hamworthy purewell classiccms.esi.info/media/documents/hamwo_purewellvariheat_ml.pdfreliable...

24
Hamworthy Purewell Classic Cast Iron, Atmospheric Gas Fired Modular Boilers Single Boiler Outputs 40kW to 120kW Multiple Boiler outputs 80kW to 720kW

Upload: others

Post on 13-Oct-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

Hamworthy Purewell ClassicCast Iron, AtmosphericGas Fired Modular BoilersSingle Boiler Outputs 40kW to 120kWMultiple Boiler outputs 80kW to 720kW

Page 2: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

Options

2

Cast Iron AtmosphericGas Fired Modular BoilersNatural Gas or LPG

Purewell Classic

Hamworthy’s atmospheric Purewell Classicfully automatic boiler range is available withoutputs from 40kW to 120kW and inmodular configurations can satisfy loads upto 720kW.Setting them aside from other commercialatmospheric boilers, the Purewell Classic canbe controlled at low fire and a primary fluedamper provides increased control of thecombustion air, enabling a low fire efficiencyof up to 85% gross (94% nett), which is 5%above the high fire efficiency.Throughout its development, the PurewellClassic has retained the traditionalatmospheric boiler and draught diverterprinciples of operation, offering simple andreliable solutions that are easy to use andstraightforward to maintain.The entry-level permanent pilot modelsprovide an alternative to the fully automaticrange of boilers and again there are eightmodels with outputs ranging from 40kW to120kW.Completing the Purewell Classic package is arange of optional pipework kits to simplifydesign and procurement. The pipework kitsare available for 2, 3 or 4 boilers, closecoupled in a multiple casing modulararrangement.

The Purewell Classic offers a simple and

reliable solution that’s easy to use and

straightforward to maintain.

Simple design, reliable performance

Fully controllable at low fire for sequencing

More accurate load matching

Compatible with condensing models

Standby losses virtually eliminated

Lower servicing & maintenance costs

BE

NE

FIT

S

Single or multiple casings

Pipework kits

Sequence controller

Hours run meters

Pump over-run timer

LPG propane

Permanent Pilot modelsPurewell Classic modular boilers with multi-casing arrangement.

Page 3: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

3

Achieving high efficiency with atmospheric boilers

Atmospheric boilers, by design, drawcombustion air through the boiler bynatural draught on the flue system.The flue is sized for maximum full loadconditions, therefore, when anatmospheric boiler fires at part loadthere will be an excess volume ofcombustion air, and this leads toreduced boiler efficiency.In 2000, Hamworthy identified theneed to improve part load efficiencieson atmospheric boilers and throughresearch and development, introducedan innovative solution.The Purewell Classic fully automaticboiler range is equipped with a two-stage primary flue damper which isfully interlocked with the boiler control system.

The two-stage damper is able tocontrol the combustion air on theboiler for increased efficiencyperformance at low fire. This enables Hamworthy atmosphericboilers to achieve gross efficiencies upto 85% at part load.In addition to increasing the firingefficiency, the damper also serves toisolate the boiler from the chimneywhen at standby, thereby preventingthe flow of air through the boiler andvirtually eliminating standby losses.

The Hamworthy method of reducingstanding losses using the primary fluedamper, in preference to shuntpumps, enables a constant water flowto be maintained through the boiler,improving the hydraulic performanceof the installation. Experience hasshown that maintaining a constantflow in the primary hot water circuitprovides a more controllable systemfrom which the secondary heatingcircuits can be taken.Individual shunt pumps are notrequired on Hamworthy Purewellboilers and therefore the capital andrunning costs can be reduced onmultiple boiler installations.

Useful Heat

78%

LOW FIRE

Efficiency 78%

Efficiency 85%

Useful Heat

85%

Combustion Losses 20.75%

Case Losses 1.5%

Useful Heat

80%

HIGH FIRE

Efficiency 80%

Case Losses 1.5%

Efficiency 80%

Combustion Losses 18.5%

Combustion Losses 14.0%

Combustion Losses 18.5%

Useful Heat

80%

Case Losses 1.25%

Case Losses 1.0%

Standby Losses Approx 3%

StandbyLosses 0%

STANDBY

WITHOUT FLUE DAMPER

WITH FLUE DAMPER

Case Losses 1.0%

Case Losses 0.75%

No AirPassage

AirAirpassagepassageduringduring

standbystandby

Airpassageduring

standbyAir

Cast Iron Atmospheric Boilers

Page 4: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

4

The Purewell Classic heat exchanger has been developed to maximise heat transfer,satisfying the efficiency requirements laid down within the European BoilerEfficiency Directive, whilst retaining a very robust construction for long life.

Heat exchangerUsing up to date casting technology,Hamworthy has a reliable provendesign for the “series flow” heatexchanger, that has been developedspecifically for the Purewell range ofboilers.

Each individual section has beendesigned exclusively to suit boiler input.

The section design incorporates anincreased finned surface areagenerating a highly efficient gas towater heat transfer.

Each individual heat exchanger isnippled at alternate ends eliminating the problem of thermal stress.

The Purewell is also designedspecifically to operate at low waterreturn temperatures for prolonged periods.

The wet base section is a crucial partof the heat exchanger and is thereforedesigned to optimise overall efficiency.

The Purewell has a deep wet base section positioned close to the burner bars. This enables the bottom of the boiler to remaincool whilst absorbing heatnormally wasted, therebyimproving boiler efficiency.

Once assembled the heat exchanger iscovered with an insulation jacketwhich retains heat within the boilerminimising radiant heat losses.

Improved Efficiency

Burner bars

Basketassembly

Full ‘R’sections

Wet basesection

Plain ‘R’section

Collectorhood

Page 5: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

5

Sequencing multiple atmospheric boilersThe Purewell Classic boiler has beendeveloped with energy efficiency as afundamental part of the designphilosophy.The unique primary flue two-stagedamper performs two important roles.Firstly it controls the combustion air atpart load to improve efficiencyperformance and secondly, when theboiler is in standby mode, it isolatesthe chimney from the boiler, andvirtually eliminates standing losses.The two-stage damper is fitted asstandard to all fully automatic models.

A new approach to sequencing Traditionally, two-stage atmosphericboilers have been operated in high/lowmode, something that Hamworthy hasadvocated for many years. In amultiple boiler installation, thisapproach would switch on the leadboiler, igniting at low fire andmodulating to high fire to meetdemand. If more heat is required, thensecond boiler ignites at low fire andmodulates to high fire, and so on untileither the demand for heat is met orall the boilers are operating at high fire(full load).

The advent of the primary flue damperand its effect on performance hasresulted in a new approach tosequencing, which achieves evengreater efficiency benefits.

Now that the Purewell Classic boilersachieve higher efficiency at part load(low fire), it is apparent that in amultiple boiler installation there arebenefits to be had in changing thesequencing.

The chart shown opposite, illustratesthe efficiency performance of amultiple installation comprising 4boilers.

When the demand for heat issignalled, boiler No. 1 ignites at lowfire. When further heat input isrequired, boilers 2, 3 and 4 each ignitein turn at low fire. When still moreheat is required then boiler No. 1switches to high fire and so on until allboilers are firing at high fire.

Heating systems operate more oftenthan not at less than full load,therefore where this system ofsequencing is adopted, then the partload performance will be greatlyimproved.

The two-stage damper arrangement consists of two concentric damper blades thatare each driven by an independent actuator. This concentric design allows precisecontrol of the damping effect.The damper blades are securely keyed to the drive shaft and fully interlocked withthe boiler controls. This ensures that the damper is always in the correct positionbefore the boiler ignites or increases firing rate.

1L

85%

8% 16% 24% 32% 50% 66% 83% 100%

EFFICIENCY

DEMAND

2L 3L

2L

1L

85%

3L

4L

2L

3L

4L

3L

4L 4L

2L

1H

84%

2H

1H

83%

2H

3H

1H

81.5%

2H

3H

4H

1H

80%

1L

85%

1L

85%

In addition to the efficiency benefits, there is the added advantage of sharing theload more evenly across each module.Making more use of the low fire capability can reduce wear and tear on the boiler.Closely modulating the output to match the load will reduce the number of timesthe boilers switch on and off, reducing the work of the ignition system and itscomponents. The responsiveness of the system is also improved because each boilercan more readily switch from low fire to high fire and back without switching theboiler off.

Purewell Classic Primary Flue Damper

Multiple boilers: A new approach to sequencingLow, low, low / high, high, high

Fully closed Low fire High fire

Page 6: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

6

Radiant baffleThe patented baffle isconstructed such that it reflectsradiant heat back into the combustionchamber, consequently minimisingheat losses from the boiler.

The combustion air is pre-heatedby extracting heat, as it passes through the baffle.

By pre-heating the air, efficiency isimproved which assists the processof combustion.

The air travels in a convolutedpattern cooling the baffle in theprocess by impacting air onto thesteel surface.

The baffle ensures that there are very low temperatures beneath theboiler which protects the floor and provides a safer environment for servicing purposes.

The baffle removes the need forceramic insulation and its associated problems.

Note: Purewell 95,105 & 120kW models only

High flow gas valve assembly

High fire rate adjuster

Low fire / Start rate adjuster

Valve 1

Valve 2

Gas inlet

Throttle adjuster

Typical

Lines of

Radiance

Burner

Flame Flame

Burner

Pre-heated Air Pre-heated Air

Combustion

Air Flow

Radiant

Baffle

Radiant

Baffle

Combustion

Air Flow

High flow gas valvesFor 95kW models and above,the Purewell fully automatic boiler hasa unique patented flow sharing gasvalve system demonstratingHamworthy’s skilled proficiency indesign engineering.

The flow share system enables a specified quantity of gas to be passed economically through smallvalves, whilst retaining the requireddegree of downstream pressure control.

All Purewell fully automatic boilershave a low fire start rate which ignitesacross all burners at a givenpercentage of total output. Thisensures a safer light up which is fullycompliant with the Gas Appliance(Safety) Regulations.

Radiant baffle schematic

Page 7: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

FRONT ELEVATION SIDE ELEVATION

Tie rod

Wet base section

Radiant baffleBasket

assembly

Burnerbars

Plain ‘R’section

Full ‘R’section

40 40

455

Flue gascollector hood

612

560

7

Purewell ClassicFully AutomaticTypical Layout

The Heat Exchanger Module

Boiler Model PC 40 PC 50 PC 60 PC 70 PC 80 PC 95 PC 105 PC 120

Base Sec. 1 1 1 1 1 1 1 1

Tie Rods 4 4 4 4 4 4 4 4

Burners 4 4 4 4 4 5 5 5

Plain ‘R’ Sec. 0 0 0 0 0 0 0 1

Half ‘R’ Sec. 0 0 1 1 1 1 1 0

Full ‘R’ Sec. 3 3 3 3 3 4 4 5

Flue Socket

Temperature Limiter(Overheat Thermostat)

Radiant Baffle

Burner Manifold

Burner Mounting Plate

Boiler Insulation

Drop Down Control Panel

High/Low Hours Run Meters (Optional)

Primary Flue Damper

Draught Diverter

Gas Valve(s)(95-120kW)

Gas Cock

Gas Pipe

Gas Valve Plug/Socket

Control Thermostat Push On/Off Button

Page 8: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

8

Heat exchangerEach individual boiler has a heatexchanger manufactured fromhorizontal cast iron sections whichwhen pressed together with nipples atalternate ends, produce a provenhorizontal series water flow pattern.During assembly each heat exchangeris pressure tested to 14bar (203 psi).The Purewell is tested to the latestboiler standards covering workingpressure up to 6bar (87 psi). The boiler sections are positioned ontoa fabricated galvanised mild steelbasket assembly which houses theburner bar and igniter assembly. Theburner bar and gas train assembliesare attached by two nuts to the basketemphasising serviceability and ease ofinspection.

LayoutThe Purewell boiler can be installed asa single unit or in modular form wherea ‘multi’ casing maximises availablefloor space.It is recommended that a maximum of6 boilers can be positioned on 533mm(21") centres if required. Largernumbers should be split into two ormore banks with 150mm (6")between each bank. The positioning of the boilers on533mm (21") centres can be donewith a high level of accuracy. Tocomplete a modular formation, thebaskets are butted against each otherwhich ensures that distances cannotbe sized incorrectly. (For further information on multiplecasings see page 11).The Purewell is supplied on adismantlable wooden pallet givingimproved ease of installation.The basket assembly incorporatesrunner type feet which increases theoverall manoeuvrability of the boilerfor final site positioning.It is recommended that under normalcircumstances a maximum of sixboilers should be connected to oneflue header with up to eight boilersbeing served by a single chimney.

BurnerThe burner arrangement of the boilercomprises a tried and tested reliableburner bar system with 4/5 burnerbars depending on thermal input. Thissystem has been specifically designedto provide clean and efficientcombustion.

Radiant BaffleA patented radiant baffle assembly ispositioned beneath the burner bars,this both protects the floorunderneath the boiler and improvesoverall efficiency. The baffle assemblyis extremely durable, constructed fromcoated steel, and obviates the need touse ceramic insulation. (For moredetailed information refer to page 6).

The draught diverterThe Purewell Classic has a low levelstainless steel draught diverter,engineered specifically to optimise theperformance of each boiler model. Down draught needs to be dispersedbefore reaching the primary flue,otherwise boiler performance and thecombustion process can be effected,producing carbon monoxide. This isachieved by a double conearrangement, which directs downdraught outside the boiler and hencedoes not affect boiler operation andefficiency. For up draught conditionsthe situation is reversed. The twincone design pulls air through withouteffecting the primary flue.

Boiler casingCareful consideration has been givento casing design. The panels are ofrobust construction and mounted tothe boiler giving greater rigidity to theunit. Due regard has been given toserviceability and easy access to theboiler. A deep removable front doorpanel provides the user with ease ofinspection and maintenance. Boilerscan be supplied with either anindividual single casing for each boiler,or with a multiple casing arrangementfor applications where the boilersstand immediately together, side byside. Where a multiple casing

arrangement is specified, outer sidepanels are supplied for each end boilerand the intermediate boilers areequipped with steel frames to supportthe top and front. Side panels are notrequired between the boilers with amultiple casing arrangement.Note: The type of casingarrangement must be specifiedat time of order. (See page 11 forfurther details).

ThermostatsAll Purewell Classic boilers are suppliedas standard with a temperature limiterthat has a range of 90-110°C, this willnormally be factory set to 100°C.Permanent pilot boilers have a controlstat supplied as standard with a rangeof 0-120°C. Fully automatic boilers arefitted with a dual stage electronictemperature control, which has astandard range of 65-90°C.The difference between the high limitstat setting and the control stat shouldnot be less than 10°C.

The gas trainThe gas train is completely detachable.Major items can be removed duringservicing within 2-3 minutes ifrequired. The gas train comprises aservice cock, union connection, gasvalve(s) and injector manifold.

Pipework KitsTo simplify the pipework arrangementat the back of the boilers, Hamworthymanufacture reverse return pipeworkheader kits. These cover 2, 3 or 4boilers in a multiple casingarrangement and include isolatingvalves, fittings and interconnectingpipework which can be cut to finishedsize on site. The design incorporatesPrimofit compression type fittingswhich means there is no need forpipework threading on site.The factory made pipework kits fromHamworthy are available for modulescomprising all Purewell boilers, allWarmwell (condensing) boilers ormixed combinations of Purewell andWarmwell boilers. (See page 14 for details).

Specification

Page 9: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

9

Hot Surface IgnitionFully Automatic boilers have a directburner ignition system that ignites theburners each time the boiler is calledto fire. This is achieved using a hotsurface ignition element that reaches atemperature of approximately 1300°C.This highly effective and reliable formof ignition requires less maintenancethan conventional spark ignition, andeliminates the electrical interferencesometimes associated with that typeof system. Flame proving is achievedusing a flame rectification probe.

Boiler FiringOn fully automatic high/low models,the boiler lights at the low fire ratewith the first stage of the flue damperopen. Once the flame has stabilised,and if there is sufficient demand in thesystem, the second stage of thedamper will open, followed by thesecond stage of the gas valve and theboiler will fire at full rate. As thesystem approaches full temperature,the boiler will return to its low firesettings for greater energy efficiency.The high/low operation provides aneffective form of control for singleboiler installations, however formodular applications full sequencecontrol is more appropriate.

Sequence ControlUsing a number of smaller boilers(modules) in order to match moreaccurately the required load isacknowledged as an excellentapproach to heating system design.In order to get the full benefit from amultiple boiler installation it isessential to fit some form of sequencecontroller, to regulate the firing ofeach module.Higher system efficiencies can beachieved by controlling a multiplePurewell Classic installation at low firebefore stepping up to high fire. (Refer to page 5 for further details.)

Time clock controlWhere boilers are operated from timeclocks, to avoid overheating andprogressive calcium deposition at zeroflow conditions, provision should bemade for a 5 minute circulating pumpover run after the last boiler hasceased firing.

Electrical detailsSupply 230V 50Hz, single phase. Wiring external to the boiler must beinstalled in accordance with IEERegulations and any local regulationswhich apply. Wiring must becompleted in heat resistant 3 corecable, ( size 1.0 mm2 c.s.a.). Fasciafuse rating is 2 amp. External fusesshould be 6 amp for all single boilersizes.

Permanent Pilot ModelsPermanent pilot models operate inon/off mode of control.The gas supply to the burner iscontrolled using a multifunctionalvalve with a permanent pilotignition system. The operation ofthe gas valve is directly controlledfrom the boiler thermostat, whichis connected via a pre-wired flyinglead with plug & socketconnections.Flame monitoring is achieved usinga simple thermocouple, which isconnected via an energy cut-off(ECO) lead to a manual reset limitthermostat that will interrupt thesignal to the pilot valve in theevent of flame failure. A piezospark ignitor unit is fitted to theboiler in order to light thepermanent pilot.The control and limit thermostatsare both housed within afabricated steel control box that isaccessed by removing the frontdoor panel. The main electricalconnection to the boiler is madeusing the fused 3-pin IEC plugsupplied with the control box.The permanent pilot models may besupplied with an optional primary fluesingle-stage damper system. Thedamper will be interlocked with thecontrol thermostat to ensure that thedamper is fully open before firing theboiler.The on/off damper arrangementconsists of a single damper bladedriven by a single actuator. It isdesigned to enable permanent pilotboilers to benefit from the reductionin standing losses that can beachieved by isolating the boiler fromthe flue system when it is not firing.

CommissioningHamworthy Heating Ltd stronglyrecommend that all boilers arecommissioned by their servicedepartment who will issue a boilerlog-book that details the initialoperating settings and can be used torecord future maintenance work.For more information oncommissioning contact HamworthyHeating Service Department:0845 450 2866.

Hot surface ignition on the fullyautomatic models

Boiler ControlsFully automatic boilers are fitted with afabricated steel control panel, whichhouses the main electronic controlsystem. The control panel has a dropdown fascia to facilitate access forservicing and a simple mimic displayallows the user to monitor the currentoperating status of the boiler.All fully automatic boilers are fitted asstandard with volt free contacts whichallow for remote monitoring of theboiler status, indicating boiler run,lockout & high temperatureconditions. The boiler can be controlled remotelyfrom a Building Management Systemor timeclock controller using theremote start/stop circuit. The high/lowoperation can also be controlledremotely in a similar manner.

Page 10: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

10

GasSupply pipes must be fitted inaccordance with BS6891 or IGE/UP/2(formerly IM/16) as appropriate. Pipework must be of adequate size. Pipesshould not be of a smaller size thanthe boiler gas connections. Thecomplete installation must be purgedand tested for soundness as describedin BS6891 or IGE/UP/1 (formerly IM/2)and IGE/UP/1A (formerly IM/5) as appropriate.Advice and guidance on the capacityof gas meters and available gaspressure can be obtained from local orregional British Gas offices.The table opposite expresses pipelengths from gas meter to appliancewhich will produce approx. 1mbarpressure loss. This table must be usedin conjunction with losses of variousfittings shown in the table below.

For example: Purewell boilers with anoutput totalling 240kW being fed by21/2" pipe with 6 elbows between gasmeter and boiler header can have amaximum length of 72m - (6x2m) = 60metres run to achieve a 1mbar loss.Note: These tables are based onIM/16, which has been replaced byIGE/UP/2, and information isprovided for guidance only.

Reductions for fittings (metres)

20mm 0.5 0.5 0.3

25mm 0.5 0.5 0.3

40mm 1.0 1.0 0.3

50mm 1.5 1.5 0.5

65mm 2.0 2.0 0.5

80mm 2.5 2.5 1.0

100mm 3.5 3.5 1.5

20mm 25mm 40mm 50mm 65mm 80mm 100mm

40 10 42 - - - - -

50 - 25 180 820 - - -

60 - 16 120 540 - - -

70 - 11 85 380 - - -

80 - - 62 280 900 - -

95 - - 42 185 580 - -

100 - - 37 170 520 - -

105 - - 33 145 470 - -

120 - - 25 110 345 - -

140 - - 17 78 245 - -

150 - - 15 66 210 - -

160 - - 12 56 180 - -

180 - - - 44 140 820 -

190 - - - 38 120 750 -

200 - - - 35 110 650 -

210 - - - 30 96 600 -

240 - - - 22 72 440 -

250 - - - 21 66 390 -

280 - - - 16 52 300 -

285 - - - 15 47 290 -

300 - - - 14 45 260 -

315 - - - 11 37 235 -

320 - - - - 37 235 -

350 - - - - 31 180 -

360 - - - - 27 170 810

380 - - - - 24 150 730

400 - - - - 23 135 640

420 - - - - 19 115 570

475 - - - - 16 90 440

480 - - - - 14 86 430

500 - - - - 14 80 380

525 - - - - 11 71 340

570 - - - - - 60 280

600 - - - - - 51 245

630 - - - - - 46 220

720 - - - - - 34 165

Gas flows in pipes

Purewell BoilerPower (output) kW

Type offitting

Perelbow

Pertee

Per 90°bend

PumpsHamworthy Heating is the exclusive distributor of Biral pumps in the UK. With a wide range of models available, you can closely match pump performance to suit your requirements.

The high quality design with innovative features include:• Unique Can system – no seals to leak• Low, medium and high speed ranges• High torque starting• Ultra low power consumption• Flat performance curves – less system noise• Operating pressures up to 16 bar• Temperatures from -20°C to 140°C• Whisper quiet pump operation

Talk to HAMWORTHY BIRAL your partners in pumps

Maximum length of gas pipe (Metres)

Page 11: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

11

Btu/hx1000

kWOutput

to Water

BoilerModel

No. ofBoilers

ModelReference

Single Boiler - Casings

PC 40 1 PC 40 40 137

PC 50 1 PC 50 50 171

PC 60 1 PC 60 60 205

PC 70 1 PC 70 70 239

PC 80 1 PC 80 80 273

PC 95 1 PC 95 95 324

PC 105 1 PC 105 105 358

PC 120 1 PC 120 120 410

Two Boilers - Multiple Casings

MPC 80/2/40 2 PC 40 80 273

MPC 100/2/50 2 PC 50 100 341

MPC 120/2/60 2 PC 60 120 409

MPC 140/2/70 2 PC 70 140 478

MPC 160/2/80 2 PC 80 160 546

MPC 190/2/95 2 PC 95 190 648

MPC 210/2/105 2 PC 105 210 717

MPC 240/2/120 2 PC 120 240 819

Three Boilers - Multiple Casings

MPC 120/3/40 3 PC 40 120 410

MPC 150/3/50 3 PC 50 150 512

MPC 180/3/60 3 PC 60 180 614

MPC 210/3/70 3 PC 70 210 716

MPC 240/3/80 3 PC 80 240 819

MPC 285/3/95 3 PC 95 285 973

MPC 315/3/105 3 PC 105 315 1075

MPC 360/3/120 3 PC 120 360 1229

Four Boilers - Multiple Casings

MPC 160/4/40 4 PC 40 160 546

MPC 200/4/50 4 PC 50 200 682

MPC 240/4/60 4 PC 60 240 819

MPC 280/4/70 4 PC 70 280 955

MPC 320/4/80 4 PC 80 320 1092

MPC 380/4/95 4 PC 95 380 1297

MPC 420/4/105 4 PC 105 420 1433

MPC 480/4/120 4 PC 120 480 1638

Five Boilers - Multiple Casings

MPC 200/5/40 5 PC 40 200 683

MPC 250/5/50 5 PC 50 250 853

MPC 300/5/60 5 PC 60 300 1024

MPC 350/5/70 5 PC 70 350 1194

MPC 400/5/80 5 PC 80 400 1365

MPC 475/5/95 5 PC 95 475 1621

MPC 525/5/105 5 PC 105 525 1792

MPC 600/5/120 5 PC 120 600 2048

Six Boilers - Multiple Casings

MPC 240/6/40 6 PC 40 240 819

MPC 300/6/50 6 PC 50 300 1024

MPC 360/6/60 6 PC 60 360 1228

MPC 420/6/70 6 PC 70 420 1433

MPC 480/6/80 6 PC 80 480 1638

MPC 570/6/95 6 PC 95 570 1945

MPC 630/6/105 6 PC 105 630 2150

MPC 720/6/120 6 PC 120 720 2457

In the example, shown above, the selection is for 3 boilers in a multi casing modularinstallation. The total output is 360kW, using 120kW boilers.

In this multiple casing arrangement, there will be an external side - casing panel foreach end boiler, but there is no need for casing panels between each boiler.

533 CRS(Typ)

533 CRS(Typ)

There may be occasions where each boiler is going to be placed further apart and insuch circumstances the boilers should be specified or ordered as single boilers withindividual casings.

For the example shown, where single casings are required, the reference would be3 No. PC 120 boilers.

532mm 532mm 532mm

Multiple CasingArrangement

Single CasingsArrangement

Using multiple boiler referencesPurewell Classic boilers can be supplied with a single casing on each boiler or withmultiple casings to enclose a complete module.The multiple casing arrangement removes the need for an external casing panelbetween each boiler.When specifying or ordering a boiler installation using multiple casings, the pre-fixto the model reference is MPC.

Multiple Boiler References - Example: MPC 360 / 3 / 120

MPC 360 / 3 / 120

Multiple Total kW Number kW outputPurewell output of of boilers of eachClassic modules used boiler

Page 12: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

12

PC 40 PC 50 PC 60 PC 70 PC 80 PC 95 PC 105 PC 120

40 50 60 70 80 95 105 120

136.5 170.6 204.7 238.8 273.0 324.2 358.3 409.5

32.5 31.4 31.6 29.2 31.6 34.4 38.0 38.7

110.9 107.1 107.8 99.6 107.8 117.4 129.7 132.0

49.3 63.4 74.5 88.4 101 120 132 150

168.2 216.3 254.2 301.6 344.6 409.5 450.4 511.8

44.4 57.1 67.1 79.6 90.9 108.5 118.8 135

151.5 194.8 229.0 271.6 310.2 370.2 405.4 460.6

30 30 37.1 37.1 37.1 44.2 44.2 51.3

6.6 6.6 8.2 8.2 8.2 9.7 9.7 11.3

0.87 1.08 1.30 1.52 1.74 2.06 2.28 2.60

11.5 14.3 17.2 20.1 22.9 27.2 30.1 34.3

0.43 0.54 0.65 0.76 0.87 1.03 1.14 1.30

5.7 7.1 8.6 10.0 11.5 13.6 15.1 17.2

5.10 7.84 15.69 20.59 26.47 37.25 50.00 84.31

2.0 3.1 6.3 8.3 10.6 15.0 20.1 33.9

6

87

0.42

6.1

4.73 5.92 7.1 8.27 9.44 11.19 12.36 14.1

167.0 209.1 250.7 292.1 333.4 395.2 436.5 497.9

20

8

25

10

13.4 12.5 11.9 11.0 9.5 11.5 11.2 11.0

5.4 5.0 4.8 4.4 3.8 4.6 4.5 4.4

62.9 78.8 94.5 110.0 125.6 148.9 164.4 187.6

2221 2783 3337 3884 4435 5258 5807 6625

190 200 190 220 230 200 215 205

365 385 365 423 442 385 413 394

Rc2"

ISO 7/1

R3/4" R1"

ISO 7/1 ISO 7/1

206 256

8.11 10.1

230v 50Hz Single phase, 6 amp fuse

Boiler output kW

Btu/h x 1000

Boiler output* (Low fire) kW

Btu/h x 1000

Boiler input (Gross) kW

Btu/h x 1000

Boiler input (Nett) kW

Btu/h x 1000

Water content l

UK gal

System design flow rate l/s

@ 11°C∆t across module UK gal/min

Minimum flow rate at any l/s

time @ 22°C∆t rise UK gal/min

Waterside pressure mbar

loss @ 11°C∆t in wg

Maximum water pressure bar

psig

Minimum water pressure modular bar

application 82°C flow 11°C∆t psig

Input rate natural gas m3/h

ft3/h

Nom.gas inlet pressure at boiler mbar

natural gas in wg

Max.gas inlet pressure at boiler

natural gas in wg

Gas setting pressure standard mbar

module natural gas in wg

Approx flue gas volume m3/h

@ 9% CO2 @ NTP ft3/h

Approx flue gas °C

temp. nett (primary flue) °F

Water flow/return

Connections

Gas inlet

Connection

Flue connections to draught mm

diverter nominal dia. in

Electrical supply

Technical DataPurewell Classic - Performance and General Data Information

Boiler Model

*Fully automatic boiler only

En

erg

yW

ate

rG

as

Flu

eC

on

nect

ion

Page 13: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

13

All dimensions in mm.

Note: The 533 centres relates to boilers close coupled in modular form. For stand alone applications, a minimum of 150mm should be allowed between casings. (Space baskets 200mm apart).

PC 40/50 PC 60/70/80 PC 95/105 PC 120

Approx. dry weight kg. 235 285 345 400

A - Boiler height (Casing) mm. 870 870 1060 1060

B - Flue height from floor mm. 1383 1475 1577 1671

C - Flow connection height mm. 580 667 761 855

D - Gas connection height mm. 769 769 957 957

E - Gas connection size - BSP.T Male R3/4" R3/4" R1" R1"

F - Flue outlet Dia. mm. (nominal) 206 206 256 256

G - Primary flue height mm. 190 285 190 285

Single units

Dimensional DataPurewell Classic - Boiler Dimensions/Clearances

SIDE VIEW

62.5

62.5

533 CRS

FRONT VIEW

235

Gas

F

460 (Recommended)

150 (Minimum)

532

C

G

269

Return

Flow

B

A

35 (Approx.)

Rc 2:"to ISO 7/1

D

E

460(Minimum)

610(Minimum) 950

380

612 74

Connectionpositions

Gas

Return

Flow

Connectionpositions

455

H

J

Damperhousing

Model PC 40/50 PC60/70/80 PC95/105 PC120

H 297 297 335 335

J 89 160 86 180

Model

Page 14: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

14

Reverse return headersPurewell Classic andWarmwell boilers

Designed to save time and simplifyprocurement, optional pipework kitsare available from Hamworthy.The latest kits enable Purewell Classicboilers to be integrated in a multipleboiler arrangement with Warmwellcondensing boilers.

The independent flow and returnheaders are prefabricated in thefactory and are available in three sizesfor connection to two, three or fourboilers, close coupled in a multiplecasing modular arrangement. Refer topage 11 for details of multiple casings.

The kits include isolating valves,fittings and interconnecting pipeworkwhich can be cut to finished size onsite. With these kits, there is no needfor pipework threading on site aftercutting to finished size.

Connections are provided on eachheader for fitting a relief valve,instrumentation and sensors. (Notsupplied by Hamworthy). A connection is available at either endof each header for the water flow andreturn pipework, giving a choice forpipework layout. It should be noted,however, that to achieve the reversereturn principle, the direction of waterflows must be concurrent.

Each header incorporates an integralbracket which interlocks with theother header and additional support isprovided by adjustable legs to the floor.

The three sizes of header are availablewith an optional insulation kit.Designed to complement the neatappearance of the boilers, theinsulation kit comprises three easy tofit sections and is lined with RockwoolRW2, 30mm thick (typical).

Pipework kits

LC

FlowHeader

Male adaptor

Male adaptor

3-way ball valve with M/Felbow and drain pipe male

Male adaptor

2-way ball valveMale adaptor

GAS

RETURN

FLOW

Scrap plan viewOn ball valve andM/F elbows showingstagger on return

Return header

A

B100

Optional insulation kit

LC

FlowHeader

CT nipple

2-way ball valve

3-way ball valve with M/Felbow and drain pipe male

Male adaptor

Male adaptor

Male adaptor

Gate Valve*

CLFLOW

Gas

RETURN

Return header

*Valve only used on Purewell Boilers when mixed with Warmwell

A

B100

Optional insulation kit

LC

Typical arrangement (side view)Purewell Classic Boilers

Typical arrangement (side view)Warmwell Boilers

Page 15: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

15

Dimensions & Layout

2310

C

Flow Flow FlowFlow

Gas Gas Gas Gas

Return Return

Drain Drain Drain Return ReturnDrain

Purewell boiler (typ)Optional insulation kitWarmwell boiler (typ)

SupportBoth ends(typical allmodules)

4 BOILER MODULE

Optional insulation kit

1244

FlowFlow

Gas Gas

Return

Drain Drain Return

C

2 BOILER MODULE

Connections shown for flow header.Return header connections will be opposite arrangement.

93 1003/4" BSP female

932" BSP female

3" BSP female3" BSP female

Optional insulation kit1777

C

3 BOILER MODULE

Flow FlowFlow

Gas Gas Gas

Return Return

Drain Drain Drain Return

Note:When Purewell boilers are installed with Warmwell condensing boilers, an additionalvalve is supplied in the kit for each Purewell boiler. This is to balance the hydraulicresistance of the system. The mix of boilers must be stated at the time of ordering (Refer to section on water systems, page 16.)

Dimensions shown are nominal andwill be subject to normal manufacturing tolerances.

Dimensions in mm

Purewell / Warmwell Pipework Kits

Boiler model Dimensions A (Min) Dimensions B Dimensions C

Purewell Classic (only)

PC 40 / PC 50 460 243 1061

PC 60 / PC 70 / PC 80 460 243 1110

PC 95 / PC 105 460 243 1204

PC 120 460 243 1298

Warmwell (only)

W 60 678 453 1235

W 80 678 453 1330

W 95 678 453 1330

W 120 678 453 1452

W 140 678 453 1522

Purewell Classic & Warmwell

PC 40 / PC 50 with W 60 678 453 1235

PC 60 / PC 70 / PC 80 with W 80/95 678 453 1330

PC 95 / PC 105 with W 120/140 678 453 1522

PC 120 with W 120/140 678 453 1522

Page 16: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

16

Application & System DataThe installation of all boilers MUST bein accordance with the relevantrequirements of Gas SafetyRegulations, I.E.E. Regulations and thebye-laws of the local waterundertaking. It should also be inaccordance with any relevantrequirements of the local gas region,local authority and relevantrecommendations of the followingdocuments:

British Standards

CR 331.3 Low pressure installationpipes.BS 5449.1 Forced circulation hotwater systems.BS 5446 Installation of gas hot watersupplies for domestic purposes.BS 5440.1 Flues (for gas appliances ofrated input not exceeding 60kW).BS 5440.2 Air supply (for gasappliances of rated input notexceeding 60kW).BS 6798 Boilers of rated input notexceeding 60kW.BS 6644 Installation of Gas Fired HotWater Boilers, 70kW to 1.8MW (nettinput).BS 6700 Design, installation, testingand maintenance of services supplyingwater for domestic use.BS 6880 Part 1,2 & 3 Code of practicefor low temperature hot water heatingsystems of output greater than 45kW.BS 6891 Installation of low pressuregas pipework of up to 28mm indomestic premises.BS 7074 Part 1 Application, selectionand installation of expansion vesselsand ancillary equipment for sealedwater systems. Part 2 Code of practicefor low and medium temperature hotwater systems.BS EN 60335 Part 1Safety ofhousehold and similar electricalappliances - general requirement.

I. Gas E. Publications

IGE/UP/1 Soundness testing andpurging of industrial and commercialgas installations.IGE/UP/1A Soundness testing anddirect purging of small low pressureindustrial and commercial natural gasinstallations.IGE/UP/2 Gas installation pipework,boosters and compressors in industrialand commercial premises.

Boiler basePurewell boilers should be positioned on a level non combustible surface that iscapable of adequately supporting its weight (when filled with water) and anyancillary equipment. Adequate space for installation and servicing should beconsidered. This should not normally be less than 460mm at the rear, for flow andreturn connections. Also allow at least 460mm on one side, the other side must beno less than 150mm. Allow 610mm (minimum) in front of the boiler for servicing.

Water systems - Modular installationsFlow and return headers should be connected in a “reverse return” arrangement(i.e. the water flow in each header follows the same direction) thus providing equalflow through each boiler. This also ensures that pressure loss across any number of boilers will never be greater than the head loss across one boiler pluslocal pipework losses.When installing Purewell boilers as part of a mixed modular system with Warmwellboilers, balancing valves should be fitted to the Purewell boilers. Balancing valves are required in order to compensate for extra pressure drop throughthe Warmwell’s condensing section. Adequate water flowThe Purewell boiler is designed as a quick response, low water content unit to runcontinuously with minimal operating problems. Care should be taken in the initialdesign and layout, having due regard for adequate water flow through the boilersand the influence of the system control. Refer to technical data table for minimumwater flows required. The control system and valves, where fitted, should beregulated to avoid lower flows occurring. The flow corresponding to 22°Ctemperature rise across the boiler is the minimum recommended flow at any time.A minimum return temperature of 30°C should be maintained. For boiler pressuredrop refer to page 12 technical data table.

System feed water qualityIf the boiler feed water has a high degree of hardness, it is recommended that thewater be treated to prevent precipitation of scale or sludge in the boiler waterpassages. Details of additives can be obtained from any specialist water treatmentmanufacturer or local water authority.

Open vent pipe and cold feed pipe

Boiler Open vent size Cold feed size

<60kW 25mm (1in) 19mm (3/4 in)

60kW-150kW 32mm (11/4 in) 25mm (1in)

150kW-300kW 38mm (11/2 in) 32mm (11/4 in)

300kW-600kW 50mm (2in) 38 (11/2 in)

Pressure relief valveEach boiler, or in the case of a modular installation, each bank of boilers must befitted with a pressure relief valve to BSEN1504126-1 and sized as shown in BS6644.BS6644 provides comprehensive information for the selection and location of safetyvalves and attention is drawn to the higher capacity requirements of safety valves forpressurised hot water systems.

IGE/UP/10 Installation of gas appliances in industrial and commercial premises, Part 1 flued appliances.

Health and Safety Executive:

Guidance note PM5 - Automatically controlled steam and hot water boilers.CIBSE Publications:- "CIBSE Guide"It is impractical in this document to specify all relevant information, but thefollowing extracts from the above references are emphasised since failure to complywith these requirements will almost certainly result in an unsatisfactory installation.

Page 17: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

17

Guidance Note PM5 Health andSafety Executive This note states that “hot waterboilers should have an automaticcontrol apparatus to cut off fuel to theburners of gas fired plant when thewater at or near the boiler flow outletrises to a pre-determined temperature.This should provide a margin of atleast 17°C below the temperature ofsaturated steam corresponding to thepressure at the highest point of thecirculation system above the boiler.”To comply with this recommendation,the minimum system pressure isdependant on system design flowtemperatures and in the case ofmodular installations, the temperaturerise across each module.

Single installationsThe minimum pressure must be equalto the gauge pressure equivalent tothe saturated steam temperatureobtained by adding 17°C to therequired boiler flow temperature. Thehighest point of the circulation systemabove the boiler should never be lessthan 2m (6.5ft).Required flow temperature 95°CSafety margin 17°CEquivalent saturated steam temperature 112°CFrom steam tablescorresponding gauge pressure -0.50 bar (7.3 psi) - 5.1m (16.7ft)head of water.

Modular installationsThe minimum pressure should beequal to the gauge pressureequivalent to the saturated steamtemperature. This is obtained byadding 17°C to the sum of therequired mixed flow temperature plusthe temperature rise across themodules.Required mixed flow temperature 82°C Temperature rise acrossmodules at minimum flow rate 11°C Safety margin 17°CEquivalent saturated steam temperature 110°CFrom steam tablescorresponding gauge pressure0.42 bar (6.1 psi) - 4.3m (14ft)head of water.

Air Supply and VentilationAn adequate supply of fresh air forcombustion and ventilation must beprovided in accordance with BS 6644. The air supply should be freefrom contamination such asbuilding dust and insulationfibres from lagging. To avoidunnecessary cleaning andservicing of the burner, werecommend that the boilers arenot fired whilst building workis being undertaken.The air supply should be achievedusing: � Natural ventilation supplying air

with a low level opening and discharge through a smaller sized high level opening.

� A fan to supply air to a low level opening with natural discharge through a high level opening.

� A fan to supply air to a low level opening and discharged by means of a fan at a high level.

Note: Fans must be selectedsuch that a negative pressure isnot created in the boiler houserelative to outside air pressure. The air supplied for boiler houseventilation should be such that themaximum temperatures within theboiler house are as follows:� At floor level 25°C

(or 100mm above the floor level)� At mid level 32°C

(1.5m above floor level)� At ceiling level 40°C

(or 100mm below ceiling level)Where natural ventilation is usedsuitable permanent openings at lowlevel and high level connected directlyto the outside air should be provided.These openings must be fitted withgrilles that cannot be blocked orflooded. The free area of the grilles should beas follows:Low Level (Inlet) 4cm2 per kW of net heat input.High Level (Outlet) 2cm2 per kW of net heat input.

System Head

Ventilation

Where a boiler installation is tooperate throughout the summermonths, e.g. for domestic hot waterproduction for more than 50% of thetime, then additional ventilationallowances are required. Refer toBS6644 for more detailed information.

DeliveryEach boiler is despatched as a fullyassembled heat exchanger and burnerbasket complete with gas train andvalve. The assembly is positioned on atimber frame to facilitate movementon site and shrink wrapped forprotection.The following items are suppliedpacked in separate cardboardcontainers:

Boiler casing complete withassembly instructions

Boiler control panel

Primary flue complete with damperassembly, where applicable

Draught diverter

All Hamworthy products are deliveredto site on a tail-lift vehicle, anddeliveries are closely co-ordinated withthe customer, to suit the siteconstruction programme. Standarddelivery is to ground level from thetail-lift of the vehicle. To enquire about special deliveryservices, please contact our customerservices team.

Limited AccessFor sites where access to the plantroom is limited or difficult, Hamworthycan arrange for heat exchangers to besupplied loose for site assembly. In addition, we offer a service of siteassembly for many of our products.Using our trained people we can offera high quality of build and theassurance of a boiler built and testedby the manufacturer. Heat Exchangersassembled by Hamworthy includeparts and labour under the two-yearwarranty.

Page 18: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

18

Example 3Split system. Completelyseparate heating and DHWsystems. Multiple boilersunder direct temperaturecompensation and adecoupled heating circuit,which may have a variableflow. DHW generated bydirect gas fired water heaters.

Example 2Combined heating anddomestic hot water withdiverting valve on DHW andmixing valve on heating.

The installation of modular boilers in commercial and industrial heating and hot water systems offer a wide choice of designoptions and applications. The following systems shown are typical and should be considered for general guidance.

System Design

Example 1Heating only; with separatetemperature compensationon each zone.

WATER SENSOR

FLOW

RETURN

CO

MM

ON

HE

AD

ER

CO

MM

ON

HE

AD

ER

MIXINGVALVE

ZONEPUMP

MIXINGVALVE

ZONEPUMP

HEATINGLOAD

(ZONE 1)

HEATINGLOAD

(ZONE 2)

BOILERPRIMARY

PUMP

BOILER1

BOILER2

BOILER3

SEQUENCECONTROLLER

21 3COMPENSATOR

COMPENSATOR

WATER SENSOR

BOILERPRIMARY

PUMP

BOILER1

BOILER2

BOILER3

SEQUENCECONTROLLER

21 3

CO

MM

ON

HE

AD

ER

WATER SENSOR

BOILERPRIMARY

PUMP

BOILER1

BOILER2

BOILER3

SEQUENCECONTROLLER

21 3

DIVERTINGVALVE

MIXINGVALVE

HEATINGPUMP

DHWPUMP

BYPASS

HEATINGLOAD

POWERSTOCKCALORIFIER

DHW FLOW

DHW RETURN

COLD FEED

DORCHESTER DIRECT GAS FIRED

WATER HEATER

HEATINGPUMP

HEATINGLOAD

FLOW

RETURN

OUTSIDE AIR SENSOR

Page 19: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

19

FLOAT VALVE

FEEDPIPE

EXPANSIONPIPE

FEED & EXPANSION TANK

VENTED TANK

HEATING LOAD ETC.FLOW

AUTOMATICAIR VENT

MAINSWATER

PUMPRETURN

BOILER

1BOILER

2BOILER

3BOILER

4

FLOW

TEMPERATURE GAUGE

PRESSUREGAUGE

TEMPERATURE GAUGE

SAFETYVALVE

2

3

4

BOILER 1

PUMP

(ROOF TOPAPPLICATION)

WATER SENSOR

AIRSENSOR

SEQUENCECONTROLLER

DRAIN DRAIN

DRAIN

DRAIN DRAIN

DRAIN

General notesIn any single or modularsystem, it is important that thewater flow rate through eachfiring boiler does not fallbelow the minimum requiredflow rate for that size of boiler(see table page 12).In applications where theminimum flow rate will not bemet a shunt pump should beinstalled, sized to provide theminimum stated flow rate perboiler at the equivalent boilerpressure drop plus pipeworkresistance.Both heating and shunt pumpsshould be controlled to providean overrun period to dissipateresidual heat.

VENTED SYSTEM

Example 4Boiler installation (typical)vented system.

UNVENTED SYSTEM

Example 5Boiler installation (typical)unvented system.

MAINSWATER

PERMANENTLYCONNECTED DOUBLECHECK VALVE ASSY

COLD FILL CONNECTION

(REMOVE IMMEDIATELY

AFTER FILLING)

ANTIGRAVITY

LOOP

LOCKSHIELD VALVELOCKSHIELD

VALVE

LOCKSHIELD VALVE

LOCKSHIELD VALVE

HAMWORTHYPORTLAND

PRESSURISATIONUNIT

PORTLANDEXPANSION

VESSEL

DRAINDRAIN 230 V.A.C.

1PH.50HzISOLATED SUPPL

HEATING LOAD ETC.FLOW

AUTOMATICAIR VENT

AUTOMATICAIR VENT

PUMPRETURN

BOILER

1BOILER

2BOILER

3BOILER

4

FLOW

TEMPERATURE GAUGE

PRESSUREGAUGE

TEMPERATURE GAUGE

SAFETYVALVE

2

3

4

BOILER 1

PUMP

(ROOF TOPAPPLICATION)

WATER SENSOR

AIRSENSOR

SEQUENCECONTROLLER

DRAIN DRAIN

DRAIN

DRAIN DRAIN

DRAIN

Page 20: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

20

230V AC 50HZFUSED ISOLATOR

LN3433323121201918171615

REMOTE CONTROL LOOP HI/LO (LINK ACROSS 3 - 4)Note terminal 3 is supplied with 230V 50Hz signal voltage.

REMOTE CONTROL LOOP ON/OFF (LINK ACROSS 1 - 2)Note terminal 1 is supplied with 230V 50Hz signal voltage.

SAFETY INTERLOCKCONTROLS

NORMAL RUN SIGNAL VOLT FREE CONNECTION

LOCKOUT SIGNALVOLT FREE CONNECTION

OVERHEAT SIGNALVOLT FREECONNECTION

VOLT FREE SIGNAL INPUTSRATED UP TO 230V

REMOTE HIGH / LOW

REMOTE TIME CLOCK,ON / OFF, SEQUENCER

Operating Voltage230 V 50 HZ AC

Operating CurrentStart and run0.4A

2 41 3

LN

230V~2Aoutput to

shunt pumprelay

PUREWELL CONTROL BOARD

Enlarged detail ofremote controlconnections

Enlarged detailof boiler panelwiring terminal

Purewell Classic - Fully Automatic

Wiring Diagram

Page 21: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

21

L

N

L

N

L

N

BROWNRED/BROWN

RED

BROWN

BROWN

BLUEBLUE

YELLOW

YELLOW

GREEN/YELLOWGREEN/YELLOWGREEN/YELLOW

GREEN/YELLOW

GAS VALVE

GAS VALVEECO LEADS

BULKHEADCONNECTORLIMIT

THERMOSTAT

LOW GAS PRESSURESWITCH (IF FITTED)

CONTROLTHERMOSTAT

GAS VALVEPLUG

GAS VALVESOCKET

FUSEDMAINS INLET

FUSE

T2A

MAINSFREE SOCKET

230V - 50HzSUPPLY FROMA FUSEDISOLATOR WITHMINIMUM 3mmCONTACTSEPARATION INALL POLES

V1L

C 2

NCC 12NC

NO

L

N

L

N

L

N

L

N

BROWNRED

BROWN

BROWN

BLUEBLUE

YELLOWYELLOW

GREEN/YELLOW

RED/BROWN

RED/BROWN

GREEN/YELLOWGREEN/YELLOW

GREEN/YELLOW

GAS VALVE

GAS VALVEECO LEADS

BULKHEADCONNECTOR

LIMITTHERMOSTAT

LOW GAS PRESSURESWITCH (IF FITTED)

CONTROLTHERMOSTAT

GAS VALVEPLUG

GAS VALVESOCKET

FUSEDMAINS INLET

FUSE

T2A

MAINSFREE SOCKET

230V - 50HzSUPPLY FROMA FUSEDISOLATOR WITHMINIMUM 3mmCONTACTSEPARATION INALL POLES

V1L

C 2

NCC 12NC

NO

L

N

L

N

REMOTEON/OFF LOOP

PLUG

REMOTEON/OFF LOOP

SOCKETFLUE DAMPER

ACTUATOR

'1'

'2'

'3' 'S1'

'S3'

'S2'REMOTE ON/OFFCONTROL LOOP(REMOVE WIRELINK IF UTILISED)

L

N

Note: Any timeclock controls or interlocks should be wired to interupt the supply to the boiler.

Note: Any timeclock controls or interlocks should be wired to interupt the supply to the boiler.

Standard Controls Wiring Diagram Schematic (with optional on/off damper)

Standard Controls Wiring Diagram Schematic

Purewell Classic - Permanent Pilot

Wiring Diagram

Page 22: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

22

H

500mm

D

H

500mm

D

D

D

Min chimney area

= sum of header

areas entering

For any atmospheric gas fired boilersystem, certain factors must be takeninto account to ensure the correctefficient and safe removal of flue gas.The table opposite gives diameters fora selection of standard typicalarrangements, and is for guidance only.Engineered flue solutions fromHamworthy may well result in areduction in sizes providing an efficientsystem at lower cost.

40 203 203 203 203 203 203

50 203 203 203 203 203 203

60 203 203 203 203 203 203

70 203 203 203 203 203 203

80 203 203 203 203 203 203

95 254 254 254 254 254 254

100 254 254 254 254 254 254

105 254 254 254 254 254 254

120 254 254 254 254 254 254

160 305 254 254 254

190 356 305 305 254

210 457 406 356 305 305 305

240 457 406 356 356 305 305

285 508 457 406 356 356 356

315 559 457 406 356 356 356

360 559 508 457 406 406 356

380 610 559 457 406 406 406

420 610 559 457 457 406 406

480 660 559 508 457 457 406

525 660 610 559 457 457 457

600 711 660 559 508 508 457

630 711 660 559 508 508 457

720 760 660 610 559 559 508

Height of chimney above draught diverter H m

Recommended Header Diameters D mm

No. ofBoilers

Power(Output)

kW20m15m10m6m3m2m

Guide to flue and header diameters

Consult Hamworthy

Midtherm flues with

details of application

design. Refer to

page 23

SingleBoilers

consult technicaldepartment at

Hamworthy FlueProducts for

multiple boilerapplications

MultipleBoilers

Page 23: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

23

Flue SystemHamworthy Purewell boilers aredesigned to be used with naturaldraught flue systems, which should be designed in accordance withcurrent regulations. The following points should be noted:

Each boiler must have its correct draught diverter fitted in an unmodified condition before connection to the flue system.

The bottom of the flue header should be at least 500mm (20”) above the draught diverter skirt bottom.

The flue system should be designedto achieve a negative suction at alltimes at the draught diverter outleton all modules in a bank. Foroptimum boiler performance,draught conditions should bebetween 0.05 to 0.125 mbar. Theboilers are suitable for connectionto a fan diluted system.

The flue system must be self supporting and facilitate access for cleaning and maintenance near theboiler connection.

When designing the flue system,care must be taken to ensure thatany condensate that may formwithin the system can be drainedsafely to a suitable waste point,and that the flue and drainmaterials are resistant to thecorrosive effect of condensate.

Purewell Classic boilers are suitablefor installation in a balancedcompartment in accordance withthe requirements of BS 6644.

Flues from Hamworthy

The Masterflue MF system from Hamworthy is a modular, twin wall, insulated, fullywelded flue solution, optimised for high efficiency and condensing boilerapplications.

Leak-Free

� Unique factory fitted tri-lip silicone gasket as standard- leak proof, high temperature seal, impervious to water and vapour

� All components fully welded and pressure tight, including traditionally troublesome elbows

Corrosion-Free

� Premium grade stainless steel construction for inner and outer walls

� 87 degree elbows and tees to ensure condensate drains effectively

Worry-Free

� Fast, push-fit assembly with no need for additional sealants

� Precision finished, reliable components for high quality installation

� Range of 'Tru-Align' adjustable wall brackets for simplifying alignment, achievinga faster installation and neater finish

� Continuous insulation from base to stub

� Fire resistant - 4 hour fire rated

� Stress-free thermal expansion

� CE mark accredited to meet 2005 legislation

Hamworthy also have the Masterflue ME flue component range which is a singlewall construction, fully welded flue system. The Masterflue ME range is totallycompatible and interchangeable with the Masterflue MF twin wall range.

Design & Install or Supply Only

Hamworthy's extensive knowledge of combustion systems, and the fluerequirements for each boiler, makes a boiler and flue package the perfect solutionfor every project.

Offering a comprehensive range of flue and chimney equipment for naturaldraught, fan assisted and fan dilution applications, Hamworthy works in partnershipwith Midtherm Engineering to provide a comprehensive flue design and installationpackage.

Alternatively, Hamworthy can provide components on a supply only basis for thecontractor to install.

Speak with Hamworthy Midtherm about your flue requirements and get peace ofmind on your next project - guaranteed.

Tel: 0845 450 2867

Email: [email protected]

Page 24: Hamworthy Purewell Classiccms.esi.info/Media/documents/Hamwo_PurewellVariHeat_ML.pdfreliable solutions that are easy to use and straightforward to maintain. The entry-level permanent

500002201 E

Customer Service Centre

Hamworthy Heating Limited

Fleets Corner, Poole, Dorset BH17 0HH

Telephone: 0845 450 2865Email: [email protected]: www.hamworthy-heating.comHamworthy reserves the right to make changes and improvements which may necessitate alteration to the specification without prior notice.