grounding and overvoltage requirements for distributed ... · grounding and overvoltage...
TRANSCRIPT
Grounding and Overvoltage Requirements for
Distributed Generation (Wind and Solar)
Reigh Walling
Walling Energy Systems Consulting, LLC
1
Scope of Presentation
We will cover:
– Temporary and transient overvoltages on distribution feeders
– Related to interconnection of distributed wind and solar plants
– Ways to avoid or mitigate these overvoltages
2
Overvoltage Definitions
• Transient overvoltage – impulses and supersynchronous oscillations lasting less than a couple of cycles
– Examples: lightning, switching, etc.
• Temporary overvoltage – oscillatory overvoltage persisting for many cycles to seconds
– Examples: load rejection, single-phase faults, ferroresonance, etc.
3
Surge Arresters
• Surge arresters are designed to limit transient overvoltages, not intended to limit TOV
• Surge arresters are the likely victims of TOV
• Failure modes of surge arresters
– MOV material fails to a low resistance
– Physical integrity of arrester housing uncertain
– Ground lead disconnects blow off
5
Impacts of TOV on Customers
• TOV withstands of consumer equipment are poorly documented
• Not defined by any formal standards
• ITIC (formerly CBEMA) curve is often cited
• Experience suggests ITIC curve is excessively conservative
• TOV can result in large claims against utility
6
1.2 p.u.
for 3 ms !!
Loss of Ground Scenario • Focus of utility concern regarding DG plants
– Ground fault on feeder
– Feeder breaker trips; losing normal ground source
– DG doesn’t trip immediately, continues to energize
– If there is no ground source, high TOV may result
7
A
N
B C
1 p.u. 1 p.u.
1.73 p.u. Phase A faulted
to ground
Effectively Grounded Systems
• Definition of effectively grounded system is where the COG < 0.8 (COG = TOV/VL-L)
–TOV < 1.39 p.u. in effectively grounded systems
• C62.91 states X0/X1<3 and R0/X1<1 generally results in COG<0.8, but is not the definition
• Multi-grounded feeders are designed to be effectively grounded
– Coordinates with arrester TOV capabilities
– Experience indicates customers are ok
8
Ground Sources – Desired and Unintended
Ground sources are the zero-sequence admittances of the circuit
• Primary substation transformer – breaker open
• Cable charging and grounded cap banks
• Grounded-wye loads
• Grounded-wye delta and zig-zag transformers
– May be added to feeder to mitigate loss-of-ground
– Subject to overload from feeder imbalance
9
Classic TOV Analysis
• Generators conventionally assumed to be voltage sources behind impedance
• Loads and shunt capacitance usually ignored
10
x
x
x
x
x
x
Z1
Z2
Z0
V1
V2
V0
I0
Sym. component
network for
single-phase fault
Wind and Solar Sources • Solar (PV) inverters – grid interactive
– Controlled current sources, not voltage source
– Three-phase inverters are ungrounded source
– Three-phase inverters may not pass I2
• Wind generation – Legacy induction generators (Types 1 and 2) approximately
a voltage source until flux collapses
– Full conversion (Type 4) are inverters just like PV
– Doubly-fed (Type 3) are current sources until they crowbar, then they are like an induction generator
11
Conventional X0/X1 only applies to: • Solar (PV) inverters – grid interactive
– Controlled current sources, not voltage source
– Three-phase inverters are ungrounded source
– Three-phase inverters may not pass I2
• Wind generation – Legacy induction generators (Types 1 and 2) approximately
a voltage source until flux collapses
– Full conversion (Type 4) are inverters just like PV
– Doubly-fed (Type 3) are current sources until they crowbar, then they are like an induction generator
12
Loading Impact on Type 1 and Type 3(crowbarred) WTG TOV
• These are the only wind and solar DG that can be assumed to behave as a voltage source
13
Inverter-Interfaced DG
• The following behave as current sources:
– PV
– Type 4 wind turbines
– Type 3 (wind turbines when not crowbarred)
• Conventional X0/X1 criteria do not apply
14
Other DG Overvoltage Issues • Abrupt isolation of inverter into light load
– Known as “load rejection overvoltage”
– Tests and field events have shown voltage > 2 p.u.
– Inverter should trip immediately
• Reclose out of phase of a compensated feeder
15
Other DG Overvoltage Issues
• Self-excitation of induction generator
– Light load
– Sufficient capacitive compensation
16
Overvoltage Mitigation
• Provision of ground source where needed – Grounded-wye delta or zig-zag grounding banks
– Grounded-wye delta interconnection transformer
– Grounded wye-wye does not make a ground source
• Adequate load relative to DG – Load to DG capacity ratio depends on type
• Coordinated transfer trip – DG disconnected before feeder opens
• Coordinated grounding switch (crowbar)
17
Overvoltage Mitigation (cont’d)
• Fast DG overvoltage tripping – DG may not see TOV on primary side
– Coordination with VRT will be needed in future
• Fast islanding detection – Increased challenge with evolving ride-through
requirements
• Sacrificial arresters – Difficult to coordinate with utility arresters
– Coordination with load withstand is uncertain
18