457 IEC 61850 Process Bus g Multilin Digital Energy Save up to 50% in protection & control labor costs Eliminate majority of copper wiring to better utilize resources for the design, building, commissioning and maintenance of power system protection and control Robust and simple architecture for deploying IEC 61850 process bus Extremely rugged hardened switchyard interface is suitable for harsh environments without requiring specialized enclosures Built as an extension of the Universal Relay (UR) family of products, is available for a wide array of protection applications ranging from generation, to transmission and distribution systems Completely secure against cyber security threats Improves employee safety by limiting the number of high- energy signals in the control building Retrofit and greenfield installations for power generation, transmission and distribution systems Generator protection Transformer protection Transmission Line protection Bus protection Feeder protection Motor protection Capacitor bank protection Wide area network protection Distributed bay control Digital fault & sequence of event recording Substation automation Air-insulated and GIS stations Copper interfaces using MIL-STD-38999 connectors designed to prevent incorrect installation Rugged outdoor fiber optic cables delivered pre-terminated to length and includes DC power wiring No configuration required in the switchyard Rack-mounted Cross Connect Panels provide dedicated point-to-point passive connections between devices Rack-mounted Cross Connect Panels distribute DC power to switchyard devices Installation Protection and Control Supported by the Universal Relay UR family of products covering most protection applications Dual-source architecture for maximum reliability Internally wetted contacts for binary status inputs High speed trip-rated solid state relay outputs Universal DC transducer inputs for RTDs, potentiometer, DC voltage or DC milliamps Communications IEC 61850 9-2 Sampled Values IEC 61850 8-1 GOOSE 100 Base-BX bi-direction fiber optic Ethernet channels HardFiber IEC 61850 PROCESS BUS SOLUTION FEATURES APPLICATIONS KEY BENEFITS

Upload: others

Post on 12-Feb-2022

9 views

Category:

Documents


0 download

TRANSCRIPT

457

IEC

6185

0 Pr

oces

s Bu

s

g MultilinDigital Energy

• Saveupto50%inprotection&controllaborcosts• Eliminatemajorityofcopperwiringtobetterutilizeresources

forthedesign,building,commissioningandmaintenanceofpowersystemprotectionandcontrol

• RobustandsimplearchitecturefordeployingIEC61850processbus

• Extremelyruggedhardenedswitchyardinterfaceissuitableforharshenvironmentswithoutrequiringspecializedenclosures

• BuiltasanextensionoftheUniversalRelay(UR)familyofproducts,isavailableforawidearrayofprotectionapplicationsrangingfromgeneration,totransmissionanddistributionsystems

• Completelysecureagainstcybersecuritythreats• Improvesemployeesafetybylimitingthenumberofhigh-

energysignalsinthecontrolbuilding

• Retrofitandgreenfieldinstallationsforpowergeneration,transmissionanddistributionsystems

• Generatorprotection• Transformerprotection• TransmissionLineprotection• Busprotection• Feederprotection

• Motorprotection• Capacitorbankprotection• Wideareanetworkprotection• Distributedbaycontrol• Digitalfault&sequenceofeventrecording• Substationautomation• Air-insulatedandGISstations

• CopperinterfacesusingMIL-STD-38999connectorsdesignedtopreventincorrectinstallation

• Ruggedoutdoorfiberopticcablesdeliveredpre-terminatedtolengthandincludesDCpowerwiring

• Noconfigurationrequiredintheswitchyard• Rack-mountedCrossConnectPanelsprovidededicated

point-to-pointpassiveconnectionsbetweendevices• Rack-mountedCrossConnectPanelsdistributeDCpowerto

switchyarddevices

InstallationProtection and Control• SupportedbytheUniversalRelayURfamilyof

productscoveringmostprotectionapplications• Dual-sourcearchitectureformaximumreliability• Internallywettedcontactsforbinarystatusinputs• Highspeedtrip-ratedsolidstaterelayoutputs• UniversalDCtransducerinputsforRTDs,

potentiometer,DCvoltageorDCmilliamps

Communications• IEC618509-2SampledValues• IEC618508-1GOOSE• 100Base-BXbi-directionfiberopticEthernetchannels

HardFiber

IEC 61850 PROCESS BUS SOLUTION

FEATURES

APPLICATIONS

KEy BENEFITS

Save Up To 50% Of your Protection & Control Labor...

458458458

HardFiber System IEC 61850 Process Bus SolutionIE

C 61

850

Proc

ess

Bus

www.GEDigitalEnergy.com

An Industrial Revolution for Protection & ControlThe HardFiber Process Bus Systemrepresents a true breakthrough in theinstallation and ownership of protectionand control systems, by reducing theoverall labor required for substationdesign, construction, and testing. Thisinnovative solution addresses the threekey issuesdriving the labor required forprotectionandcontroldesign,constructionandtesting:

• Everysubstationisuniquemakingdesignanddraftingaone-offsolutionforeverystation

• Milesofcopperwiresneedstobepulled,splicedandterminated

• Timeconsumingtestingandtroubleshootingofthousandsofconnectionsmustbeperformedbyskilledpersonnel

The HardFiber System was designed toaddressthesechallengesandreducethe

overalllaborassociatedwiththetasksofdesigning, documenting, installing andtestingprotectionandcontrolsystems.Byspecifically targeting copperwiring andallof the labor it requires, theHardFiberSystemallowsforgreaterutilizationandoptimizationofresourceswiththeultimategoalofreducingtheTotalLifeCost(TLC)forprotection&control.

Key Benefits of the HardFiber SystemThe underlying driver for the HardFiberSystemisthereductionofTotalLifeCostsofprotectionandcontrolthroughlaborandresourceoptimization.Thisoptimizationisachieved by replacing individual, labor-intensive, individually terminatedcopperwireswithstandardizedphysicalinterfacesandopendigitalcommunications

• Reducesupto50%oflaborforprotection&control

• Replacesextensivecopperwiringwithpre-terminatedcopperandfibercables

• Reducesspecializedon-sitelaborbyshiftingspendingtoreadilyavailablematerials

• Improvesemployeesafetybyleavingpotentiallydangeroushigh-energysignalsintheswitchyard

• Reducesthechancesforoperationalmistakesmadeduringisolationandrestorationforroutinemaintenance

• BuiltontheUniversalRelay(UR)family,allowingforfasttransitionintomostprotectionandcontrolapplicationsincluding:

• Generatorprotection• Transformerprotection• TransmissionLineprotection• Busprotection• Feederprotection• MotorProtection• CapacitorBankprotection• Wide-Areanetworkprotection

+Labor

•HeadOfficeEngineeringandDrafting

•Construction&Installation

• CommissioningandTesting

• On-goingMaintenance

Materials

• Relays

•CopperCabling

•TerminalBlocks

•TestSwitches

• Misc.Materials

Traditional Substation

=

Traditional substation designs require large amounts of skilled labor to create engineering drawings, pull and terminate miles of copper cables, and test and troubleshoot thousands of connections.

Designing... Documenting... Installing... Testing...

459459459

HardFiber System IEC 61850 Process Bus Solution

IEC

6185

0 Pr

oces

s Bu

s

www.GEDigitalEnergy.com

the labor requirementsbeingtheon-sitelabor. This labor is almost exclusivelymanual, with very little opportunity ofautomationoroptimization.Theendresultisavery labor-intensiveanderror-proneprocess that adds significant time andcosttoeveryprojectandmakeslong-termmaintenance and changes difficult toimplement.

The Challenges of Copper WiringWith the introduction and progressionof microprocessor-based protectionand control devices, there has been thecontinuedintegrationofdiscretefunctionsinto a single device. This integrationhas delivered cost savings in terms ofmaterials, but the installation uses thesame labor-intensive technology datingbacktoelectromechanicalrelays.

Copperwiring is installed inasubstationto integrate the protection and controldevicesbyprovidingasetofsignalpathstomove raw information, in the formofanalogcurrentsandvoltages,representingthestatusofandcontrollingtheoperationoftheprimarypowersystem.Thesecopperwireshaveanextremelylowsignaldensity,and the installation details are highlydependentoneachspecificapplication.

The process of designing, installing andtestingallofthesecopperconnectionsisexceedinglylabor-intensive,withmostof

The HardFiber System replaces labor-intensive processes with quick installation, off-the-shelf equipment and made-to-order cables.

Materials

• Relays

•Cabling

• PatchPanel

HardFiber SubstationCUT P&C LABOR

50%+ =Labor

•HeadOfficeEngineeringandDrafting

•Construction&Installation

• CommissioningandTesting

• On-goingMaintenance

Extensive amounts of copper cables need to be distributed from each switchyard apparatus back to the control house

Many connections need to be made in each apparatus in the high voltage equipment switchyard

Thousands of terminations need to be connected and tested for each protection and control device found in the control house

460460460

HardFiber System IEC 61850 Process Bus SolutionIE

C 61

850

Proc

ess

Bus

www.GEDigitalEnergy.com

All copper wiring ends at the Brick

• Eliminate33%ofbreakerterminations

• EasyreplacementofBricksreduces maintenance

Outdoor fiber cable replaces copper wiring in trenches

• Reducecoppercablingneededby 40%

• Pre-terminatedfibercablesensure high quality

• Lowdensitycopperneeds1000sof terminations

• Manual,one-by-oneinstallationby highly skilled workers

Traditional breaker wiring

1• Outdoorcablescarrycopperwires

to control building

• Milesofcopperwirethroughoutatypical switchyard

Traditional cable trenches

2

Before

After HardFiber

2

1 1

HardFiber - Save Up To 50% On Protection & Control Labor

• Performsallmeasurementandcontrolforprimary apparatus

• Suitableforoutdoorinstallation-IP-66,-40°C to 85°C

• Error-proofcopperandfiberinstallationvia standard connectors

Brick - Hardened Switchyard Interface Outdoor Fiber Cables• Point-to-pointfibercommunicationsand

fused power supply• Cuttolength,pre-terminatedcablesrequire

no field splicing• Extremelyrugged:runincabletrays,pullthroughconduits,directbury

461461461

HardFiber System IEC 61850 Process Bus Solution

IEC

6185

0 Pr

oces

s Bu

s

www.GEDigitalEnergy.com

Fiber cross connect panels replace copper terminations

• Eliminate90%ofcontrolbuildingterminations

• Fewerhighenergysignalsimproveemployee safety

Only fiber connections at the relay via the UR IEC 61850 Process Card

• Powersystemprotectionbehavesas today

• BuiltonestablishedUniversalRelayplatform

• Thousandsofhandwiredterminations into a rack

• Labor-intensiveusingspecializedworkers

Thousands of individual copper wires from switchyard

3• Thousandsofconnectionsto

protection and control devices

• Manualwiringpronetoerrorsandextendedtesting

Labor-intensive copper wiring on relay panels

4

3 4

Cross Connect Panel• Breaksoutfibercommunicationchannels

from Bricks and devices• Mappingis‘hard-fibered’usingsimple

patch cord connections• Nofirmware,settings,ormaintenance

required

Universal Relay IEC 61850 Process Card• Communicationsinterfacebetweentherelay

and up to 8 Bricks• CommunicateswithBrickstooperateprimary

power systems apparatus• Securereal-timesystemhealthmonitoring

462462462

HardFiber System IEC 61850 Process Bus SolutionIE

C 61

850

Proc

ess

Bus

www.GEDigitalEnergy.com

What is IEC 61850 Process Bus?ProcessBus isatermusedtodescribeaprotectionandcontrol system thatusesadigitalcommunicationsarchitecturetocarryinformationbetweentheswitchyardand protection and control devices inthe control building. This informationconsists of sampled values, equipmentstatusandoutputcommands. IEC61850istheinternationalstandardthatdefinesthe specific communication protocol forProcess Bus implementations used forprotectionandcontrolapplications.

HardFiber Process Bus SystemTheHardFiberSystemisaKEMAtestedIEC61850 Process Bus Solution that allowsthe mapping of measurements madein the switchyard to protection relayslocatedinthecontrolhouseusingsecurecommunications. The HardFiber Systemaddresses the key technical and logisticchallenges affecting the labor requiredfor substation design, construction andmaintenance.Thisuniquesystemprovidesa total laborsavingsolutionandyetstilladheres to the practices used today forprotectiverelayingandcontrol.

Adheringtoexistingpractices:

• Providingacompletesystemwithallthenecessarycomponentsformeasurement,control,andprotection

• Coveringallutilitysubstationprotectionapplications

• Beingunderstoodanddeployedbythecurrentutilityworkforce

Addedbenefits:

• Reducededicatedon-sitelaborwithpre-fabricatedmaterialtoreducecosts

• Ispracticaltocommissionandmaintain

• Isasreliableasexistingprotectionandcontrolsystems

• UsesanopenIEC61850ProcessBusarchitecturethatcansupportsmulti-venderapplications

• Isscalableandcanbeintegratedintoexistingsubstationdesigns

Copper connections from apparatus are made directly to Bricks and end in the switchyard

A single fiber patch cord makes all of the connections between relays and Bricks

A single fiber optic connection replaces dozens of wires on a protection relay

The HardFiber System uses IEC 61850 to communicate measurements and commands between Bricks and relays in the control building over dedicated point-to-point fiber optic connections that avoids cyber-security issues altogether.

463463463

HardFiber System IEC 61850 Process Bus Solution

IEC

6185

0 Pr

oces

s Bu

s

www.GEDigitalEnergy.com

System ArchitectureThearchitectureoftheHardFiberSystemisdrivenbythemappingofsignalsbetweentheprimaryapparatusandtheprotectionandcontroldevices.

The measurement of field signals andrespectivemappingofthesesignals,usingthe open IEC 61850 communicationsprotocol,backtothecontrolhouseisdonethroughahardenedinterfacedevicecalledtheHardFiberBrick.

Usingmade-to-orderOutdoorFiberCablesconnecting theBrick toaCrossConnectPanel in the control houseprovides fastand error-proof installationwithout theneedforon-sitesplicingorterminating.

Keeping true to theexisting topologyoftraditional substations, each protectionand control device included in the zoneof protectionwill be connected directlyto Bricks through dedicated fiber opticconnections.

This simple, purpose-drivenarchitecturethatusestheIEC61850openstandardforcommunications,providesdedicatedpoint-to-point connections between the Brickandprotectiverelayswithoutintroducinganyissuesrelatingtodatasynchronization,settingmanagementorCyber-Security.

The HardFiber System can easily be incrementally scaled to include new equipment as stations evolve. Duplicated Bricks in the switchyard provide a drastic improvement in reliability and security over today’s technology.

Each Brick transmits measurements and accepts controls from up to 4 separate protection and control devices.

464464464

HardFiber System IEC 61850 Process Bus SolutionIE

C 61

850

Proc

ess

Bus

www.GEDigitalEnergy.com

Dedicated Digital Cores within each Brick allows for application additions and modifications without affecting other devices accepting information from the Brick

ScalabilityThe true test of any system, includinga Process Bus system, is its ability toincrementally scale up tomeet specificapplicationswithoutadverselyaffectingtheotherdevicesinthesystem.Today’sprotection and control systems arealreadynaturallyscalable.

Thechallengeforcommunication-basedprotection systems becomes makingextensions and modifications withoutdisrupting the in-serviceprotectionandcontrolsystem.

Byrecognizingthatthemappingbetweenpowersystemsignalsandprotectionandcontroldevicesisfundamentallydrivenbythetopologyoftheunderlyingsubstation,the HardFiber System is optimallypartitioned and connected to allow foradditions,modificationsandupgradestothesystem–withoutriskinginterruptionor degradation to critical in-serviceprotection.

Reliability,Dependability,SecurityThe HardFiber System provides anunprecedented level of diagnostics andself-checking,allowingcriticalprotectionandcontrolsystemstodosomethingthattheyhavenever donebefore – operatewithoutroutinemaintenance.

Internaldiagnosticsandself-testswithineach Brick monitor dozens of criticalinternal subsystems and provide thisinformation several hundred timesper second. Duplicate Bricks can beprovisionedtoacquireeach inputsignaltwice, allowing protection and controldevices to continuously crosscheckcriticalprotectionmeasurementsbeforeexecutingcommandsviafullyredundantoutputs.

WiththeHardFiberredundantarchitecture,eachprotectionandcontroldevicecanbeconfiguredtomaximizedependabilityandsecurity,addressingspecificapplicationrequirements.

The Challenge for UtilitiesModern electricity companies dealwithmany individual challenges every daywithoneof the largestbeing theabilityto address the constant inflationarypressures on both labor and materialswhilestillhavingtomanagetheirdemandforincreaseinloadbytheircustomers.

The HardFiber IEC 61850 Process BusSystemisasolutionthataddressestheseveryconcernsandprovidesutilitieswithameanstoreducethelaborassociatedwithsubstation construction and expansion,andatthesametimeusestechnologiesand methodologies familiar to existingresourcesandskillsets.

465465465

HardFiber System IEC 61850 Process Bus Solution

IEC

6185

0 Pr

oces

s Bu

s

www.GEDigitalEnergy.com

Technical SpecificationsBRICK INPUTSAC CURRENTNumberofInputs 4or8CTratedsecondary 1Aor5ANominalfrequency 50Hzor60HzRelayburden <0.2VAatratedsecondaryConversionrange 0to46×CTratingRMS

symmetricalCurrentwithstand 20msat250timesrated

1sec.at100timesratedContinuousat3timesrated

AC VOLTAGEVTratedsecondary 25.0to240.0VNumberofInputs 4or0Nominalfrequency 50Hzor60HzRelayburden <0.25VAat120V,60HzConversionrange 0to260VRMSVoltagewithstand continuousat260Vtoneutral,1

min./hrat420VtoneutralCONTACT INPUTS (18)Wettingpower Brickinternal24VDCpowersupplyExternalcontacts drycontact,drysolidstatecontactVoltagethreshold 6±1VDCSpeed RefreshedatsamplingrateCurrentDraw >2.5mAat6VDC,5mAat0VDCUNIVERSALDCINPUTS(3)MODE RTDTypes(3-wire) 100ΩPlatinum,100&120Ω

NickelSensingcurrent 2.5mARange –50to+250°CAccuracy ±2°CExternalleadresistance

25Ωmaximumperlead

MODE DCMVType differentialinputRange ±5VDCInputimpedance ≥500kΩ.Accuracy ±0.2mVDCor0.1%ofreading,

whicheverisgreaterMODE DCMACurrentinput(mADC) 0to–1,0to+1,–1to+1,0to5,0

to10,0-20,4-200to20,4to20Externalresistor 200Ω±0.2ΩConversionrange –1to+20mADCAccuracy ±0.2%of1mAor0.2%ofreading,

whicheverisgreaterMODE POTENTIOMETERRange 2kΩto20kΩSensingvoltage 5VAccuracy ±5mVdcBRICK POWER SUPPLyNominalDCvoltage 110Vto250VMin/MaxDCvoltage 88Vto300VNominalACvoltage 100to240Vat50/60HzMin/MaxACvoltage 88/264Vat25to100HzPowerconsumption <25WVOLTAGE INTERRUPTIONHold-Uptime* 0msBrickrecoverytime** 1msVoltagewithstand 2*HighestNominalVoltagefor

10ms,220Vac+20%continuouslyBRICK OUTPUTSSOLID-STATE OUTPUT RELAy (4)Operateandreleasetime

<100us

Maximumvoltage 280VDCMaximumcontinuouscurrent

5Acontinuousat+45°C, 4Acontinuousat+65°C

MakeandCarryCurrent

300ADC,0.03s,25oC30ADC,0.2s(ANSIC37.90)20ADC,1min,25oC

Breaking CapacityUL508 UtilityApp.

(AutorecloseScheme)

IndustrialApp.

Operations/Interval

5000ops/1s-On,9s-Off

5ops/ 0.2s-On, 0.2s-Off, within1minute

10000ops/ 0.2s-On 30s-Off1000ops/0.5s-On,

0.5s-Off

BreakCapability(0to250VDC)

3.2AatL/R=10ms 10AatL/R=40ms

30AatL/R=4ms

10AatL/R=40ms 30AatL/R=4ms

1.6AatL/R=20ms0.8AatL/R=40ms

LATCHING RELAy (1)Maximumvoltage 280VDCMaximumcontinuouscurrent

6A

Makeandcarryfor0.2s

30AasperANSI/IEEEC37.90

Breakingcapacity (L/R=40ms)DCVoltage DCCurrent24V 1A48V 0.5A125V 0.3A250V 0.25A

Operatetime <4msMin.numberofoperations

10,000

Controlmode Separatecloseandopencommands.Underconflictingcommands,theoutputshallopen

FORM-C RELAy (2)MaximumVoltage 280VDCMaximumcontinuouscurrent

8A

Makeandcarryfor0.2s

30AasperANSI/IEEEC37.90

Breakingcapacity (L/R=40ms)DCVoltage DCCurrent24V 1A48V 0.5A125V 0.3A250V 0.2AOperatetime <8msMin.numberofoperations

10,000

BRICK COMMUNICATIONSBricktransceiver 1310nmTX/1550nmRX,100Mb/s,

bidirectional1-Fiber50/125um,complieswithIEEE802.3100Base-BX-U

MULTI-MODE MODULEOpticaltransmitpower -14dbm~-8dbmMaximumopticalinputpower

-8dbm

Opticalreceivedsensitivity

-30dbm

Terminus SocketterminusM29504/5BRICK ENVIRONMENTALTEMPERATURE RANGESStorage -40to+85ºCContinuousOperating -40to+70ºCOTHERAltitude upto2000mInstallationCategory IIIPrating IP66,NEMA4XBRICK TyPE TESTSCold IEC60068-2-1,16hat–40ºCDryheat IEC60068-2-2,16hat+85ºCHumidity IEC60068-2-30,55ºC,>95%,

Variant1,6daysTemperature/humiditycyclic

IEC60068-2-38,-10°Cto+65°C

IPrating IEC60529,NEMA250Solarradiation IEC60068-2-9,MIL-STD-810F

Method505.4procedureIIworldwidedeployment

Vibration IEC60255-21-12Gclass2Shockandbump IEC60255-21-2class2Seismic IEC60255-21-3,ANSI/IEEEC37.98Insulation ANSI/IEEEC37.90,IEC60255-5Impulse 5kVimpulseDielectricstrength 3kVAC/1minforACinputs,

2.3kVAC/1minforothersInsulationresistance 100MΩat500VDCElectrostaticdischarge ANSI/IEEEC37.90.3,IEC

60255-22-2Class4,8kVC/15kVAFasttransient IEC60255-22-4 2.5kVat5kHz,4kVat2.5kVIEEEC37.90.1 4kVforcommonmodetestand

transversemodetestIEC60255-22-1 2.5kVforcommonmodetest,1kV

fordifferentialmodetestIEEEC37.90.1 2.5kVforcommonmodetestand

transversemodetestIEC-1000-4-12 2.5kVforcommonmodetestand

differentialmodetestSurge IEC60225-22-5,4kVforcommon

modetest,2kVfortransversemodetest

MagneticFieldImmunity

IEC61000-4-8 1000A/mfor3s,100A/mforcontinuous

IEC61000-4-9 1000A/mRadiatedimmunityIEC60255-22-3 35V/mat80/160/450/900MHzIEC60255-22-3 35V/mfrom80M~1000MHzIEC50204 35V/mat900/1890MHzIEEEC37.90.2 35V/mfrom25M~1000MHzIEC60255-22-6 35V/mfrom150k~80MHzIEC61000-4-16 30V,300V/1sfrom0~150kHzElectromagneticemission

IEC60255-25/CISPR11/22classA

BRICK PRODUCTION TESTSProductsgothroughanenvironmentaltestbaseduponanAcceptedQualityLevel(AQL)samplingprocessAPPROVALSCE CELVD2006/95/EC:EN/IEC

61010-1:2001/EN60255-52000CEEMC89/336/EEC:EN60255-262004-08

IEC 61850 COMMUNICATIONSSampledValues IEC618509-2Max.SamplingRate 128samples/cycleSVDatasetsperSVFrame

8

SVFastDataset 11Analoguevalues(TypeINT32)SVDataset DataItems Samples Per

SVFrameFast AnalogueValues:11(INT32)

StatusIndications:3x32(PackedListperIEC618508-18.135)

8

Slow AnalogueValues:6(INT16)Status Indications: 32 (PackedListperIEC618508-18.1.3.5)

1

Commands IEC618508-1CommandstoBricksentasproperlyconfiguredGOOSEmessagesasdefinedin“GEMultilinTechnicalDescriptionforInteroperability”BRICK OUTDOOR FIBER CABLESOPTICAL CHARACTERISTICSOpticalFibers 4FiberType GradedIndex,Multimode

(50/125mm)Specification MIL-PRF49291/1-01MaximumDistance 500m(1650ft)ELECTRICAL PROPERTIESPowerConductors (2)Size 1.31mm2(16AWG)VoltageRating 600VACShield Aluminium/polyestertapeDrainWire 0.33mm2(22AWG)stranded

tinnedcopperMECHANICAL PROPERTIESJacket FRLSZHpolyurethane,rodent

resistantCableO.D. 12mm(0.5in)nominalMaximumInstallationTension

1780N(400lbs)

MaximumOperatingTension

670N(150lbs)

MinimumBendRadius(Installation)

25cm(10in)

MinimumBendRadius(Operating)

12cm(5in)

CableWeight 164kg/km(110lbs/1000ft)ENVIRONMENTALStorageTemperature -40°to+85°COperatingTemperature

-40°to+85°C

BRICK COPPER CABLES ELECTRICAL PROPERTIESVoltageRating 600VConductor InformationCable Type ConductorsOutputs(CUB) 16x1.31mm2(16AWG)Inputs(CUC) 29x1.31mm2(16AWG)CC55ACInputCable(CUD-CC55)

16x3.31mm2(12AWG)

CV50ACInputCable(CUD-CV50)

8x3.31mm2(12AWG),8x1.31mm2(16AWG)

CC11ACInputCable(CUD-CC11)

16x1.31mm2(16AWG)

CV10ACInputCable(CUD-CV10)

16x1.31mm2(16AWG)

MECHANICAL PROPERTIESJacket FRPVCCableSizesCable Type Cable O.D.Outputs(CUB) 18mm(0.7in)Inputs(CUC) 25mm(1.0in)CC55ACInputCable(CUD-CC55)

23mm(0.9in)

CV50ACInputCable(CUD-CV50)

23mm(0.9in)

CC11ACInputCable(CUD-CC11)

18mm(0.7in)

CV10ACInputCable(CUD-CV10)

18mm(0.7in)

INDOOR FIBER CABLESOPTICAL PROPERTIESOpticalFibers 4FiberType GradedIndex,Multimode(50/125

mmMECHANICAL PROPERTIESJacket FRLSZHpolyurethaneCableO.D. 8mm(0.3in)nominalMaximumInstallationTension

2180N(490lbs)

MaximumOperatingTension

490N(110lbs)

MinimumBendRadius(Installation)

13cm(5in)

MinimumBendRadius(Operating)

6cm(2.5in)

CableWeight 50kg/km(34lbs/1000ft)ENVIRONMENTALStorageTemperature -40°to+85°COperatingTemperature

-40°to+85°C

MaximuminterruptiondurationforwhichBrickopera-tionisunaffected.TheBrickcomplieswithtypetestsapplicabletopowersupplyterminals

MaximumdurationbetweenapplicationofratedpowersupplyvoltageandBrickreadytoprovidefullservice.

* **

466466466

HardFiber System IEC 61850 Process Bus SolutionIE

C 61

850

Proc

ess

Bus

www.GEDigitalEnergy.com

Dimensions

Brick

467467467

HardFiber System IEC 61850 Process Bus Solution

IEC

6185

0 Pr

oces

s Bu

s

www.GEDigitalEnergy.com

Dimensions

Cross Connect Panel

Outdoor Brick Cable

Front

Back

468468468

HardFiber System IEC 61850 Process Bus SolutionIE

C 61

850

Proc

ess

Bus

www.GEDigitalEnergy.com

Ordering

Brick - 4 - HI - **** Brickbaseunit,4digitalcores,125/250VDCnominalpowersupplyCT/VTInputs CC55 5A/5A8xCTInputs CV50 5A4xCT&4xVTInputs CC11 1A/1A8xCTInputs CV10 1A4xCT&4xVTInputs

Brick

FOA - 0000 - M*** OutdoorBrickconnectioncable,fourfiberopticcorespluscopperDCsupplyCableLength 001 1meterto500meters(3feetto1650feet) - 500

FOR - 0000 - M*** Indoorrelayfibercable,fourfiberopticcoresCableLength 003 005 010 015 020 025 030 040 050

Fiber Cables

XPC - 16 - HI HardFiberCrossConnectPanel,16positions,125/250VDCDistribution

Cross Connect Panel

CUB - 0000 - M*** ContactOutputCableCableLength 002 2meters(6feet) 005 5meters(16feet) 010 10meters(32feet) 020 20meters(64feet)

Brick Copper Cables

CUC - 0000 - M*** Contact&TransducerInputCableCableLength 002 2meters(6feet) 005 5meters(16feet) 010 10meters(32feet) 020 20meters(64feet)

CUD - **** - M*** ACInputCableCT/VTInputs CC55 5A/5A8xCTInputs CV50 5A4xCT&4xVTInputs CC11 1A/1A8xCTInputs CV10 1A4xCT&4xVTInputsCableLength 002 2meters(6feet) 005 5meters(16feet) 010 10meters(32feet) 020 20meters(64feet)

071408-v1