governor modes of operation

Upload: chikkam

Post on 06-Apr-2018

287 views

Category:

Documents


11 download

TRANSCRIPT

  • 8/3/2019 Governor Modes of Operation

    1/21

    Governor Modes of Operation

    The Governor is the primary speed/load controller of the turbine. Turbine

    governor is the one which controls the fuel/steam input to the turbine thus controlling

    the speed and power output from the turbine. The turbine governor usually has

    different modes of operation which can be selected depending on the operating

    conditions of the generator. The response of the governor during system disturbance,

    both small signal which is common during normal operating conditions and large

    signal which is during a rare fault condition; depends on which mode of turbine

    control is selected in the governor.

    There are mainly three Governor Modes

    a. Turbine Droop Control

    b. Turbine Load Control

    c. Turbine Isochronous Control

    The turbine droop control is the basic turbine governor mode. In this mode the

    speed reference is reduced with the increase in load of the turbine. The droop refers to

    the change in speed expressed as a percentage of rated speed when the machine is

    loaded from no load to full load. In this mode the speed is the reference to which the

    governor takes action. The droop controlled is a proportional controller. The droop

    control is used for both Islanding operation and also for operation with the gird.

    The turbine load control is a modified droop control. In this mode the Load of the

    turbine is the reference and the governor tries to maintain a constant load under all

    operating conditions irrespective of the frequency changes. The turbine load control is

    a either a PI or a PID controller depending on how it is configured in the governorcontrol system. The Turbine load control is used only for operation with the grid and

    not for operation in independent island condition.

    The Turbine Isochronous control is the frequency control. In this mode the

    frequency of the turbine is the set point and the governor tries to maintain a constant

    frequency under all operating conditions irrespective of load changes. The Turbine

    isochronous control is either a PI or a PID controller depending on how it is

    configured in the governor control system. The turbine isochronous control is used

    only for operation in island condition and not for operation with the grid.

  • 8/3/2019 Governor Modes of Operation

    2/21

    Turbine Droop control Mode

    When the Turbine is put in droop control mode, the speed reference is

    decreased with increase in the load of the machine. The droop in effect refers to the

    change (reduction) in frequency when the machine is loaded from no load to full load.

    The droop is expressed as a percentage of the change in frequency from no load to fullload to the turbine rated frequency.

    For example, if the turbine is rated at 3000 rpm, and the machine speed

    reduces from 3000 rpm to 2880 rpm when it is loaded from full load to no load, then

    the droop % is given by

    Droop % (Turbine) = Rated No load speed Full load speed / Rated No load speed

    = 3000 2880 / 3000

    = 4%

    Thus the above machine has 4% droop. In frequency terms, if the Generator

    connected to the machine is rated at 50 Hz, the generator output frequency would

    have reduced to 48 Hz when it was loaded to full load. Thus the generator droop is

    given by

    Droop % (Generator) = Rated No load speed Full load speed / Rated No load speed

    = 50 48 / 50

    = 4%

    The Figure shows the Droop characteristics of the Turbine in the given example.

  • 8/3/2019 Governor Modes of Operation

    3/21

    The Turbine Droop Mode can be used during both parallel operation with the

    grid and also during independent island operation. It is a preferred operational tool in

    gird level as it yields well to multi machine operation. In small islands which do not

    go for isochronous control, droop gives stable operation.

    Turbine Droop Control in Independent OperationWhen a Turbine is put in droop control in a independent island the turbine the

    frequency of the turbine is now dependent on the section load.

    a. Operation when the system load changes -

    In the figure, it can be seen that the initial condition, the turbine was feeding a

    load L with frequency F. In case the section load increases to L2 the frequency gets

    reduced to f2. The change in frequency is in accordance with the droop of the

    machine. It can be calculated by the formula

    Change in Frequency = (L2-L) * Droop % / Full load of the turbine.

    New frequency f2 = f Change in frequency

    The reverse happens when the section load reduces. In this case as the load

    gets reduced to L2 the frequency gets increased from f to f1. The new frequency will

    be in accordance with the droop characteristics of the machine. It can be calculated by

    the formula

    Change in Frequency = (L1-L) * Droop % / Full load of the turbine.

    New frequency f1 = f + Change in frequency

  • 8/3/2019 Governor Modes of Operation

    4/21

    b. Operation when the manual raise/lower command is given -

    In an independent operation, the turbine frequency is the output frequency,

    and in case we give a manual raise lower command the frequency of the turbine raises

    and lowers.

    Initially the machine was feeding to a section load L with frequency f, now let

    the sped reference in this case be R. If the section load is a constant and a manual

    speed increase command is given in the governor, it shifts the speed reference to R2.This increased speed reference means the turbine frequency goes up from f to f2 as

    shown in the figure.

    In case a manual speed lower command is given to the governor, it shifts the

    reference to R1. This reduced speed reference causes the turbine frequency to go

    down from f to f1 as shown in the figure.

    c. Operation when More than one machine is put in droop in the same island -

    In case more than one machine is present in the island and all the machines are

    put in droop, the turbine governor behaviour is different. Let us assume a small island

    with two machines put in droop mode. In case there are more than two machines putin droop then the load is shared by the turbines depending on the droop percentage

    and also on the droop reference on which the turbines are present.

    A turbine with a greater droop reference will take up a greater load and vice

    versa. In the same manner the machine with the lowest droop will take up more load

    than the machine with a greater droop. In practice all machines put in droop mode will

    have a same droop so that in case of a system disturbance they can take up load or

    reject load in the same manner.

  • 8/3/2019 Governor Modes of Operation

    5/21

    The figure shows how two machines with same droop and same speedreference react to the load changes. The initial load of the machines is L1 and L2,

    were L1+L2 forms the total system load. In case of an increase in the section load,

    both machines take up the load as shown in the figure. Now the system frequency

    reduces to f and the load by each machine is L1 and L2. The reverse happens in

    case there is a reduction in the section load, the two machines uniformly shed the load

    and the system frequency rises to a new steady state point. The basic concept is both

    the machine when paralled to one another operate on the same frequency.

    The figure shows how the machine operates in case when a manual speed raise

    is given to only one of the machine. A manual speed rise in generator 2 increases the

    reference to a new point as shown in the figure. When the speed reference of

    generator 2 raises from R1 to R2, the system frequency also rises from f to f. In the

    initial condition, generator 1 was supplying load L1 and generator 2, load L2 with

    system frequency f. When the reference of generator 2 is raised, it takes up more load,

    and its load changes to L2. As the section load remains the same the, generator

    reduces its load to L1. The reverse happens in case a manual speed lower command

    is given. In that case the net system frequency drops, generator on which the speedlower command is given reduces its load and the other generator increases the load.

  • 8/3/2019 Governor Modes of Operation

    6/21

    d. Operation of Two or more machine with unequal droop in the same island -

    The figure shows how two machines with different droops behave when put in

    parallel to one another in an island condition. From the figure it can be seen that

    generator 1 has a much higher droop than generator, but both have the same reference.

    In the initial condition, at frequency F, we see that the generator with the smaller

    droop is taking up more load. If generator 1 load is L1 and generator 2 load is L2, wehave L2 > L1. Now in case of a section load increase it is seen that the machine with

    the smaller droop is taking more load. At a increased load and reduced system

    frequency f, the generator 1 is supplying L1 and generator 2 is supplying L2, but it

    is seen that L2- L2 > L1-L1. Thus the machine with a smaller droop will take up

    more load in case of a section load rise and will shed more load in case of a section

    load reduction.

    This is however an unwanted condition, it is desirable that all machine which

    are put in droop and operating in an island have the same droop. This will help in

    uniform rise and fall in the loading pattern and help in maintaining a stable operation.

  • 8/3/2019 Governor Modes of Operation

    7/21

    Turbine Droop Control in operation with the Grid

    A generator when paralled to the grid has no control over its frequency, the

    frequency of the gird in the machine frequency for all practical steady state

    considerations.

    The figure shows how the machine when parallel to the grid behaves to grid

    frequency changes. In the initial condition the generator is supplying a load L at

    frequency f. when the grid frequency increases to f1, the generator loading reduces to

    L1 as shown in figure. The reverse happens in case of a lowering of grid frequency,when the grid frequency reduces to f2, the generator loading rises to L2 and shown in

    the figure. Thus the loading and unloading of the machine depends on the grid

    frequency and the droop % of the controller.

  • 8/3/2019 Governor Modes of Operation

    8/21

    The figure shows how a machine will react when a manual speed raise or

    lower is given when the machine is paralled to the grid. In the initial condition, the

    machine is supplying a load L with frequency f and a speed reference R. when a

    manual speed raise is given; the speed reference is raised to R2, and for a unchanged

    system frequency, the load supplied by the generator increases to L2. The reverse

    happens for a manual speed lower command. Here the droop reference is shifted toR1 and for an unchanged system frequency the load reduces to L1 as shown in figure.

  • 8/3/2019 Governor Modes of Operation

    9/21

    Implementation of Droop in GE Gas turbine systems

    Droop is a proportional controller. In GE gasturbine systems, the FSRN block

    is used to configure the droop.

    Speed Control Fuel Stroke Reference

    190:FSRNV4

    100 %G3\FSRMAX17.3006 %G3\FSRMIN

    22.2 %G3\FSKRN10 %G3\TLC_COMP

    14.1 %/%G3\FSKRN2100.3 %G3\TNR

    0 %G3\TNH0G3\L83ISOK

    100 %G3\TNRI

    1 %/%G3\FSKRN30 %G3\FSR

    0.06 %/secG3\FSKRN5

    0G3\L83SCI_CMD

    0.5 %G3\FSKRN6

    100 % G3\FSRN

    0 % G3\FSRNI

    0 G3\L60IR

    0 G3\L60IL

    x

    +

    +

    -+

    0

    + -

    ++

    +

    +

    +-

    x

    +- +

    FSRN

    MIN

    -1

    Z

    x

    FSRMAX

    A > B

    A

    B

    A < -BA

    B

    CLAMP

    max

    min

    FSRMAX

    FSRMIN

    FSKRN1

    TLC_CMP

    FSKRN2

    TNR

    TNH

    LISOK

    TNRI

    FSKRN3

    FSR

    FSKRN5

    LI_CMD

    FSKRN6

    L60IL

    L60IR

    FSRNI

    FSRN

    The Block shown above is taken from a GE gas turbine application code. In the droop

    mode of operation, the FSRN , which is the fuel flow reference to the turbine is given

    by the formula

    FSRN = FSKRN1 + (TNR-TNH)*FSKRN2

    Where

    FSRN furl stroke refernce

    TNR Turbine speed/droop reference

    TNH turbine speed

    FSKRN1 no load fuel reference

    FSKRN2 Droop gain for fuel

    The control equation can be redrawn as the control system block as shown in the

    figure , as seen the droop mode is a P (proportional) controller. In the figure , TNR is

    the setpoint ,or it is the droop reference for turbine , The variation of TNR is doneusing the TNRV1 block.

  • 8/3/2019 Governor Modes of Operation

    10/21

    Speed/ Load Setpoint

    770:_COMMENT

    780:_MOVE_B

    SRC1TRUE

    ENABLE1TRUE

    DEST 1 G3\L83TNROP

    800:TNRV1

    0G3\L83HOST

    0FALSE113.5 %G3\TNKHOST

    00

    107 %G3\TNKR3

    95 %

    G3\TNKR4 1G3\L83TNROP

    100 %G3\TNKR5

    0G3\L70L

    0G3\L70R

    0FALSE

    0FALSE

    0G3\L83JD2

    0G3\L83JD3

    0G3\L83JD4

    0G3\L83JD50FALSE

    0FALSE

    0G3\L83JD8

    0FALSE

    0G3\L83JD10

    0FALSE

    0 %/secG3\TNKR1

    100.3 %G3\TNKR2

    100.3 %G3\TNKR7

    0G3\L83PRES1

    0G3\L83PRES2

    0 G3\L33CDMN

    0 G3\L33CDMX

    100.3 % G3\TNR

    A=BA

    B

    A=BA

    B

    CLAMP

    max

    min

    +

    +

    -1

    Z

    -+

    L83PRS2

    L83PRS1

    TNKR7

    TNKR2

    TNKR1_0

    L83JD11

    L83JD10

    L83JD9

    L83JD8

    L83JD7

    L83JD6

    L83JD5

    L83JD4

    L83JD3

    L83JD2

    L83JD1

    L83JD0

    L70R

    L70L

    TNKR5

    LTNROP

    TNKR4

    TNKR3

    TNKLOST

    TNKHOST

    L83LOST

    L83HOST

    TNR

    L33CDMX

    L33CDMN

  • 8/3/2019 Governor Modes of Operation

    11/21

    The control equation for TNR can be writtern as

    TNR = TNR * Z^-1 + (L83JD#) ( L70R L70L)

    In the time domain it can be writtern as

    TNR(t) = TNR(t-1) + (L83JD#) ( L70R L70L)Where

    TNR Speed/Droop reference

    L83JD# - Load rate of the turbine

    L70R Manual Raise command

    L70L Manual Lower command

    This is pure integration using backward integration. As the auto load rate is

    already specified, it cannot be taken to be a controller as such as the response is fixed

    and not dependent on the error value. the L70R and L70l can be triggered by either

    the manual raise command , the auto synch command , the temperature limit

    command or more importantly the MW control block which is what is used by thepreselect load controller.

    How to set the droop% in the controller

    Note - this is a sample calculation only, some typical values here, and it may not be

    what is present at your site.

    Let us assume that the droop percentage needed to be set is 4 %. This means

    that at full load of the machine the difference between the TNR and the TNH needs to

    be 4%. so in the above equation we can fix

    TNR - TNH = 4

    The FSNL FSR is already known from chara graphs of the machine or by a

    field test at site. Let us say that it is 20%.

    The maximum base load FSR value is also calculated from graphs in

    accordance to the site conditions and in later stages from the base load test of the

    machine. Let us say that this is 75%. There is usually some amount of changes to this

    constant during the commissioning.

    So from the above it can be seen that at base load conditions

    75 = 4*FSRKN2 + 20

    FSRKN2 = 13.75%

    There is usually some amount of changes to this constant during the

    commissioning to reflect the field conditions.

  • 8/3/2019 Governor Modes of Operation

    12/21

    Turbine Load control Mode (Preselect Mode in GE Terminology)

    When the turbine is put in the load control mode, the reference is the generator

    power output and the governor tries to maintain a constant power output from the

    generator irrespective of the frequency changes in the gird. Turbine load control mode

    is used only when parallel to the grid and a theoretical Load controller would have agraph like figure

    In the load control mode the governor tries to maintain a constant power

    according to the setpoint in the whole range of frequency operation. Fl and Fh

    indicates the lowest and highest operational frequency, thus making Fh-Fl the

    operational frequency range of the generator. In the initial condition, the machine is

    supplying a power L at frequency f. In case the gird frequency changes in the

    operational frequency range the power output remains the same. When the set point is

    raised to L1, the machine loads to load L1 and when the set point is reduced to load

    L2, the machine unloads to load L2 as shown in the figure.

    The Load control mode is an extension of the droop control. When you put the

    machine in droop control and parallel it to the grid the machine load is dependent on

    the frequency of the gird as shown in figure

  • 8/3/2019 Governor Modes of Operation

    13/21

    The figure shows how the droop reference is varied by the turbine governor to

    maintain a steady power output in the generator.

    In the initial condition let the generator was supplying a load L with frequency

    f. The set point of the machine is L. Now if there is a reduction in frequency to f1 , the

    load point shifts from point a to point b such that the power output is now b. Now thecontroller reduces the droop reference from R to R1 so that the new frequency f1 the

    power output remains the same at L. thus with the lowering of the droop speed

    reference to R1 the operating point is shifted to c as shown in the figure.

    If the frequency had risen to f2 , the new operating point of the generator

    would have been point d such that the power output from the generator would have

    reduced to L2. Now the governor would raise the droop reference to R2 such that for

    the frequency f2, the power output remains the same at L, thus shifting the point of

    operation to point e.

    Why Load control should not be used for a independent generator in an island

    The load control tries to maintain a fixed power output from the generator. In

    case of independent operation the section load varies a lot depending on the nature of

    the process load. If a fixed setpoint is given to the generator and the section load

    rises , the governor tries to reduce the load and decreases the droop reference.

    However as the section load remains the same the governor goes on reducing the

    droop reference such that the machine frequency goes on reducing till the machine

    trips in under frequency. If the section load had reduced, the reverse would have

    happened, in order to increase the load the governor would go on increasing the droop

    reference and thus the speed till the machine trips on overspeed. Thus from the above

    it is clear that load control is not suitable for independent operation.

  • 8/3/2019 Governor Modes of Operation

    14/21

    When can a Machine be put in load control in an independent island

    A generator can be put in load control mode in an independent island if there

    is at least one machine in the same section which can crater to the changes in the

    section load. Let us consider the following example.

    Let us suppose that there are two generators, gen-1 and Gen-2 with equal

    droop and equal droop reference feeding to a common section load as shown in the

    figure.

    In the Initial Condition Generator 1 is at point a feeding a load L1 and

    generator L2 at point a feeding a load L2 such that L1+L2 is equal to the total section

    load in the independent island. Now let there be a increase in the section load such

    that both the generators take up the load with the system frequency reducing to f.Now the new point of operation is b for generator 1 with load L1 and b for generator

    2 with load L2. Now if the generator 1 is put in load control mode and given a

    setpoint L1 , the governor tries to reduce the load by reducing the droop reference ,

    now the overall system frequency reduces as the generator 1 sheds the load on its way

    to the new reference R. The load shed by generator 1 is taken up by generator 2

    which is in droop mode , finally the generators settle at a new frequency f . Here

    generator 1 is in a new operating point with Load L1 and generator 2 with load L2

    such that L2 L2 is equal to (L2-L2)+(L1-L1). Thus the generator 2 takes up the

    entire increase in the section load. Thus as long as there is a machine put in droop

    mode which can take up the load changes Load control will offer a stable operation in

    independent island operation.

  • 8/3/2019 Governor Modes of Operation

    15/21

    Implementation of Load control in GE Gas turbine Systems

    The Turbine Load control is implemented in mainly two blocks

    Preselcted Load Setpoint

    290:_COMMENT

    300:MANSET3

    29.4 MWG3\K90PSMX

    2 MWG3\K90PSMN0FALSE

    0.1 Meg/sG3\K90PSR0.1 Meg/sG3\K90PSR

    2 MWG3\90PSEL_CMD

    0FALSE0

    0FALSE0FALSE0FALSE

    0 G3\L33PSMX

    1 G3\L33PSMN

    2 MW G3\90PSEL

    A=BA

    B

    A=BA

    B

    MED

    -1

    Z

    x

    -

    +

    -1

    RATE

    CLAMP

    +

    +

    rate

    MEDMAX_LIMIT

    MIN_LIMIT

    dt

    +

    +

    +

    -rate

    CDM

    -1

    Z

    MAXLMT

    MINLMT

    RT2SEL

    RATE2

    RATE1

    CMD

    LPRESET

    VPRESET

    RAISE

    LOWER

    RL_ENA

    AT_MAX

    AT_MIN

    REF_OUT

    Megawatt Load Control

    310:_COMMENT

    320:L90LV2

    100 %G3\FSRN

    100 %G3\FSRT

    3 %G3\LK90DB3

    6 %G3\LK90DB4

    0G3\L83RMAX

    0G3\L83PS29.4 MWG3\LK90MAX

    2 MWG3\90PSEL

    2.6 MWG3\LK90SPIN

    0.0178608 MWG3\DWATT

    0.13 MWG3\LK90DB1

    0.33 MWG3\LK90DB2

    1 G3\L90LR

    0 G3\L90LL

    -+

    A > BA

    B

    A

    B

    inhibit raise

    lower

    A

    B

    |A -B|A

    B

    raise

    A

    B

    A

    B

    db1

    db2

    db2 db1 raiseInhibit

    raise

    L90LR

    L90LL

    lower

    "1

    "

    A > B

    A > B

    A > B

    A > B

    L90LR

    L90LL

    K90DB2

    K90DB1

    LOAD

    K90SPIN

    PRESEL

    K90MAX

    L83PS

    L83RMAX

    K90DB4

    K90DB3

    FSRT

    FSRN

  • 8/3/2019 Governor Modes of Operation

    16/21

    Physical implementation of the Load controller

    In the above diagram let point a be the initial machine position. In this condition the

    grid frequency is f and load is L . Now let us suppose that the grid frequency has

    reduced to f1 , now the machine for a instant will shift from load L to load L1 , ie tooperating point b. The load controller now comes into action and reduces the

    reference from R to R1 , such that the initial load condition is attained , with the dead

    band gap of L+ub & L-lb. Now the new machine operating point is c , with frequency

    f1 and load L with a new reduced reference R1.

    The reverse happens in case there is a increase in the grid frequency , now the

    operating point shifts to point d from the initial position a. Now the load controller

    comes into action and shifts the reference to R2 such that the initial load condition is

    obtained. Now the new machine operating point is e , with frequency f2 and load L

    with a increased reference R2.

  • 8/3/2019 Governor Modes of Operation

    17/21

    Turbine Isochronous control ModeWhen a Turbine is put in isochronous control Mode, the reference to the

    controller is the frequency of the generator and the controller tries to maintain a

    constant frequency irrespective of load conditions. The Turbine isochronous mode is

    used only on independent island conditions and should not be used when in parallel to

    the grid. The theoretical isochronous controller would be

    In the isochronous control mode the governor tries to maintain a constant

    frequency according to the setpoint in the whole range of frequency operation. Fl and

    Fh indicates the lowest and highest operational frequency, thus making Fh-Fl the

    operational frequency range of the generator. In the initial condition, the machine issupplying a power L at frequency f. In case the section load changes the frequency of

    the machine remains the same. When the set point is raised to f , the machine

    accelerates to frequency f and when the set point is reduced f, the machine

    decelerates to frequency f as shown in the figure.

    The Isochronous control mode can also be taken as a extension of the droop

    control. When you put the machine in droop control in an independent island the

    frequency of the machine is dependent on the section load as shown in fig

  • 8/3/2019 Governor Modes of Operation

    18/21

    The figure shows an implementation of the isochronous control. The figure

    shows how the droop reference is varied to keep the output frequency constant. Let

    the machine have a frequency setpoint of f.

    In the initial condition the generator is at operation point a supplying as load L

    with frequency f. Now if the section load increases to L2 the frequency drops down to

    f2 with the new operating point b. Now the isochronous controller sensing a reduction

    in speed increases the speed reference to R2 such that for the same operating load L2the frequency is f. Thus the new operating point of the machine is c, where the

    machine is supplying to a increased load L2 with the same frequency f.

    In case there is a reduction in the load to L1, the frequency rises to f1 and the

    machine moves to the operating point d. Now the isochronous controller reduces

    droop reference to R1 such that the frequency recues to the initial operating frequency

    f. Now the new machine operating point is e as shown in the figure. Thus by

    increasing and reducing the droop reference a constant frequency of f is maintained

    even with changing section loads.

    Why isochronous controller should not be turned on when the machine is with

    the gridWhen a machine which is in parallel to the grid, it has no control over the

    frequency, the grid frequency is the machine frequency. Let us suppose that the

    machine is put in iso mode and given a particular frequency setpoint. If this setpoint is

    higher than the grid frequency, the controller will go on increasing the droop

    reference, but the machine speed will not rise, instead the machine power output rises

    and goes on rising till it reaches it maximum load. In case the given frequency

    setpoint is lower than the grid frequency , the controller will go on reducing the droop

    reference thus unloading the machine , it will go on unloading till the machine trips on

    reverse power. Thus depending on the frequency setpoint and the actual gird

    frequency the machine will either load itself to base load or unload itself to reverse

    power trip. Thus a machine in parallel to the grid must never be put in isochronous

    controller mode.

  • 8/3/2019 Governor Modes of Operation

    19/21

    Implementation of Isochronous controller in GE Gas turbines

    The Isochronous controller is a PI controller and it is predominantly implemented in

    the FSRN block.

    Speed Control Fuel Stroke Reference

    190:FSRNV4

    100 %G3\FSRMAX17.3006 %G3\FSRMIN

    22.2 %G3\FSKRN10 %G3\TLC_COMP

    14.1 %/%G3\FSKRN2100.3 %G3\TNR

    0 %G3\TNH0G3\L83ISOK

    100 %G3\TNRI1 %/%G3\FSKRN3

    0 %G3\FSR0.06 %/secG3\FSKRN5

    0G3\L83SCI_CMD

    0.5 %G3\FSKRN6

    100 % G3\FSRN

    0 % G3\FSRNI

    0 G3\L60IR

    0 G3\L60IL

    x

    +

    +

    -+

    0

    + -

    ++

    +

    ++

    -x

    +- +

    FSRN

    MIN

    -1

    Z

    x

    FSRMAX

    A > B

    A

    B

    A < -BA

    B

    CLAMP

    max

    min

    FSRMAX

    FSRMIN

    FSKRN1

    TLC_CMP

    FSKRN2

    TNR

    TNH

    LISOK

    TNRI

    FSKRN3

    FSR

    FSKRN5

    LI_CMD

    FSKRN6

    L60IL

    L60IR

    FSRNI

    FSRN

    The isochronous mode algorithm is explained below

    a. once you put the iso mode on in a independent machine , the LISOK signal goes

    high.

    the following calculation takes place

    FSRNI(t) = FSRNI(t-1) + (TNRI -TNH(t))*FSRKN3

    (as you can see this is a form of the velocity PI algorithm , and this were the PI is

    actually implemented in the controller)

    b. After the calculation the following check is done.

    If (mod (FSRNI (t)) > FSRKN6)The respective l60ir ( iso setpoint raise) or the l60il (iso setpoint lower)

    goes high. The LISOK signal goes low thus cutting off the TNRI signal from the FSR

    block. The L60IR OR the L60IL increases/decreases the TNR, with the help of the

    L70R/L70L logic, thus raising or lowering the droop reference.

    ElseThe FSRNI (t) is added to the FSR to get the new FSR value.

    FSR(t) = (TNR - TNH(t))*FSRKN2 + FSRKN1 + FSRNI(t-1) +

    (TNRI -TNH(t))*FSRKN3

    In the above equation, the (TNR - TNH (t)) is no longer a error signal because,

    "TNR is not a setpoint any more". When the iso mode is selected, the TNR raise and

    lower is inhibited from any other source.

  • 8/3/2019 Governor Modes of Operation

    20/21

    Only the L60IR and the L60IL have the permissive to change the TNR. as this

    particular code is executed only when L60IR AND L60IL is both zero , TNR is

    nothing but a constant in the equation. Now rewriting the equation

    FSR(t) = FSRNI (t-1 ) + ( (fsrkn3 * TNRI) - ( TNH(t) * (FSRKN3+FSRKN2)) ) +

    FSRKN1 + (TNR*FSRKN2)

    Here now the FSR and the FSRNI now represent the same common output canbe renamed as FSRI

    FSRI(t) = FSRI (t-1 ) + ( (fsrkn3 * TNRI) - ( TNH(t) * (FSRKN3+FSRKN2)) ) +

    FSRKN1 + (TNR*FSRKN2)

    Here now the equation ((fsrkn3 * TNRI) - (TNH (t) * (FSRKN3+FSRKN2)) )

    is the error signal E(t)

    FSRI(t) = FSRI (t-1 ) + E(t) + + FSRKN1 + (TNR*FSRKN2)

    The last equation is the final iso mode calculation equation. if you will see , it

    is analogous to the velocity form of the pi algorithm.

    Physical implementation of the isochronous controller

    Now that we have looked into how the FSR is calculated in the iso algorithm ,

    let us see the controller inaction during actual conditions.

  • 8/3/2019 Governor Modes of Operation

    21/21

    a. For small load variations

    The small load variations are taken care by the FSRNI block. Let us suppose

    that the machine is running in point a where the load (MW) is l1 and the frequency f1.

    In this condition it is assumed that the machine is already in iso mode and reached a

    steady state such that the TNRI and the TNH are now equal(near equal) , the now let

    us suppose that there is a small load increase. The TNH value of the machine will godown as per the droop reference R1. Now FSRNI is calculated and it will be found

    that FSRNI is less than the deadband limit. The value of FSRNI will be positive and it

    will be added to the FSR block. This additional FSR will help in increasing the speed

    of the machine to its previous value. The reverse happens if the load goes down by a

    small amount. The speed of the machine will rise; the FSRNI will be negative and

    reduce the actual FSR thus reducing the machine speed back to its previous value.

    b. for large load variations

    For large load variations the droop characteristics is changed before the TNRI

    comes into play. Let us suppose that the machine is in the initial condition Point a.

    now for a sudden load increase from l1 to l2, the frequency changes from f1 to f2.Now the FSRNI is calculated and it will be found that it is more than the deadband

    FSRKN6. Now the L60IR command is issued which inturn increases the TNR value.

    The rise in the TNR value will raise the droop reference and the speed of the machine

    as already discussed in the droop mode study. Thus when the machine reaches the

    point b, the droop characteristics is raised from Reference R1 to R2. This goes on till

    the TNH reaches the TNRI and the calculated FSRNI is below the deadband limit.

    From that point onwards the isochronous changes to the PI mode and FSRNI takes

    care of the rest.

    Thus from the above it can be seen that, the for small load variations the

    FSRNI is responsible for maintaining constant frequency. In this mode, there is no

    droop reference change. For large variations, the FSR reference itself is changed till

    the speed becomes more or less equal to the setpoint value. Only then does the FSRNI

    come into play.