Pioneers
The increa sing dema nds o f indus try for depend a ble explos ionproof lighting, motivated Ba liga to pioneer the design
and manufacture of a quality line way back in 1962, when the first Indian Standards were just being formulated.
Quality and Dependabilityhave bee n synonymous w ith Ba liga produc ts, ever since.
Ex-ENGINEERING
In order to maintain their poisition as market leaders,
Baliga have a continuous program of value engineering
and product d evelopment. This ha s ens ured a
continuous flow of new ideas and new products. A
programe aided by the latest CAD, and photometric
equipment.
Quality
Customers rely on Baliga as a very dependable source
and for good reason since each product goes through
regorous c hecks a t every stage of manufacture with the
results docmented for traceability. And ofcourse Baliga
products have the stamp of approval of various
ce rtifying a uthorities .
-
8/10/2019 General Technical Info
2/10
Self Sufficient Factory
Quality can only be achieved with matching production
facilities. Baliga products are manufactured in a completely self
sufficient factory in Madras with over 35,000 sq.f t . of
manufacturing space. A factory that houses a wide range of
machine tools for machining, sheet metal fabrication and
moulding of plastic components. In line with the polcy of
continuous upgradation of technology, a sophisticated epoxy
pow der co ating eq uipment wa s installed in 1982. And a lmost all
operations are computerised, right from order processing,
co sting, produc tion planning and des igning. This g ives the
customer, high-quality products delivered on time.
Customer Service
Baliga is proud to offer their extensive experience in lighting
hazarous areas, as another area of total commitment to the
customer. A nationwide network of experienced agents and
representatives are available to discuss any lighting or
Exproblem and arrive at the ideal cost effective solution. Baliga
The na me sp ells q uality w ithout a single comp romise.
-
8/10/2019 General Technical Info
3/10
Introduction
It is an inevitable fact that the manufacture, processing and
storage of petroleum products and chemicals in the liquid or
vapour form, leads to the formation of highly explosive
atmospheres due to the leakage of ga ses a nd vapours. When
these combine with the oxygen in the atmosphere, potentially
explosive mixtures comes into accidental contact with an
electrical spark or hot surface, with the resulting explosion
ca using extensive da mag e to life and property. Explosion
protec tion is therefore the sc ience of d esigning and developing
electrica l produc ts for sa fe use in these highly explosive a rea s.
Combustion PrinciplesThree ba sic co nditions mus t be sa tisfied for a fire or explosion
to occur :
1. A flammab le, liquid, vapour or combustible dust must be
present in s ufficient q uantity.
2. The flamma ble liq uid, vapo ur or dust must be mixed w ith
air or oxygen in the proportions required to produce an
explosive mixture.
3. A source of energy must be a pplied to the explosive
mixture.
The a pplica tion of the ab ove principles involves a clea r
understanding of the characteristics of the flammable gas or
liquid and the source of ignition.
Flammable gas/vapour risk
To d esign or s elect an e q uipment for haza rdous areas , it is
essential to understand the various parameters which affect
the explosive cha rac teristics o f the fla mma ble ga s/air mixture.
The pow er of a ny explosion de pends upon the inherent
properties of the gas and its concentration in the atmosphere.
Not all concentrations of the flammable gas in air will burn or
explode.
The Low er Explosive Limit (LEL) is the low es t co nc entra tion of
the gas in air which can cause an explosion.
The U ppe r Explos ive Limit (UEL) is the m a ximum co nc entra tion
of the gas in air beyond which no explosion can take place.
Upper and Lower Explosive Limits in Gases
Flam ma ble liquids g enera lly have a low Flas h Po int. This is the
low est temperature a t w hich vapour is given off at a sufficient
rate to fo rm a n explosive mixture with air. Therefo re liq uids
with flash points below ambient temperature will automatically
release vapour in sufficient quantities to provide an explosive
mixture.
Vapo ur Density is a mea sure of the de nsity of the ga s relative
to air. A know ledg e of this pa rameter is important a s g as es
lighter than a ir tend to rise up from the po int of es ca pe a nd ma y
therefore disperse e as ily. Heavier than air ga ses tend to s ink
and accumulate over a period of time to form concentrations
between the LEL and UEL ready to explode as soon as a
source of ignition is introduced.
When a n explosive mixture of s ufficient co nce ntration has b een
developed, it ca n be ignited by a spa rk o s ufficient energy or if
it is exposed to a surface at a sufficiently high temperature.
The lowe st te mpera ture which w ill ca use the mixture to
explode is ca lled the Ignition Temperature.
Sources of Ignition
A source of energy is all that is required to touch off an
explosion where flammable gases or combustible dusts are
mixed in the proper proportion with air.
For ignition of gas mixture to take place, it is necessary that
atleast a small portion of the mixture be raised to the ignitiontempe rature. By the b urning of this portion, sufficient hea t will
be e volved to ca use the ignition of the who le volume. It follow s
from this that any ignition source has two essential
characteristics.
They a re :
Tempera ture : This mus t be equa l to or h igher than the
ignition Temp era ture.
Energ y : The so urc e mus t s upply suffic ient ene rg y a t
a high enough rate, to raise enough gas
mixture to the ignition point to start a self
sustaining explosion.
The different so urce s o f energy c an b e effec tively grouped into3 categories.
a) Flames
b) S pa rks - electric or percus sive
c) Hot surfac es.
Flames
These usually have a tempera ture b etw een 1000C and
2000C. They are also ca pab le of supplying energy at a high
rate a nd c an therefore b e effective sources o f ignition.
Sparks
These have very high temperatures betw een 1000C and
3000C and are capable of supplying large amounts of energy
over short periods of time.
One prime so urce o f spa rks is elec tricity. Equipment suc h as
switches, motor starters and push button stations produce
arcs and spa rks d uring normal operation.
Area Most Prone
LEL to ignition UEL
Wea k Ignition S trong
Mixture Area Mixture
6% 14% 20% 40% 100%
Hydrogen (H2) 4% 14% 34% 76%
Acetylene(C2H2) 1% 6% 12% 80%
Metha ne(CH4) 5% 8% 9% 15%
-
8/10/2019 General Technical Info
4/10
Another source of sparks is static electricity. Present wherever
there is a flow of liq uids &ga ses through hos es and pipelines,
the static charge accumulated can over a period of time
generate sparks of sufficient energy to initiate an explosion.
Non-electrical hazards such as sparking of metal can also
ea sily ca use a n ignition. A ham mer, file or other tools w hen
dropped o n masonry or on a ferrous surface ca n cause a spark
with sufficient energy to trigger an explosion.
It is therefore necessary that in order to ignite a given
flamma ble atmos phere, sufficient energy has to b e s upplied to
raise the temperature of gases locally to their ignition
tempe rature. The minimum energy req uired to do this is
dependant upon the gas present and varies widely from one
ga s to another. Bec ause of this wide variation, it has b een
found c onvenient to determine the Minimum Ignition Energy
for four gas groups classified I to IIC in the direction of their
increa sing s ens itivity to spa rk ignition.
They a re :
G a s G roup No. Minimum ignition Energy
Metha ne I 280
P ropa ne IIA 260
Ethylene IIB 85
Hydrogen IIC 19
Hot Surfaces
The third s ource o f ignition is the s urface tempe rature
developed by the product during normal operation like in
lighting fixtures or mo tors.
Here the surface temperature may exceed the safe limits of
many flamma ble a tmospheres, thereby initiating a n explosion.
Other components of the electrical system can also become
potential sources of ignition in the event of insulation failures
for example : in trans formers, impeda nce coils, s olenoids and
in the ba sic w iring s ystem.
Electrical safety therefore, is of crucial importance and the
electrical installation must be designed to prevent the
accidental ignition of flammable liquids, vapours and dusts
released to the atmosphere.
Classification of Hazardous materials
The NEC has c lass ified a ll ma terials c a pa ble of forming a n
explosive atmos phere into three major clas ses :-
C la ss I : A C la s s I a tmo sp he ric h a za rd is a n a re a
cons isting of gas es a nd liq uids w hich have be en
further divided into 4 groups.
C la s s II : A C la s s II ha z a rd c o vers 3 d iffe rent g ro up s o f
comb ustible dus ts ba sed upon their resistivity
C la s s III : A C la s s III h a z a rd c o v ers lo c a t io n s where
combustible fibres or flyings are present.
Zone Classification
All haza rdous areas ca n be c las sified into 3 zones a cc ording to
the probability of there being an explosive gas air mixture
prese nt .
Zone O Areas where an explosive gas atmosphere is
continuously present.
Typica l eg .: inside o f conta iners or reac tors.
Zone 1 Areas where an explosive gas atmosphere
is likely to occur under normal operation.
Typica l eg .: area s s urround ing Zone 0, a reas
surrounding drains, discha rge eq uipment.
Zone 2 Areas where an explosive atmosphere is not
likely to occur in normal operation and if it doesit is only for short periods.
Typica l eg.: a rea s surrounding flang ed ga skets,
areas surrounding Zone 0 or Zone 1.
Gas Grouping
All gases and vapours can be classfied into 4 major gas
groups . The cla ss ifica tion criteria is ba se d upon lab orato ry
tests to determine the Maximum Experimental Safe Gap
(MESG) and the Minimum Ignition Current (MIC). Gas group
class ifica tion for typica l gas es will be :
IS2206
EN 50018 US A
Representa tive G a s B S 5501 P t 5 UL 698
IEC 79-1
G ROUP G ROUP
Metha ne (mining Use) I D
P ropa ne IIA D
Ethylene IIB C
Hydrogen IIC B
Ca rbon Disulphide* IIC
Acetylene* IIC A
Gases belonging to the IIC group are the most dangerous with
the se verity de crea sing d ow n the sc a le to the IIA group. The
performanc e a nd te sting req uirements of electrica l equipment
is consequently more stringent for applications in areas
conta ining IIC g as es that in areas cons isting IIA ga ses .
*IS 2206 has not yet class ified these ga ses .
Conditions for explosion
%
Concentra tion EnergyMechanical
Heat Electrica l
UPPER
EXPLOS IVE
LEVEL
LOWER
EXPLOS IVE
-
8/10/2019 General Technical Info
5/10
Classification of flammable liquids
All flammable liquids vary in volatality and have a flash point
below 93% and a vapour pressure not excee ding 2.81 kg/m2.
These liq uids ca n be divided into 3 class es.
C lass A : Flammable liqu ids hav ing a f la sh po in t below
23C. Thes e liq uids produc e large volumes o f
vapour when relea sed in appreciable q uantities to
the open.
C lass B : Flammable liqu ids having a fla sh poin t between
23 and 65C. Thes e liq uids are hea vier and les s
volatile and have a flash point slightly below
normal ambient temperature. At elevatedtemperatures, Class B liquids approach the
characteristics of Class A liquids in vapour
release.
C lass C : Flammable liqu ids having a f la sh po in t between
65and 93C. These liq uids have a low deg ree o f
haza rd b eca use the rate of relea se is nil at normal
amb ient temperature. These include a broad
range from cleaning solvents to heavy fuel oils in
commercial grades.
Temperature Class
It is an essential requirement that for electrical equipment to
wo rk sa fely in an explosive a tmosphere, the ma ximum surfac e
temperature of the exposed surface of the equipment ust
always be lower than the ignition temperature of the gas
mixture.
In order to properly select electrical equipment with regard to
the ignition temperature, all ga ses are c las sified ac co rding to a
temperature classification scale shown below:
EN 50014
Ma ximum B S 5501 P t 1
S urfa ce IS 8239 US A
Tempera ture IEC 79-1 UL 698
C
450 T1 T1300 T2
280 T2A
260 T2B
230 T2C
215 T2D
200 T3 T3
180 T3A
165 T3B
160 T3C
135 T4 T4
120 T4A
100 T5 T585 T6 T6
Any electrical equipment to be used in an hazardous area is
also tested and rated for its maximum surface temperature.
It now bec omes relatively s imple to ensure that the temperatre
rating o f the eq uipment is alwa ys c ompa tible with temperature
classification of the gas.
For example electrical eq uipment w ith a T5 ra ting c a n be us ed
in all areas where g as es have a temperature rating from T1 to
T5 but not T6 ca tion.
IS 2206 currently requires temperature classification of Ex d
luminaires as X, Y or Z being the temperature rise of 125C,
75C and 50C respectively at an ambinet of 30C. This
sta nda rd is to b e revised shortly.
Types of Protection
The b as ic principles of providing explosion protec tion requires
the use o f a number of techniques to prevent the simultaneo us
availability of a gas air mixture of sufficient concentration and
volume and an ignition s ource w ith sufficient ene rgy. Where this
is unavoidab le, then spec ial meas ures a re taken to conta in any
explosion.
Worldw ide , se ven different type s o f protection a re currently
reco gnised as effective tec hniq ues to prvent explosions. These
types of protection are listed below.
1. Ex i : Intrinsic S afe ty
2. Ex d : Flame proof3. Ex e : Increase d S afety
4. Ex p : P ress urise d
5. Ex o : Oil Immersion
6. Ex q : P ow de r filling
7. Ex n : Non spa rking (ba sica lly in UK and India)
A new standard for providing protection using moulding
techniques Ex m is under preparation.
Each type of protection however, can be used only in specific
Zones. In Zone 0 for example, appa ratus with Ex is c ateg ory of
protection can only be used. Ex n category of apparatus cn be
used only in Zone 2 areas .
An apparatus certified for use in Zone 0 can also be used inZones 1 and 2. similarly those certified for use in Zone 1 areas
can be used in Zone 2 areas, but not in Zone 0 areas.
Zone Type of Protection
Zone 0 Ex ia
Zone 1 Ex ib
Ex d
Ex e*
Ex p
Zone 2 Ex n
Ex o
Ex q
* As per IS 5572, Ex e equipment may be used in zone 2 areas only.
As revision of this standard is under consideration.
-
8/10/2019 General Technical Info
6/10
TE C H NIC AL D ATA
Type of protection Basic principle Schematic Applicationsto IEC or EuropeanStandard
flameproof A type of protection in which the parts, which Sw itchgea r, control andenclosure Ex d can ignite an explosive atmos phere are indicating equipment,
pla ced in a n enc losure, w hic h ca n w iths ta nd contro l boa rds , motors ,the press ure developed during a n interna l tra ns formers , light fittingsexplos ion o f a n explos ion mixture a nd w hich a nd o ther s pa rk-produc ingprevents the transmission of the explosion parts.to the explosive a tmospheres surroundingthe enclosure.
in cre a se d s a fe ty A t yp e o f p ro te ct io n in w hic h m ea s ure s a re Te rm in a l a n d c o nn ec tio n
Ex e applied so as to prevent with a higher boxes, control boxesdegree o f s a fety the pos s ibility of exces s ive hous ing Ex-modules (of atempera tures a nd of the oc cura nc e different type of protec tion)of a rcs or spa rks in the interior a nd sq uirrel ca ge motors ,on the externa l pa rts o f elec trica l lig ht fittings .apparatus, which does not producethem in normal service.
pressurized appara tus A type o f pro tec tion in which the entry o f a as above , but especia l ly forEx p surrounding atmos phere into the enclosure large equipment and
of the electrical appa ratus is prevented by complete rooms.maintaining inside the s aid enclosure aprotective gas (air, inert or other suitable gas)at a higher pressure than tha t of thesurrounding atmo sphe re. The overpress ureis maintained either with or withoutcontinuous flow of the protective ga s.
intrinsic safety Ex i A type of protec tion in w hich the elec tric a l Mea s urement a nd contro lappa ratus conta ins intrinsically safe circuits, equipment.which are inca pable of ca using an explosionin the surrounding atmospheres. A circuit orpart of a circuit is intrinsically safe, when nospark or any thermal effect in this circuit,produced in the test c onditions presc ribedin the standard (which include normaloperation and specific fault conditions) iscapa ble of ca using ignition.
oil immersion Ex O A type of protec tion in w hich the elec tric a l Tra ns formers (only us ed ra rely now )appa ratus are immersed in oil in such a wa ythat an explosive atmosphere, which may be
abo ve the oil or outside the enclosurecannot be ignited.
power filling Ex q A type of protec tion in w hich the enc losure Tra ns formers , ca pa c itors , hea terof elec trica l a ppa ra tus is filled w ith a ma teria l s trip connection boxes elec tronicin a finely g ra nula ted s ta te s o tha t, in the a s semblies .intended c onditions o f service, a ny arcoccuring within the enclosure of an electricalapparatus will not ignite the surroundingatmos phere. No ignition s hall be ca usedeither by flame or b y exces sive temperatureof the surfaces of the enclosure.
encapsulation Ex m A type of protec tion in w hich the pa rts w hich only sma ll c a pa c ity sw itchg era ,(in prepa ra tion) ca n ig nite a n explos ive a tmosphere a re contro l gea r, indica ting eq uipment,
enc losed in a res in suffic iently res is ta nt to sensors .environmental influences in such a wa y thatthis explosive atmosphere cannot b eignited by either sparking or heating, whichmay o ccur within the enca psulation.
Types of Protection
-
8/10/2019 General Technical Info
7/10
TE C H NIC AL D ATA
IP Degree of Protection
All electrica l apparatus, d epending on the ultimate applica tion, need to be protected to varying d eg rees from the effects of
conta ct w ith foreign b odies, d ust a nd w ater. This d egree of protection is s hown in the tab le b elow.
1st figure : 2nd figure : 3rd figure :
protection against solid protection against liquids mechanical
IP tests IP tests IP tests
0 No protection 0 No protec tion 0 No protection
P rotec ted a g a ins t P rotec ted a g a ins t Impa ct energ y
solid bodies la rg er vertica lly - fa lling 0.225 joule1 than 50 mm 1 drops of water 1
(eg . : a cc identa l (c ondens a tion)contac t with thehand)
P rotec ted a g a ins t P rotec ted a g a ins t Impa ct energ ysolid bodies la rg er drops of wa ter 0.375 joule
2 than 12 mm 2 falling at up to 2(eg . : fing er of the 15 from theha nd) vertica l
P rotec ted a g a ins t P rotec ted a g a ins t Impa ct energ ysolid bodies la rg er drops of ra in 0.500 joule
3 than 2.5 mm 3 wa ter at up to 60 3(eg . : tools w ires ) from the vertica l
P rotec ted a g a ins t P rotec ted a g a ins t Impa ct energ ysolid bodies la rg er drops of ra in 2.00 joules
4 than 1 mm 4 water from all 5(fine tools a nd direc tionssma ll wires)
P rotec ted a g a ins t P rotec ted a g a ins t Impa ct energ y5 dust (no ha rmful 5 jets of water from 7 6.00 joules
depos it a ll direc tions
C ompletely P rotec ted a g a ins t Impa ct energ y6 protected against 6 jets o f wa ter of 9 20.00 joules
dus t s imila r force toheavy seas
The 3rd figure is specific to the FrenchProtected against standard U.T.E. 20 010
7 the effects o fimmers io n S ta nd ard EN 500 14 defines the impa ct
tests to b e ca rried out a cco rding tomaterials used and the groups to whichthey belong.
Protected aginst
prolonged effects8 of immersion
under press ure
-
8/10/2019 General Technical Info
8/10
TE C H NIC AL D ATA
Selection of Electrical Equipment
A number of logical steps are involved in the proper selection
of electrica l eq uipment for hazardous a reas.
Step 1 : Clearly identify the gas/vapour, its gas group and
temperature class.
S e tp 2 : D efine the a rea Zo ne 0, 1, or 2
Step 3 : Selec t the type o f p ro tec t ion appropria te to the
Zone
S t ep 4 : Fo r t he g iv en t y pe o f p ro t ec tio n s e lec t t he
eq uipment keeping in mind the g as group and the
temperature rating
Step 5 : Depending on whether the equ ipment is to be
installed indoor or outdoor, ensure the correct IP
protection for the equipment
Guide to certification code
Apparatus marking requirements normally include a
certification code which includes the following elements.
a . Symbol f r the type o f p ro tec t ion
b . The a pp a ra tus g ro up
c . The tempera ture c l a ss if ica t ion
EXAMP LE 1. Ex d II B T5
This indicat es a unit having flameproof typ e of protec tion d
suitable for apparatus gas group IIA and II B and having a
maximum surface temperature classification of 100C (T5)
EXAMP LE 2. Ex. N II T6
This indicat es a unit having non-spa rking typ e of protec tion N
suitable for apparatus gas groups IIA, IIB and IIC (absence of
letter indicates all gas groups ) having maximum surface
temperature classification of 85C (T6)
Inspection, maintenance and testingThe sa fe and sa tisfac tory operation of electrica l apparatus is
dependant on a high standard of inspection, maintenance and
testing by trained and competent personnel.
General recommendations for inspection, maintenance and
testing given herein apply particularly to type of protection d
flame proof enclosures.
Initial and periodic inspections
All electrical apparatus, systems and installations should be
inspected prior to commissioning and after replacement in
ac cordance w ith the initialc olumn of the inspec tion s ched ule.
Following any repair, adjustment or modification, those parts of
the installation that have bee n disturbed should b e c hecked in
ac corda nce w ith the relevant items in the initia lcolumn of the
inspec tion s ched ule.
If, at any time, there is a cha nge in the a rea class ifica tion or in
the characteristics of the flammable material used in the area,
or if the apparatus is moved from one location to another, a
check should b e ma de to ensure that the a pparatus c oncerned
has the correct a pparatus subgroup and temperature c las s and
that it complies with the relevant area classification.
A system should be established to record the results of all
inspections and the action taken to correct defects.
Maintenance
No alteration that might invalidate the certificate or other
document relating to the safety of the apparatus should be
made to any apparatus without appropriate approval.
If replacement components such as cable glands, conduit or
cond uit ac ces sories, are a vailab le only with threa d forms w hich
differ from those provided on the a pparatus, suitab le a da ptors
having component approval should be employed.
Checks should be made for obstructions around flanges of
eq uipment. The dimensions of the ga ps at flam eproof jointsshould b e chec ked periodica lly during ma intenance to se e that
they do not exceed the maximum figure specified in IS-2148.
At such intervals as experience may prove desirable, the
flanged joints should be separated and the faces examined for
possible defects resulting from corrosion, erosion or other
ca uses. If flanges are to be sea led, then new nonsetting grease
or tape should be used on reassembly.
Equipment enclosures and fittings should be examined to see
that all stopping plugs and bolts are in position and tight.
Locking a nd se aling de vices should be c hecked to c onfirm that
they a re s ecured in the presc ribed manner.
Replacement cover securing fasteners, nuts, studs and bolts
should be types spec ified by the manufac turer for the pa rticular
apparatus.
No attempt should be made to replace or repair a glass in a
flameproof enclosure e.g. in a luminaire or other enclosures,
except by the complete assembly or part obtainable from the
manufacturer, or complying with the flameproof certificate.
Repairs and refurbishing of apparatus with type of protection
d should be performed only by the original manufacturer, his
authorised agents or a repairer who is conversant with the
construction standards for flameproof equipment and
demo nstrates the a bility to understand certifica tion restraints.
-
8/10/2019 General Technical Info
9/10
TE C H NIC AL D ATA
Inspection Category
C heck tha t Initia l P eriodic Notes
Appa ra tus is a ppropria te to a rea c la ss ifica tion A B
S urfa c e tempera ture c la ss is correc t A B
Appa ra tus subgroup is c orrec t A A
Appa ra tus ca rries the c orrec t c ircuit identific a tion A B Appa ra tus should be pos itively
identified w ith its circuit to ens ure
that correct isolation can be
ca rried out.
Obs truc tions a re not present nea r fla nged joints A AEnc losures , g la ss es and gla ss/meta l sea ls are sa tis fa c tory A A
G a ps a re free from c orros ion, d irt a nd pa int A B
Dimens ions of g a ps a re correc t A B
There a re no una uthorized modifica tions A A
B olts , g la nds a nd s toppers a re complete a nd tight. A A
There is no undue a c cumula tion of dus t or d irt B B Acc umula tion of dus t or d irt ca n
interfere with heat dissipation and
result in surface temperatures
higher than those permitted in the
hazardous area.
All c ond uits runs and fitting s a re tig ht a nd fre e fro m c orro sio n A B
Ea rthing is s a tis fa c tory A A
Elec tric a l c onnec tions a re tight A B
Motor fa ns and couplings are not rubbing on cow ls/gua rds A A
La mp ra ting a nd type a re c orrec t A B An initia l inspection is nec essa ry
after relamping
S topper boxes a nd ca ble boxes a re c orrec tly filled A B
There is no lea ka ge of c ompound from B B
stopper or cable boxes
There is no obvious da ma ge to ca bles , A A
c a ble shea ts or c a ble g la nds P a rtic ula r a ttention should be pa id to
flexible ca bles use d w ith portable
apparatus.
Appa ra tus is a d eq ua te ly pro te cte d a g a ins t c orro sio n, A A
the w ea ther, vibration and o ther adverse fa torsG ua rds , w here used , a re present a nd c orrec tly loc a ted A B
*Category A inspections should be carried out in all cases and, where periodic, at intervals not exceeding two years. More
freq uent and /or more deta iled inspec tion w ill be nec ess ary w here there is co rrosive or other ad verse a tmosphere, a high risk
of mecha nica l da mag e or vibration, or where there are other onerous c ircumstance s. The need for more freq uent inspec tion
may also be determined by operating experience.
The need for, the method , a nd the frequenc y of c ateg ory B inspec tions is at the discretion of the engineer respo nsible. It is not
intended that periodic inspec tions s hould incur undue disturba nces of appa ratus, unless cons idered nec ess ary by the eng ineer
responsible.
The a bove cha rt is reproduced from B S 5345 P art I.
Sample Inspection Schedule
-
8/10/2019 General Technical Info
10/10
TE C H NIC AL D ATA
Indian Standards for Explosive Atmospheres / Areas
General specifications
IS4051/1967 Cod e o f practice for installation &maintenanc e o f electrica l equipment used in mines.
IS 5571/1979 Guide for the selection of electrica l eq uipments for haza rdous areas .
IS 5572/1978 P a rt I Class ifica tion o f ha zardous areas for electrica l insta llation.
IS 7820/1975 Method of test for ignition temperatures.
IS 8239/1976 Classification of maximum surface temperatures of electrical equipment for use in
explosive atmos pheres.
IS 8240/1976 Guide for e lectrica l equipment for explosive a tmospheres.
IS 8241/1976 Method of marking for identifying electrical equipment for explosive atmospheres.
IS9570/1980 Class ifica tion o f flamma ble ga ses ac cording to their MESG /MICIS 9559/1980 Guide for selection of electrical &electronic equipment for coal mines.
IS 13408/1992 P a rt I Cod e of prac tice for the selection, insta llation and maintenance o f electrica l apparatus for
use in explosive atmospheres (other than mining applications).
IS 139417(Pt 1)/1993 Ingners P rotec tion
Specification for the types of protection
IS 13346 /1992 Ge neral req uirements for electrica l appa ratus for e xplosive a tmospheres
IS 2148 /1981 Spe cifica tion for flame proof enclosures of electrica l appa ratus.
IS 5780 /1980 Intrinsically safe electrical apparatus and circuits.
IS 6381 /1972 Spe cifica tion for c onstruction &tes ting of electrica l appa ratus w ith type of protection e .
IS 7389 /1976 Part I Spe cifica tion for pressurised enclosures of electrica l apparatus for use
in e xplosive a tmospheres.IS 7693 /1975 Spe cifica tion for oil immersed electrica l apparatus for use in explosive ga s atmos pheres.
IS 7724 /1975 Specification for sand filled protection of electrical equipment for use in
explosive atmos pheres.
IS 8289 /1976 Specification for electrical equipment with type of protection n
IS 11005 /1984 Spe cifica tion for dust tight ignition proof enclosures of electrical equipment
Product specifications
IS 2206/1984 P a rt I S pec ifica tion fo r FLP electric lighting fittings Wellglas s &Bulkhea d
IS 2206 /1976 P a rt II S pec ifica tion for FLP e lec tric lighting fittings using glass tubes
IS 2206 /1987 Part IV S pec ifica tion fo r FLP electric lighting fittings Portable flameproof hand lamps.
IS 4012 /1967 Dust p roof elec tric light fittings .
IS 4013 /1967 Dust t ight electric light fittings .IS 4821 /1968 Specification for cable glands and cable sealing boxes for use in mines.
IS 6539 /1972 Intrinsically sa fe ma gneto telephones for use in haza rdous atmos pheres
IS 6789 /1972 Bolted flameproof cable couplers &adaptors
IS 8224 /1976 S pec ifica tion fo r lighting fittings for Division 2 a reas
IS 8945 /1987 Spe cifica tion for e lectrica l meas uring instruments for explosive g as atmos pheres
IS 9099 /1979 Part I Pe rformance testing of pow ered industrial trucks wo rking in haza rdous a reas
(IC engine powered)
IS 9099 /1980 Part II Pe rformance testing of pow ered industrial trucks wo rking in haza rdous a reas
(ba ttery operate d)
IS 9628 /1980 Three phas e induction motors w ith type of protec tion n