heat pump water heater modeling - energy.gov · 4) hpwh sizing . new model “percent unmet...

37
NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, operated by the Alliance for Sustainable Energy LLC Heat Pump Water Heater Modeling in EnergyPlus Building America Residential Energy Efficiency Stakeholder Meeting Eric Wilson Craig Christensen March 1, 2012

Upload: others

Post on 27-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, operated by the Alliance for Sustainable Energy LLC

Heat Pump Water Heater Modeling in EnergyPlus

Building America Residential Energy Efficiency Stakeholder Meeting

Eric Wilson Craig Christensen March 1, 2012

Page 2: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

2

Modeling Issues Results Motivation

Heat Pump Water Heater Modeling…

Page 3: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

3

Gap: Existing analysis tools cannot accurately model HPWHs with reasonable runtime.

Page 4: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

4

What have we achieved so far?

Laboratory Evaluations

14 x

Field Monitoring

Page 5: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

5

Closing the Gap

Laboratory Evaluations

6 sec timestep

hourly timestep

14 x

Field Monitoring

CA

RB

Page 6: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

6

Why is modeling important?

• Performance varies: Can’t just use EF

• System interaction

o HPWH affects building heating and cooling

o Space conditions affect HPWH performance

Page 7: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

7

Modeling Goals

• Manage Risks o Accuracy o Run time o Occupant satisfaction

• Flexibility to explore the effects of:

o Tank location, volume, setpoint o Hot water use patterns

• HPWH vs. all other measures (optimization)

Page 8: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

8

Heat Pump Water Heater Modeling…

Results Motivation

1) Tank Stratification

2) Draw Profile

3) Performance Maps

4) Sizing

Modeling Issues

Page 9: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

9

1) Tank Stratification

Mixed tank

Tmains

Existing Model EnergyPlus HPWH mixed tank

Page 10: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

10

1) Tank Stratification

Mixed tank

Tmains

Existing Model EnergyPlus HPWH mixed tank

Tmains

Stratified tank

Realistic Performance Stratified tank

Page 11: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

11

1) Tank Stratification

Mixed tank

Tmains

2) warmer coil worse performance

1) Colder water supplied

Existing Model EnergyPlus HPWH mixed tank

Tmains

Stratified tank

Realistic Performance Stratified tank

Implications of using a mixed tank model…

Page 12: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

12

1) Tank Stratification

Tmains Mixed tank

Mixed tank

New Model Two tanks in Series

Tmains

Realistic Performance Stratified tank

Stratified tank

Page 13: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

13

2) Draw Profile

HPWH Power

Hot Water Use

Existing Model Smooth Draw Profile

Hourly Timestep

Page 14: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

14

2) Draw Profile Existing Model

Smooth Draw Profile Hourly Timestep

Page 15: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

15

2) Draw Profile Realistic Performance

Discrete Draw Events 6 Second Timestep

Existing Model Smooth Draw Profile

Hourly Timestep

HPWH Energy

14 MBtu/yr HPWH Energy

23 MBtu/yr

~4.5 kW

~1.0 kW

If these draw profiles are used for an annual simulation…

Page 16: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

16

2) Draw Profile Realistic Performance

Discrete Draw Events 6 Second Timestep

New Model Hourly Averaged Discrete Draws

Hourly Timestep

~4.5 kW

~1.0 kW

Page 17: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

17

2) Draw Profile Realistic Performance

Discrete Draw Events 6 Second Timestep

New Model Hourly Averaged Discrete Draws

Hourly Timestep

February9 10 11 12 13 14 15

0.00

0.02

0.04

0.06

0.08

0.10

Tota

l Hot

Wat

er F

low

Rat

e (c

fm)

Hourly Time Series

~4.5 kW

~1.0 kW

Page 18: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

18

2) Draw Profile Realistic Performance

Discrete Draw Events 6 Second Timestep

New Model Hourly Averaged Discrete Draws

Hourly Timestep

HPWH Energy

~23 MBtu/yr HPWH Energy

23 MBtu/yr

~4.5 kW (element)

~1.0 kW (heat pump)

With the new model draw profile, annual results match:

Page 19: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

19

3) Performance Maps Existing Model

Constant Performance?

Page 20: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

20

(constant 67°F, 50% RH air)

Mfgr 1 Mfgr 2

Mfgr 3

Realistic Performance Manufacturer Specific

3) Performance Maps Existing Model

Constant Performance?

Page 21: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

21

3) Performance Maps New Model

Generic Normalized Performance Map

(constant 67°F, 50% RH air)

Realistic Performance Manufacturer Specific

Mfgr 1 Mfgr 2

Mfgr 3

= 1 at rating point

Page 22: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

22

3) Performance Maps New Model

Generic Normalized Performance Map

(constant 67°F, 50% RH air)

Realistic Performance Manufacturer Specific

Mfgr 1 Mfgr 2

Mfgr 3

Page 23: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

23

3) Performance Maps New Model

Generic Normalized Performance Map

(constant 67°F, 50% RH air)

Realistic Performance Manufacturer Specific

Mfgr 1 Mfgr 2

Mfgr 3

Use rated values to get specific performance map:

Page 24: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

24

4) HPWH Sizing

• No existing method for HPWH sizing

Conventional Electric WH Sizing:

Existing Model

0 10 20 30 40 50 60 70

1 2 3 4 5

Tank

Vol

ume

(gal

)

# Bedrooms

Range = f(# baths)

Page 25: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

25

4) HPWH Sizing

• No existing method for HPWH sizing

Conventional Electric WH Sizing:

Existing Model

0 10 20 30 40 50 60 70

1 2 3 4 5

Tank

Vol

ume

(gal

)

# Bedrooms

Reduced capacity to meet DHW demand (vs. conventional WHs)

Function of: o Climate o # bedrooms o Tank Volume o Setpoint Temperature

April

Realistic Performance

Range = f(# baths)

Page 26: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

26

4) HPWH Sizing

New Model “Percent Unmet Showers”

Realistic Performance

Reduced capacity to meet DHW demand (vs. conventional WHs)

Function of: o Climate o # bedrooms o Tank Volume o Setpoint Temperature

Option Display Variable

April

Percent Unmet Showers • Function of climate, # bedrooms, tank volume, setpoint • Estimate of shower time < 110 F • Helps users select acceptable options • Sensitive to hot water use patterns so will vary from one set of occupants to the next

Page 27: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

27

Modeling Issues Results Motivation

Heat Pump Water Heater Modeling…

Page 28: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

28

Model Calibration Calibrated to TRNSYS results ±5%

12 cases: Chicago, Houston; 1, 3, 5 BR; 50, 80 gal

Page 29: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

29

Model Calibration

Daily Draw Volume (gal/day)

Dai

ly S

yste

m C

OP

Chicago, 50 gal Unfinished Basement

Page 30: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

30

Model Calibration

Daily Draw Volume (gal/day)

Dai

ly S

yste

m C

OP

Chicago, 50 gal Unfinished Basement

Page 31: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

31

Model Calibration

Daily Draw Volume (gal/day)

Dai

ly S

yste

m C

OP

Houston, 50 gal Garage

Page 32: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

32

Model Calibration

Daily Draw Volume (gal/day)

Dai

ly S

yste

m C

OP

Houston, 50 gal Garage

Page 33: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

33

BEoptE+ Modeling Results HPWH vs. Electric Resistance

With Cooling Impact (Air-Source HP)

Model: A-B Setpoint: 120-140°F Location: Conditioned, Unconditioned

Page 34: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

34

BEoptE+ Optimization Results Space Conditioning = Air-Source Heat Pump

Maximum Energy Savings Lowest Life-Cycle Cost 1 BR 3 BR 5 BR 1 BR 3 BR 5 BR

Orlando HP HP HP Elec Elec/HP Elec/HP

Austin HP HP HP Elec/HP Elec/HP Elec/HP

Sacramento HP HP HP Elec/HP Elec/HP Elec/HP

Seattle HP HP HP Elec Elec Elec

Boston HP HP HP Elec/HP Elec/HP Elec/HP

Maximum Energy Savings Lowest Life-Cycle Cost 1 BR 3 BR 5 BR 1 BR 3 BR 5 BR

Orlando Gas/HP Gas/HP Gas/HP Gas Gas Gas

Austin Gas/HP Gas/HP Gas/HP Gas Gas Gas

Sacramento Gas Gas Gas Gas Gas Gas

Seattle Gas Gas Gas Gas Gas Gas

Boston Gas Gas Gas Gas Gas Gas

Space Conditioning = Gas Furnace

(“Gas” includes: standard, premium, tankless, or tankless condensing.)

(“HPWH” includes various models/volumes, locations, and setpoints)

(state average utility rates, Nat’l avg Source/Site ratio)

Page 35: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

35

Conclusions

HPWH model for EnergyPlus/BEopt • Market Benefits:

o Integrated with existing tool o Fast o Flexible o Accurate

Page 36: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

36

Conclusions

Lessons Learned • Rated EF for HPWHs not good indicator of performance • Don’t use “smooth” BA HSP draw profile for HPWH testing • Control logic matters • Sizing HPWHs for adequate HW delivery: many factors

Remaining Issues • Better draw profiles for HPWH modeling/testing • Performance in enclosed spaces

Page 37: Heat Pump Water Heater Modeling - Energy.gov · 4) HPWH Sizing . New Model “Percent Unmet Showers” Realistic Performance . Reduced capacity to meet DHW demand (vs. conventional

For more information:

Laboratory Testing Report:

Sparn, B.; Hudon, K.; Christensen, D. (2011). Laboratory Performance Evaluation of Residential Integrated Heat Pump Water Heaters. 77 pp.; NREL Report No. TP-5500-52635.

TRNSYS Modeling Results: Maguire, J. (2011). A Parametric Analysis of Residential Water Heaters. Master’s

Thesis. Boulder, CO: University of Colorado.