gx20w paperless recorder wireless model general specifications · gx90wd digital i/o modules. • a...
TRANSCRIPT
GeneralSpecifications
GX20WPaperless Recorder Wireless Model
Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
GS 04L51B11-01EN
GS 04L51B11-01EN©Copyright November 2014
9th Edition Nov. 25, 2019
OVERVIEWThe GX20W is a paperless recorder equipped with a gateway function for the ISA100 field wireless network. It can (1) display in real time on its touch screen measurement data from compatible field wireless devices, such as the YTMX580 Multi-input Temperature Transmitter, and I/O modules installed in the GX20W and (2) save the data in an SD card.● Upto50fieldwirelessdevicescanbeconnected.● Upto500channelsoffieldwirelessdevicedatacan
be measured.● TheGX20WreceivesPublish*1datafromfield
wireless devices and stores it in the Modbus registers.TheModbusclientfunctioncanbeusedto read the Modbus registers (which are assigned to communication channels) to display and record the data.*1 Actiontomeasuretheprocessvalueatintervals
presetinthefieldwirelessdeviceitselfandtransmit it via wireless communication
● Upto500channels*2canbemeasured.*2 MaximumtotalnumberofI/Ochannels.
● TheGX20Whavethelargeinternalmemory(1.2GB), and prolonged record and preservation are possible.
● Astheinputsignal,aDCvoltage,thermocouple,resistancetemperaturedetector,DI(DCVinput(TTL),contactsignal),mA(DCcurrent),orPulseinput can be set to each channel.
● Analogoutputiscapableofretransmissionoutputofvarioustypesofchannelsandalsomanualoutput.Itprovidescurrentoutputwithchannelsthatareisolated.(Analogoutputmodule)
● Inputandoutputhavemodulestructureanditcanextendthemeasily.(max.10)
● Amoduletypeissixtypes,ananaloginput,aanalog output, a digital input, a digital output, a digitalinput/output,andapulseinput.
● Theintuitiveoperationbyflick,pinchin,pinchout,and swipe are possible.
● Thepasttrendunderrecordingcanbeseamlesslydisplayed on a trend screen.
● Moreover,themeasurementdataofthetimespecifiedonthecalendarscreencanbesearchedand displayed.
● Variousfunctions,suchasafreehandmessage,aPDF/Exceloutputofareportfile,adirectoutputtoanetworkprinter,ascalemovementofatrenddisplay, and a buzzer sound, are equipped.
● ItcanbehookeduptonetworkviaEthernet,whichenablestoinformbyEmailandtomonitoronWebsiteaswellastotransferfilesbyusingFTP.Also,itcancommunicatewithModbus/RTUorModbus/TCP.
● Thewirelessgatewayfunctioncanbeconfiguredfromtheaccompanyingsoftware(FieldWirelessConfigurator).
● AsetupofGX20Wcanbeperformedon-linefromthewebbrowseronPC.Asetupbyoff-lineisalsopossible.(UsingHardwaresettingsoftware)
● UniversalViewersoftwareallowsaPCtodisplaywaveformsonitsscreenandtoprintoutwaveforms.
● TheGX20Whasactualvaluesthatunderliesaccuratemeasurements.(Inputmodules)
The measuring accuracies noted in the general specificationshaveamarginoferrorthattakesinto account the product's components and the equipmentusedforadjustmentandtesting.However,theactualvaluescalculatedfromtheaccuracytestingdatauponshipmentoftheinstrumentfromthefactoryareasfollows.Inputtype Measuringaccuracy*3(typicalvalue*4)
DCV 20mV ±(0.01%ofrdg+5μV)
60mV ±(0.01%ofrdg+5μV)
6V (1-5V) ±(0.01%ofrdg+2mV)
TC*5 R, S ± 1.1 °C
B ± 1.5 °C
K (-200.0 to 1370.0°C)
±(0.01%ofrdg+0.2°C)for0.0to 1370.0 °C;±(0.15%ofrdg+0.2°C)for-200.0 to 0.0 °C
K(-200.0to500.0 °C)
±0.2°Cfor0.0to500.0°C;±(0.15%ofrdg+0.2°C)for-200.0 to 0.0 °C)
J ±0.2°Cfor0.0to1100.0°C;±(0.10%ofrdg+0.2°C)for-200.0 to 0.0 °C
T ±0.2°Cfor0.0to400.0°C;±(0.10%ofrdg+0.2°C)for-200.0 to 0.0 °C
N ±(0.01%ofrdg+0.2°C)for0.0to 1300.0 °C;±(0.22%ofrdg+0.2°C)for-200.0 to 0.0 °C
Continuedonnextpage
GX20W
2
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
Inputtype Measuringaccuracy*3(typicalvalue*4)
RTD Pt100(-200.0 to 850.0 °C)
±(0.02%ofrdg+0.2°C )
Pt100(high resolution)(-150.00 to 150.00 °C)
±(0.02%ofrdg+0.16°C)
*3 AppliestoGX90XA-10-U2,A/Dintegrationtime16.67 ms or more, General operating conditions: 23±2ºC,55±10%RH,supplyvoltage90–132,180–250VAC,supplyfrequencywithin50/60Hz±1%,warm-upof30minutesormore,novibrationsorotherhindrancestoperformance.
*4 Forthemeasuringaccuracy(guaranteed),seethemodule'sgeneralspecifications(GS04L53B01-01EN).
*5 Thesevaluesdonotincludethereferencejunctioncompensationaccuracy.
rdg: reading value.
FUNCTIONAL SPECIFICATIONS (MAIN UNIT)
■ Input/OutputSpecifications PleaseseeGeneralSpecificationsforGX90XA/
GX90XD/GX90YD/GX90WD/GX90XP/GX90YAI/OModule.
Model Name GeneralSpecificationNo.
GX90XA* Analoginputmodule GS 04L53B01-01EN
GX90DX Digitalinputmodule
GX90YD Digitaloutputmodule
GX90WD Digitalinput/outputmodule
GX90XP Pulse input module
GX90YA Analogoutputmodule
* Thefollowingtypesarenotsupported. High-speeduniversal (-H0) 4-wireRTD/resistance(-R1) Highwithstandvoltage(-V1)
MeasuringFunctions• ThenumberofinstallablemodulesandI/Ochannels
Item SpecificationNumberofmodule Max.10
Numberofinput/outputmodule Max.500(ormax.100forAIonly)
Restrictionsofmoduleconnection:• Amaximumof10modulescanbeinstalled,as
atotalforGX90YDdigitaloutputmodulesandGX90WDdigitalI/Omodules.
• AmaximumofoneGX90WDdigitalI/Omodulecan be installed in GX20W.
• AmaximumoftwoGX90YAanalogoutputmodule can be installed in GX20W.
• ExpandableI/Oconnection Theexpansionmodule(GX90EX)andthe
expandableI/O(GX60)cannotbeconnectedtotheGX20W.
DisplayFunctionsDisplaygroups: Numberofgroups;60 Numberofchannelsthatcanbeassignedto
each group; 20 Scan interval: 100*1*2, 200*1*2, 500 ms*1, 1, 2, 5 s*1 Cannotbespecifiedifanelectromagneticrelay
scannertype(TypeSuffixCode:-T1)analoginputmodule is in use.
*2 CannotbespecifiedforL-modelDCV/TC/DI,scannertype(TypeSuffixCode:-L1).
Displaycolor(Trend/Bargraph/Digitaldisplay): Channel:Selectfrom24colors Adesireddisplaycolorcanbeselectedfreely
using its RGB value. Background:Selectfromwhiteorblack
Displaytype:● Trenddisplay(T-Y) Displaymethod:
Direction:Horizontal,verticalTrend interval: 5*1*2, 10*1*2, 15*1,30s/div,1,2,
5,10,15,20,30min/div,1,2,4,10h/div*1 Cannotbespecifiedifanelectromagneticrelay
scanner type analog input module is in use.*2 CannotbespecifiedforL-modelDCV/TC/DI,
scannertype(TypeSuffixCode:-L1). Trend line width: Thick, normal, thin Scale;Max.10
Current value bar graph, color scale band, and alarm point marks can be displayed on the scale.
Moving scale; Scale can be moved on any waveform. Abitmapimagescalecanbeattached.
Others;Grid(Auto,4to12),Tripline,Message,Zonedisplay,Partialexpandeddisplay
● Historicaltrenddisplay(T-Ydisplay) Redisplays the display data or event data in the
internalmemoryorexternalstoragemedium Timeaxisoperation:Thetimeaxiscanbe
reducedorexpanded. Datasearch:Waveformsfromtheinternal
memory can be displayed through the specificationofadateandtime,calendar,eachsummary Movingscale;Abitmapimagescalecanbeattached.
Allhistoricaltrendscanbedisplayedinonescreen.
● Bargraphdisplay Direction:Verticalorhorizontal Scale:Displayascaleforeachchannel
Color scale band, and alarm point marks can be displayed on the scale.
● Digitaldisplay Displaysmeasuredvaluesnumerically ADIinputstatecanbedisplayedasanarbitrary
characterstring(0=Off/1=On,etc.) Updaterate:0.5s● Overviewdisplay Displayformat:Allchannels,eachgroups Displaysthemeasuredvaluesofallchannels
and the alarm statuses● Alarmsummarydisplay Displaysalogofupto1000alarms Specifyanalarmwiththecursorandjumpto
the corresponding section on the historical trend display.
3
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
● Messagesummarydisplay Timeandcontentofupto500messages
(including 50 add messages) Specifyamessagewiththecursorandjumpto
the corresponding section on the historical trend display.
● Memory summary display Displaystheinformation(upto500)ofthedata
in the memory Specifyafilewiththecursorandjumptothe
corresponding section on the historical trend display.
● Reportdisplay Displaysthereportdataresidingintheinternal
memory Formoredetails,see"MATHEMATICAL
FUNCTIONSWITHREPORTFUNCTION(/MT)."● Logdisplay Displaystheeventlog,errorlog,communication
log,FTPlog,Weblog,e-maillog,SNTPlog,DHCPlog,andModbuslog.
● Multi-paneldisplay Dividesthescreenintotwotosixsectionsand
displayssomedifferentdisplayformats.● Internalswitch/relaystatedisplay DisplaystheinternalswitchandON/OFFstateofDO OperatestheinternalswitchandON/OFFstate● Otherdisplays Networkinformationdisplay Systeminformationdisplay Systemconfigurationdisplay
AutoscrollON/OFF: The displayed groups can be automatically
switchedataspecifiedinterval. The display switches in ascending group order.
Namesofchannels:
Channel number; Analog input: 01 to 10 Digital input: 01 to 16 Digital output: 01 to 06 Digital input/output; DI: 01 to 08, DO: 09 to 14 Pulse input: 01 to 10 Analog output: 01 to 04
X X X X
Slot number; 0 to 9 Unit number; 0
Tags:• Tag and Tag numbers can be displayed.• Tagnumber;Numberofcharacters:Upto16 Displayablecharacters:Alphanumericcharacters Tag numbers can be enabled or disabled.• Tag;Numberofcharacters:Upto32 Displayablecharacters:Alphanumericcharacters
Message:• Write messages to the trend display.• Numberofmessages:100• Numberofcharacters:Upto32• Write method: Write a preset message or write
an arbitrary message on the spot.• Write destination: Select only the displayed
group or all groups.• Automessage:Writeamessagewhenthe
GX20Wrecoversfromapowerfailurewhilememory sampling is in progress.
Write a message when the trend interval is switched during memory sampling.
Addmessage:• Write messages to the past data positions.• Message: The same as the “Message” item
above Numberofwritablemessagesperfile:50
messages(including10freehandmessages)Freehandmessage:
• Can be written by dedicated pen. Numberofwritablemessagesperfile:50
messages(including10Addmessages)
DataSavingFunctionsInternalmemory:• Temporarilysavesvarioustypesofdata.• Medium:Flashmemory• Filestoragecapacity;1.2GB
Externalstoragemedium:• Medium:SDcard(SD/SDHC)(upto32GB)• Format:FAT32orFAT16
Datatype:• Displaydata,Eventdata,Alarmsummarydata,
Manual sampled data, Screen image data, Setup data, and Report data
Displaydata:• Target:Measurement(input/outputmodule)/
math/communicationchannels,alarmsummary,message summary
Description:Maximumorminimumvalueperrecording interval
• Recordingintervals:Determinedbythetrendinterval,recordingdatatype(displaydata/displaydata+eventdata)Trendinterval(div) Numberofchannels
Displaydata
Displaydata+Eventdata
5 s 200 100
10 s 500 200
15 s 1000 500
30 s or longer 1000 1000
• Datasize; Analoginputdata:12bytes/ch. Analogoutputdata:12bytes/ch. DigitalI/Odata:4bytes/ch. Mathchanneldata:12bytes/ch. Communicationchanneldata:12bytes/ch.
• Filesize:Upto18MB• Numberoffiles:Upto1000(includingevent
data) Operationintheinternalmemory:FIFO(FirstInFirstOut)
4
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
• Dataformat:Binaryortext• Recording: Records data at all times.• Displaydatafilesampletime Measurement channel = 30. Math Channel = 0
InternalMemory 1.2 GB
Trendinterval(minute/div) 30 minutes
Recording interval (s) 60 s
Total sample time Approx.6years
Eventdata:• Target:Measurement(input/outputmodule)/
math/communicationchannels,alarmsummary,message summary, operation log
Description:Instantaneousvalueperrecordinginterval
• Recordingintervals:Determinedbythesamplerate,recordingdatatype(displaydata/displaydata+eventdata)
Trendinterval(div) NumberofchannelsDisplaydata
Displaydata+Eventdata
100 ms 500 100
200 ms 500 200
500 ms 1000 500
1 s or longer 1000 1000
• Datasize; Analoginputdata:6bytes/ch. Analogoutputdata:6bytes/ch. DigitalI/Odata:2bytes/ch. Mathchanneldata:6bytes/ch. Communicationchanneldata:6bytes/ch.
• Filesize:Upto18MB• Numberoffiles:Upto1000(includingdisplay
data)• Operationintheinternalmemory:FIFO(FirstIn
FirstOut)• Dataformat:Binaryortext• Mode;Free:Recordsdataatalltimes.
Trigger: Starts recording data when a certaineventoccursandrecordsforthespecifiedinterval.
Repetition trigger: Repeat Trigger mode• Eventdatafilesampletime Measurement channel = 30. Math Channel = 0
InternalMemory 1.2 GB
Recording interval (s) 1 s
Total sample time Approx.2.4month
AlarmFunctions• Numberofalarms:Uptofouralarms(level)for
each measurement channels• Alarmtype:Highlimit,lowlimit,differencehigh
limit,differencelowlimit,highlimitonrate-of-changealarm,lowlimitonrate-of-changealarm,delay high limit, and delay low limit
• Alarmdelaytime:1sto24hours(foreachchannel)
• Rate-of-changecalculationintervalofrate-of-change alarms: 1 to 32 times the scan interval (common to all channels)
• Hysteresis:0.0to5.0%ofthespan(foreachalarm (level))
• Alarmoutput:Outputtotheinternalswitch Internalswitchoperation:AND/ORoperation
selectable• Display:Displaysthestatusontherespective
operation screen and an alarm icon on the status display section when an alarm occurs.
Displayoperation:Holdornotholdthedisplayuntil the alarm acknowledge operation
• Alarmhidefunction(alarmnologgingfunction) Not display alarms nor record to the alarm
summary(foreachchannel)• Alarminformation:Displaysalogofalarm
occurrences on the alarm summary• Reflash:Thedurationforwhichthereflashrelays
are deactivated can be set to 500 ms, 1 s, or 2 s.• IndividualalarmACKfunction: Alarmdisplayandrelayoutputcanbecancelled
on individual alarms
EventActionFunctions• Eventaction:Executeaspecifiedoperation
when a given event occurs.• Numberofsettings:50 Events: Remote control input, etc. Timer;Numberoftimers:12 Matchtimetimer;Numberoftimers:12 Action:Specifymemorystart/stop,alarmACK,
etc.
SecurityFunctions• Operationlockfunction:Limitationstotouch
operation,accesstotheexternalstoragemedium, and various operations
• Loginfunction:Onlyregistereduserscanoperate the GX20W.
Itcanbesettoeachoftouchoperationandcommunication access.
SystemadministratorsandUsers:50(totally) NumberofAuthorityofuser:10level
ManualSampledData• Item:Instantaneousvalueatanarbitrarytime• Target:Measurement(input/outputmodule)/
math/communicationchannels• Numberofrecordingchannels;Max.100• Maximumnumberofdatavaluesthattheinternal
memory can store: 400• Dataformat:Text
ReportData• Item:Reportateachscheduledtimeofreport• Target:Measurement(input/outputmodule)/
math/communicationchannels• Maximumnumberofreportsthattheinternal
memory can store: 800• Dataformat:Text
SnapshotData• Item:Displayedscreenimagedata• Dataformat:PNG• Outputdestination:Externalmediumor
communication output
5
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Jul. 7, 2020-00
SetupData• Item:GX20Wsetupdata• Dataformat:Text• Output/readdestination(forsaving/loading):
Externalmedium
ClockFunctions• Clock:Withacalendarfunction• Accuracy:±5ppm(0to50°C),excludinga
delay(of1second,maximum)causedeachtimethe power is turned on.
• Timesetting:Usingtouchoperation,communicationcommand,eventactionfunction,orSNTPclientfunction
• Timeadjustmentmethod: Limitinwhichthetimeisgraduallyadjusted:
Selectfromtheavailablesettingsbetween5sand 15 s.
Whethertochangeanout-of-limitoperationimmediately or report it as an error can be selected.
While memory sampling: Corrects the time by 1 msforeachsecond.
Whilememoryisstopped:Immediatelychangethe time.
• DST:Thedate/timeforswitchingbetweenstandardtimeandDSTcanbespecified.
• Timezone:SetsthetimedifferencefromGMT.• Dateformat:Select"YYYY/MM/DD","MM/DD/
YYYY","DD/MM/YYYY"or"DD.MM.YYYY". MMexpressioncanbeselectedfromthe
numericcharacterorellipsis.Ex.January:01orJan
Thedelimitercanbeselectedfrom"/",".","-".
EthernetCommunicationFunctions• Electricalspecifications:ConformstoIEEE802.3• Connection:Ethernet(10BASE-T/100BASE-TX)• Max.segmentlength:100m• Max.connectingconfiguration:CascadeMax.4
level(10BASE-T),Max.2level(100BASE-TX)• Connector: RJ-45• Protocols:TCP,UDP,IP,ICMP,ARP,DHCP,
HTTP,FTP,SMTP,SNTP,Modbus,anddedicated protocols
• E-mailclient:Automaticallysende-mailatspecifiedtimes.
E-mail is sent by events as below.- Alarmoccurring/alarmcanceling(Max.50ch)- Recoverfrompowerfailure- Report data generating- Storagemediumerror,FTPclientfunction
error- Specifiedtimeperiod
POPbeforeSMTPandSMTPauthentication(PLAINandCRAM-MD5)isavailable.
• FTPclient:AutomaticallytransferdatafilestotheFTPserver.
Applicablefiles:Displaydata,eventdata,screenimage data, report data, etc.
• FTPServer:Transferfiles,deletefiles,manipulatedirectories,andoutputfilelistsoftheGX20W.
Numberofthesimultaneousconnection:Max.4
• Web server: GX20W real-time monitoring and settingchanges/operationscanbeperformedwith the Web browser.
The screen layout can be determined independentlyofthescreenoftheGX20Wmainunit.
Numberofthesimultaneousconnection:Max.4• SNTPclient:InquiresthetimetotheSNTP
server and sets the GX20W.• SNTPserver:OutputstheGX20Wtime. Time resolution: 10 ms• DHCPclient:Automaticallyobtainthenetwork
addresssettingsfromtheDHCPserver.• Modbusclient:Readsdatafromanotherdevice
and writes to the registers. Numberofconnectablesever;Max.32• Modbus server: Loads measurement and math
channel data. Loads and writes communication channel data. Some control commands such as memory start. Modbus client register access limitations.
Numberofthesimultaneousconnection:Max.4• Setting/Measurementserver:Operate,set,and
outputdataoftheGX20Wusingadedicatedprotocol.
Numberofthesimultaneousconnection:Max.4• DARWINcompatiblecommunicationserver:
SupportssomeDARWINcommands. Communication with GX20W is possible using
DARWINcommunicationcommands.• Output-relatedcommands:Outputmeasurement
(IO)channeldata,Outputcalculationchanneldata,Outputrelaystatus,Outputthepositionofthedecimalpointforthemeasurement(IO)channel,Outputthepositionofthedecimalpointforthecalculationchannel,Outputtheinformationonsystemconfiguration
• Setup-related commands: Range, Scale unit, Alarm,Time,Movingaverage
• Operation-relatedcommands:Resetalarm,Resettimer,StartMATHcalculation,Rebuildsystem,Initialize,Inputcommunication,OutputcommunicationDO,Writemessage
CommunicationChannelFunctions• Numberofcommunicationchannels;500(C001
to C500) TheModbusclientfunctionisusedtoread
the Modbus registers and assign them to communication channels.
BatchFunction• Function:Datamanagementusingbatchnames.
Entertextfieldsandbatchcommentsinthedatafile.• Batchname:Addedtothefilenameofthe
display data and event data. Structure:Batchnumber(upto32characters)+
lot number (up to 8 digits) Use/notuseselectableforlotnumber,on/off
selectableforautoincrementfunction.• Textfield:Addstexttothedisplaydataandevent
data. Thereare24availabletextfields. Upto20titlecharactersand30othercharacters
canbeenteredperfield.• Batchcomment:Addstexttothedisplaydata
and event data. 3comments(max.50characters)areavailable.
6
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
PrinterOutputFunction• SnapshotDatacanbeprintedoutwithany
LAN-connectedprintersupportingtheHPPCL5clanguage and the port 9100.
SSLCommunicationFunctions Communicationthatsendsandreceivesinformation
encrypted by the SSL (Secure Socket Layer) protocol is possible.• Serverfunction: Supportedservers:HTTPserverandFTPserver
(Port number: 443 when encryption is used) Private key: Created in GX20W and saved in the
internal memory Servercertificate:Servercertificatescreatedby
users can be saved in the internal memory. Self-signedcertificatescanbecreatedin
GX20W.• Clientfunction: Supportedclients:FTPclientandSMTPclient
(Port number: 443 when encryption is used) Trustedcertificate:Trustedcertificates(atotal
ofupto100KB)canbesavedintheinternalmemory.
ElectronicSignatureFunction Electronicsignaturescanbeaddedtoreportfiles
createdinPDFformatusingthePDFformcreationfunction.Anelectronicsignatureisprovidedeachtimeareportfileiscreated.• Certificateforelectronicsignature:Certificates
forelectronicsignaturescreatedbyuserscanbesaved in the internal memory.
OtherFunctions• Buzzer: GX20W makes a buzzer sound at touch
screen operation, or when alarm occurs.• Backlightsaverfunction:Dimorturnoffthe
LCDbacklightifthereisnokeyoperationforaspecifiedtime.
• Favoritedisplay:RegisterfrequentlyuseddisplaystotheFavoriteandshowthemthroughsimple operation.
• ThemainalarmisindicatedusingtheMENUkeyLED.
No alarm: Blue (same condition as power-on) Alarmcondition:Red.• Userfunctionfeature:Abutton(userfunction
key) to which the user can assign a desired functionisprovided.Itcanbeassignedtoaneventtriggeredbytheeventactionfunction.
• Firmwareupdatefunction:TheWebapplicationortheIOmodulefirmwarecanbeupdatedbyoperating GX20W.
■ WirelessCommunicationSpecificationsCommunication protocol: Compliant with
ISA100.11a(IEEE802.15.4)Frequency:2.400-2.4835GHzlicensefreeISM
bandRFTransmitterpower:Max.11.6dBm(fixed)Datarate:250kbpsAntenna:Externalantenna,+2dBiOmnidirectional
typeRadiosecurity:AES128bitcodifiedNumberoffieldwirelessdeviceconnections:Upto
50
■ FunctionsNotAvailableontheGX20W(firmwareversionnumber4.06)
FunctionGX20W-2 specifications(firmwareversionnumber4.06)
GX20-2 specifications(firmwareversionnumber4.06)
HighwithstandvoltageAImodule(GX90XA-10-V1)
Cannot be used Supported
High-speedAImodule(GX90XA-04-H0)
Cannot be used Supported
4-wireRTD/resistance module(GX90XA-06-R1)
Cannot be used Supported
PIDcontrolmodule(GX90UT)
Cannot be used Supported
Measuremet mode Measurement mode cannot be used.
SelectfromNormal,Highspeed,Dualinterval.
Custom display (/CGoption)components
Control components cannot be used.
Controller, control alarm indicator, components were added.
Initializefunction Initializefunctioncannot be used.
Control settings, individual settings (display group settings, recording channel settings) are available.
Controlfuction Controlfunction cannot be used.
• Control settings• Prpgram pattern
settings• Control display
(control group, tuning, program select, program operation, control over view, control alarm summary, control summary) were added
• program pattern load/save
Event action Event action functioncannot be used.
• Group select ofeventtrigger(dual interval measurement )•Loadpatternfile
Continuedonnextpage
7
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
FunctionGX20W-2 specifications(firmwareversionnumber4.06)
GX20-2 specifications(firmwareversionnumber4.06)
Control event action
Control event action cannot be used.
Control event functionwasadded.
Operationlock/user property
Control operation cannot be used.
Control operation are available.
DARWINcompatible communication command
Thefollowingcommands cannot be used.•Handling
depending on the high-speed AI,4-wireRTD/resistance module
• Command (EX, PS, MS) that runs when the measurement mode is set to dualInterval•PIDmoduleoutputbyCFcommand•Handling
depending on the Measurement Mode
•Handlingdepending on the high-speed AI,4-wireRTD/resistance module
• Command that runs when the measurement mode is set to dualInterval•SupportDR
command (SZ, SC, PT ) are added•HandlingofSettingsAvailableontheGX/GPbutNotonDARWIN•Handling
depending on the Measurement Mode
Program control(/PG)
Not supported Supported
HARDWARE SPECIFICATIONS (MAIN UNIT)
DisplayDisplayunit*:12.1-inchTFTcolorLCD(800×600dots)* Asmallnumberofmissingorsteady-onLCD
pixelsandminorvariationsinbrightnessuniformityisanormaldisplaycharacteristicandnotamalfunction.
Touchscreen:4 wire resistive touch screen
WirelessantennaAntennaconnectortype:Ntypejackatchedantennaimpedance:50Ω
Construction• Mounting:Flushpanelmounting(onavertical
plane)• Mountingangle:Inclinedbackwardupto30
degreesfromahorizontalplane.Leftandrighthorizontal
• Panel thickness: 2 to 26 mm• Material;
Case: Metal plate Bezel and display cover: Polycarbonate• Color;
Case: Smoke blue Bezel: Charcoal grey light• Frontpanel:Wateranddustproof:Complieswith
IEC529-IP65andNEMANo.250TYPE4(exceptExternalIcingTest),exceptforside-by-sidemounting
• Externaldimensions: When installing modules 288(W)×288(H)×220(D)mm When uninstalling modules 288(W)×288(H)×169(D)mm (D:depthfromthepanelmountingplane)
• Weight: Approx.6.4kg (excludingmodules,antenna,antennacable)
PowerSupply• Ratedsupplyvoltage:100to240VAC• Allowablepowersupplyvoltagerange:90to132,
180to264VAC• Ratedpowersupplyfrequency:50/60Hz• Power consumption:Supplyvoltage
LCDbacklightoff
Normaloperation
Maximum
100VAC 38VA 47VA 90VA
240VAC 50VA 59VA 110VA
* ThefollowingcombinationsareassumedforLCDbacklightoffandnormaloperation.
5AImodules,4DOmodules,1DImodule• Module power supply voltage: The total allowable
powerconsumptionofrespectivemodulesisupto 20 W.
• Allowableinterruptiontime:Lessthan1cycleofthepowersupplyfrequency
8
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
Isolation• Insulationresistance:BetweentheEthernet,
RS-422/485,andeachinsulationterminalsandearth:20MΩorgreaterat500VDC
• Withstand voltage: Betweenthepowerterminalandearth:3000VACat50/60Hzforoneminute
Between the contact output terminal and earth: 3000VACat50/60Hzforoneminute
Betweentheinput/outputmodulesandearth:DependsonthespecificationofI/Omodule.
• Grounding: Be sure to set a low grounding resistance.
• Isolation:
Power terminal
The circuits divided by lines are insulated mutually.
Internal circuit
FAIL output terminalEthernet portRS-422/485 terminalInput and output module terminal
Input and output module internal circuitEarth (PE) terminalRS-232 terminalSD card slotUSB port
CompliantStandardsGX20W contains the wireless module.Pleaseconfirmthatainstallationregionfulfillsastandards,requireadditionalregulatoryinformationandapprovals, contact to Yokogawa Electric Corporation.GX20Wsatisfiesthefollowingstandards:•CSA:CSA22.2No.61010-1,OvervoltagecategoryII*1, pollution degree 2 *2,andCSA-C22.2NO.61010-2-030-12
•UL:UL61010-1,UL61010-2-030(CSANRTL/C)
• CE marking (Onlythemodelswith/CEoption): Radio equipment directive (RE)
Radio Spectrum: EN 300 328EMC: EN 301 489-1, EN301 489-17, EN61326-1 ClassATable2(Foruseinindustrial locations), EN 61000-3-2, EN 61000-3-3Safety: EN61010-1,EN61010-2-030,Overvoltage
categoryII*1 Pollution degree 2 *2 Measurement category *3
EN 62331• EMC and Radio communication compliance in AustraliaandNewZealand(RCM):AS/NZS4268,AS/NZS2772.2,EN61326-1,ClassA
•FCC:FCCPart15SubpartBClassAGX20WcontainstransmittermoduleFCCID:
SGJWFC001.(Part15SubpartC)•IC:ICES-003ClassA
GX20WcontainstransmittermoduleIC:8999A-WIC001(RSS-Gen,RSS-210)
•CompliantwithISA100.11a(IEEE802.15.4)
*1 Overvoltagecategory II: Describesanumberwhichdefinesatransient
overvoltage condition. Impliestheregulationforimpulsewithstand
voltage. “II”appliestoelectricalequipmentwhich
issuppliedfromthefixedinstallationlikeadistribution board.
*2 Pollutiondegree2: Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or surfaceresistivityisadhering.
“2” applies to normal indoor atmosphere. Normally, only non-conductive pollution occurs.
*3 Measurementcategory:Dependsonthespecificationofeachmodules
Category Measurementcategory
Description Remarks
II CATII Availableinthetestingand measuring circuits directly connected to a usage location (receptacle or the like) ofalow-voltagemainpowersupplyfacility.
Appliances,portable equipment, etc.
III CATIII Availableinthetestingand measuring circuits connected to a power distributionportionofa low-voltage main powersupplyfacility.
Distributionboard, circuit breaker, etc.
IV CATIV Availableinthetestingand measuring circuits connected to a power sourceofalow-voltage main power supplyfacility.
verhead wire, cable systems, etc.
NormalOperatingConditions• Powersupplyvoltage:100to240VAC±10%• Powersupplyfrequency:50/60Hz±2%• Ambienttemperature:0to50°C• Ambienthumidity:20to80%RH(at5to40°C)
(no condensation)• Magneticfield:400A/morless(DCand50/60
Hz)• Vibration: 5≤f<8.4Hzamplitude3.5mm(peak) 8.4≤f≤160Hzacceleration9.8m/s2
• Shock: Non-energization,500m/s2 orless,approximate10 ms, 6 directions (±X, ±Y, ±Z), 3 times in each direction
• Mounting position: Can be inclined up to 30 degreesbackward.Leftandrighthorizontalwhen installing the panel mount and wall mount.
• Altitude:2000morless• Installationlocation:Indoors• Warm-uptime:Atleast30minutesafterpower
on
9
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
OtherSpecifications• Memorybackup:Abuilt-inlithiumbatterybacks
up the settings and runs the clock• RecommendedreplacementperiodsofBattery:
Approximately10years(atroomtemperature)
TransportandStorageConditions• Ambienttemperature:–25to60°C• Ambienthumidity:5to95%RH(no
condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:490m/s2maximum(inpackaged
condition)
EXTERNAL DIMENSIONS AND PANEL CUTOUT DIMENSIONS
GX20W
360 min.(1.417)
361
min
.
Panel cut dimensions
281+2 0
281
+2 0
*1: With module*2: Without module*3: When fixing cable
(*1)(*2)
(Dimensions after attachingthe mounting bracket)
(Dimensions before attachingthe mounting bracket)
(Allowable panel thickness)
7.5
(0.3
0)9.
4 (1
0.37
)28
0.2
(11.
03)
247.3 (9.74)
32.3 (1.27)
MAX 219.3 (8.63)168.8 (6.65)
152.6 (6.01)2 to 26
28 (1.11)
295.
2 (1
1.62
)
288
(11.
34)
148
(5.8
3)
295.2 (11.62)
288 (11.34)144 (5.67)
280.2 (11.03)
(*3)MIN 293 (11.54)
Unit: mm (approx. inch)Unless otherwise specified,tolerance is ±3% (however,tolerance is ±0.3 mm whenbelow 10 mm).
(11.06)
(14.
21)
(11.
06)
Rearview
Power supply terminalRS-422A/485 terminal (/C3)USB port (/UH)Ethernet portFAIL/STATUS terminal (/FL)
VGA output terminal (/D5)
I/O module (slot 0)I/O module (slot 1)I/O module (slot 2)I/O module (slot 3)I/O module (slot 4)
I/O module (slot 5)I/O module (slot 6)I/O module (slot 7)I/O module (slot 8)I/O module (slot 9)
Remote antenna connector
Precautions to Be Taken While WiringWith a screw terminal, we recommend that you use a crimp-onlugwithaninsulationsleeve(M4forpowersupplywiring,M3forsignalwiring).Recommended signal wiring crimp-on lugN1.25-MS3(JSTMfg.Co.,Ltd.)
10
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
RemoteAntenna
Ø20.5(0.81)
□ Remote anttena
Anttena
• Non-direction antenna
• Gain : +2 dBi
• Part number: F9193DH
Unit: mm (approx. inch)Unless otherwise specified,tolerance is ±3% (however,tolerance is ±0.3 mm whenbelow 10 mm).
150(
5.91
) 18
(0.7
1)
RemoteAntennaCable□ Antenna cable High-frequency coaxial cable
• Sheath dia : 11.11mm
Main unit
Antenna
CableLength: 1m or 3m (selectable)
<Without arrester>
Main unit
Antenna
Cable 2Length: 3 m or10m(selectable)
Cable 1Length: 1m or 3 m (selectable)
<With arrester>
Arrester
Attachthearresterinthemiddleoftheantennaextensioncable.Groundthearrestergroundterminal.Connect the grounding wire to the GX20W’s protective ground terminal.
RemoteAntenaBracket
2-intch pipe
71.7(2.82)17(0.67) 37.3(1.47)17.5(0.69)
87.7
(3.4
5)
98(3.86)
135(
5.31
)
292(
11.5
0)
minimum R67
Unit: mm (approx. inch)Unless otherwise specified, tolerance is ±3% (however, tolerance is ±0.3 mm when below 10 mm).
11
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
SPECIFICATIONS OF OPTIONAL FUNCTIONS
SERIALCOMMUNICATIONINTERFACE(/C3)• Connection:EIARS-422/485• Protocol:DedicatedprotocolorModbusprotocol• Setting/measurementserverfunction:Operation,
settingoroutputofmeasurementdataareavailable by dedicated protocol.
• Synchronization: Start-stop synchronization• Transmissionmode(RS-422/485):
RS-422:Four-wirehalf-duplexmulti-dropconnection (1:n (n = 1 to 31)) RS485:Two-wirehalf-duplexmulti-dropconnection (1:n (n = 1 to 31))
• Baud rate: 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200 bps
• Datalength7or8bits• Start bit: 1 bit• Stop bit: 1 bit or 2 bit• Parity:ODD,EVEN,orNONE• HandshakingOff:Off,XON:XON,XON:RS,and
CS: RS• Communication distance; 1200 m (Applicablecable:AWG24to16)• Modbus/RTUcommunication:Readingorwriting
ofmeasurementdataonotherinstrumentsisavailable by Modbus protocol.
• Operationmodes:Masterorslave• Executionofacommunicationcommandusinga
barcode:Theenteredtextcanbeexecutedasacommunication command.
CUSTOMDISPLAY(/CG) UsingDXA170DAQStudio,screencreation
software,acustomscreencanbeconstructedanddisplayed in which display components (such as trend,digital,andbargraphs)arefreelyplaced.
ThescreendataistransferredfromDAQStudiotothe internal memory via communication, or loaded fromanexternalmediumtotheinternalmemoryand displayed.• Numberofscreens:30(internalmemory)• Displaycomponents:
• Normal components (digital value, bar graph, tag No., tag comment, simple digital value, simple bar graph, alarm mark, unit, alarm indicator, lower-limit span value, upper-limit span value, group name, systemicon,memorysamplebar,date/timeview, batch name, and user name)
• Trend components (trend group display (with scale board))
• List components (alarm list view and message list view)
• Operationcomponents(DO(DOoperable),internal switch (internal switch operable), numeric value operations (viewing data ofandwritingdatatocommunicationchannels), and button operations (writing numeric values, operating bits, switching screens,andexecutingcommunicationcommands)
• Textcomponents(labels)• Figurecomponents(lineview,rectangle
view, and circle view)• Imagecomponents(PNGimagedata)• Batch components (Batch number, Lot
number,Textfield,Batchcomment,Batchgroupnumber*)
* OnlyonGX20WwiththeMultibatchfunction(/BToption)
• Configuringscreens:Screencreationsoftware CreationusingDXA170DAQStudio(GX20W
doesnothaveacreationfunction)• Saving/loadingscreendata: Aspecifiedscreenorallthescreensis/are
loadedfromanexternalstoragemediumtotheinternalmemory,oraspecifiedscreenorallthescreensintheinternalmemoryis/aresavedonanexternalstoragemedium.
VGAVIDEOOUTPUT(/D5)(mustbeselected)• Externaldisplay: Resolution:800×600dots(VGA) Connector:15-pinD-Sub(female)
EtherNet/IPCOMMUNICATION(PLCcommunicationprotocol)(/E1)
CanbejoinedtoanEthernet/IPnetworkasanadapter (or a server).• LoadingdatafromtheI/Ochannelorcalculation
channel(/MT) I/Ochannel:500 Calculation channel: 200• Loadingandwritingdatafrom/tothe
communication channel Communication channel: 500• Maximumnumberofconnections:20(upto10at
theTCP/IPlevel)
WTCOMMUNICATION(/E2) Collects data by connecting to WT equipment
manufacturedbyYokogawaMeters&InstrumentsCorp. via Ethernet communication.• Supported models: WT1800, WT500, and
WT300• Numberofconnectableunits:16• Communicationcycle:500ms/1s/2s/5s/10s/15
s/20s/30s• Typesofdatathatcanbeobtained:Voltage,
current,power,powerfactor,phase,electricalenergy,high-frequencywave,etc.
• Numberofdataallocations:300
FAILOUTPUT(/FL)(mustbeselected)• Contact: C contact, 1 point• FAILoutput: The relay contact output on the rear panel
indicatestheoccurrenceofCPUfailure. Relay operation: Energized during normal
operationandde-energizedonCPUfailure.• Status output: The relay contact, which is de-
energized in normal output state, is energized upontheoccurrenceofamemory/mediaerror,measurement error, communication error, recording stop, or alarm.
12
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
• Ratedpowersupplyvoltage:24VDCor250VACorless
• Ratedloadcurrent:3A(DC)/3A(AC),resistanceload
• Min.loadcurrent:100mA• Recommendedreplacementperiodsofcontact: Electrical:30,000moreON-OFFoperations,
Mechanical:5,000,000moreON-OFFoperations
LogSCALE(/LG) Alogarithmicvoltagethathasbeenconvertedfrom
a physical value is applied to the GX20W, and then the GX20W’s Log scale (logarithmic scale) is used to display and record the physical value.• Inputtype:Loginput(logarithmicinput),Pseudo
loginput:Aninputthatsupportspseudologs,Loglinearinput:Inputthatislinearonalogarithmic scale.
• Range:20mV/60mV/200mV/1V/2V/6V/ 20V/50V
• Scalable range:• Log input: 1.00E-15to1.00E+15(15decade
maximum) Scale_L<Scale_U Ifthelowerlimitmantissais1.00,the
differencebetweentheexponentsmustbe1 or more.
Ifthelowerlimitmantissaisavalueotherthan1.00,thedifferencebetweentheexponentsmustbe2ormore.
• PseudoLogInput/Loglinearinput 1.00E-15to1.00E+15(15decade
maximum) The higher limit mantissa is the same as
the lower limit mantissa). Ifthelowerlimitmantissais1.00,thevalue
mustbebetween1.00E–15and1.00E+15,thedifferencebetweentheexponentsmustbe1ormore,andthemaximumdecadesis15.
Ifthelowerlimitmantissaisavalueotherthan 1.00, the value must be between 1.00E–15and9.99E+14,thedifferencebetweentheexponentsmustbe1ormoreandthemaximumdecadesis15.
• Alarmtype:Highlimit,lowlimit,delayhighlimit,and delay low limit
• Alarmsettingrange:TherangeconvertedintotheLOGscalecorrespondingto-5%to105%ofthe span width.
• Alarmhysteresis:Fixedto0• Green band setting range: The lower limit to the
upperlimitofthescale.However,thelowerlimitofthedisplaypositionmustbesmallerthantheupper limit.
• Positionofthedecimalpoint:1to2• Misc: Nonlinear input is possible by correcting
the input value
MATHEMATICAL FUNCTIONS WITH REPORT FUNCTION(/MT)MathematicalFunction:• Numberofmathchannels;200• Operation: Generalarithmeticoperations:Fourarithmetic
operations(+,-,*,/),squareroot,absolute,common logarithm, natural logarithm, exponential,andpower
Relationaloperations:<,≤,>,≥,=,and≠ Logicoperations:AND,OR,NOT,andXOR Statisticaloperations:TLOGorCLOG Specialoperations:PRE,HOLD,RESET,and
CARRY Conditional operation: [a?b:c] Bitoperation:BIT Integerextractingoperation:INT Remainderextractingoperation:MOD Trigonometricfunctions:SIN,COS• Computationaccuracy:Double-precisionfloating
point• Datathatcanbeused; Channel data: Measurement channels (0001 to
6516),mathematicalchannels(A001toA200),Communication channels (C001 to C500), Communication channels raw data (RC001 to RC500),Constants:100(K001toK100),Variableconstant:W001toW100,Internalswitch:100(S001toS100),Flag:20(F01toF20),Recordingstate(REC01),Integerdata:Z000toZ999
Logicmathfunction:Afunctionthatoutputscalculatedresultsas0or1
toDOsorinternalswitches• Numberoflogiccalculationsmaths:50• Expression:Upto120characters• Computation type: Basic arithmetic, relational,
logical, conditional, bit• Datathatcanbeused:Allchanneldata• Logic math: LM001 to LM050• Outputdestination:DOchannels,internal
switches (only when set to Manual in either case)• Setting change: Cannot be changed during
recording• Mathinterval:100ms(fastest)
Reportfunction:• Numberofreportchannels;60• Reporttypes:Hourly+daily,daily+weekly,daily
+monthly,Batch,Daycustom• Computationtypes:Average,maximum,
minimum, sum, or instantaneous value• Unitofsum:OFF,/s,/min,/hour,/day• Reporttemplates:OfficeOpenXMLspreadsheet
files(whichcanbedisplayedwithMicrosoftOfficeExcel)orPDFfilescanbeoutputorprintedoutwithanyLAN-connectedprintersupportingtheHPPCL5clanguageandtheport9100.
13
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
USBINTERFACE(/UH)(mustbeselected)• USBport:ComplieswithUSB2.0andhost
function• Numberofports:2(oneeachonthefrontpanel
and rear panel)• Connectabledevices:Onlyconnectthedevices
listed below to prevent damage to the devices.Keyboard:ComplieswithHIDClassVer.1.1 104/89keyboard(US)and109/89
keyboard (Japanese)Mouse:ComplieswithHIDClassVer.1.1Externalmedium:USBflashmemory Doesnotguaranteetheoperationofall
USBflashmemories Externalmediumsuchasaharddisk,ZIP,
MO,andopticaldiscsarenotsupported.Barcodereader:USBHIDClassVer.1.1
compatible English(U.S.)standardUSBkeyboard
compatible• Executionofacommunicationcommandusinga
barcode:Theenteredtextcanbeexecutedasacommunication command.
• Powersupply:5V±10%,500mA*1*1: Deviceswhichneedmorethan500mAtotalbuspower
for2portscannotbeconnectedatthesametime. Forlowpowereddevices(buspower<100mA):
5V±5% Forhighpowereddevices(buspower<500mA):
5V±10%
AEROSPACEHEATTREATMENT(/AH)SupportsheattreatmentapplicationAMS2750/
NADCAP.Schedulemanagementforperiodicallyexecuting
calibrationcorrectionconfigurationandthelike.Incorrectioncoefficientmodeofcalibration
correction,twobiasescanbespecified:onebased on thermocouple and another based on device
• Numberofmanageableschedules:12• Calibration correction mode: Off,Linearizerapproximation,Linearizerbias,
correctionfactor• Numberofsetpoints:2to12• Notificationcontents Title,Notificationmessage,DuedateNotificationbuzzercanbesounded.
MULTI-BATCHFUNCTION(/BT)Recordingstart/stopanddatafilecreationis
possibleforeachbatch.• Numberofmulti-batches:max.12• Batchsingleoperation:Memorystart/stop,math
reset, message writing• Batchoverviewoperation:Computationstart/
stop,reportstart/stop,manualsampling,setupdatasave/load
• Scan interval: 500 ms, 1 s, 2 s, 5 s (common to all batches)
• Datatype:DisplayoreventonlyTriggermodenotavailableforeventdata.
• Recording interval: Common to all batches• Datafile:Displayoreventdatafilecreatedfor
each batch
• Numberofdisplaygroups: 12max.perbatch Numberofchannelspergroup:20 Channelsassignedtothedisplaygroupofeach
batch and those set as recording channels are recordedtodatafiles.
• Batchsinglesettings:Group,tripline,fileheader,datafilename,textfield,batchnumber,lotnumber
OPC-UASERVER(/E3)DataacquiredbytheGX20Wcanbeaccessed
throughEthernetcommunicationfromahostsystem(OPC-UAclient).
• Communication Mode:OPC-UAServer Encoding:UABinary Protocol:OPCUATCP Maximumnumberofconnections:3sessions Profile MicroEmbeddedDeviceServer• Security Type: None Encryption: None Login:Anonymous,Username• Dataacquisition: Measurement value, alarm status, and alarm
value Computation value, alarm status, and alarm
value Communication value, alarm status, and alarm
value Batchinformation• Datawriting:Measurementchannel(DOchannel
only), communication channel, alarm value, batchinformation
• Otheracquiredinformation:Devicename,serialnumber, time, device status
• Port number: 4840 (changeable: 1 to 65535)• Numberofitems:300max.(MonitoredItem/
Session)• Fastestperiod:100ms• Service set:Discovery FindServers,GetEndpoints
SecureChannel OpenSecureChannel,CloseSecureChannel
Session CreateSession,ActivateSession,CloseSession
View Browse,BrowseNext,TranslateBrowsePathsToNodeIds
Attribute Read, Write
MonitoredItem CreateMonitoredItems,ModifyMonitoredItems,DeleteMonitoredItems,SetMonitoringMode
Subscription CreateSubscription,ModifySubscription,DeleteSubscriptions,Publish,Republish,SetPublishingMode
14
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
SLMPCOMMUNICATION(MitsubishiPLC)(/E4)Protocolfunctionthatenablesconnectionfrom
a GX20W to Mitsubishi Electric PLCs without sequencer programs.
• Numberofconnectiondestinationservers:16max.• Readcycle:100ms/200ms/500ms/1s/
2s/5s/10s/20s/30s/1min• Communicable internal data: Specialrelay(SM),specialregister(SD),input
(X), output (Y), internal relay (M), latch relay (L), annunciator(F),edgerelay(V),linkrelay(B),dataregister(D),linkregister(W),timercontact(TS), timer coil (TC), current timer value (TN), integration timer contact (SS), integration timer coil (SC), current integration timer value (SN), counter contact (CS), counter coil (CC), current counter value (CN), special link relay (SB), special link register (SW), direct access input (DX),directaccessoutput(DY),indexregister(Z),fileregister(R,ZR),extendeddataregister(D),extendedlinkregister(W)
Devicecodeisindicatedinparentheses.
ACCOMPANYINGSOFTWARE(onDVD)• FieldWirelessConfigurator• FieldWirelessManagementTool
FieldMateisrequiredtoconfigurefieldwirelessdevices.ParameterconfigurationviaISA100.11awireless communication requires version R2.02.01 orlater.Parameterconfigurationviainfraredcommunication requires version R2.03.00 or later.
FordetailsonFieldMate,seeFieldMateVersatileDeviceManagementWizard(GS01R01A01-01E).
SystemRequirements(Hardaware)1
Server 2003Processor:IntelPentium42.8GHzormoreMemory: 1 GB or moreHardDiskDrive:20GBormore(minimumfreespace:15GBormore)Display:1024x768Highcolor,32bitNetwork port: Ethernet Network port
SystemRequirements(Software)OS2:Windows7ProfessionalEdition(32bit/64bit)Windows Server 2008 Enterprise Service Pack 2 or later(32bit/64bit)Windows Server 2008 Enterprise R2 (64 bit)
1 FieldWirelessConfiguratorandFieldWirelessManagement Tool can be installed in one PC.
2 Language: Japanese or English
15
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
INPUT/OUTPUTMODULESPECIFICATIONS
ANALOGINPUTMODULE(ModelGX90XA)
DIGITALINPUTMODULE(ModelGX90XD)
DIGITALOUTPUTMODULE(ModelGX90YD)
DIGITALINPUT/OUTPUTMODULE(ModelGX90WD)
PULSEINPUTMODULE(ModelGX90XP)
ANALOGOUTPUTMODULE(ModelGX90YA)
PleaseseeGX90XA/GX90XD/GX90YD/GX90WD/GX90XP/GX90YAInput/OutputModuleGeneralSpecification(GS04L53B01-01EN).
ACCESSORIESRemoteAntennaCable(optionalaccessories)(Onlybyorderofoption) SpecificationofCable:8D-SFA(HDPE) OutsideDiameterofCable:11.1mm MinimumBendRadius:69.6mm(whenfixing) 174 mm (when wiring) Cable End Treatment: N type connector, one end is maleandtheotherisfemale. Operationaltemperaturerange:-40to+85°C(-40to185°F)
* “Whenfixing”showsthebendingradiusforfixing(thestateismaintainedforalongtime).
“When wiring” shows the bending radius while checking the wiring position. This bending radius issetlargerthanthatforfixinginordertopreventdamage to the cable because the cable is likely to berepeatedlybentwhencheckingthefinalwiringposition.
APPLICATION SOFTWARESMARTDAC+STANDARD• Universalviewer• Webapplication/HardwareconfiguratorDownloadthelatestversionofthesoftwarefromthefollowingURL; www.smartdacplus.com/software/en/
OperatingenvironmentOS:
OS TypeWindows 7 HomePremiumSP1(32-bitand64-bit
Editions)
ProfessionalSP1(32-bitand64-bitEditions)
Windows 8.1 Update
ProUpdate
Windows 10 Home(32-bitand64-bitEditions)
Pro (32-bit and 64-bit Editions)
Enterprise (32-bit and 64-bit editions)
Processorandmainmemory:OS Processorandmainmemory
Windows 7Windows 8.1Windows 10
32-biteditionIntelPentium4,3GHzorfasterx64orx86,2GBormore
64-biteditionIntelx64processorthatisequivalenttoIntelPentium4,3GHzorfaster,2 GB or more
Browser:Browser Version
WindowsInternetExplorer InternetExplorer11
Google Chrome �
Harddisk:• 100MBormoreoffreespace
Display:• AvideocardthatisrecommendedfortheOS
andadisplaythatissupportedbytheOS,hasaresolutionof1024x768orhigher,andthatcanshow 65,536 colors (16-bit, high color) or more.
16
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
UniversalViewersoftwareTheuniversalviewercandisplaythefollowingdatagenerated by the recorder on the screen and print it out on the printer.• Displaydatafile• Eventdatafile• Reportdatafile(IncludingHour,Day,WeekMonth)• Manualsampledatafile
• Viewerfunction Waveformdisplay,digitaldisplay,circulardisplay,
list display, report display, operation log display etc.
• Dataconversion: FileconversiontoASCIIorMS-Excelformat
Webapplication/Hardwareconfigurator• OnlinesettingonWebbrowser• OfflinesettingonWebbrowserSettings can be made using browsers such as InternetExplorer11andChrome(ExcludingHardwareconfigurator).
17
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
MODEL AND SUFFIX CODESModelCode Optionalcode Description
GX20W-2E/BC/D5/FL/UH Paperless recorder Wireless model (Panel mount type, Large display) *2*5
-2:LargememoryType(Max.measurementchannels:500ch)
E:Displaylanguage:English,degF,DST(summer/wintertime)*3
/BC:Blackcover*1
/D5:VGAoutput*1
/FL:Failoutput,1point*1
/UH:USBinterface(Host2ports)*1
Optionalfeatures /AH Aerospaceheattreatment
/BT Multi-batchfunction
/C3 RS-422/485
/CE ConformtoCEmarking(REandRoHSDirective)*8
/CEN NotconformtoCEmarking*8
/CG Custom display *4
/E1 EtherNet/IPcommunication
/E2 WT communication
/E3 OPC-UAserver
/E4 SLMP communication (Mitsubishi PLC)
/LG Log scale
/MT Mathematicalfunction(withreportfunction)*6*7
*1 /BC,D5,/FL,and/UHarestandardfunctionsonGX20W.*2 TheexpandableI/O(GX60)cannotbeconnectedtotheGX20W.*3 TheDisplaylanguageisselectablefromEnglish,German,French,Russian,Korean,Chinese,Japanese.(AsofMar.,2013) Toconfirmthecurrentavailablelanguages,pleasevisitthefollowingwebsite. URL:http://www.yokogawa.com/ns/language/*4 CreatingcustomdisplaysrequiresDXA170DAQStudio(soldseparately).(GX20Wdoesnothaveacreationfunction.)*5 Includesthebasicrighttousetheaccompanyingsoftware.*6 Optionalcode/MT(MATH)requiredifusingtheGX90XD'sorGX90WD'spulseinput.*7 The/MToption(computation)isrequiredtoperformpulseintegrationonGX90XPpulseinputmodules.*8 Either/CEor/CENoptionismandatorytobespecified.
Analoginput/outputmodule,DigitalI/Omodule(soldseparately):MODELandSUFFIXCode(GX90XA)MODELandSUFFIXCode(GX90XD)MODELandSUFFIXCode(GX90YD)MODELandSUFFIXCode(GX90WD)MODELandSUFFIXCode(GX90XP)MODELandSUFFIXCode(GX90YA) PleaseseeGX90XA/GX90XD/GX90YD/GX90WD/GX90XP/GX90YAInput/OutputModuleGeneralSpecification
(GS 04L53B01-01EN.)
StandardAccessoriesProduct Qty
Mounting bracket 2
SDmemorycard(1GB) 1
Stylus pen (touch pen) 1
+2dBiRemoteAntenna 1
FieldWirelessConfigurator,FieldWirelessManagementTool(providedDVD-ROM)
1
Tag sheet 1
Sheet 1
Dummycover(Foremptyslots) 10
18
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L51B11-01EN Nov. 25, 2019-00
OptionalAccessories(SoldSeparately)Product Partno. Description
Remoteantennacable*1(With remote antenna mounting bracket)
F9193UA 1 m
F9193UB 3 m
F9193UC 4m(1m+3m)with arrestor
F9193UD 6m(3m+3m)with arrestor
F9193UE 13m(3m+10m)with arrestor
Product Model/partno.ModelSDmemorycard(1GB) 773001
Mounting bracket B8740DY
Stylus pen (touch pen) B8740BZ
ShuntresisterforM3terminal(250Ω±0.1%) 415940
ShuntresisterforM3terminal(100Ω±0.1%) 415941
ShuntresisterforM3terminal(10Ω±0.1%) 415942
ShuntresisterforClampterminal(250Ω±0.1%) 438920
ShuntresisterforClampterminal(100Ω±0.1%) 438921
ShuntresisterforClampterminal(10Ω±0.1%) 438922
Dummycover B8740CZ
ApplicationSoftware(SoldSeparately)Model Description OS
DXA170 DAQStudio Windows7/8/8.1/10
GA10 DataLoggingSoftware Windows7/8.1/10Windows Server 2008/2012
Calibrationcertificate(soldseparately)Foranaloginputmodules,acalibrationcertificateisprovidedonanindividualmodulebasis.
Testcertificate(QIC,soldseparately)ForanaloginputmodulesanddigitalI/Omodules,aQICisprovidedonanindividualmodulebasis.
User'sManualProductuser'smanualscanbedownloadedorviewedatthefollowingURL.Toviewtheuser'smanual,youneedtouseAdobeReader7orlaterbyAdobeSystems.URL:www.smartdacplus.com/manual/en/
ProductPurchaseSpecificationsTheGX20Wiscomposedofthemainunit,I/Omodules.GX90XA(Somemodulecannotbeused),GX90XD,GX90YD,GX90WD,andGX90XP,GX90YAI/Omodulescanbe purchased individually.Remote antenna cables (with mounting brackets) are sold separately.TheexpandableI/O(GX60)cannotbeconnectedtotheGX20W.
Trademarks TheTCP/IPsoftwareusedinthisproductandthedocumentforthatTCP/IPsoftwarearebasedinpartonBSDnetworkingsoftware,Release1licensedfromTheRegentsoftheUniversityofCalifornia.
•SMARTDAC+istrademarkofYokogawaElectricCorporation.•Microsoft,MSandWindowsareregisteredtrademarksofMicrosoftCorporationUSA.•PentiumareregisteredtrademarksofIntelCorporation.•ModbusisaregisteredtrademarkofAEGSchneider.•Othercompanyand/orproductnamesareregisteredtrademarkoftheirmanufactures.