºC Tamb 70 ºC)

Input Parameters:

Ui = 60 VIi = 200 mACi = 0Li = 0

SPECIAL CONDITIONS FOR SAFE USE (X):The transmitter must be installed to minimize the risk of impact or friction with other metal surfaces.

11

Page 12: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AA

April 2012Rosemount 751

4378_revAA.fm Page 12 Monday, April 2, 2012 9:16 AM

Figure 5. 751 Declaration of Conformity

EC Declaration of Conformity No: RMD 1012 Rev. E

Vice President, Quality (signature) (function- printed)

Timothy J. Layer March 1, 2012 (name-printed) (date of issue)

We,

Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA

declare under our sole responsibility that the product,

Model 751 Field Signal Indicator manufactured by,

Rosemount Inc. 12001 Technology Drive and 8200 Market Boulevard Eden Prairie, MN 55344-3695 Chanhassen, MN 55317-9687 USA USA

to which this declaration relates, is in conformity with the provisions of the European Community Directives, including the latest amendments, as shown in the attached schedule. Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Community notified body certification, as shown in the attached schedule.

12

Page 13: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AAApril 2012 Rosemount 751

4378_revAA.fm Page 13 Monday, April 2, 2012 9:16 AM

Schedule EC Declaration of Conformity RMD 1012 Rev. E

File ID: Page 2 of 3 C:\Documents and Settings\sharrem\Local Settings\Temporary Internet Files\Content.Outlook\RJ7U20GO\751_RMD1012_E (2).doc

EMC Directive (2004/108/EC)

Harmonized Standards: EN 61326-1:2006

ATEX Directive (94/9/EC)

Baseefa03ATEX0448X Intrinsic Safety Equipment Group II Category 1 G; Ex ia IIC T5 or T6 Ga,

T5(-60°C � Ta � +80°C), T6 (-60°C � Ta � +40°C); Harmonized Standards Used:

EN60079-0:2009; EN60079-11:2007 Baseefa03ATEX0454X Type n

Equipment Group II Category 3 G; Ex nA IIC Gc T6 (-40°C � Ta � +70°C); Harmonized Standards Used:

EN60079-0:2009; EN60079-15:2010

DEKRA11ATEX0240X Flameproof Equipment Group II Category 2 G; Ex d IIC T5 or T6 Gb, T5(-20°C � Ta � +70°C), T6(-20°C � Ta � +40°C) Harmonized Standards Used:

EN60079-0:2009; EN60079-1:2007

13

Page 14: Rosemount 751 Field Signal Indicator - Spartan Controls/media/resources/... · Use the following wiring diagrams to wire the Rosemount 751 Field Signal Indicator, in series or in

Quick Installation Guide00825-0100-4378, Rev AA

April 2012Rosemount 751

4378_revAA.fm Page 14 Monday, April 2, 2012 9:16 AM

Schedule EC Declaration of Conformity RMD 1012 Rev. E

File ID: Page 3 of 3 C:\Documents and Settings\sharrem\Local Settings\Temporary Internet Files\Content.Outlook\RJ7U20GO\751_RMD1012_E (2).doc

ATEX Notified Bodies for EC Type Examination Certificate

DEKRA Certification B.V. [Notified Body Number: 0344] Utrechtseweg 310, 6812 AR Arnhem, The Netherlands Baseefa. [Notified Body Number: 1180] Rockhead Business Park Staden Lane Buxton, Derbyshire SK17 9RZ United Kingdom

ATEX Notified Body for Quality Assurance Baseefa. [Notified Body Number: 1180]

Rockhead Business Park Staden Lane Buxton, Derbyshire SK17 9RZ United Kingdom

14