guidelines relay setting

Upload: 1453h

Post on 03-Jun-2018

314 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 Guidelines Relay Setting

    1/467

    MODEL SETTING CALCULATIONS FOR TYPICAL IEDs

    LINE PROTECTION SETTING GUIDE LINES

    PROTECTION SYSTEM AUDIT CHECK LIST

    RECOMMENDATIONS FOR PROTECTION MANAGEMENT

    SUB-COMMITTEE ON RELAY/PROTECTION UNDER TASK

    FORCE FOR POWER SYSTEM ANALYSIS UNDER

    CONTIGENCIES

  • 8/11/2019 Guidelines Relay Setting

    2/467

    Protection subcommittee report

    Preamble

    As a follow up of one of the recommendations of the Enquiry Committee headed by Chairman,CEA on grid disturbances that took place in Indian grid on 30th and 31st July 2012, Ministry of

    Power constituted a Task Force on Power System Analysis under Contingencies in December

    2012. The Terms of Reference of Task Force broadly cover analysis of the network behaviour

    under normal conditions and contingencies, review of the philosophy of operation of protection

    relays, review of islanding schemes and technological options to improve the performance of

    the grid.

    Apart from the main Task Force two more sub-committees were constituted. One for system

    studies for July-September 2013 conditions and another for examining philosophy of relay and

    protection coordination.

    The tasks assigned to the protection sub-committee were to review the protection setting

    philosophy (including load encroachment, power swing blocking, out of step protection, back-up

    protections) for protection relays installed at 765kV, 400kV, 220kV (132kV in NER) transmission

    system and prepare procedure for protection audit. This was submitted to the Task Force on

    22.07.2013.

    Further one more task assigned to the protection sub-committee was to prepare model setting

    calculations for typical IEDs used in protection of 400kV line, transformer, reactor and busbar.

    This document gives the model setting calculations, line protection setting guide lines,

    protection system audit check lists, recommendations for protection system management and

    some details connected with protection audit.

  • 8/11/2019 Guidelines Relay Setting

    3/467

    Protection subcommittee report

    Acknowledgement

    The Protection sub-committee thanks members of Task Force for Power System Analysis

    under Contingencies for all the support and encouragement. Further the Protection sub-

    committee acknowledges the contribution from Mr Rajil Srivastava, Mr Abhay Kumar, Mr

    Kailash Rathore of Power Grid, Mr Shaik Nadeem of ABB and Mr Vijaya Kumar of PRDC to the

    work carried out by the sub - committee.

    Sub-committee

    Convener

    B.S. Pandey, Power Grid

    Members

    P. P. Francis, NTPC

    S.G. Patki, Tata Power

    R. H. Satpute, MSETCL

    Nagaraja, PRDC

    Bapuji Palki, ABBVikas Saxena, Jindal Power

  • 8/11/2019 Guidelines Relay Setting

    4/467

    Protection subcommittee report

    LIST OF CONTENTS

    PreambleSection Description Pages

    1 : Introduction 1-3

    2 : Model setting calculations -Line 1-149

    3 : Model setting calculations-Transformer 1-132

    4 : Model setting calculations- Shunt Reactor 1-120

    5 : Model setting calculations- Busbar 1-15

    6 : Relay setting guide lines for transmission lines 1-19

    7 : Recommendations for protection system management 1-5

    8 : Check list for audit of fault clearance system 1-16

    9 : Details of protection audit 1-5

  • 8/11/2019 Guidelines Relay Setting

    5/467

    Protection subcommittee report

    MODEL SETTING CALCULATION DOCUMENTS FOR

    TYPICAL IEDs USED FOR THE PROTECTION OF DIFFERENT

    POWER SYSTEM ELEMENTS IN 220kV, 400kV AND 765 kV

    SUBSTATIONS

    INTRODUCTION

    In addition to setting criteria guide lines prepared by Subcommittee on relay/protection under

    Task Force for Power System Analysis under Contingencies for 220kV, 400kV and 765kV

    transmission lines, the Subcommittee has prepared model setting calculation documents for

    IEDs used for protection of following elements.

    400kV Transmission line

    400/220/33kV Auto Transformer

    400kV Shunt Reactor

    400kV Bus Bar

    While guide lines as finalized by the Subcommittee have been used for the setting calculation

    document on transmission lines, for other power system elements like transformer, shunt

    reactor and bus bar, guide lines as given in CBIP documents and manufacturer's manuals have

    been used. The documents presented should serve as a model to various utilities in preparing

    similar documents for different power system elements that are used in 220kV, 400kV and

    765kV EHV and UHV transmission systems. The documents are prepared to meet following

    expectations given in the Protection subcommittee report.

    The numerical terminals referred as IED (Intelligent electronic device) contain apart from main

    protection functions several other protection & supervision functions which may or may not be

  • 8/11/2019 Guidelines Relay Setting

    6/467

    Protection subcommittee report

    and Control functions. It is also recommended that graphical representation of distance relay

    zones on R-X plane including phase selection, load encroachment & power swing

    characteristics should be done showing exact setting calculated.

    Each of these documents has following main sections:

    1. BASIC SYSTEM PARAMETERS: This section contains all the system related information

    including single line diagram that will be required in carrying out the setting calculations andthus form an important part. This information is unique to each element like line, transformer,

    reactor or busbar. This helps not only in carrying out the setting calculations; it also helps in

    future, if there is a need to revisit this data.

    2. TERMINAL IDENTIFICATION AND LIST OF FUNCTIONS: This section contains brief details

    of the IED and lists all the functions that are available in the IED and clearly identifies the ones

    which are activated and those that are required to be set. Thus this section serves as a checklist

    of all the functions used and gives a quick overview of functions that needs to be set.

    3. SETTING CALCULATIONS AND RECOMMENDED SETTINGS: This section contains

    subsections viz., Setting guide lines, Setting calculations and Recommended settings for each

    function.

    Setting guidelines:This subsection contains guide lines for each of the parameter to be set for

    the function. The guidelines are taken from the report prepared by Protection subcommittee and

    CBIP guide lines mentioned in the report. In addition to the main settings the IED also has

    various other settings that need to be set. Guide lines for these settings are taken mainly from

    manufacturer's user manuals and these are also given here in brief. In such instances, where

    the setting is straight forward and does not involve any calculations, the recommended value

    are given and where applicable the reasoning for the adopted setting is given. Settingcalculation based on the relay type, relay function is a major concern for utilities and

    understanding each setting and basis for setting helps in arriving at right settings. Further the

    guide lines help not only in carrying out the setting calculations, but also help in future, if

    there is a need to revisit the settings to take corrective actions in case of any mal-operations

  • 8/11/2019 Guidelines Relay Setting

    7/467

    Protection subcommittee report

    mal-operations (if excel based sheets with macros are used for setting calculations, they should

    be used cautiously in a transparent manner and explained the reasoning associated with

    macros / formulae).

    Recommended settings: This subsection details recommended setting list with settings for all

    the parameters. Settings given in this section need to be used by site engineer for setting the

    IED.

    It is recommended that these model setting calculations are reviewed periodically to take care ofany changes in manufacturer's design, use of simulation tools, RTDS, or better understanding

    of settings and guidelines etc. It is also recommended that setting calculation documents are

    prepared for IEDs of different manufacturers that are used in the system.

    Disclaimer: The model setting calculations and recommended settings presented in this

    document are for the specific case considered here. Further, the make of the relay considered is

    also for illustration purpose only. In the settings which do not require any calculations based on

    network data, few of the settings may need review for other practical cases. For settings that

    require calculations, power system network data pertaining to respective cases is to be

    considered. However, the methodology adopted in this example shall be used for calculating the

    line and other equipment protection relay settings and arriving at list of recommended settings.

  • 8/11/2019 Guidelines Relay Setting

    8/467

    MODEL SETTING CALCULATION DOCUMENT FOR A TYPICAL

    IED USED FOR TRANSMISSION LINE PROTECTION

  • 8/11/2019 Guidelines Relay Setting

    9/467

    Model setting calculation document for Transmission Line

    TABLE OF CONTENTS

    TABLE OF CONTENTS...............................................................................................................2

    1.0 BASIC SYSTEM PARAMETERS .........................................................................................8

    1.1 Network line diagram of the protected line and adjacent circuits ...................................8

    1.2 Single line diagram of the double circuit line....................................................................9

    1.3 Line parameters ..................................................................................................................9

    2.0 TERMINAL IDENTIFICATION AND LIST OF FUNCTIONS................................................10

    2.1 REL670...............................................................................................................................10

    2.1.1 Terminal Identification..........................................................................................102.1.2 List of functions available and those used............................................................10

    2.2 REC670 ..............................................................................................................................16

    2.2.1 Terminal identification..........................................................................................162.2.2 List of functions available and those used............................................................16

    3.0 SETTING CALCULATIONSAND RECOMMENDED SETTINGS FOR REL670.................23

    3.1 REL670...............................................................................................................................23

    3.1.1 Analog Inputs.......................................................................................................233.1.2 Local Human-Machine Interface ..........................................................................263.1.3 Indication LEDs....................................................................................................263.1.4 Time Synchronization ..........................................................................................283.1.5 Parameter Setting Groups ...................................................................................313.1.6 Test Mode Functionality TEST.............................................................................32

    3.1.7

    IED Identifiers......................................................................................................34

    3.1.8 Rated System Frequency PRIMVAL....................................................................353.1.9 Signal Matrix For Analog Inputs SMAI .................................................................353.1.10 General settings of Distance protection zones.....................................................373.1.11 Distance Protection Zone, Quadrilateral Characteristic (Zone 1) ZMQPDIS.........393.1.12 Distance Protection Zone, Quadrilateral Characteristic (Zone 2) ZMQAPDIS .....443.1.13 Distance Protection Zone, Quadrilateral Characteristic (Zone 3) ZMQAPDIS ......473.1.14 Distance Protection Zone, Quadrilateral Characteristic (Zone 5) ZMQAPDIS ......503.1.15 Phase Selection with Load Encroachment, Quadrilateral Characteristic FDPSPDIS

    543.1.16 Broken Conductor Check BRCPTOC (Normally used for Alarm purpose only) ....623.1.17 Tripping Logic SMPPTRC....................................................................................633.1.18 Trip Matrix Logic TMAGGIO.................................................................................653.1.19 Automatic Switch Onto Fault Logic, Voltage And Current Based ZCVPSOF........663.1.20 Power Swing Detection ZMRPSB........................................................................68

  • 8/11/2019 Guidelines Relay Setting

    10/467

    Model setting calculation document for Transmission Line

    3.2.1 Analog Inputs.......................................................................................................933.2.2 Local Human-Machine Interface ..........................................................................95

    3.2.3 Indication LEDs....................................................................................................963.2.4 Time Synchronization ..........................................................................................973.2.5 Parameter Setting Groups .................................................................................1013.2.6 Test Mode Functionality TEST...........................................................................1023.2.7 IED Identifiers....................................................................................................1033.2.8 Rated System Frequency PRIMVAL..................................................................1033.2.9 Signal Matrix For Analog Inputs SMAI ...............................................................1033.2.10 Synchrocheck function (SYN1) ..........................................................................1063.2.11 Autorecloser SMBRREC....................................................................................1103.2.12 Disturbance Report DRPRDRE .........................................................................118

    APPENDIX-A: COORDINATION OF 400KV LINE PROTECTION ZONE-2 AND ZONE-3 WITH

    IDMT O/C & E/F RELAYS OF 400KV SIDE OF ICT AND 220KV LINE................................... 121

    APPENDIX-B: EFFECT OF NETWORK CHANGE DUE TO A LINE LILO ON RELAY

    SETTINGS OF LILO LINE & ADJACENT LINES.................................................................... 131

  • 8/11/2019 Guidelines Relay Setting

    11/467

    Model setting calculation document for Transmission Line

    LIST OF FIGURES

    Figure 1-1: Network line diagram of the protected line ....................................................................................... 8Figure 1-2: Equivalent representation of the protected line with source impedance .......................................... 9Figure 3-1: Setting angles for discrimination of forward and reverse fault........................................................ 37Figure 3-2: Characteristic for phase-to-earth measuring, ohm/loop domain..................................................... 39Figure 3-3: Characteristic for phase-to-phase measuring................................................................................. 40Figure 3-4: Relation between distance protection ZMQPDIS and FDPSPDIS for phase-to-earth faultloop>60........................................... ............................................................................................................... 54Figure 3-5: Relation between distance protection (ZMQPDIS) and FDPSPDIS characteristic for phase-to-phase fault for line>60........................................... ........................................................................................ 55

    Figure 3-6: Load encroachment characteristic .................................................................................................. 56Figure 3-7: Operating characteristic for ZMRPSB function ............................................................................... 68Figure 3-8: Characteristics for Phase to Phase faults ....................................................................................... 75Figure 3-9: Characteristics for Phase to Earth faults ........................................................................................ 76

    Figure A-1: System details for the network under consideration for relay setting........................................... 123Figure A-2: 3-Ph fault current for 220 kV side fault ......................................................................................... 124Figure A-3: Over Current Relay Curve Co-ordination and Operating Time .................................................... 125Figure A-4: Ph-G fault current for 220 kV side fault ........................................................................................ 126

    Figure A-5: Earth Fault Relay Curve Co-ordination and Operating Time ....................................................... 127Figure A-6: Earth fault relay co-ordination for 400 kV bus fault at Station B (Remote bus of the protected line)......................................................................................................................................................................... 128Figure A-7: Earth fault relay operating time co-ordinated with Zone 3 time setting ....................................... 129

    Figure B-1: Network line diagram of the system after the LILO of one circuit of line AB................................ 131Figure B-2: SLG Fault at bus B with source at Station A and Line A-S out of service and Earthed ............... 134Figure B-3: SLG Fault at bus B with sources at Station A & B and Line A-S out of service and Earthed ...... 135Figure B-4: SLG Fault at bus B with sources at Station A, B & S and Line A-S out of service and Earthed .. 136

    Figure B-5: SLG Fault at bus B with source at Station A and Line B-S out of service and Earthed ............... 137

    Figure B-6: SLG Fault at bus B with sources at Station A & B and Line B-S out of service and Earthed ...... 138Figure B-7: SLG Fault at bus B with sources at Station A, B & S and Line B-S out of service and Earthed .. 139Figure B-8: SLG Fault at bus S with source at Station A and Line A-B out of service and Earthed ............... 140Figure B-9: SLG Fault at bus S with sources at Station A & B and Line A-B out of service and Earthed ...... 141Figure B-10: SLG Fault at bus S with sources at Station A, B & S and Line A-B out of service and Earthed 142Figure B-11: SLG Fault at bus B with source at Station A .............................................................................. 143Figure B-12: SLG Fault at bus B with sources at Station A and B.................................................................. 144Figure B-13: SLG Fault at bus B with sources at Station A, B & S ................................................................. 145Figure B-14: SLG Fault at bus S with source at Station A .............................................................................. 146

    Figure B-15: SLG Fault at bus S with sources at Station A and B.................................................................. 147Figure B-16: SLG Fault at bus S with sources at Station A, B & S ................................................................. 148

  • 8/11/2019 Guidelines Relay Setting

    12/467

    Model setting calculation document for Transmission Line

    LIST OF TABLES

    Table 2-1: List of functions in REL670 .......................................................................................................... 10Table 2-2: List of functions in REC670 .......................................................................................................... 16Table 3-1: Analog inputs ................................................................................................................................. 24Table 3-2: Local human machine interface ....................................................................................................... 26Table 3-3: LEDGEN Non group settings (basic) ............................................................................................... 27Table 3-4: Time synchronization settings.......................................................................................................... 29Table 3-5: Parameter setting group................................................................................................................... 32Table 3-6: Test mode functionality .................................................................................................................... 34Table 3-7: IED Identifiers ................................................................................................................................... 34

    Table 3-8: Rated system frequency .................................................................................................................. 35Table 3-9: Signal Matrix For Analog Inputs ....................................................................................................... 36Table 3-10: General settings for distance protection ........................................................................................ 38Table 3-11: ZONE 1 Settings ............................................................................................................................ 43Table 3-12: ZONE 2 Settings ............................................................................................................................ 46Table 3-13: ZONE 3 Settings........................................................................................................................... 49Table 3-14: ZONE 5 Settings........................................................................................................................... 52Table 3-15: Phase Selection with Load Encroachment, Quadrilateral Characteristic ...................................... 61Table 3-16: Broken Conductor Check ............................................................................................................... 63Table 3-17: Tripping Logic................................................................................................................................. 64Table 3-18: Trip Matrix Logic............................................................................................................................. 65Table 3-19: Automatic Switch Onto Fault Logic ................................................................................................ 67Table 3-20: Power Swing Detection ............................................................................................................... 73Table 3-21: Scheme Communication Logic For Distance Or Overcurrent Protection ...................................... 77Table 3-22: Stub Protection............................................................................................................................... 78Table 3-23: Fuse Failure Supervision ............................................................................................................... 79Table 3-24: Four Step Residual Overcurrent Protection ................................................................................... 83Table 3-25: Two Step Overvoltage Protection .................................................................................................. 86Table 3-26: Setting of fault locator values ......................................................................................................... 89

    Table 3-27: Disturbance Report ........................................................................................................................ 92Table 3-28: Analog Inputs ................................................................................................................................. 93Table 3-29: Local human machine interface ..................................................................................................... 96Table 3-30: LEDGEN Non group settings (basic) ............................................................................................. 96Table 3-31: Time Synchronization..................................................................................................................... 99Table 3-32: Parameter Setting Groups ........................................................................................................... 102Table 3-33: Test Mode Functionality ............................................................................................................... 102Table 3-34: IED Identifiers ............................................................................................................................... 103Table 3-35: Rated System Frequency............................................................................................................. 103

    Table 3-36: Signal Matrix For Analog Inputs ................................................................................................... 105

    Table 3-37: Synchrocheck function ................................................................................................................. 108Table 3-38: Autorecloser ................................................................................................................................. 116Table 3-39: Disturbance Report ...................................................................................................................... 119Table A-1 Settings of Over current and Earth fault relays............................................................................... 122Table B-1: Fault At Station-B With Source At Station A and Line A-S Earthed........................................... 134Table B-2: Fault At Station-B With Sources At Station A & B and Line A-S Earthed .......................... 135

  • 8/11/2019 Guidelines Relay Setting

    13/467

    Model setting calculation document for Transmission Line

    Table B-13: Fault At Station-S With Sources At Station A & B .................................................................... 147Table B-14: Fault At Station-S With Sources At Station A, B & S................................................................ 148

  • 8/11/2019 Guidelines Relay Setting

    14/467

    Model setting calculation document for Transmission Line

    SETTING CALCULATION EXAMPLE

    SUB-STATION: Station-A

    FEEDER: 400kV OHL from Station-A to Station-B

    PROTECTION ELEMENT: Main-I Protection

    Protection schematic Drg. Ref. No. XXXXXX

  • 8/11/2019 Guidelines Relay Setting

    15/467

    Model setting calculation document for Transmission Line

    1.0 BASIC SYSTEM PARAMETERS

    1.1 Network line diagram of the protected line and adjacent circuitsThe network line diagram (Figure 1-1) of the system under consideration showing

    protected line along with adjacent associated elements should be collected. The

    network diagram should indicate the voltage level, line length, transformer/generator

    rated MVA & fault contributions of each element for 3-ph fault at station-A and for

    3-ph fault at Station-B.

  • 8/11/2019 Guidelines Relay Setting

    16/467

    Model setting calculation document for Transmission Line

    1.2 Single line diagram of the double circuit line

    Equivalent representation of the protected line based on network line diagram indicated at Figure 1-1 is prepared as shown in Figure 1-2 indicating the source fault impedance at station-A and Station-

    B, positive and zero sequence impedance of the protected line.

    Figure 1-2: Equivalent representation of the protected line with source impedance

    1.3 Line parameters

    Line: Substation-A to Substation-B

    Frequency: 50Hz

    Line data: R1 + jX1 = 0.0288 + j0.307 /km

    R0 + jX0 = 0.2689 + j1.072 /km

    R0M + jX0M = 0.228 + j0.662 /km

    Line length: 190km

    CT ratio: 1000/1A

    CVT ratio: 400/0.11kV

    Maximum expected load on line both import and export: This shall be obtained from the load flowanalysis of the power system under all possible contingency. From the load flow studies, 1500MVA

    is the maximum expected load under worst contingency on this line at 90% system voltage.

  • 8/11/2019 Guidelines Relay Setting

    17/467

    Model setting calculation document for Transmission Line

    2.0 TERMINAL IDENTIFICATION AND LIST OF FUNCTIONS

    The various functions required for the line protection are divided in two IEDs namely REL670 and

    REC670 for the purpose of illustration. The terminal identification of this and list of various functions

    available in these IEDs are given in this section.

    2.1 REL670

    2.1.1 Terminal Identification

    Station Name: Station-A

    Object Name: 400kV OHL from Station-A to Station-B

    Unit Name: REL670 (Ver 1.2)

    Relay serial No: XXXXXXXX

    Frequency: 50Hz

    Aux voltage: 220V DC

    2.1.2 List of functions available and those used

    Table 2-1 gives the list of functions/features available in REL670 relay and also indicates the

    functions/feature for which settings are provided in this document. The functions/feature are

    indicative and varies with IED ordering code & IED application configuration.

    Table 2-1: List of functions in REL670

    Sl.No. Function/features available In REL670

    Function/featureactivated

    Yes/No

    RecommendedSettingsprovided

    1 Analog Inputs YES

    2 Local Human-Machine Interface YES

    3 Indication LEDs YES

  • 8/11/2019 Guidelines Relay Setting

    18/467

    Model setting calculation document for Transmission Line

    Sl.No. Function/features available In REL670

    Function/featureactivated

    Yes/No

    RecommendedSettingsprovided

    8 Change Lock CHNGLCK NO

    9 IED Identifiers YES

    10 Product Information YES

    11 Rated System Frequency PRIMVAL YES

    12 Signal Matrix For Binary Inputs SMBI YES

    13 Signal Matrix For Binary Outputs SMBO YES

    14 Signal Matrix For mA Inputs SMMI NO

    15 Signal Matrix For Analog Inputs SMAI YES

    16 Summation Block 3 Phase 3PHSUM NO

    17 Authority Status ATHSTAT NO

    18 Denial Of Service DOS NO

    19

    Distance Protection Zone, Quadrilateral

    Characteristic (Zone 1) ZMQPDIS YES

    20Distance Protection Zone, Quadrilateral

    Characteristic (Zone 2) ZMQAPDISYES

    21Distance Protection Zone, Quadrilateral

    Characteristic (Zone 3) ZMQAPDISYES

    22Distance Protection Zone, Quadrilateral

    Characteristic (Zone 4) ZMQAPDISNO

    23Distance Protection Zone, Quadrilateral

    Ch i i (Z 5) ZMQAPDISYES

  • 8/11/2019 Guidelines Relay Setting

    19/467

    Model setting calculation document for Transmission Line

    Sl.No. Function/features available In REL670

    Function/featureactivated

    Yes/No

    RecommendedSettingsprovided

    27Automatic Switch Onto Fault Logic, VoltageAnd Current Based ZCVPSOF

    YES

    28Instantaneous Phase Overcurrent ProtectionPHPIOC

    NO

    29 Four Step Phase Overcurrent ProtectionOC4PTOC

    NO

    30Instantaneous Residual Overcurrent ProtectionEFPIOC

    NO

    31Four Step Residual Overcurrent ProtectionEF4PTOC

    YES

    32Sensitive Directional Residual Overcurrent AndPower Protection SDEPSDE

    NO

    33Thermal Overload Protection, One TimeConstant LPTTR

    NO

    34 Stub Protection STBPTOC YES

    35 Broken Conductor Check BRCPTOC YES

    36 Two Step Undervoltage Protection UV2PTUV YES

    37 Two Step Overvoltage Protection OV2PTOV YES

    38 Loss Of Voltage Check LOVPTUV NO

    39 General Current And Voltage ProtectionCVGAPC-4 functions NO

    40 Current Circuit Supervision CCSRDIF NO

    41 Fuse Failure Supervision SDDRFUF YES

  • 8/11/2019 Guidelines Relay Setting

    20/467

    Model setting calculation document for Transmission Line

    Sl.No. Function/features available In REL670

    Function/featureactivated

    Yes/No

    RecommendedSettingsprovided

    45 Generic Double Point Function Block DPGGIO NO

    46Single Point Generic Control 8 SignalsSPC8GGIO

    NO

    47

    Automationbits, Command Function For

    DNP3.0 AUTOBITS NO

    48 Single Command, 16 Signals SINGLECMD NO

    49Scheme Communication Logic For Distance OrOvercurrent Protection ZCPSCH

    YES

    50Current Reversal And Weak-End Infeed Logic

    For Distance Protection ZCRWPSCH

    NO

    51 Local Acceleration Logic ZCLCPLAL NO

    52 Direct Transfer Trip Logic YES

    53Low Active Power And Power Factor ProtectionLAPPGAPC

    NO

    54 Compensated Over and UndervoltageProtection COUVGAPC

    NO

    55Sudden Change in Current VariationSCCVPTOC

    NO

    56 Carrier Receive Logic LCCRPTRC NO

    57Negative Sequence Overvoltage ProtectionLCNSPTOV NO

    58Zero Sequence Overvoltage ProtectionLCZSPTOV

    NO

    Negative Sequence Overcurrent Protection

  • 8/11/2019 Guidelines Relay Setting

    21/467

    Model setting calculation document for Transmission Line

    Sl.No. Function/features available In REL670

    Function/featureactivated

    Yes/No

    RecommendedSettingsprovided

    63 Tripping Logic SMPPTRC YES

    64 Trip Matrix Logic TMAGGIO YES

    65 Configurable Logic Blocks NO

    66 Fixed Signal Function Block FXDSIGN NO

    67 Boolean 16 To Integer Conversion B16I NO

    68

    Boolean 16 To Integer Conversion With LogicNode

    Representation B16IFCVI

    NO

    69 Integer To Boolean 16 Conversion IB16 NO

    70

    Integer To Boolean 16 Conversion With LogicNode

    Representation IB16FCVB

    NO

    71 Measurements CVMMXN YES

    72 Phase Current Measurement CMMXU YES

    73 Phase-Phase Voltage Measurement VMMXU YES

    74Current Sequence Component MeasurementCMSQI

    YES

    75 Voltage Sequence Measurement VMSQI YES

    76 Phase-Neutral Voltage Measurement VNMMXU NO

    77 Event Counter CNTGGIO YES

    78 Event Function EVENT YES

  • 8/11/2019 Guidelines Relay Setting

    22/467

    Model setting calculation document for Transmission Line

    Sl.No. Function/features available In REL670

    Function/featureactivated

    Yes/No

    RecommendedSettingsprovided

    83 Event List YES

    84 Indications YES

    85 Event Recorder YES

    86 Trip Value Recorder YES

    87 Disturbance Recorder YES

    88 Pulse-Counter Logic PCGGIO NO

    89Function For Energy Calculation And DemandHandling ETPMMTR

    NO

    90 IEC 61850-8-1 Communication Protocol NO

    91IEC 61850 Generic Communication I/OFunctions SPGGIO, SP16GGIO

    NO

    92IEC 61850-8-1 Redundant Station BusCommunication

    NO

    93 IEC 61850-9-2LE Communication Protocol NO

    94 LON Communication Protocol NO

    95 SPA Communication Protocol NO

    96 IEC 60870-5-103 Communication Protocol NO

    97

    Multiple Command And TransmitMULTICMDRCV,

    MULTICMDSND

    NO

    98 Remote Communication NO

  • 8/11/2019 Guidelines Relay Setting

    23/467

    Model setting calculation document for Transmission Line

    2.2 REC670

    2.2.1 Terminal identification

    Station Name: Station-A

    Object Name: 400kV OHL

    Unit Name: REC670 (Ver 1.2)

    Relay serial No: XXXXX

    Frequency: 50Hz

    Aux voltage: 220V DC

    2.2.2 List of functions available and those used

    Table 2-2 gives the list of functions/features available in REC670 relay and also indicates the

    functions/feature for which settings are provided in this document. The functions/feature are

    indicative and varies with IED ordering code & IED application configuration.

    Table 2-2: List of functions in REC670

    Sl.No. Functions/Feature available In REC670

    Features/Functionsactivated

    Yes/No

    RecommendedSettingsprovided

    1 Analog Inputs YES

    2 Local Human-Machine Interface YES

    3 Indication LEDs YES

    4 Self supervision with internal event list YES

    5 Time Synchronization YES

    6 Parameter Setting Groups YES

    7 Test Mode Functionality TEST YES

  • 8/11/2019 Guidelines Relay Setting

    24/467

    Model setting calculation document for Transmission Line

    Sl.No. Functions/Feature available In REC670

    Features/Functionsactivated

    Yes/No

    RecommendedSettingsprovided

    12 Signal Matrix For Binary Inputs SMBI YES

    13 Signal Matrix For Binary Outputs SMBO YES

    14 Signal Matrix For Ma Inputs SMMI NO

    15 Signal Matrix For Analog Inputs SMAI YES

    16 Summation Block 3 Phase 3PHSUM NO

    17 Authority Status ATHSTAT NO

    18 Denial Of Service DOS NO

    19 Differential Protection HZPDIF NO

    20Instantaneous Phase Overcurrent ProtectionPHPIOC

    NO

    21Four Step Phase Overcurrent ProtectionOC4PTOC

    NO

    22Instantaneous Residual Overcurrent

    Protection EFPIOCNO

    23Four Step Residual Overcurrent ProtectionEF4PTOC

    NO

    24Four step directional negative phasesequence overcurrent protection NS4PTOC

    NO

    25Sensitive Directional Residual OvercurrentAnd Power Protection SDEPSDE NO

    26Thermal Overload Protection, One TimeConstant LPTTR

    NO

    Thermal overload protection two time

  • 8/11/2019 Guidelines Relay Setting

    25/467

    Model setting calculation document for Transmission Line

    Sl.No. Functions/Feature available In REC670

    Features/Functionsactivated

    Yes/No

    RecommendedSettings

    provided

    31Directional Underpower ProtectionGUPPDUP

    NO

    32Directional Overpower ProtectionGOPPDOP

    NO

    33 Broken Conductor Check BRCPTOC NO

    34 Capacitor bank protection CBPGAPC NO

    35Two Step Undervoltage ProtectionUV2PTUV

    NO

    36 Two Step Overvoltage Protection OV2PTOV NO

    37Two Step Residual Overvoltage ProtectionROV2PTOV

    NO

    38 Voltage Differential Protection VDCPTOV NO

    39 Loss Of Voltage Check LOVPTUV NO

    40 Underfrequency Protection SAPTUF NO

    41 Overfrequency Protection SAPTOF NO

    42Rate-Of-Change Frequency ProtectionSAPFRC

    NO

    43General Current and Voltage ProtectionCVGAPC

    NO

    44 Current Circuit Supervision CCSRDIF NO

    45 Fuse Failure Supervision SDDRFUF NO

    46Synchrocheck, Energizing Check, AndSynchronizing SESRSYN

    YES

  • 8/11/2019 Guidelines Relay Setting

    26/467

    Model setting calculation document for Transmission Line

    Sl.No. Functions/Feature available In REC670

    Features/Functionsactivated

    Yes/No

    RecommendedSettings

    provided

    50Logic Rotating Switch For FunctionSelection And LHMI Presentation SLGGIO

    NO

    51 Selector Mini Switch VSGGIO NO

    52Generic Double Point Function Block

    DPGGIONO

    53Single Point Generic Control 8 SignalsSPC8GGIO

    NO

    54Automationbits, Command Function ForDNP3.0 AUTOBITS

    NO

    55 Single Command, 16 Signals SINGLECMD NO

    56Scheme Communication Logic For DistanceOr Overcurrent Protection ZCPSCH

    NO

    57Phase Segregated Scheme CommunicationLogic For Distance Protection ZC1PPSCH

    NO

    58Current Reversal And Weak-End Infeed

    Logic For Distance Protection ZCRWPSCHNO

    59 Local Acceleration Logic ZCLCPLAL NO

    60Scheme Communication Logic For ResidualOvercurrent Protection ECPSCH

    NO

    61Current Reversal And Weak-End InfeedLogic For Residual Overcurrent ProtectionECRWPSCH

    NO

    62Current Reversal And Weak-End InfeedLogic For Phase SegregatedCommunication ZC1WPSCH

    NO

    M d l i l l i d f T i i Li

  • 8/11/2019 Guidelines Relay Setting

    27/467

    Model setting calculation document for Transmission Line

    Sl.No. Functions/Feature available In REC670

    Features/Functionsactivated

    Yes/No

    RecommendedSettings

    provided

    66Sudden Change In Current VariationSCCVPTOC

    NO

    67 Carrier Receive Logic LCCRPTRC NO

    68Negative Sequence Overvoltage Protection

    LCNSPTOVNO

    69Zero Sequence Overvoltage ProtectionLCZSPTOV

    NO

    70Negative Sequence Overcurrent ProtectionLCNSPTOC

    NO

    71Zero Sequence Overcurrent ProtectionLCZSPTOC NO

    72 Three Phase Overcurrent LCP3PTOC NO

    73 Three Phase Undercurrent LCP3PTUC NO

    74 Tripping Logic SMPPTRC NO

    75 Trip Matrix Logic TMAGGIO NO

    76 Configurable Logic Blocks NO

    77 Fixed Signal Function Block FXDSIGN NO

    78 Boolean 16 To Integer Conversion B16I NO

    79

    Boolean 16 To Integer Conversion WithLogic Node

    Representation B16IFCVI

    NO

    80 Integer To Boolean 16 Conversion IB16 NO

    Model setting calc lation doc ment for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    28/467

    Model setting calculation document for Transmission Line

    Sl.No. Functions/Feature available In REC670

    Features/Functionsactivated

    Yes/No

    RecommendedSettings

    provided

    84Phase-Phase Voltage MeasurementVMMXU

    YES

    85Current Sequence ComponentMeasurement CMSQI

    YES

    86 Voltage Sequence Measurement VMSQI YES

    87Phase-Neutral Voltage MeasurementVNMMXU

    NO

    88 Event Counter CNTGGIO YES

    89 Event Function EVENT YES

    90 Logical Signal Status Report BINSTATREP NO

    91 Fault Locator LMBRFLO NO

    92Measured Value Expander BlockRANGE_XP

    NO

    93 Disturbance Report DRPRDRE YES

    94 Event List YES

    95 Indications YES

    96 Event Recorder YES

    97 Trip Value Recorder YES

    98 Disturbance Recorder YES

    99 Pulse-Counter Logic PCGGIO NO

    100Function For Energy Calculation AndDemand Handling ETPMMTR

    NO

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    29/467

    Model setting calculation document for Transmission Line

    Sl.No. Functions/Feature available In REC670

    Features/Functionsactivated

    Yes/No

    RecommendedSettings

    provided

    104 IEC 61850-9-2LE Communication Protocol NO

    105 LON Communication Protocol NO

    106 SPA Communication Protocol NO

    107 IEC 60870-5-103 Communication Protocol NO

    108

    Multiple Command And TransmitMULTICMDRCV,

    MULTICMDSND

    NO

    109 Remote Communication NO

    Note: For setting parameters provided in the function listed above, refer section 3 of

    application manual 1MRK511230-UEN, version 1.2.

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    30/467

    Model setting calculation document for Transmission Line

    3.0 SETTING CALCULATIONS AND RECOMMENDED

    SETTINGS FOR REL670

    The various functions required for the line protection are divided in two IEDs namely REL670 and

    REC670. The setting calculations and recommended settings for various functions available in

    these IEDs are given in this section.

    3.1 REL670

    3.1.1 Analog Inputs

    Guidelines for Settings:

    Configure analog inputs:

    Current analog inputs as:

    Ch 1 Ch 2 Ch 3 Ch 4 Ch 5 Ch 6

    Name# IL1-CB1 IL2-CB1 IL3-CB1 IL1-CB2 IL2-CB2 IL3-CB2

    CTprim 1000A 1000A 1000A 1000A 1000A 1000A

    CTsec 1A 1A 1A 1A 1A 1A

    CTStarPoint parameter indicates the CT secondary winding neutral earthing towards object

    (ToObject) or towards busbar (FromObject).

    Voltage analog input as:

    Ch 1 Ch 2 Ch 3 Ch 4 Ch 5 Ch 6

    Name# UL1 UL2 UL3 UL2BUS1 UL2BUS2 UL2L2

    VTprim 400kV 400kV 400kV 400kV 400kV 400kV

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    31/467

    Model setting calculation document for Transmission Line

    Recommended Settings:

    Table 3-1 gives the recommended settings for the analog inputs.

    Table 3-1: Analog inputs

    SettingParameter

    DescriptionRecommended

    Settings Unit

    PhaseAngleRefReference channel for phase angle

    PresentationTRM40-Ch1 -

    CTStarPoint1ToObject= towards protected object,

    FromObject= the oppositeToObject -

    CTsec1 Rated CT secondary current 1 A

    CTprim1 Rated CT primary current 1000 A

    CTStarPoint2ToObject= towards protected object,

    FromObject= the oppositeToObject -

    CTsec2 Rated CT secondary current 1 A

    CTprim2 Rated CT primary current 1000 A

    CTStarPoint3

    ToObject= towards protected object,

    FromObject= the opposite ToObject -

    CTsec3 Rated CT secondary current 1 A

    CTprim3 Rated CT primary current 1000 A

    CTStarPoint4ToObject= towards protected object,

    FromObject= the oppositeToObject -

    CTsec4 Rated CT secondary current 1 A

    CTprim4 Rated CT primary current 1000 A

    ToObject towards protected object

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    32/467

    ode sett g ca cu at o docu e t o a s ss o e

    SettingParameter

    DescriptionRecommended

    Settings Unit

    FromObject= the opposite

    CTsec6 Rated CT secondary current 1 A

    CTprim6 Rated CT primary current 1000 A

    VTsec7 Rated VT secondary voltage 110 V

    VTprim7 Rated VT primary voltage 400 kV

    VTsec8 Rated VT secondary voltage 110 V

    VTprim8 Rated VT primary voltage 400 kV

    VTsec9 Rated VT secondary voltage 110 V

    VTprim9 Rated VT primary voltage 400 kV

    VTsec10 Rated VT secondary voltage 110 V

    VTprim10 Rated VT primary voltage 400 kV

    VTsec11 Rated VT secondary voltage 110 V

    VTprim11 Rated VT primary voltage 400 kV

    VTsec12 Rated VT secondary voltage 110 V

    VTprim12 Rated VT primary voltage 400 kV

    Binary input module (BIM) Settings

    Operation OscBlock(Hz) OscRelease(Hz)I/O Module 1 On 40 30 Pos Slot3

    I/O Module 2 On 40 30 Pos Slot3

    I/O Module 3 On 40 30 Pos Slot3

    I/O Module 4 On 40 30 Pos Slot3

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    33/467

    g

    3.1.2 Local Human-Machine Interface

    Recommended Settings:Table 3-2 gives the recommended settings for Local human machine interface.

    Table 3-2: Local human machine interface

    SettingParameter

    DescriptionRecommended

    Settings Unit

    Language Local HMI language English -

    DisplayTimeout Local HMI display timeout 60 Min

    AutoRepeatActivation of auto-repeat (On) or not(Off)

    On -

    ContrastLevel Contrast level for display 0 %

    DefaultScreen Default screen 0 -

    EvListSrtOrder Sort order of event list Latest on top -

    SymbolFont Symbol font for Single Line Diagram IEC -

    3.1.3 Indication LEDs

    Guidelines for Settings:

    This function block is to control LEDs in HMI.

    SeqTypeLED1: Normally this parameter is set to LatchedAck-S-F. When trip occurs, it will glow

    steady and latched till manually reset. When manually reset, it will go OFF when trip is not there. Iftrip still persist, it will f lash.

    tRestart: Not applicable for the above case.

    tMax:Not applicable for the above case.

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    34/467

    Recommended Settings:

    Table 3-3 gives the recommended settings for Indication LEDs.

    Table 3-3: LEDGEN Non group settings (basic)

    SettingParameter

    DescriptionRecommended

    Settings Unit

    Operation Operation mode for the LED function On -

    tRestart Defines the disturbance length 0.0 s

    tMaxMaximum time for the definition of a

    disturbance0.0 s

    SeqTypeLED1 Sequence type for LED 1 LatchedAck-S-F -

    SeqTypeLED2 Sequence type for LED 2 LatchedAck-S-F -

    SeqTypeLED3 Sequence type for LED 3 LatchedAck-S-F -

    SeqTypeLED4 Sequence type for LED 4 LatchedAck-S-F -

    SeqTypeLED5 Sequence type for LED 5 LatchedAck-S-F -

    SeqTypeLED6 Sequence type for LED 6 LatchedAck-S-F -

    SeqTypeLED7 Sequence type for LED 7 LatchedAck-S-F -

    SeqTypeLED8 Sequence type for LED 8 LatchedAck-S-F -

    SeqTypeLED9 Sequence type for LED 9 LatchedAck-S-F -

    SeqTypeLED10 Sequence type for LED 10 LatchedAck-S-F -

    SeqTypeLED11 Sequence type for LED 11 LatchedAck-S-F -

    SeqTypeLED12 Sequence type for LED 12 LatchedAck-S-F -

    SeqTypeLED13 Sequence type for LED 13 LatchedAck-S-F -

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    35/467

    3.1.4 Time Synchronization

    Guidelines for Settings:These settings are used for synchronizing IED clock time with network time. Ex: GPS or IRIG-B time.

    CoarseSyncSrc: Select the time synchronization source available such as SPA, LON, SNTP etc.

    Synchronization messages from sources configured as coarse are checked against the internal relay

    time and only if the difference in relay time and source time is more than 10s then relay time will be

    reset with the source time. This parameter need to be based on time source available in site.

    FineSyncSource: Select the time source available in network like IRIG-B, GPS, SNTP, SPA etc.

    once it is selected, time of available time source in network will update to relay if there is a difference

    in the time between relay and source. This parameter need to be based on time source available in

    site.

    SyncMaster:Normally it is set OFF. If time to the relay is received from a GPS antenna (example),

    make the relay as master to synchronize with other relays.

    TimeAdjustRate:Fast

    HWSyncSrc: This is applicable if process bus IEC61850-9-2 protocol is used for receiving analog

    values (optical CT PTs). In this case select time source available same as that of merging unit. This

    setting is not applicable in present case.

    AppSynch: If there is any loss of time sync, protection function will be blocked if AppSynch set to

    Synchbased on SyncAccLevel. If AppSunch set to NoSynch, protection functions are not blocked.Recommended setting is NoSynch.

    SyncAccLevel: If this is set to Class T5 (1us) and time synch error is more than 1us, protection

    functions will be blocked. SyncAccLevel should be set to Unspecified when Nosynch is selected at

    AppSynch. This parameter is not applicable in present case.

    ModulePosition: if BIN is set for FineSyncSource, ModulePosition setting is applicable. Here slot

    position of IO module in the relay is to be set (Which slot is used for BI). This parameter is not

    applicable in present case.

    BinaryInput: Which binary input is used for time sync input shall be set here. This parameter is

    applicable if BIN is set for FineSyncSource. This parameter is not applicable in present case.

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    36/467

    MonthInYear, DayInWeek, WeekInMonth and UTCTimeOfDay for DSTBEGIN and DSTEND are

    applicable where Day light saving is used. If it is not used set same date for both DSTBEGIN and

    DSTEND. This setting is not applicable in this case.

    NoHalfHourUTC: Time shift from GMT has to be set a multiple of half hours. Example for India it is

    +05:30, means +11. Hence this parameter is set to +11 in present case.

    SYNCHIRIG-B Non group settings:These settings are applicable if IRIG-B is used. This parameter

    is not applicable in present case.

    SynchType:Type of hardware input used for time sync, whether Opto or BNC. This parameter is not

    applicable in present case.

    TimeDomain:In present case this parameter is set to LocalTime.

    Encoding:In present case this parameter is set to IRIG-B.

    TimeZoneAs1344:In present case this parameter is set to PlusTZ.

    Recommended Settings:

    Table 3-4 gives the recommended settings for Time synchonization.

    Table 3-4: Time synchronization settings

    TIMESYNCHGEN Non group settings (basic)

    Setting

    Parameter Description

    Recommended

    Settings Unit

    CoarseSyncSrc Coarse time synchronization source Off -

    FineSyncSource Fine time synchronization source 0.0 -

    SyncMaster Activate IED as synchronization master Off -

    TimeAdjustRate Adjust rate for time synchronization Off -

    HWSyncSrc Hardware time synchronization source Off -

    AppSynch Time synchronization mode for application NoSynch -

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    37/467

    SYNCHBIN Non group settings (basic)

    SettingParameter Description

    Recommended

    Settings Unit

    ModulePositionHardware position of IO module for time

    Synchronization3 -

    BinaryInputBinary input number for time

    synchronization1 -

    BinDetection Positive or negative edge detection PositiveEdge -

    SYNCHSNTP Non group settings (basic)

    Setting Parameter DescriptionRecommended

    Settings Unit

    ServerIP-Add Server IP-address 0.0.0.0 IP Address

    RedServIP-Add Redundant server IP-address 0.0.0.0 IP Address

    DSTBEGIN Non group settings (basic)

    SettingParameter

    Description RecommendedSettings Unit

    MonthInYear Month in year when daylight time starts March -

    DayInWeek Day in week when daylight time starts Sunday -

    WeekInMonthWeek in month when daylight time

    starts

    Last -

    UTCTimeOfDayUTC Time of day in seconds when

    daylight time starts3600 s

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    38/467

    DSTEND Non group settings (basic)

    SettingParameter

    DescriptionRecommended

    Settings Unit

    MonthInYear Month in year when daylight time starts October -

    DayInWeek Day in week when daylight time starts Sunday -

    WeekInMonth

    Week in month when daylight time

    starts Last -

    UTCTimeOfDayUTC Time of day in seconds when

    daylight time starts3600 s

    TIMEZONE Non group settings (basic)

    SettingParameter

    DescriptionRecommended

    Settings Unit

    NoHalfHourUTC Number of half-hours from UTC +11 -

    SYNCHIRIG-B Non group settings (basic)

    SettingParameter

    DescriptionRecommended

    Settings Unit

    SynchType Type of synchronization Opto -

    TimeDomain Time domain LocalTime -

    Encoding Type of encoding IRIG-B -

    TimeZoneAs1344 Time zone as in 1344 standard PlusTZ -

    Note: Above setting parameters have to be set based on available time source at site.

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    39/467

    t: The length of the pulse, sent out by the output signal SETCHGD when an active group has

    changed, is set with the parameter t. This is not the delay for changing setting group. This parameter

    is normally recommended to set 1s.

    MAXSETGR:The parameter MAXSETGR defines the maximum number of setting groups in use to

    switch between. Only the selected number of setting groups will be available in the Parameter

    Setting tool (PST) for activation with the ActiveGroup function block. This parameter is normally

    recommended to set 1.

    Recommended Settings:

    Table 3-5 gives the recommended settings for Parameter setting group.

    Table 3-5: Parameter setting group

    ActiveGroup Non group settings (basic)

    SettingParameter

    Description RecommendedSettings Unit

    tPulse length of pulse when setting

    Changed1 s

    SETGRPS Non group settings (basic)

    SettingParameter

    DescriptionRecommended

    Settings Unit

    ActiveSetGrp ActiveSettingGroup SettingGroup1 -

    MAXSETGR Max number of setting groups 1-6 1 No

    3.1.6 Test Mode Functionality TEST

    Guidelines for Settings:

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    40/467

    Table 3-6 gives the recommended settings for Test mode functionality.

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    41/467

    Table 3-6: Test mode functionality

    TESTMODE Non group settings (basic)

    SettingParameter

    DescriptionRecommended

    Settings Unit

    TestMode Test mode in operation (On) or not (Off) Off -

    EventDisable Event disable during testmode Off -

    CmdTestBitCommand bit for test required or not

    during testmodeOff -

    3.1.7 IED Identifiers

    Recommended Settings:

    Table 3-7 gives the recommended settings for IED Identifiers.

    Table 3-7: IED Identifiers

    TERMINALID Non group settings (basic)

    SettingParameter

    DescriptionRecommended

    Settings Unit

    StationName Station name Station-A -

    StationNumber Station number 0 -

    ObjectName Object name Line-1 -

    ObjectNumber Object number 0 -

    U itN U it REL670 M1

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    42/467

    3.1.8 Rated System Frequency PRIMVAL

    Recommended Settings:

    Table 3-8 gives the recommended settings for Rated system frequency.

    Table 3-8: Rated system frequency

    PRIMVAL Non group settings (basic)

    SettingParameter

    Description RecommendedSettings Unit

    Frequency Rated system frequency 50.0 Hz

    3.1.9 Signal Matrix For Analog Inputs SMAI

    Guidelines for Settings:

    DFTReference: Set ref for DFT filter adjustment here. These DFT reference block settings decide

    DFT reference for DFT calculations.

    The settings InternalDFTRef will use fixed DFT reference based on set system frequency.

    AdDFTRefChn will use DFT reference from the selected group block, when own group selected

    adaptive DFT reference will be used based on calculated signal frequency from own group. The

    setting ExternalDFTRef will use reference based on what is connected to input DFTSPFC.

    There are three different task groups of SMAI with 1ms, 3ms and 8ms. Use of each task group is

    based on requirement of function, like differential protection requires 1ms, which is faster.

    Each task group has 12 instances of SMAI, in that first instance has some additional features which

    is called master. Others are slaves and they will follow master. If measured sample rate needs to be

    transferred to other task group, it can be done only with master.

    Receiving task group SMAI DFTreference shall be set to External DFT Ref.

    DFTReference shall be set to default value InternalDFTRef if no VT input is available Since VT input

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    43/467

    connected to 3rdSMAI of 1ms task group, AdDFTRefCh3 is to be set in DFTRefExtOut of 1ms task

    group.

    DFTRefExtOut shall be set to default value InternalDFTRef if no VT input is available. Configuration

    file has to be referred for this purpose.

    Negation: Set negation of the function block here. If R, Y, B and N inputs are connected and

    Negation is set to NegateN, it will give output R, Y, B and N. If Negation is set to Negate3Ph, it will

    give output -R, -Y, -B and N.

    If R, Y, B inputs are connected, N=R+Y+B, and it will do as above. This parameter is recommended

    to be set to OFF normally.

    MinValFreqMeas: Set the measured minimum value here. It is applicable only for voltage input.

    SMAI will work only if measured input magnitude is greater than set value in MinValFreqMeas. This

    parameter is recommended to set 10% normally.

    UBase:Set the base voltage here. This is parameter is set to 400kV.

    Recommended Settings:

    Table 3-9 gives the recommended settings for Signal Matrix For Analog Inputs.

    Table 3-9: Signal Matrix For Analog Inputs

    SettingParameter

    DescriptionRecommended

    Settings Unit

    DFTRefExtOut DFT reference for external output InternalDFTRef -

    DFTReference DFT reference InternalDFTRef -

    ConnectionType Input connection type Ph-Ph -

    TYPE 1=Voltage, 2=Current1 or 2 based oninput

    Ch

    Negation Negation Off -

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    44/467

    3.1.10 General settings of Distance protection zones

    Guidelines for Settings:

    Figure 3-1 gives the setting angles for discrimination of forward and reverse fault.

    ArgDir and ArgNegRes:Set the Directional angle Distance protection zones at ArgDir and set the

    Negative restraint angle for Distance protection zone at ArgNegRes.

    The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115respectively. It should

    not be changed unless system studies have shown the necessity.

    IBase:set to the current value of the primary winding of the CT. This parameter is set to 1000A in

    present case.

    UBase:set to the voltage value of the primary winding of the VT. This parameter is set to 400kV in

    present case.

    IMinOpPP:This is the minimum current required in phase to phase fault for directionality purpose.

    To be set to 20% of IBase.

    IMinOpPE:This is the minimum current required in phase to earth fault for directionality purpose.

    To be set to 20% of IBase.

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    45/467

    Recommended Settings:Table 3-10 gives the recommended settings for General settings for distance protection.

    Table 3-10: General settings for distance protection

    ZDRDIR Group settings (basic)

    SettingParameter

    DescriptionRecommended

    Settings Unit

    IBase Base setting for current level 1000 A

    UBase Base setting for voltage level 400 kV

    IMinOpPPMinimum operate delta current forPhase-Phase loops

    20 %IB

    IMinOpPEMinimum operate phase current for

    Phase-Earth loops20 %IB

    ArgNegResAngle of blinder in second quadrant for

    forward direction115 Deg

    ArgDirAngle of blinder in fourth quadrant for

    forward direction15 Deg

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    46/467

    3.1.11 Distance Protection Zone, Quadrilateral Characteristic (Zone 1)

    ZMQPDIS

    General guide lines for Setting Distance protection Zones:

    The zones are set directly in primary ohms R, X. The primary ohms R, X are recalculated to

    secondary ohms with the current and voltage transformer ratios. Figures 3-2 and 3-3 show the

    characteristics for phase-to-earth measuring and phase-to-phase measuring respectively.

    The secondary values are presented as information for zone testing.

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    47/467

    Figure 3-3: Characteristic for phase-to-phase measuring

    Guidelines for Setting:

    Zone-1:

    Setting X1, R1 and X0, R0: To be set to cover 80% of protected line length. Zero sequence

    compensation factor is (Z0 Z1) / 3Z1.

    RFPP and RFPE: For phase to ground faults resistive reach should be set to give maximum

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    48/467

    In case of phase to phase fault, resistive reach should be set to provide coverage against all types

    of anticipated phase to phase faults subject to check of possibility against load point encroachment

    considering minimum expected voltage and maximum load expected during short time emergency

    system condition.

    To minimize the risk for overreaching, limit the setting of the zone 1 reach in resistive direction for

    phase-to-phase loop measurement to:

    RFPP 3 X1.

    IBase:Set the Base current for the Distance protection zones in primary Ampere here. Set to thecurrent value of the primary winding of the CT. This parameter is set to 1000A in present case.

    UBase: Set the Base voltage for the Distance protection zones in primary kV here. Set to the

    voltage value of the primary winding of the VT. This parameter is set to 400kV in present case.

    IMinOpPP:Setting of minimum sensitivity for zone Phase-Phase elements. Measures IL-IL for each

    loop. This is the minimum current required in phase to phase fault for zone measurement. To be set

    to 20% of IBase.

    IMinOpPE: Setting of minimum operating current for Phase faults. Measures ILx. This is the

    minimum current required in phase to earth fault for zone measurement. To be set to 20% of IBase.

    IMinOpIN:This is the minimum 3I0current required in phase to earth fault for zone measurement.

    To be set to 10% of IBase.

    Setting Calculations:

    OperationDir = Forward

    Operation PP = On

    Operation PE = On

    Zone 1 phase fault reach is set to 80.0% of the total line reactance

    X1Z1' = 46.664 Note! Zone will send carrier signal

    The secondary setting will thus be

    X1Z1 = 12.833

    Set the positive sequence resistance for phase faults to (this gives the characteristic angle)

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    49/467

    The secondary setting will thus be

    X0Z1 = 44.81

    Set the zero sequence resistance for earth faults to

    R0Z1' = 40.873

    The secondary setting will thus be

    R0Z1 = 11.24

    Setting of the fault resistive cover

    The resistive reach(phase to Phase) is set to cover a maximum expected fault resistance arrived

    from Warrington formula given below

    Rarc =

    It is set to 15.0 . (Considering a minimum expected ph to ph fault current of 1500A and arc length

    of 15meter).

    Note that setting of fault resistance is the loop value whereas reactance setting is phase value forphase faults.

    The resistive reach (phase to earth) is set as 50 keeping a value of 10 for tower footing

    resistance, arc-resistance of 15and remote end infeed effect of 25(considering equal fault feed

    from both side)

    Set the resistive reach for phase faults to:

    RFPPZ1' = 30(loop value)

    The secondary setting will thus be

    RFPPZ1 = 8.25

    Set the resistive reach for earth faults to

    RFPEZ1= 50

    The secondary setting will thus be

    RFPEZ1 = 13.75

    Set the Base current for the Distance protection zones in primary Ampere.

    Zone 1 setting of timers.

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    50/467

    Recommended Settings:

    Table 3-11 gives the recommended settings for ZONE 1 Settings.

    Table 3-11: ZONE 1 Settings

    SettingParameter

    DescriptionRecommended

    Settings Unit

    Operation Operation Off / On On -

    IBase Base current , i.e rated current 1000 A

    Ubase Base voltage , i.e.rated voltage 400.00 kV

    OperationDir Operation mode of directionality Forward -

    X1 Positive sequence reactance reach 46.664 ohm/p

    R1 Positive sequence resistance reach 4.378 ohm/p

    X0 Zero sequence reactance reach 162.944 ohm/p

    R0 Zero sequence resistance for zone 40.873 ohm/p

    RFPP Fault resistance reach in ohm/loop , Ph-Ph 30 ohm/l

    RFPE Fault resistance reach in ohm/loop , Ph-E 50 ohm/l

    OperationPP

    Operation mode Off/On of Ph-Ph loops On -

    Timer tPPOperation mode Off/On of Zone timer, Ph-Ph

    On -

    tPP Time delay of trip,Ph-Ph 0.000 s

    OperationPE

    Operation mode Off/On of Ph-E loops On -

    Timer tPE Operation mode Off/On of Zone timer, Ph-E On -

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    51/467

    IMinOpINMinimum operate residual current forPhase-Earth loops

    10 %IB

    3.1.12 Distance Protection Zone, Quadrilateral Characteristic (Zone 2)

    ZMQAPDIS

    Guidelines for Setting:

    Setting X1, R1 and X0, R0:

    To be set to cover minimum 120% of length of principle line section. However, in case of double

    circuit lines 150% coverage must be provided to take care of under reaching due to mutual coupling

    effect. Zero sequence compensation factor is (Z0 Z1) / 3Z1.

    tPP and tPE settings:

    A Zone-2 timing of 0.35s (considering LBB time of 200mS, CB open time of 60ms, resetting time of

    30ms and safety margin of 60ms) is set for the present case.

    RFPP and RFPE:

    Guidelines given for resistive reach under zone-1 is applicable here also. Due to in-feeds, the

    apparent fault resistance seen by relay is several times the actual value. This should be kept inmind while arriving at resistive reach setting for Zone-2.

    IBase:Set the Base current for the Distance protection zones in primary Ampere here. Set to the

    current value of the primary winding of the CT. This parameter is set to 1000A in present case.

    UBase: Set the Base voltage for the Distance protection zones in primary kV here. Set to the

    voltage value of the primary winding of the VT. This parameter is set to 400kV in present case.

    IMinOpPP:Setting of minimum sensitivity for zone Phase-Phase elements. Measures IL-IL for each

    loop. This is the minimum current required in phase to phase fault for zone measurement. To be set

    to 20% of IBase.

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    52/467

    Setting Calculations:

    OperationDir = ForwardOperation PP = On

    Operation PE = On

    Zone 2 phase fault reach is set to 150.0%of the total line reactance

    X1Z2' = 87.495 Zone is accelerated at receipt of Carrier signal.

    The secondary setting will thus be

    X1Z2 = 24.061

    Set the positive sequence resistance for phase faults to (this gives the characteristic angle)

    R1Z2' = 8.208

    The secondary setting will thus be

    R1Z2 = 2.257

    Setting of zone earth fault zero sequence values

    X0Z2' = 305.52 150.0%of the total line reactance

    The secondary setting will thus be

    X0Z2 = 84.018

    Set the zero sequence resistance for earth faults to

    R0Z2' = 76.637

    The secondary setting will thus beR0Z2 = 21.075

    Setting of the fault resistive cover

    The resistive reach for phase to phase is set to cover a maximum expected fault resistance of

    30.0

    (Considering a factor of 2 on the Zone-1 resistive reach value to take care of in-feed effect)

    Set the resistive reach for phase faults to:

    RFPPZ2' = 60

    The secondary setting will thus be

    RFPPZ2 =16 5

    Model setting calculation document for Transmission Line

    Z 2 ti tti

  • 8/11/2019 Guidelines Relay Setting

    53/467

    Zone 2 timers setting

    Setting of Zone timer activation for phase-phase and earth faults

    tPP2 = On

    tPE2 = On

    Setting of Zone timers:

    tPP2 = 0.35s

    tPE2 = 0.35s

    Note: In this case, Zone-2 reach is not encroaching into 220kV side of the transformer due to in-

    feeds and therefore zone-2 tripping delay need not be coordinated with HV side backup protection

    of Transformer as explained in Appendix-I.

    Recommended Settings:

    Table 3-12 gives the recommended settings for ZONE 2 Settings.

    Table 3-12: ZONE 2 Settings

    SettingParameter

    DescriptionRecommended

    Settings Unit

    Operation Operation Off / On On -

    IBase Base current , i.e. rated current 1000 A

    Ubase Base voltage , i.e. rated voltage 400.00 kV

    OperationDir Operation mode of directionality Forward -

    X1 Positive sequence reactance reach 87.495 ohm/p

    R1 Positive sequence resistance reach 8.208 ohm/p

    X0 Zero sequence reactance reach 305.52 ohm/p

    R0 Zero sequence resistance for zone 76.637 ohm/p

    RFPPFault resistance reach in ohm/loop Ph-

    60 h /l

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    54/467

    SettingParameter

    DescriptionRecommended

    Settings Unit

    tPP Time delay of trip,Ph-Ph 0.35 s

    Operation PE Operation mode Off/On of Ph-E loops On -

    Timer tPEOperation mode Off/On of Zone timer,Ph-E

    On -

    tPE Time delay of trip,Ph-E 0.35 s

    IMinOpPPMinimum operate delta current for Phase-Phase loops

    20 %IB

    IMinOpPEMinimum operate phase current forPhase-Earth loops

    20 %IB

    3.1.13 Distance Protection Zone, Quadrilateral Characteristic (Zone 3)

    ZMQAPDIS

    Guidelines for Setting:

    Setting X1, R1 and X0, R0: Zone-3 should overreach the remote terminal of the longest adjacent

    line by an acceptable margin (typically 20% of highest impedance seen) for all fault conditions.

    Zero sequence compensation factor is (Z0 Z1) / 3Z1.

    tPP and tPE settings: Zone-3 timer should be set so as to provide discrimination with the

    operating time of relays provided in subsequent sections with which Zone-3 reach of relay

    being set, overlaps. In present case, Zone-3 time is set to 1.0s.

    RFPP and RFPE: Guidelines given for resistive reach under zone-1 is applicable here also. Due to

    in-feeds, the apparent fault resistance seen by relay is several times the actual value. This should

    be kept in mind while arriving at resistive reach setting for Zone-3.

    Model setting calculation document for Transmission Line

    IMinOpPP: Setting of minimum sensitivity for zone Phase Phase elements Measures IL IL for each

  • 8/11/2019 Guidelines Relay Setting

    55/467

    IMinOpPP:Setting of minimum sensitivity for zone Phase-Phase elements. Measures IL-IL for each

    loop. This is the minimum current required in phase to phase fault for zone measurement. To be set

    to 20% of IBase.IMinOpPE: Setting of minimum operating current for Phase faults. Measures ILx. This is the

    minimum current required in phase to earth fault for zone measurement. To be set to 20% of IBase.

    Setting Calculations:

    OperationDir = Forward

    Operation PP = On

    Operation PE = On

    Setting of zone 3 Phase fault reach

    Zone 3 phase fault reach is set to 120% of sum of protected line and adjacent longest lines

    reactance is considered. Effect of in-feed not considered for practical reasons in the Zone-3 reach

    setting.X1Z3' = 199.304

    The secondary setting will thus be

    X1Z3 = 54.809

    Set the positive sequence resistance for phase faults to (this gives the characteristic angle)

    R1Z3' = 18.697

    The secondary setting will thus be

    R1Z3 = 5.142

    Setting of zone earth fault zero sequence values

    X0Z3' = 695.942 120% of sum of protected line and adjacent longest lines

    reactance is considered.

    The secondary setting will thus be

    X0Z3 = 191.384

    Set the zero sequence resistance for earth faults to

    R0Z3' = 174.57

    Model setting calculation document for Transmission Line

    The faults on remote lines will have in-feed of fault current through the fault resistance from other

  • 8/11/2019 Guidelines Relay Setting

    56/467

    The faults on remote lines will have in-feed of fault current through the fault resistance from other

    remote feeders which will make an apparent increase of the value. The setting is selected to take

    care of above factors. Set the resistive reach for phase faults to:RFPPZ3' = 75(Loop value)

    The secondary setting will thus be

    RFPPZ3 = 20.625

    Set the resistive reach for earth faults to

    RFPEZ3= 125

    The secondary setting will thus be

    RFPEZ3 = 34.375

    Zone 3 timers setting

    Setting of Zone timer activation for phase-phase and earth faults

    tPP3 = On

    tPE3 = On

    Setting of Zone timers:

    tPP3 = 1s

    tPE3 = 1s

    Note: In this case, Zone-3 reach is not encroaching into 220kV side of the transformer due to in-

    feeds and therefore zone-3 tripping delay need not be coordinated with HV side backup protection

    of Transformer as explained in Appendix-I.

    Recommended Settings:

    Table 3-13 gives the recommended settings for ZONE 3 Settings.

    Table 3-13: ZONE 3 Settings

    Setting

    ParameterDescription

    Recommended

    Settings Unit

    O ti O ti Off / O O

    Model setting calculation document for Transmission Line

    Setting Recommended

  • 8/11/2019 Guidelines Relay Setting

    57/467

    Setting

    ParameterDescription

    Recommended

    Settings Unit

    X0 Zero sequence reactance reach 695.942 ohm/p

    R0 Zero sequence resistance for zone 174.57 ohm/p

    RFPP Fault resistance reach in ohm/loop , Ph-Ph 75 ohm/l

    RFPE Fault resistance reach in ohm/loop , Ph-E 125 ohm/l

    Operation

    PPOperation mode Off/On of Ph-Ph loops On -

    Timer t1PP Operation mode Off/On of Zone timer, Ph-Ph On -

    tPP Time delay of trip,Ph-Ph 1 s

    Operation

    PEOperation mode Off/On of Ph-E loops On -

    Timer t1PE Operation mode Off/On of Zone timer, Ph-E On -

    t1PE Time delay of trip,Ph-E 1 s

    IMinOpPPMinimum operate delta current for Phase-

    Phase loops20 %IB

    IMinOpPEMinimum operate phase current for

    Phase-Earth loops20 %IB

    3.1.14 Distance Protection Zone, Quadrilateral Characteristic (Zone 5)

    ZMQAPDIS

    Guidelines for Setting:

    Setting X1, R1 and X0, R0: Reverse reach setting shall be 50% of shortest line connected to the

    local bus bar. Zero sequence compensation factor is (Z0 Z1) / 3Z1.

    tPP and tPE settings: Zone-5 time delay would only need to co-ordinate with bus bar main

    t ti f lt l d ith Z 1 f lt l f li t f th b t ti F

    Model setting calculation document for Transmission Line

    IBase:Set the Base current for the Distance protection zones in primary Ampere here. Set to the

  • 8/11/2019 Guidelines Relay Setting

    58/467

    p p y p

    current value of the primary winding of the CT. This parameter is set to 1000A in present case.

    UBase: Set the Base voltage for the Distance protection zones in primary kV here. Set to thevoltage value of the primary winding of the VT. This parameter is set to 400kV in present case.

    IMinOpPP:Setting of minimum sensitivity for zone Phase-Phase elements. Measures IL-IL for each

    loop. This is the minimum current required in phase to phase fault for zone measurement. To be set

    to 20% of IBase.

    IMinOpPE: Setting of minimum operating current for Phase faults. Measures ILx. This is the

    minimum current required in phase to earth fault for zone measurement. To be set to 20% of IBase.

    Setting Calculations:

    OperationDir = Reverse

    Operation PP = On

    Operation PE = On

    Zone 5 phase fault reach is set to 50.0%of the shortest line reactance connected to the same bus.

    X1Z5' = 6.14

    The secondary setting will thus be

    X1Z5 = 1.689

    Set the positive sequence resistance for phase faults to (this gives the characteristic angle)

    R1Z5' = 0.576

    The secondary setting will thus be

    R1Z5 = 0.158

    Setting of zone earth fault zero sequence values

    X0Z5' = 21.44

    The secondary setting will thus beX0Z5 = 5.896

    Set the zero sequence resistance for earth faults to

    R0Z5' = 5.378

    Model setting calculation document for Transmission Line

    RFPPZ5 = 20.625

  • 8/11/2019 Guidelines Relay Setting

    59/467

    Set the resistive reach for earth faults to

    RFPEZ5= 125The secondary setting will thus be

    RFPPZ5 = 34.375

    Zone 5 (Reverse Zone) timers setting

    Setting of Zone timer activation for phase-phase and earth faults

    tPP5 = On

    tPE5 = On

    Setting of Zone timers:

    tPP5 = 0.35s

    tPE5 = 0.35s

    Note: Time setting of this zone is not overlapping with zone-2 time of the adjacent shortest line on

    the same bus.

    Recommended Settings:

    Table 3-14 gives the recommended settings for ZONE 5 Settings.

    Table 3-14: ZONE 5 Settings

    SettingParameter

    DescriptionRecommended

    Settings Unit

    Operation Operation Off / On On -

    IBase Base current , i.e. rated current 1000 A

    Ubase Base voltage , i.e. rated voltage 400.00 kV

    OperationDir Operation mode of directionality Reverse -

    X1 Positive sequence reactance reach 6.14 ohm/p

    Model setting calculation document for Transmission Line

    Setting Recommended

  • 8/11/2019 Guidelines Relay Setting

    60/467

    SettingParameter

    DescriptionRecommended

    Settings Unit

    RFPE Fault resistance reach in ohm/loop , Ph-E 125 ohm/l

    OperationPP

    Operation mode Off/On of Ph-Ph loops On -

    Timer t1PP Operation mode Off/On of Zone timer, Ph-Ph On -

    tPP Time delay of trip,Ph-Ph 0.35 s

    OperationPE

    Operation mode Off/On of Ph-E loops On -

    Timer t1PE Operation mode Off/On of Zone timer, Ph-E On -

    t1PE Time delay of trip,Ph-E 0.35 s

    IMinOpPP Minimum operate delta current for Phase-Phase loops 20 %IB

    IMinOpPEMinimum operate phase current for Phase-Earth loops

    20 %IB

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    61/467

    3.1.15 Phase Selection with Load Encroachment, Quadrilateral Characteristic

    FDPSPDIS

    Figures 3-4, 3-5 and 3-6 show the characteristics for Phase selector and load encroachment:

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    62/467

    1-FDPSPDIS (red line), 2-ZMQPDIS, 3-0.5 x RFRvPP PHS, 4- X1PHS/ tan (60), 5-0.5 x

    RFFwPPPHS, 6-0.5 x RFPPZm, 7-X1PHS, 8-X1Zm

    Figure 3-5: Relation between distance protection (ZMQPDIS) and FDPSPDIS characteristicfor phase-to-phase fault for line>60

    Model setting calculation document for Transmission Line

  • 8/11/2019 Guidelines Relay Setting

    63/467

    RLdFw: Forward resistive reach within the load impedance areaRLdRv: Reverse resistive reach within the load impedance area

    ArgLd: Load angle determining the load impedance reach

    Figure 3-6: Load encroachment characteristic

    Guidelines for Setting:

    With the extended Zone-3 reach settings, that may be required to address the many under reaching

    factors already considered, load impedance encroachment is a significant risk to long lines of an

    interconnected power system. Not only the minimum load impedance under expected modes of

    system operation be considered in risk assessment, but also the minimum impedance that might be

    sustained for seconds or minutes during abnormal or emergency system conditions. Failure to do

    so could jeopardize power system security.

    For high resistive earth fault where impedance locus lies in the Blinder zone, fault clearance shall be

    provided by the back-up directional earth fault relay.

    IBase:Set the Base current for the Phase selection function in primary Ampere here. Set to the

    current value of the primary winding of the CT. This parameter is set to 1000A in present case.

    UBase:set to the voltage value of the primary winding of the VT. This parameter is set to 400kV in

    present case

    Model setting calculation document for Transmission Line

    3I0 residual current must fulfill the conditions according to the equations given below

  • 8/11/2019 Guidelines Relay Setting

    64/467

    3.I00.5 IMinOpPE

    |3.I0| . Iphmax

    where:

    IMinOpPE is the minimum operation current for forward zones

    Iphmax is the maximum phase current in any of three phases.

    Conditions that have to be fulfilled in order to release the phase-to-phase loop are:

    3I0< IMinOpPE

    |3.I0| < . Iphmax

    where:

    IMinOpPE is the minimum operation current for earth measuring loops,

    Iphmax is maximal magnitude of the phase currents.

    Guidelines for Load encroachment:

    The minimum load impedance can be calculated on the basis of maximum permitted power flow of

    1500MVA over the protected line and minimum permitted system voltage. Minimum permitted system

    voltage assumed is 360kV (90% of base voltage)

    For setting angle for load blinder, a value of 30is set which is adequate.

    Guidelines for Phase selection:Reactive reach

    The reactive reach in forward direction must as minimum be set to cover the measuring zone used

    in the Teleprotection schemes, mostly zone 2.

    X1PHS1.44 X1Zm

    X0PHS1.44 X0Zm

    where:

    X1Zm is the reactive reach for the zone to be covered by FDPSPDIS, and the constant 1.44 is a

    safety margin

    X0 is the zero sequence reactive reach for the zone to be covered by FDPSPDIS

    Model setting calculation document for Transmission Line

    where:

    RFPE i h i RFPE f h l hi b d b FDPSPDIS

  • 8/11/2019 Guidelines Relay Setting

    65/467

    RFPEZmis the setting RFPE for the longest overreaching zone to be covered by FDPSPDIS.

    Phase-to-earth fault in reverse directionReactive reach

    The reactive reach in reverse direction is the same as for forward so no additional setting is

    required.

    Resistive reach

    The resistive reach in reverse direction must be set longer than the longest reverse zones. In

    blocking schemes it must be set longer than the overreaching zone at remote end that is used in the

    communication scheme.

    RFRvPE 1.2 RFPE ZmRv

    Phase-to-phase fault in forward direction

    Reactive reach

    The reach in reactive direction is determined by phase-to-earth reach setting X1.

    No extra setting is required.

    Resistive reach

    In the same way as for phase-to-earth fault, the reach is automatically calculated based on setting

    X1. The reach will be X1/tan(60) =X1/(3).

    Fault resistance reach

    The fault resistance reaches in forward direction RFFwPP, must cover RFPPZm with at least 25%margin. RFPPZm is the setting of fault resistance for phase to phase fault for the longest

    overreaching zone to be covered by FDPSPDIS

    RFFwPP 1.25 RFPPZm

    where:

    RFPPZmis the setting of the longest reach of the overreaching zones that must be covered by

    FDPSPDIS .

    RFRvPP 1.25 RFPPzmRv

    The proposed margin of 25% will cater for the risk of cut off of the zone measuring characteristic

    that might occur at three phase fault when FDPSPDIS characteristic angle is changed from 60to

    Model setting calculation document for Transmission Line

    IMinOpPE: Setting of minimum operating current for Phase faults. Measures ILx. This is the

    i i t i d i h t th f lt f t T b t t 20% f IB

  • 8/11/2019 Guidelines Relay Setting

    66/467

    minimum current required in phase to earth fault for zone measurement. To be set to 20% of IBase.

    Setting Calculations:Calculations for Load encroachment:

    Ur = 400kV, Umin = 0.90x400 = 360kV,

    CT ratio = 1000/1A and PT ratio = 400kV/110V

    Maximum load in MVA = 1500

    ZLmin= 360 x 360/ (1500),

    = 86.4

    RLmin= 86.4 x cos30 = 74.82. Since considered load