Group: PTAC Part No.: 106018541 Date: May 1999 Installation & Maintenance Data IM 420-1 ©1999 AAF–McQuay Incorporated IM 420-1 / Page 1 (Rev. 5/99) Suite II Wall Sleeves Wall opening requirement Before installing the unit, check the wall opening to be sure the cabinet/wall sleeve will slide into the opening unobstructed. For masonry walls, a lintel must be used to provide support over each opening. The rough opening should measure 16 1 /4" x 42 1 /4" (413mm x 1023mm) wide (see note 3, Figure 2). When no subbase is used, the opening should be a minimum of 3" (76mm) off the floor. This distance is available in 3" (76mm) or 4" (102mm) heights. For units with hydronic heat, the subbase is 8 1 /4" (210mm). Each subbase has leveling legs providing for up to 1" (25mm) additional height. Attaching cabinet wall sleeve to subbase After the electrical or hydronic subbase has been set in place and the rough-in for plumbing and/or electrical is complete, the cabinet/wall sleeve can be installed. 1. Install cabinet/wall sleeve as described on pages 2 through 4. 2. Attach the subbase to the cabinet/wall sleeve using the clips provided. 3. Secure the two sections by installing the clip screws supplied with the hardware bag. Figure 1. Wall Sleeve 4. Caulk indoor/outdoor perimeter of cabinet/wall sleeve with resilient caulk such as silicone. 5. Finish any uncompleted electrical and/or plumbing connections. Notes: *Subbase Side Dimension: Electric: 4 3 /8" to 13 3 /4" (111mm to 349mm) Hydronic: 0" to 13 3 /4" (0mm to 349mm) **Subbase Height Dimension: Electric: 3" to 4" (76mm to 102mm) with 0" to 1" (0mm to 25m) leveling screw Hydronic: 8" (203mm) with 1 /4" (6mm) to 1 1 /4" (32mm) leveling bolts Unit pictured with subbase installed. Subbase is optional on 208V and 230V units. Subbase is standard on all 265V units and units with hydronic heat. Hydronic subbase is flush with the front of the cabinet. Electric subbase is flush with wall sleeve. Subbase extends to front edge of unit when furnished with hydronic heat. Opening needs to be 16 5 /8" x 42 5 /8" (422mm x 1083mm) when using a louver frame. Subbase side channels are adiustable from 4 3 /8" to 13 3 /4" (111mm to 349mm). Figure 2. Unit with Subbase Note: Wall sleeve shown with optional insulation installed. Tinnerman Clips 42" (1067 mm) 13 3 /4" (349 mm) 43" (1092 mm) 16 1 /2" (419 mm) 41 1 /2" (1054 mm) 16" (406 mm) 8 1 /4" (210 mm) * ** 22" (559 mm) 4

Upload: vutu

Post on 19-Jul-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

Group: PTAC

Part No.: 106018541

Date: May 1999

Installation & Maintenance Data IM 420-1

©1999 AAF–McQuay Incorporated IM 420-1 / Page 1 (Rev. 5/99)

Suite II™ Wall Sleeves

Wall opening requirementBefore installing the unit, check the wall opening to be sure thecabinet/wall sleeve will slide into the opening unobstructed. Formasonry walls, a lintel must be used to provide support over eachopening. The rough opening should measure 161/4" x 42 1/4"(413mm x 1023mm) wide (see note 3, Figure 2). When nosubbase is used, the opening should be a minimum of 3"(76mm) off the floor. This distance is available in 3" (76mm)or 4" (102mm) heights. For units with hydronic heat, thesubbase is 81/4" (210mm). Each subbase has leveling legsproviding for up to 1" (25mm) additional height.

Attac hing cabinet wall slee ve to subbaseAfter the electrical or hydronic subbase has been set in placeand the rough-in for plumbing and/or electrical is complete, thecabinet/wall sleeve can be installed.1. Install cabinet/wall sleeve as described on pages 2 through 4.2. Attach the subbase to the cabinet/wall sleeve using the clips

provided.3. Secure the two sections by installing the clip screws supplied

with the hardware bag.

Figure 1. Wall Sleeve

4. Caulk indoor/outdoor perimeter of cabinet/wall sleeve withresilient caulk such as silicone.

5 . Finish any uncompleted electrical and/or plumbingconnections.

Notes:*Subbase Side Dimension:

Electric: 43/8" to 133/4" (111mm to 349mm)Hydronic: 0" to 133/4" (0mm to 349mm)

**Subbase Height Dimension:Electric: 3" to 4" (76mm to 102mm) with 0" to 1" (0mm to 25m) leveling

screwHydronic: 8" (203mm) with 1/4" (6mm) to 11/4" (32mm) leveling bolts

➀ Unit pictured with subbase installed. Subbase is optional on 208V and 230V units.Subbase is standard on all 265V units and units with hydronic heat. Hydronicsubbase is flush with the front of the cabinet. Electric subbase is flush with wallsleeve.

➁ Subbase extends to front edge of unit when furnished with hydronic heat.

➂ Opening needs to be 165/8" x 425/8" (422mm x 1083mm) when using a louverframe.

Subbase side channels are adiustable from 43/8" to 133/4" (111mm to 349mm).

Figure 2. Unit with Subbase

Note: Wall sleeve shown with optional insulation installed.

TinnermanClips

42"(1067 mm)

133/4"(349 mm)

43"(1092 mm)

161/2"(419 mm)

411/2"(1054 mm)

16" (406 mm)

81/4"(210 mm) *

**22" (559 mm)

4

IM 420-1 / Page 2 (Rev.5/99)

A heavy-gauge, corrosion resistant cabinet/wall sleeve isprovided for each unit. The cabinet/wall sleeve is either shippedin a separate carton, shipped in a multipack of 15 or in a singlecarton with the heating/cooling chassis.

The standard cabinet/wall sleeve is designed to be easilyinstalled in a variety of wall constructions. Note: The center of grav-ity is 101/4" (260mm) from the rear face of the wall sleeve. The wallsleeve must be inserted into the wall at least 101/4" (260mm) or othersupport must be employed. Support can be from a factory suppliedsubbase or from other field supplied materials. Recommendedinstallation procedures are described below.1. Clean the opening of all debris that may interfere with installation.2. If the unit is to be supplied with a subbase, install subbase

before installing cabinet/wall sleeve (see IM 419 or IM 420).3. lf the optional drain kit is to be employed (heat pump only),

see IM 430-2.4. Place a thin pad of soft mortar on the bottom of the opening

and slide in the cabinet/wall sleeve. Be sure to recess the wallsleeve enough to accommodate outside louver. This recessis 3/8" (9.5mm) for stamped louvers and 11/4" (32mm) for ar-chitectural louvers. Louver should be flush to exterior surfacewith complete. Note: The wall sleeve is not intended to re-place the lintel.

5. Level cabinet/wall sleeve in both directions and secure by an-choring with appropriate fasteners. A 5/16" (8mm) hole is pro-vided on each side, 2" (51 mm) down from the top and 2"(51mm) in from the rear of the cabinet/wall sleeve. Additionalholes may be required to firmly secure the cabinet/wall sleeve.Caution: Do not drill holes in the base of the cabinet/wallsleeve. Where a subbase is used, secure wall sleeve to sub-base with clips provided.

6. Caulk the cabinet/wall sleeve to the wall opening on both theinside and outside perimeter. Be careful not to plug the weepholes. Caulking should be resilient, nonhardening type suchas silicone.

Wall sleeve installation — frame and brick

Note : Standard subbase is available in 3" or 4" (76 mm or 102 mm) height.Leveling legs provide adjustment of 1" (25 mm).

Figure 3. Frame and brick with cord connection

STEEL LINTEL (BYOTHERS)

81/4"(209mm)

16"(406mm)

ROOMCABINET

3" MIN.(76mm)

FINISHEDFLOOR OR

CARPET

WALLRECEPTACLEBY OTHERS

CAULKPERIMETER

OUTDOORLOUVER

MOUNTINGSCREWS BY

INSTALLER

133/4"(349mm)

WALL SLEEVE

Figure 4. Frame and brick with standard electrical subbase Figure 5. Frame and brick with hydronic subbase

STEEL LINTELBY OTHERS

43/8"(111mm)

OUTSIDELOUVER

MOUNTINGHOLES BY

INSTALLER

81/4"(209mm)

CAULKPERIMETERBOTHINDOORS &OUTDOORSBEFOREINSTALLINGLOUVER

POWER SUPPLY CONNECT(ALTERNATE ENTRY)

LEVELING LEGFINISHED

FLOOR ORTOP OF

CARPET

SEE NOTE

133/4"(349mm)

WALL SLEEVE

ROOMCABINET

SUBBASE

16"(406mm)

MOUNTINGSCREWS BY

INSTALLER

OUTDOORLOUVER

STEEL LINTEL(BY OTHERS)

HYDRONICHEATINGCOIL

16"(406mm)

81/4"(209mm)

133/4"(349mm)

CAULKPERIMETERBOTHINDOORS &OUTDOORSBEFOREINSTALLINGLOUVER

SUBBASESIDE

CHANNELALTERNATEELECTRICAL

CONNECTIONS

HYDRONICSUBBASE

FINISHEDFLOOR ORCARPET

81/4"(209mm)

ROOMCABINET

WALLSLEEVE

17"(432mm)

17"(432mm)

17"(432mm)

Certified Drawing

IM 420-1 / Page 3 (Rev. 5/99)

Wall sleeve installation–panel wall construction

Note : Standard subbase is available in 3" or 4" (76 mm or 102 mm) height.Leveling legs provide adjustment of 1" (25 mm).

Figure 7. Panel wall construction withstandard electrical subbase Figure 8. Panel wall installation with hydronic subbase

For panel wall and thin wall construction, it is recommended thata louver frame be used.

Panel wall and thin wall construction varies only slightly fromframe and brick construction. Note: The center of gravity is 10"(260mm) from the rear face of the wall sleeve. The wall sleevemust be inserted into the wall at least 10" (260mm) or othersupport must be employed. Support can be from a factorysupplied subbase or from other field supplied materials.Installation for this application is as follows:1. Clean the opening of all debris that may interfere with

installation.2. If the unit is to be supplied with a subbase, install subbase

before installing cabinet/wall sleeve (see IM 419 or IM 420).3. If the optional drain kit is to be employed, see IM 430-3.4. Be sure the cabinet/wall sleeve is mechanically attached to

the wall and caulked to assure a proper seat. It isrecommended that the louver frame be used for this purpose.

5. Recess the wall sleeve so that the louver is flush with theexterior of the building.

6. Level cabinet/wall sleeve in both directions and secure byanchoring with appropriate fasteners or drill additional holesas required to secure firmly. Caution: Do not drill holes in thebase of the cabinet/wall sleeve. Where a subbase is used,secure wall sleeve to subbase with clips provided.

7. Caulk the cabinet/wall sleeve to the wall opening on both theinside and outside perimeter. Be careful not to plug the weepholes. Caulking should be resilient, nonhardening type suchas silicone.

Figure 6. Panel wall construction with cord connection

OUTDOORLOUVER

3"MIN. (76mm) CAULKPERIMETER

BOTHINDOORS &OUTDOORS

MINIMUM 2SUPPORTS FIELD

SUPPLIED

CONDUIT

ROOMCABINET

WALLSLEEVE

133/4"(349mm)

81/4"(209mm)

16"(406mm)

FLOOR

LOUVERFRAME

SEE NOTE

ROOMCABINET

16"(406mm)

81/4"(209mm)

LOUVERFRAME

133/4"(349mm)

ELECTRICALSUBBASE

WALL SLEEVE

POWER SUPPLYCONDUIT

(ALTERNATE ENTRY)SUBBASE SIDE

CHANNEL

GASKET &CAULK

PERIMETER

OUTSIDELOUVER

16"(406mm)

LOUVERFRAME

WALLSLEEVE

POWER SUPPLY CONDUIT(ALTERNATE ENTRY)

CAULKPERIMETER

BOTH INDOORS& OUTDOORS

SUBBASESIDE

CHANNEL

ROOMCABINET

81/4"(209mm)

81/4"(209mm)

OUTDOORLOUVER

133/4"(349mm)

HYDRONICHEATING

COIL

LEVELING LEGSW/1" ADJUSTMENT

RECEPTACLESBY OTHERS

17"(432mm) 17"

(432mm)

17"(432mm)

IM 420-1 / Page 4 (Rev. 5/99)

AAF–McQuay Incorporated

4900 Technology Park Boulevard, Auburn, New York 13021-9030 USA (315) 253-2771

Printed on recycled paper containing at least 10% post-consumer recycled material.

Installation of cabinet/wall sleeves for thick walls requires specialconsideration. Table 1 should be used to determine themaximum wall thickness allowed for the standard cabinet/wallsleeve. For thicker walls, cabinet/wall sleeve extensions areavailable from your representative. Wall sleeve installation in thick walls is similar to frame andbrick installation. Install as follows:1. Clean the opening of all debris that may interfere with

installation.2. If the unit is to be supplied with a subbase, install subbase

before installing cabinet/wall sleeve (see IM 419 or IM 420).3. If the optional drain kit is to be employed (heat pump only),

see IM 430-3.4. If wall thickness exceeds dimensions shown in Table 1, a

cabinet/wall sleeve extension must be used. Once theextension is attached to the cabinet/wall sleeve, place a thinpad of soft mortar on the bottom of the opening and slide inthe wall sleeve/extension assembly. Be sure to recess the wallsleeve enough to accommodate outside louver. This recessis 3/8" (9.5mm) for stamped louvers and 11/4" (32mm) for ar-chitectural louvers. Louver should be flush to exterior surfacewhen completed. Note: The wall sleeve is not intended to re-place the lintel.

5. Level cabinet/wall sleeve in both directions and secure byanchoring with appropriate fasteners or drill additional holesas required to secure firmly. Caution: Do not drill holes in thebase of the cabinet/wall sleeve. Where a subbase is used,secure wall sleeve to subbase with clips provided.

6. Caulk the cabinet/wall sleeve to the wall opening on both theinside and outside perimeter. Be careful not to plug the weepholes. Caulking should be resilient, nonhardening type suchas silicone.

Wall slee ve installation– thic k wall construction

Figure 11. Thick wall installation with hydronic subbase

Figure 9. Thick wall construction with cord connection

Figure 10. Thick wall construction withstandard electrical subbase

Note : ➀ Standard subbase is available in 3" or 4" (76 mm or 102 mm) height.Leveling legs provide adjustment of 1" (25 mm).

➁ Wall sleeve extension is available in various depths and supplied asrequired.

CAULKPERIMETER

OUTDOORLOUVER

MOUNTINGSCREWS BYINSTALLER

WALLSLEEVEEXTENSION

WALLRECEPTACLEBY OTHERS

3"MIN.(76mm)

17"(432mm)

SEETABLE 1

STEELLINTEL (BYOTHERS)

1/8"(3mm)MIN.

81/4"(209mm)

ROOMCABINET

WALLSLEEVE

FLOOR

133/4"(349mm)

SEETABLE 1

16"(406mm)

CAULKPERIMETER

MOUNTINGSCREWS BYINSTALLER

SEENOTE

2133/4"

(349mm)

OUTDOORLOUVER

WALL

SLEEVE

EXTENSION ELECTRICALSUBBASE

81/4"(209mm)

ROOMCABINET

STEELLINTEL(BY OTHERS)

SEE NOTE 1

FLOOR

43/8"MIN.

(111mm)

SEE TABLE 1

1" (25mm)

CAULKPERIMETER

MOUNTINGSCREWS BYINSTALLER

OUTDOORLOUVER

WALLSLEEVEEXTENSION

HYDRONICSUBBASE

HYDRONICHEATING

COIL

81/4"

(209mm)

ROOMCABINET

16"

(406mm)

81/4"

(209mm)

FLOOR

WALL SLEEVE133/4"

(349mm)

STEELLINTEL BYOTHERS

LOUVERTYPE

Stamped

Architectural

NOSUBBASE

STANDARDSUBBASE

HYDRONICSUBBASE

MAXIMUM WALL THICKNESS

14"(356mm)

147/8"(378mm)

91/2"(241mm)

103/8"(264mm)

131/8"(333mm)

14"(356mm)

16"(406mm)

17"(432mm)

17"(432mm)