hancess atb catalogue
DESCRIPTION
HANCESS ATB CATALOGUETRANSCRIPT
Automatic Transfer Breaker
Automatic Transfer SwitchAir Circuit Breaker Type
Applied Standard & code/Features/Interlock condition of switch systemAppearance and Operation MethodStandard Rating
Installation MethodProtection equipment of Trip RelayTrip Relay CurveSpecial Functions of ATB-CTTS(Closed Transition Transfer Switch)-ATB Transfer & Retransfer Operation with Time Delay-Operation Method for By-Pass system Built-in ATB-Application of InterlockingControl Circuit DiagramDimension of Appearance
Contents
"ATB (Automatic Transfer Breaker) " of HANCESS Co., Ltd.
ATB has been developed with mechanical and electrical interlocking system for stable electric power supply to the critical demands, such as hospital, communication & broadcasting center, computer room,power plant, main facilities for factories & buildings and others eliminating the problems of conventional ATS.
The compact and light weight designed ATB with high speed switching system and excellent breaking performance detecting over current and ground fault current protects the electric power system from the fault and abnormal current.
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
4
[ Main Features ]
• Design in according to well-known International Standard and Code
• Electric Motor Charging System
• Both sources OFF position available, Neutral Position
• Draw-out type, economical �xed type, By-pass built-in type are available
• Combined Circuit Breaker as both sources trip device(Uninterrupted By-Pass system)
• Compact & Ligh weight design, high installation e�ciency inside cubicle accordingly
• Digital OCR ( Over Current Protection Relay )
- Easy sense for load capacity, over current & earth fault current and ab-normal current
- Pre-alarm function
• AC/DC combined operating voltage
• Automatic switching time setting available employing the suitable controller
Features
Applied Standard & Code
Interlock Condition of Switch System
Open
Open* Close
* Option at CTTS Function
Close OpenOpen
* CloseClose
- IEC-60947-6-1
- EN-60947-6-1
- BS 4652 part 1
- VDE 0660
- ANS 1(27.13)
- KSC 8325
- JIS 160
- GB/T 14048.11
HANCESS ATB5
[ Appearance and Operation Method ]
Appearance & Operation Method
Caution)
In case of manual operation, if one source
put in on, the ATB must be tripped before
input the other source to avoid the electrical
accident & clash.
Ex) A Source --> Transfer B Source
- A(On) --> A(O�) --> B(On)
B Source --> Transfer A Source
- B(On) --> B(O�) --> A(On)
Manual Operation Method
• When input charging completely, the charging display shows “CHARGE”
• The Input and the Trip button is not working simultaneously because of
mechanical interlock system.
• The condition of main contact of ATB, Close or Open, is represented on
State Display.
• In order to keep the right position of Handles, the both sources should be
charged completely.
After input charging spring using handle, if input button (On) push,
it throws in. If trip button (O�) push, it trips.
Motor charging operation
• Input spring charge automatically by electric motor. After charging,
charging display shows “CHRAGE”
• When Input button push (On) manually, it throws in showing
“DISCHARGE” on Charging Display and “Close” on State Display.
• At this time, Input spring charge automatically by electric motor.
After charging, charging display shows “CHRAGE”
• When Trip button push (O�) manually, it trips showing “OPEN” on State
Display.
• At this time, the spring charge automatically by electric motor.
After charging, charging display shows “CHRAGE”
• The Both sources are not working simultaneously because of mechanical
interlock system.
• When both sources OPEN position, the both sources should be shutted
o�.
Air Circuit Break Type Automatic Transfer Switch
Items ATB-06 ATB-32
630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300Rated Current (A)
AC 1000VInsulation Level (V)
AC 690VRated Voltage (V)
50/60HzFrequency (Hz)
3P/4PNumber of Poles
OCR Setting Steps
Endurance
Rated Breaking Current(KA, Sym)[lcs]
Rated Input Current(KA, peak)[1cm]
Rated Impulse Voltage [Uimp]
Max. Electricity Breaking time [mSec]
Making Time [mSec]
Time of Motor Charging[Max. Sec]
Weight (kg, 3 pole)Fixed Type
DrawableType
Fixed Type
DrawableType
Weight (kg, 4 pole)
Dimensions (4pole)
Mechanical
Electrical
AK58AK58 AK56 AK56 AK56AK56
AK781AK781 AK341 AK341 AK341AK341
VK8
05 04
08 06
10 sec
100 105 110 120 130 140 150 160 170 200 220
110 115 120 130 140 150 160 170 180 220 240
135 142 150 162 176 190 203 216 230 270 300
150 155 162 176 190 203 216 230 243 - -
019 018 017 036 055 035 054 W
055 H
095 065 005 D
6
[ Standard Rating ]
ATB-08 ATB-10 ATB-12 ATB-16 ATB-20 ATB-25 ATB-40 ATB-50 ATB-63
1.0 - 0.9 - 0.8 - 0.7 -0.6 (5steps)
10,000 times
3,000 times
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
Fixed Type (630-6300A)
Manual Change Type
OCR / GR
ATB
Electric Powered Charge Type
ShutterPosition S/WArc Barrier
Digital Type
LED Type
AUX S/W (5a+5a)
Keying Circuit
Keying Inter Lock
Key Lock
Special Function of ATB
UVT / Voltage Trip Condenser Trip
Drawable Type (630-4000A)1. Mounting Method
2. Accessoried for Drawable Type
3. Method of Input Operation
4. Protection Tools
5. Electrical Trip Tools
6. Accessories
7. Front Panel Accessories
Air Circuit Break Type Automatic Transfer Switch
HANCESS ATB7
ATB-06 ATB-32ATB-08 ATB-10 ATB-12 ATB-16 ATB-20 ATB-25 ATB-40 ATB-50 ATB-63
[ Rating ][ Rating ]
8
[ Installation Method ]
Drawable type ATB
Fixed type ATB
Circuit breaker is �xed in distributing board.
Main circuit and control circuit are isolated and door of
wiring room can be closed.
ATB is drew from draw-out frame completely.
Main circuit is isolated and control circuit is contacted.
Test can be performed by closing the door of wiring room.
Main circuit and control circuit are contacted.
They are used at normal state.
It is composed of circuit breaker and draw-out frame. only draw of circuit breaker is possible. Draw-out cradle is �xed at distributing board.
In this type, there are three positions such as 'Connected', 'Test', and 'Isolated'. It is possible to close panel door at isolated position.
Draw-out PositionIsolated Position
Connected Position Test Position
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
HANCESS ATB9
[ Protection Device for Trip Relay ]
Appearance
Setting rated current (0.7-0.8-0.9-0.95-1.0) x In Max
(0.8-0.85-0.9-0.95-1.0) x In
If setting value is exceeded, ‘LTD’ ‘LED’ turns On.
15-30-60-120-240-480 sec
(2-3-4-6-8-10) x In
If setting value is exceeded, ‘STD’ ‘LED’ turns On.
0.05-0.1-0.2-0.3-0.4-0.5 sec
(4-6-8-10-13-16) x In
If setting value is exceeded, ‘STD’ ‘LED’ turns On.
(0.7-0.8-0.9-0.95-1.0) x lc.
If setting value is exceeded, ‘PTA’ ‘LED’ turns On.
15-30-60-120-240-480 sec
(0.1-0.2-0.3-0.4-0.5-0.6) x In
If max setting value is exceeded, ‘GFT’ ‘LED’ turns On.
0.1-0.3-0.8-1.5-3.0 sec
Setting long-time delay tripping current
Setting long-time delay tripping time
Setting short-time delay tripping time
Setting instantaneous-time delay tripping current
Setting pre-alarm current
Setting pre-alarm time
Setting ground fault current
Setting ground fault time
Setting short-time delay tripping current
LCD Display : pre fault alarm setting Value 90%, over current trip indication,
ground fault trip indication, phase balance [(Im-lav)/lav]*100lav=[la+lb+lc]/3, Im=maximum
Knob Name Mode Set-up Procedure
Air Circuit Break Type Automatic Transfer Switch
ATB 2007F
Rated Current of CT Primary Current (I ct)
Ground Fault Setting range (GFT)Pre - Trip Alarm range (PAT)Long - Time Delay Setting range (LTD)Short - Time Delay Setting range (STD)Instantaneous - Time Delay Setting range (INST)
10
[ Trip Relay Curve ]HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
CTTS (Closed Transition Transfer Switch) of ATB
Speci�cations
HANCESS ATB11
[ Special Function of ATB ]
Generally, the Circuit Breakers should be designed and installed at the front and rear of ATS in order to protect the electric equipment
from fault current, such as ground fault, short circuit and surge.
When fault and abnormal current occurs, ATB must designed and produced in order to stand at least 20 times of rated current and
3 cycles before trip.
Fg 1) when switch from Norm. source to Emergency source,
at the Closed position, transfer to emergence source.
(Test or Electric power transferring)
Fg 2) when switch from Emergency source to Norm. source,
at the Closed position, transfer to Norm. source.
Fg 3) when switch from Norm. source to Emergency source,
at the Open position, transfer to Emergence source.
(Norm. source O�)
No. of Phase & Wires
Rated voltage
Rated frequency
Rated current
Phase angle Di�erence at Switch
Frequency di�erence at switch
Voltage at switch
instantaneous after installation related time
Note
After installation and wiring connection completely, the both sources’ phase order must be con�rmed and the over current
must be considered due to the phase angle di�erence and voltage di�erence which is cause of over current.
Single Phase, Single Phase three wires, 3Phase three-wires / four wires
110V / 220V / 380V / 440V / 480V
50Hz / 60Hz
630A - 6300A
Within 10 Phase Degree
within 0.2Hz
Voltage di�erence is within 5% with normal source
within 50mSec
Fg 4) when switch from Emergency source to Norm. source,
at the Closed position, transfer to Norm. source.
(Transferring to Norm. source without any Interrupt)
Item Speci�cations
Air Circuit Break Type Automatic Transfer Switch
[ Note : If Permitted by the Utility Company ]
Operation Method for By-Pass System Built-in ATB
ATB Transfer & Retransfer Operation with Time Delay
12
[ Special Function of ATB ]
LOAD is accessed to A Source and
operated by ATB.
Input ByPass ATB to the same
power source(A Source) of ATB.
(It is safe because mechanical
and electrical interlock is built-in.)
1. Transfer ATB to operation position
(Same as draw motion)
2. When transfer from test position to
operation position.
3. ATB and ByPass ATB should be
interlocked
Normal operation1)
2)
3)
A,B Source Main circuit is accessed
and load side is isolated.
Therefore electrical operation
test is safety.
Draw of ATB (Test position)
Undraw of ATB
Draw out Main ATB.
All main circuits are isolated.
Inspect Drew out ATB after transfer
ByPass ATB.
Draw of ATB(isolated, drawable position)
ATB check & Test
In case of ATB test or uninterrupted facilities (Broadcasting station, hospital, computer room, power plant and others). ByPass Isolation switch has all characteristics that
ATB has to prevent power failure of loading side that is occurred in case of test or maintenance of general ATS add one ByPass Isolation Switch to ATS and operate it as following
�gure. It is the switch that test or repair can be performed without di�culties to loading side.
ATB
ATB
ATB
ATB
ATB
ATB
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
LOAD is accessed to B Source and
operated by ATB.
By-pass Isolation Switch function of ATB
Applications of Interlocking
HANCESS ATB13
ATB 1 + ACB 1
ATB 2 SetACB 5 Set
Air Circuit Break Type Automatic Transfer Switch
ACB1 ACB2 ACB3
ACB 3 Set
ACB1 ACB2
ACB3
ACB4 ACB5
ACB
ACB 2 Set
ACB1 ACB2
ATB 1 Set
ATB
ATB ATB
ATB
14
[ Control Circuit Diagram ]HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
01. PP, PN : OCR CONTROL SOURCE DC 110V02. M+, M- : MOTOR SOURCE DC 110V03. APC1, APC2 : “A” SIDE CLOSING04. APT, ANT : “A” SIDE TRIP05. BPC1, BPC2 : “B” SIDE CLOSING06. BPT, BNT : “B” SIDE TRIP07. A11 ~ A22 : “A” SIDE AUXILIARY CONTACTOR08. B11 ~ B22 : “B” SIDE AUXILIARY CONTACTOR09. A / L : PRE TRIP ALARM10. 51 : OVER CURRENT FAULT11. 51G : GROUND OVER CURRENT FAULT12. COM : UVR COM13. A UVR, B UVR : UNDER VOLTAGE FAULT14. C1, C2 : OCR TRIP
NOTEDC 110V OCR CONTROL
A Side Closing Coil
B Side Closing Coil
A Side Trip Coil
B Side Trip Coil
ACC
BCC
ATC
BTC
Air Circuit Break Type Automatic Transfer Switch
Auto Transfer Breaker
"A"SOURCE
"A" OFF
MANU.
LCD-H3
AUTO "A" POWER
"A" ON
"A" TIMER
ON
CONTROLLER
"B" POWER"B" TIMER
"B" ON
ON
"B" OFF
"B"SOURCE
MANUAL
AUTO
15
(Unit : mm)
Fixed Type / 630-4000 A 3P
Front View Side View Rear View
130 270
75
t
500
100
Fixed Hole
D
15 15
55061
0
60 60
C
A B
15 15
FixedHole 12
JK
LM
E F G H
A
LOAD
B
Type A B C D E F
Type G H J K L M
ATB - 16
ATB - 20
ATB - 25
ATB - 32
ATB - 40
ATB - 16
ATB - 20
ATB - 25
ATB - 32
ATB - 40
16
[ Dimension ]
225
225
225
225
225
225
225
225
225
305
450
450
450
450
530
70
70
70
90
90
125
105
105
95
105
100
120
120
130
160
100
120
120
130
160
125
105
105
95
105
162.5
162.5
162.5
162.5
159.5
120
120
120
120
123.5
120
120
120
120
123.5
134.8
134.8
132.5
132.5
132.5
( 630-1200 : 12t / 1600-2000 : 15t / 2500- 3000 : 20t / 3200-6300 : 25t )
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
(Unit : mm)
( 630-1200 : 12t / 1600-2000 : 15t / 2500- 3000 : 20t / 3200-6300 : 25t )
Fixed Type / 630-4000 A 4P
15 15
550
C
A B
15 15
FixedHole 12
130 270
75
t
500
100
Fixed Hole
D
Type A B C D E F
Type G, H J K L M N
ATB - 16
ATB - 20
ATB - 25
ATB - 32
ATB - 40
ATB - 16
ATB - 20
ATB - 25
ATB - 32
ATB - 40
JK
LM
E F G H N
N T S R
A
LOAD
B
Front View Side View Rear View
HANCESS ATB17
225
225
225
225
304
225
305
305
325
385
450
530
530
550
689
70
70
70
70
90
75
85
80
80
104
100
120
120
130
160
100
120
120
130
160
162.5
162.5
162.5
159.5
159.5
120
120
120
120
123.5
134.8
134.8
132.5
132.5
132.8
120
120
120
120
123.5
75
85
85
85
104
Air Circuit Break Type Automatic Transfer Switch
Fixed Type / 630-4000 A 3P
3P Rear View
JK
LM
E F G GF F E
A
LOAD
B
4P Rear View
JK
LM
E N G GF GF F E
A
LOAD
B
C
C
A B
1515
550
15 15
FixedHole 12
Front View
130 270
75
t
500
100
Fixed Hole
D
Side View
5000A BUS BAR
23 23
35 3535
6300A BUS BAR
15 1530 30
30 3030 30
70
Type G J K L M N
ATB - 50 3P
ATB - 63 3P
ATB - 50 4P
ATB - 63 4P
Type A B C D E F
ATB - 50 3P
ATB - 63 3P
ATB - 50 4P
ATB - 63 4P
18
[ Dimension ]
(Unit : mm)
( 630-1200 : 12t / 1600-2000 : 15t / 2500- 3000 : 20t / 3200-6300 : 25t )
30
40
30
40
162.5
159
162.5
159
123.5
123.5
123.5
123.5
123.5
123.5
123.5
123.5
132.5
132.5
132.5
132.5
150
-
150
150
315
465
387
545
315
525
387
625
630
990
774
1170
90
90
90
90
60
95
42
105
150
280
150
280
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
Drawable Type / 1600-4000 A
HANCESS ATB19
Bottom View
650 D
190
120
120
E
Side View
CA B
610
610
60 60
Front View
<ATB - 06 ~ 16> <ATB - 20, 25,32>
<ATB - 40> <ATB - 50>
30
30
2020
55
120
35
20
150
25
20
80
Type
ATB - 06 ~ 16
ATB - 20
ATB - 25
ATB - 32
ATB - 40
A B C D E
A
B 650
4 - 13 ATB
No. of Pole
3P
4P
3P
4P
3P
3P
4P
4P
Rated Current A B
Size
600 - 1600A 290 427
290 427
370 427
290 444
390 444
370
470 444
444
2000A
2500A
3200A
4000A
4000A
268
268
268
268
348
268
348
348
370
428
536
616
616
638
776
70
70
70
70
70
12 / 15
15
20
20
20
(Unit : mm)
Air Circuit Break Type Automatic Transfer Switch
( 630-1200 : 12t / 1600-2000 : 15t / 2500- 3000 : 20t / 3200-6300 : 25t )
Head O�ce144, Achasan-ro, Seongdong-gu, Seoul, KoreaTEL : 82 - 2 - 462 - 3731 ~ 3FAX : 82 - 2 - 463 - 8350
Plant48, Daram-ro 57beon-gil, Docheock-Myeon, Gwangju-si, Gyeonggi-Do, KoreaTEL : 82 - 31 - 762 - 7500FAX : 82 - 31 - 764 - 0302
Agent
note) The specifications are subject to change without notice in order to improve the performance and quality.
WWW.HANCESS.COM
Transter & Bypass Status
Normal Source Emergency Source
SourceAvailable
Main MainByPass ByPass
LOAD
Lamp Test
Hanpro 3000
ATB CTTS & ByPass Controller Based on DSP
Vietnam Represented Office:Hancess Vietnam - Quanpham Co.,ltd285 Dien Bien Phu, Ward 07 -district 03, Ho Chi Minh City - VietnamTel: +84 39304952 - 39302400Fax: +84 39304953E-mail: [email protected]: www.quanpham.vn