guide for high-voltage circuit breakers
TRANSCRIPT
-
8/18/2019 Guide for High-Voltage Circuit Breakers
1/12
ANSI C37.06.1-2000
American National Standard
Guide for High-Voltage Circuit BreakersRated on Symmetrical Current BasisDesignated “Denite Purpose forFast Transient Recovery VoltageRise Times”
Approved 03/30/00
American National Standards Institute, Inc.
-
8/18/2019 Guide for High-Voltage Circuit Breakers
2/12
-
8/18/2019 Guide for High-Voltage Circuit Breakers
3/12
ANSI C37.06.1-2000Page i
Approval of an American National Standard requires verification by ANSI that the
requirements for due process, consensus, and other criteria for approval havebeen met by the standards developer.
Consensus is established when, in the judgment of the ANSI Board of StandardsReview, substantial agreement has been reached by directly and materiallyaffected interests. Substantial agreement means much more than a simplemajority, but not necessarily unanimity. Consensus requires that all views andobjections be considered, and that a concerted effort be made toward theirresolution.
The use of American National Standards is completely voluntary; their existencedoes not in any respect preclude anyone, whether he has approved the standardsor not, from manufacturing, marketing, purchasing, or using products, processes,or procedures not conforming to the standards.
The American National Standards Institute does not develop standards and will inno circumstances give an interpretation of any American National Standard.Moreover, no person shall have the right or authority to issue an interpretation ofan American National Standard in the name of the American National Standards
Institute. Requests for interpretations should be addressed to the secretariat orsponsor whose name appears on the title page of this standard.
CAUTION NOTICE: This American National Standard may be revised orwithdrawn at any time. The procedures of the American National StandardsInstitute require that action be taken periodically to reaffirm, revise, or withdrawthis standard. Purchasers of American National Standards may receive currentinformation on all standards by calling or writing the American National StandardsInstitute.
AmericanNationalStandard
-
8/18/2019 Guide for High-Voltage Circuit Breakers
4/12
ANSI C37.06.1-2000Page ii
-
8/18/2019 Guide for High-Voltage Circuit Breakers
5/12
ANSI C37.06.1-2000Page iii
FOREWORD (This foreword is not part of American National Standard C37.06.1-2000)
Following reports of circuit breaker failures in applications where very fast TRVs were determined to be thecause, and after thorough analysis of TRV data gathered from all parts of the world, this guide wassuggested by the IEEE Switchgear Committee’s Task Force on Transient Recovery Voltages. The task forcesuggested that another class of definite purpose circuit breakers was needed for fast TRV applications.Circuit breakers designated as definite purpose for fast transient recovery voltage rise times applicationswould be subjected to special fast TRV parameters during both Test Duty 2 (30% of rated short-circuitcurrent) and Test Duty 1 (7% of rated short-circuit current) trials, to demonstrate the capability to interruptcircuits characterized by fast inherent TRVs. A few words of clarification are in order:
• No fast T 2 values or tests are proposed for fault currents greater than 30% of rated short-circuitcurrent.
• The proposed fast T 2 values were chosen to meet 90% of the known fast TRV circuits, but eventhese fast values do not meet the requirements of all fast TRV applications.
• A circuit breaker that would meet the requirements for definite purpose for fast TRV rise timesapplications may or may not also meet the requirements for definite purpose circuit breakers forcapacitor switching.
It is the purpose of this guide to communicate the suggested values to those in the industry who areinterested and who would be in a position to offer comments and suggestions for further revisions.
Table 1B contains values for circuit breakers designed and tested to the circuit breaker ratings contained in ANSI C37.06-2000, Table 1. These circuit breaker ratings have a rated voltage range factor (K) equal to 1.0.
Tables 2B and 3B contain values for circuit breaker ratings contained in ANSI C37.06-2000, Tables 2 and 3.
This guide was initially approved as a “trial-use” guide in 1997. Experience with the trial-use document sincethen has been favorable, and the document is now approved for more general use as a guide. Only minoreditorial revisions have been made to the guide, plus suitable revisions to the text of this “Foreword.”
Comments and suggestions relative to the revision of this document should be sent to:
-
8/18/2019 Guide for High-Voltage Circuit Breakers
6/12
ANSI C37.06.1-2000Page iv
Organizations Represented Name of Representative
Electric Light and Power Group ........................................... D.E. GaliciaJ.L. KoepfingerG.J. MartuscelloY. MusaE. Worland
Institute of Electrical andElectronics Engineers......................................................... T. Burse
K. Gray
A. MonroeB. PuckettT.E. RoysterR. Garzon (Alt)J.G. Wood (Alt)
National Electrical Manufacturers Association ......................................................................... G. Jones
W. LongT. OlsenG. SakatsD. StoneE. Byron (Alt)
International Electrical Testing Association ......................................................................... A. Peterson
National Electrical Contractors Association ......................................................................... D. Harwood
Testing Laboratory Group .................................................... P. NotarianE. Roseen
Tennessee Valley Authority J Nelson
-
8/18/2019 Guide for High-Voltage Circuit Breakers
7/12
ANSI C37.06.1-2000Page v
CONTENTS Page
Foreword.....................................................................................................................................................iii
1 Scope..........................................................................................................................................................1
2 Purpose.......................................................................................................................................................1
3 References .................................................................................................................................................1
4 Rated values...............................................................................................................................................1
TablesTable 1B—Transient recovery voltage parameters fast time-to-peak (T 2 )
values for definite purpose indoor circuit breakers with voltage rangefactor K=1.0 ....................................................................................................................................2
Table 2B—Transient recovery voltage ratings fast time-to-peak (T 2 ) valuesfor definite purpose circuit breakers 72.5 kV and below, including
circuit breakers applied in gas insulated substations.....................................................................3
Table 3B—Transient recovery voltage ratings fast time-to-peak (T 2 ) valuesfor definite purpose circuit breakers 123 kV and above ................................................................4
-
8/18/2019 Guide for High-Voltage Circuit Breakers
8/12
ANSI C37.06.1-2000Page vi
-
8/18/2019 Guide for High-Voltage Circuit Breakers
9/12
AMERICAN NATIONAL STANDARD C37.06.1-2000
Guide for High-Voltage Circuit Breakers Rated on a Symmetrical Current BasisDesignated “Definite Purpose for Fast Transient Recovery Voltage Rise Times”
1 Scope
This guide is issued as a supplement to C37.06 for high-voltage circuit breaker applications where thetransient recovery voltages (TRV) rise to the crest value much more rapidly than those specified in ANSIC37.06:
Table 1, Preferred ratings for indoor circuit breakers with voltage range factor K=1.0;
Table 2, Preferred ratings for outdoor circuit breakers 72.5 kV and below; or
Table 3, Preferred ratings for outdoor circuit breakers rated 123 kV and above.
2 Purpose
The purpose of this guide is to provide suggested values of fast transient recovery voltage rise time ratings.The proposed ratings were suggested by the IEEE Switchgear Committee, and apply ONLY to currents in the
ranges of 7 percent to 30 percent of Rated Short-Circuit Current. The TRVs for currents more than or equalto 60% of rated short-circuit current remain the same as for general purpose circuit breakers. Circuitbreakers not identified by the manufacturer as "definite purpose for fast transient recovery voltage rise times"shall be understood to be "general purpose circuit breakers," meeting the C37.06 standard TRVrequirements in table 1, 2, or 3 as appropriate.
3 References
ANSI/IEEE C37.04-1999, Rating Structure for AC High-Voltage Circuit Breakers Rated on a Symmetrical
Current Basis ANSI C37.06-2000, AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis - PreferredRatings and Related Required Capabilities
-
8/18/2019 Guide for High-Voltage Circuit Breakers
10/12
Table 1B – Transient recovery voltage parameters fast time-to-peak (T 2 ) valuesfor definite purpose indoor circuit breakers with voltage range factor K=1.0
Rated
Maximum
Rated
Voltage
RatedShort-Circuit
and Short-Time
Rated TransientRecovery Voltage
(1)
Definite Purpose TRV Parameters at
30% of Rated Short-Circuit Current
Definite Purpose TRV Parameters at
7% of Rated Short-Circuit Current
Line
VoltagekV, rms
(1)
RangeFactor K
(1)
CurrentkA, rms
(1)
PeakVoltage E 2
KV
Time toPeak T 2
µµ secCurrentkA, rms
PeakVoltage
kV
Time toPeakµµ sec
CurrentkA, rms
PeakVoltage
kV
Time toPeakµµ sec
No. Col. 1 Col. 2 Col. 3 Col. 4 Col. 5 Col. 6 Col. 7 Col. 8 Col. 9 Col. 10 Col. 11
12345
67
8910
1112131415
4.764.764.768.2515
1515
151527
2738383838
1.01.01.01.01.0
1.01.0
1.01.01.0
1.01.01.01.01.0
31.540504020
2531.5
405016
251625
31.540
8.98.98.9
15.528
2828
282851
5171717171
5050506075
7575
7575105
105125125125125
9.51215126
7.59.5
12154.8
7.54.87.59.512
10.110.110.117.531.6
31.631.6
31.631.658
5880808080
43.93.74.58.3
7.77
6.66.213
11141211
10.5
2.22.83.52.81.4
1.82.2
2.83.51.1
1.81.11.82.22.8
10.410.410.418
32.8
32.832.8
32.832.860
6083838383
7.26.568
15
13.512
111025
2027
21.520
17.5
Note(1) See Table 1 of C37.06 for circuit breaker ratings.
Copyright © 2003 IEEE. All rights reserved.
-
8/18/2019 Guide for High-Voltage Circuit Breakers
11/12
Table 2B–Transient recovery voltage ratings fast time-to-peak (T 2) values for definite purpose circuit breakers72.5 kV and below, including circuit breakers applied in gas insulated substations
Rated Rated
Rated
Short-Circuit
Rated TransientRecovery Voltage
(1)
Definite Purpose TRV Parameters at
30% of Rated Short-Circuit Current
Definite Purpose TRV Parameters at
7% of Rated Short-Circuit Current
Line
MaximumVoltage
kV, rms (1)
VoltageRange
Factor (1)
and Short-Time Current
kA, rms (1)
PeakVoltage E 2 kV, peak
Time toPeak T 2
µµ secCurrentkA, rms
PeakVoltagekV, peak
Time toPeakµµ sec
CurrentkA, rms
PeakVoltagekV, peak
Time to Peakµµ sec
No. Col 1 Col 2 Col 3 Col 4 Col 5 Col 6 Col 7 Col 8 Col 9 Col 10 Col 1112345
6789
10
1112131415
1617
15.515.515.515.525.8
25.838.038.038.038.0
38.048.348.348.372.5
72.572.5
1.01.01.01.01.0
1.01.01.01.01.0
1.01.01.01.01.0
1.01.0
12.5202540
12.5
25162025
31.5
4020
31.54020
31.540
29292929
48.5
48.571717171
71919191
136
136136
3636363652
5263636363
63808080
106
106106
3.86.07.5
12.03.8
7.54.86.07.59.5
12.06.09.5
12.06.0
9.512.0
3333333355
5581818181
81103103103154
154154
10887
13
1014131211
1115131219
1615
0.91.41.82.80.9
1.81.11.41.82.2
2.81.42.22.81.4
2.22.8
3434343457
5784848484
84106106106159
159159
1414141121
1825242220
1828232135
2825
Note
(1) See Table 2 of C37.06 for circuit breaker ratings.
Copyright © 2003 IEEE. All rights reserved.
-
8/18/2019 Guide for High-Voltage Circuit Breakers
12/12
Table 3B–Transient recovery voltage ratings fast time-to-peak (T 2) valuesfor definite purpose circuit breakers 123 kV and above
Rated RatedRated
Short-Circuit
Rated Transient
Recovery Voltage(1)
Definite Purpose TRV Parameters at30% of Rated Short-Circuit Current
Definite Purpose TRV Parameters at7% of Rated Short-Circuit Current
Line
MaximumVoltage
kV, rms (1)
VoltageRange
Factor (1)
and Short-Time Current
kA, rms (1)
PeakVoltage E 2 kV, peak
Time toPeak T 2
µµ secCurrentkA, rms
PeakVoltagekV, peak
Time toPeakµµ sec
CurrentkA, rms
PeakVoltagekV, peak
Time toPeakµµ sec
No. Col 1 Col 2 Col 3 Col 4 Col 5 Col 6 Col 7 Col 8 Col 9 Col 10 Col 1112345
6789
10
1112131415
161718
1920
2122
123123123145145
145145170170170
170170245245245
245362362
550550
800800
1.01.01.01.01.0
1.01.01.01.01.0
1.01.01.01.01.0
1.01.01.0
1.01.0
1.01.0
2040632040
638016
31.540
5063
31.54050
634063
4063
4063
216216216255255
255255299299299
299299431431431
431637637
968968
14081408
275260260330310
310310395360360
360360520520520
520775775
13251325
15301530
612196
12
19248
9.512
15199.51215
191219
1219
1219
245245245288288
288288338338338
338338487487487
487720720
10941094
15911591
28.323.521.430.925.8
23.522.635.229.127.8
26.425.434.833.331.6
30.340.737.1
49.044.7
60.755.3
1.42.84.41.42.8
4.45.61.12.22.8
3.54.42.22.83.5
4.42.84.4
2.84.4
2.84.4
253253253299299
299299350350350
350350505505505
505745745
11331133
16471647
48.736.531.053.440.0
34.031.263.447.043.2
35.736.756.251.647.4
43.863.255.7
76.163.9
94.179.9
Note(1) See Table 3 of C37.06 for circuit breaker ratings.
Copyright © 2003. All rights reserved.