Heat Pumps Are Not Boilers ACEEE – HOT WATER FORUM 2018 | Shawn Oram, PE, LEED AP Director of Engineering & Design ECOTOPE.COM MAR 2018

Upload: others

Post on 30-Mar-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

Heat Pumps Are Not Boilers

ACEEE – HOT WATER FORUM 2018 | Shawn Oram, PE, LEED AP Director of Engineering & Design

E C O T O P E . C O M

MAR

2018

Page 2: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

AGENDA

• OVERVIEW

• END GAME

• WHAT’S AVAILABLE NOW

• PROBLEMS WE ARE SEEING

• MARKET DEVELOPMENT NEEDS

• QUESTIONS

E C O T O P E . C O M 2

Page 3: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

MULTIFAMILY ENERGY END USES

3

DHW Heat, 10

Common Non-Heat,

10

Unit Non-Heat, 10

Unit Space Heat, 5

Common Space Heat,

5

2009 Multifamily EUI

(KBTU/Sf/Yr)

Breakdown By Energy

End Use Type

1/3 OF THE LOAD IS

TEMPERATURE

MAINTAINANCE

Seattle 2014 Benchmarking Data

Median EUI (kBtu/SF/yr)

Lowrise EUI = 32

Midrise EUI = 36

Highrise EUI = 51

Page 4: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

4

Optimize storage design to

use coldest water possible

HEAT PUMP WATER HEATING

E C O T O P E . C O M

“Heat Pumps Move Heat”

Page 5: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

10900

4657

3922

3500

2088

1810

1744

1430

675

124

6

6

4

4

3

3

2

1

0

R-12

R-502

R-404A

R-125

R-410A

R-22

R-407C

R-134a

R-32

R-152a

R-170

R-1234ze

R-1150

R-1234yf

R-600a

R-290

R-1270

R-744

R-717

E C O T O P E . C O M

REFRIGERANT TYPES

GWP OF SELECTED REFRIGERANTS

(Carbon Dioxide Equivalents, CO2e)

WORSE

BETTER

Variable Capacity | PHNIX,

ALTHERMA, VERSATI

Fixed Capacity| AERMEC

Fixed Capacity| MOST HPWH’s

COLMAC, AO SMITH

CO2 Variable Capacity | SANDEN,

MAYEKAWA, MITSUBISHI Eco-Cute

5

Proposed HFO replacement refrigerant

Refrigerants have 10% of the climate

forcing impact of CO2 Emissions

Page 6: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

MAGNETO-CALORIC HEAT PUMP

6

• No Refrigerant

• 20-30% Less Energy

• Quiet

• GE/Oak Ridge Pilot

• Ready for Market -2020

Page 7: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

SINGLE-PASS VS. MULTI-PASS

7

140˚

50˚

HOT WATER

STORAGEHEAT PUMP

WATER

HEATER110˚

120˚

HOT WATER

STORAGEHEAT PUMP

WATER

HEATER

Heat the water up to usable temp in a single pass.

Sanden (Inverter variable compressor)

Colmac RCC (throttling water flow)

Heat the water up 10-15 degrees per pass.

Inverter Air-to-Water (Daikin Altherma or sim. 410a)

Aermec Constant Volume 410a

Page 8: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

What’s Available Now

8

Refrigerant/Compressor Qty Single Pass Double Wall HX

R-410a Inverter Driven Variable Capacity 5

R-410a Fixed Capacity 3

R-134a Variable Capacity 1 1 1

R-134a Fixed Capacity 3

R-744 (CO2) Inverter Driven Variable

Capacity 3 3 3

Page 9: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

END GAME - CENTRAL HPWH

9

• Low GWP Refrigerant

• Variable and Fixed Capacity

• Air Source

• Plug and Play Design - Modular Setup

• Redundancy Built In

• High Performance Hot Water Distribution Design

• M&V Systems Temps, Power and Flow Meter

• Demand Response Capable

Page 10: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

Heat Pumps Aren’t Boilers

E C O T O P E . C O M

Page 11: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

What Do Gas Hot Water Boilers Do?

11

GAS HOT WATER BOILERS

• Can be Oversized

• Smart Controls

• Modulating Output

• Can Short Cycle

• Can be instantaneous heaters

• Compact Footprint

• Modular

• Plug and Play

• Don’t care about outside temp

• Incoming water temp isn’t an

issue

Problem….

They Burn Fossil Fuels

Page 12: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

Heat Pumps are Not Boilers

12

HEAT PUMPS ARE NOT BOILERS• Efficiency impacted by Air and Water Temps

• Limited Temperature Ranges

• Output temperature limited

• Different refrigerants for different applications

• Larger Hot Water Plant Footprints

• Expensive Oversize

• Require Right Sizing (Both Loads)

• Shouldn’t cycle more than 6x/Hr

• Defrost Cycles

• Complex Controls

Page 13: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

Application Issues

E C O T O P E . C O M

Page 14: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

Poor Stratification

14

Stratification is Key to System and

Heat Pump Performance and

Longevity.

Problems:

• Selecting horizontal tanks that

cannot stratify

• Storage is too small and leads to

mixing at peaks when makeup

water flows are highest.

• Poorly insulated tanks lead to

degradation of hot water temp

Page 15: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

Routing Recirculation through HW Storage

15

Risky to Route Recirc through hot

water storage with current

equipment offerings

Problems

• Recirculation Load is hard to

calculate and setup

• If primary water heat plant goes

down, your recirc line will

deplete the storage in minutes

• Recirc into storage tanks up

mixing tank and you get a big

efficiency hit at the heat pump.

HWC

CW

DHW

CW

HWC

DHW

HP

HP

HP

Page 16: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

Swap Boiler With Heat Pump - Oversized

16

Do NOT size a heat pump using a Boiler

sizing methodology.

• 2 Loads Present

• Temperature Maintenance

• Heating Hot Water

• If Heat Pump cannot modulate down to

TM load, decouple it.

• Better to have smaller stages of

primary heat pump to deal with part

load and provide redundancy.

• Err on the side of less capacity and

more storage

Page 17: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

Redundancy in Plants

17

Do Not Allow a situation where a Building

Loses the Hot Water Plant.

• Add multiple Heat Pump stages

• Ensure 100% backup electric capacity

• Install Alarms to alert maintenance

2 Primary Heat Pumps in stages

1 Backup Electric Stage

1 Primary Temperature Maintenance heat pump

1 backup Electric tanks

Page 18: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

Inefficient Hot Water Distribution

18

Problems

• Un-Insulated hot water lines will use a

factor of 6-8X more Temperature

Maintenance energy than Code

Insulated lines.

• Larger Temperature Maintenance Pit

the building owner with a higher life-

cycle cost system both equipment and

operating cost, insulation is cost

effective.

• Remote Located Heat Plants lead to

excessive losses and energy use.

• The closer the heat plant is to the

source, the less pipe UA

REDUCE

PIPING

UA

Page 19: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M

NO HEAT TRAPS INSTALLED

19

No HEAT TRAPS installed on both Cold

and Hot side of Storage

Problems:

• Runaway Heat Loss as Hot Water

migrates out of storage tanks

• Reduced Efficiency on the Heat Pump

as our precious cold water entering

heat pumps are hot.

Install Heat Traps on both Hot and Cold

Page 20: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

CASE STUDY ECOTOPE “RCC”

SYSTEM-194 UNIT

E C O T O P E . C O M

Page 21: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M 21

RCC 3.0 (Revision 5)

Page 22: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

E C O T O P E . C O M 22

RCC 3.0 M&V Data for Tuning

Page 23: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

MARKET

DEVELOPMENT NEEDS

E C O T O P E . C O M 23

Page 24: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

Circulation loop losses and reheat

sizing

Primary plant sizing (capacity &

storage) optimization

Simulation Protocol

MARKET

DEVELOPMENT

NEEDS

E C O T O P E . C O M 24

DESIGN TOOLS

Page 25: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

Double-wall heat exchangers integrated in

current heat pump offerings

5-15 Ton low-GWP refrigerant air source

heat pumps needed

Variable capacity temperature maintenance

heat pump designed to handle ~110 degree

incoming water

MARKET

DEVELOPMENT

NEEDS

E C O T O P E . C O M 25

TECHNOLOGY

Page 26: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

Performance Test of Current Equipment

Cost benefit analysis on piping insulation

levels within de-Carb Environment

Pilot projects of design innovation

MARKET NEEDS

E C O T O P E . C O M 26

RESEARCH

Page 27: Heat Pumps Are Not Boilers€¦ · NO HEAT TRAPS INSTALLED 19 No HEAT TRAPS installed on both Cold and Hot side of Storage Problems: • Runaway Heat Loss as Hot Water migrates out

SHAWN ORAM, PE

E C O T O P E . C O M

[email protected]

ecotope.com

Director of Engineering & Design

206 . 596 . 4703

QUESTIONS