  • 100% Stator Ground100% Stator Ground(59N/27TH)(59N/27TH)

  • Stator Ground ProtectionStator Ground ProtectionProvides protection for stator ground fault on generators which are high impedance groundedUsed on unit connected generatorsGround current limited to about 10A primary

    Provides 100% stator ground protection (entire winding)

    High Impedance Grounding

  • 3rd Harmonic Comparator for 100% 3rd Harmonic Comparator for 100% Stator Ground Fault ProtectionStator Ground Fault Protection

    3rd harmonic levels change with position of ground fault and loading

    Using a comparator technique of 3rd harmonic voltages at line and neutral ends allows an overvoltage element to be applied

  • Third-Harmonic Undervoltage Ground-Fault Protection Scheme

    100% Stator Ground Fault (59N/27TN)

  • Settings summary per IEEE C37.102

    59G element: Pickup = 5 V; t = 5 s Note: Time setting must be selected to provide coordination with other system protective devices.

    27TH element: Pickup = 50% of minimum normal generator 3rd harmonic. t = 5 s

    Stator GroundStator Ground