flexible gas piping

Upload: kasandra01

Post on 04-Apr-2018

229 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 flexible gas piping

    1/60

    Flexible Gas Piping

    DESIGN GUIDEAND

    INSTALLATION

    INSTRUCTIONMANUAL

    888-80-Snake(888-807-6253)

    Products of

    Metal Fab, Inc.

    P.O. Box 1138 Wichita, KS 67201

    316-943-2351 Fax: 316-943-2717

  • 7/29/2019 flexible gas piping

    2/60

    1.0 introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

    User Warnings

    Limitations of Manual

    DIAMONDBACK Applications

    Listing of Applicable Codes and Standards

    Code Caution

    2.0 dEScriPtion oF SYStEM And coMPonEntS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    System Description

    Hardware Description

    Tubing

    Fittings

    Manifolds, Regulators, and Valves

    Striker Plates

    Conduit, and Mounting Brackets

    3.0 conFigurAtionS And Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    3.1 SystemCongurations

    Series and Parallel Low Pressure Systems

    Elevated/Dual Pressure Systems

    3.2 Sizing Methods and Examples

    Use of Sizing Table

    Low Pressure Systems

    Elevated/Dual Pressure Systems

    Diamondback CSST System with Other Approved Fuel Gas Piping Materials

    4.0 inStAllAtion PrActicES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    4.1 General installation practices

    Minimum Bend Radius

    Debris Protection

    Support

    4.2 Fitting Assembly

    Minimum Tightening Torque

    Tubing Cutting and End Preparation

    Assembly and Re-Assembly Procedure

    tABlE oF contEntS

  • 7/29/2019 flexible gas piping

    3/60

    4.3 Routing

    Vertical Runs

    Horizontal Runs

    Clearance Holes and Notching

    Concealed Locations For Fittings

    Indoor/Outdoor Issues

    4.4 Protection

    Striker Plate Requirements

    Spiral Metal Hose Requirements

    Outdoor Installations

    Other Practices.

    4.5 Meter Hook-Ups

    Special Tubing Termination

    Direct Connection

    4.6 Appliance Connections

    Termination Fittings with Appliance Connectors

    Direct Connections

    Gas Convenience Outlet

    Special Applications

    - Roof Top Units

    - Outdoor Appliances

    - Fireplace Appliances

    - Other Appliances

    4.7 Manifold Stations

    Allowance Locations

    Arrangements

    4.8 Pressure Regulators

    Installation Requirements

    Vent Limiter Option

    Vent Line and Sizing Requirements

    Adjustments

    Over Pressure Protection

    4.9 Underground Installations

    Acceptable Usage

    4.10 Electrical Bonding/Grounding

  • 7/29/2019 flexible gas piping

    4/60

    5.0 inSPEction, rEPAir & rEPlAcEMEnt. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    Minimum Inspection Requirements

    Repair/Replacement of Damaged Tubing

    6.0 PrESSurE/lEAKAgE tESting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

    Requirements for Low Pressure Systems

    Requirements for Elevated Pressure Systems

    7.0 Sizing tABlES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    7.1 DIAMONDBACKTM CSST SIZING TABLES

    Table N1 - 7w.c./.5w.c. Drop (13.08 mmHg/.93 mmHg Drop)

    Table N2 - 7w.c./1w.c. Drop (13.08 mmHg/1.90 mmHg Drop)

    Table N3 - 10w.c./3w.c. Drop (18.68 mmHg/5.60 mmHg Drop)

    Table N4 - 12w.c./6w.c. Drop (22.42 mmHg/11.21 mmHg Drop)

    Table N5 - 2psi/1psi Drop (13.79 kPa/6.90 kPa Drop) Table N6 - 2psi/1.5psi Drop (13.79 kPa/10.34 kPa Drop)

    Table N7 - 5psi/3.5psi Drop (34.48 kPa/24.13 kPa Drop)

    Table P1 - 11w.c./0.5w.c. Drop (20.55 mmHg/.93 mmHg Drop)

    Table P2 - 0.5psi/3w.c. Drop (3.45 kPa/5.60 mmHg Drop)

    Table P3 - 2psi/1psi Drop (13.79 kPa/6.90 kPa Drop)

    Table P4 - 2psi/1.5psi Drop (13.79 kPa/10.34 kPa Drop)

    Table P5 - 5psi/3.5psi Drop (34.48 kPa/24.13 kPa Drop)

    7.2 BLACK IRON PIPE SIZING TABLE

    Table N8 - 7 w.c./0.5 w.c. Drop (13.08 mmHg/.93 mmHg Drop)

    8.0 dEFinitionS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    Appendix A (Conversion Factors & Terminology)

    AppendixB(SpecicGravityFactor)

    Appendix C (Installation Checklist)

  • 7/29/2019 flexible gas piping

    5/60

    1

    uSEr wArning! Please read all instructions before starting installation. Improper installationcan result in serious damage, injury and/or death.

    The words SHALL or MUST indicate a requirement which is essential to satisfactory and safe produc

    performance. The words SHOULD or MAY indicate a recommendation or advice which is not essentiaand not required, but which may be useful or helpful.

    DIAMONDBACKexiblegaspiping,byMetal-FabInc.,mustonlybeinstalledbyapersonwhoisqualied

    throughtheDIAMONDBACKGasPipingInstallationProgram.Anyinstallermustalsomeetqualications

    in accordance with state and/or local requirements as established by the administrative authority which

    enforces the plumbing or mechanical code where the gas piping is installed.

    Due to the explosive nature of fuel gas, it can be dangerous. It may cause injury to persons or damage to

    property.Improperinstallationoffuelgaspipingcouldcauseexplosions,res,ordeath.Soundengineering

    practices and principles must be exercised, as well as diligent adherence to the proper installation proceduresfor the safe operation of the piping system.

    Precautions must be taken by the installer to ensure that the tubing is not damaged or abused during the

    construction process. The tubing ends must be plugged or sealed prior to installation to prevent moisture

    dirt or debris from entering. Contact with sharp objects or harmful substances, including, but not limited to

    acids and solvents, must be avoided. Sharp bends, stretching, kinks, twisting or undue stress or strain on

    thetubingandttingsmustbeavoided.Allinstalledsystemsmustpasscustomaryinstallationinspectionsby

    thelocalbuildingofcialhavingauthoritypriortobeingplacedintoservice.Ifthepipingsysteminstallation

    requires components in addition to those supplied by Metal-Fab, the installation instructions shall specify the

    speciccomponentsrequired.Theinstructionsshallstatethattheonlycomponentsprovidedorspeciedby

    Metal-Fab are to be used in the installation.

    TheuseofDIAMONDBACKexiblegaspipingwithanyotherexiblegastubingsystemisinappropriate

    The guidelines set forth must be used in conjunction with state and local building codes. Local codes wil

    take precedence in the event of a conict between this manual and the local code. In the absence o

    local codes, installation must be in accordance with the current edition of NATIONAL FUEL GAS CODE

    ANSI Z223.1/NFPA 54 (USA), or INSTALLATION CODES CAN/CGA-B149.1 & B149.2 (CANADA).

    WARNING: The Installer Must Follow The Installation Instructions Exactly.

    This system must be installed with strict adherence to this guide as well as local building codes.

    Metal-Fab Inc. shall have no responsibility for any misinterpretation of the information contained in this guide

    or any improper installation or repair work or for other deviation from the procedures recommended in this

    manual,whetherpursuanttolocalbuildingcodesorengineeringspecicationsorotherwise.

    This system and related components must be used only with fuel gases, only where the operating gas

    pressure does not exceed 5 psi. The maximum actual operating pressure including transients shall not in any

    case exceed 6.5 PSI.

    cHAPtEr 1.0: introduction

  • 7/29/2019 flexible gas piping

    6/60

    2

    liMitAtionS oF MAnuAl

    This document is intended to aid the user in the design, installation and testing of DIAMONDBACKCorrugated

    Stainless Steel Tubing (CSST) that is used to distribute fuel gas in residential housing units and light

    commercial applications. It is not possible for this guide to anticipate and cover every possible variation in

    housingcongurationsandconstructionstyles,applianceloadsandlocalrestrictions.Therefore,therewillbe

    applications which are not covered in this guide. For applications beyond the scope of this guide, contact the

    DIAMONDBACKdistributor for the area or Metal-Fabs Application Engineering Department for assistance.

    The techniques included within this guide are recommended practice for generic applications. These practicesmustbereviewedforcompliancewithallapplicablelocalfuelgasandbuildingcodes.Whereconictexists

    between the recommended practice and local requirements, local requirement must take precedence unless

    a variance is obtained from the local authority having jurisdiction. This system and related components must

    be used only as fuel gas piping where the operating gas pressure does not exceed 5 psi (34.48 kPa).

    diAMondBAcK APPlicAtionS

    The use of DIAMONDBACK is not restricted by the style, size, age, type of construction, height, orphysical layout of the building where fuel gas service is to be installed. DIAMONDBACK can be used in

    bothresidentialandlightcommercialapplications,aswellasnewconstructionandretrottingapplications.

    The requirements of this guide, in regard to system design, installation, inspection and testing, are the same

    regardless of building application.

    The installer must meet local building codes with respect to ame spread and smoke

    density regulations for nonmetallic materials. DIAMONDBACK must not be routed in or

    through heating and cooling ductwork.

    DIAMONDBACKexiblegaspiping canbeused toprovideoutdoorconnections to appliances

    that are attached to, or in close proximity to the building.

    DIAMONDBACKexiblegaspipingcanberoutedinmostlocationswheretraditionalgaspiping materialsareinstalled:insidehollowwallcavities,alongorthroughoorjoistsinbasements,ontop

    ofthejoistsinattics,onrooftopsoralongsoftsorinchasesoutsideofbuildings.

    DIAMONDBACK exible gas piping can be run directly to the shut off valves of most xed

    appliances without installing an appliance connector. For moveable appliances such as ranges or

    dryers,theuseofanapprovedexibleapplianceconnectorisrequired.DIAMONDBACKcannot

    be substituted as a connector for this use when the appliance is free to move for cleaning, etc.

    DIAMONDBACK exible gas piping can be used for Natural gas and propane (Liqueed

    Petroleum gas) and other fuel gases recognized in ANSI Z223.1/NFPA 54 National Fuel Gas Code.

    Forundergroundorconcreteburial,theexiblegaspipingrunmustbeencasedinasleeveofPVC,

    polyethylene, or other approved water resistant material.

    DIAMONDBACKexiblegaspipingcanbeusedinconjunctionwithblackironpipeineithernew

    construction or renovation and replacement piping installations. All DIAMONDBACK

    ttingsterminate in standard NPT male pipe ttings to interface with appliances, valves, tees,

    unions and couplings.

  • 7/29/2019 flexible gas piping

    7/60

    3

    liSting oF APPlicABlE codES And StAndArdS

    REGIONAL/MODEL CODES LISTING CSST AS AN ACCEPTABLE GAS PIPING MATERIAL:

    ANSILCICSA6.26Standard

    CANADA - CAN B149.1 Natural GAS and B149.2 Propane

    NFPA 54/ANSI Z 223.1 National Fuel Gas Code

    ICBO - Uniform Mechanical Code

    BOCA - National Mechanical Code

    CABO-1 and -2 Family Dwelling Code

    SBCCI - Standard Gas Code

    ICC - International Mechanical Code

    IAPMO - Uniform Plumbing Code

    IAPMO - File Listing #C-3859

    City of Los Angeles Research Report #RR5506

    In Canada, the installationofANSI/CSA certied DIAMONDBACK exiblegas tubing fornatural andpropane gas piping systems must be in accordance with the applicable sections of the current CAN/CGA-

    B149.1 or .2 installation codes, and the requirements or codes of the local utility or other authority having

    jurisdiction.AllgascomponentsusedinconjunctionwiththegastubingmustbecertiedforuseinCanada

    DIAMONDBACK has been tested to the ANSI standard for Fuel Gas Piping Systems using Corrugated

    StainlessSteelTubing.ANSILC1CSA6.26-1997AddendumANSILC1aCSA6.26a-1999;LC1b-2001

    and the CAN/CGA Certication Laboratories Requirements LAB-009. FLEXIBLE GAS TUBING FOR

    NATURAL AND PROPANE PIPING SYSTEMS.

    codE cAution

    This document is intended only to provide the installer with general guidance and assistance when designing

    and installing a DIAMONDBACK corrugated stainless steel tubing (CSST) fuel gas system. While everyeffort has been made to prepare this document in accordance with the regional model codes in effect at its

    printing, Metal-Fab cannot guarantee that the local administrative authority will accept these regional codes.

    It is the ultimate responsibility of the installer to determine suitability of the DIAMONDBACK gas piping

    system for use in construction. Metal-Fab assumes no responsibility for labor or materials which have been

    installed without prior determination of local code authority acceptance.

    USC

  • 7/29/2019 flexible gas piping

    8/60

    4

    SYStEM dEScriPtion

    A. The DIAMONDBACK system has a number of hardware and design differences from

    conventional gas piping system using black iron pipe. These differences can be described as

    follows: The DIAMONDBACK system uses exible annular corrugated tubing made of 300 series

    stainless steel.

    The tubing is connected using special mechanical ttings designed for Metal-Fabs

    DIAMONDBACK.

    In many applications, the tubing is sized for individual gas appliance loads and is, therefore,

    usually smaller in diameter. The tubing is often piped in parallel from a central distribution

    manifold rather than in series, as is common with black iron systems.

    The system can be used for elevated pressure systems up to 5 psi (34.48kPa).

    Different handling and installation procedures are required during installation.

    DIAMONDBACK can be used for both a low pressure (below 0.5 psi (3.45 kPa)) system and anelevated (5.0 psi (34.48kPa)) pressure system design. It complies with the ANSI/CSA LC-1

    standard and is approved for fuel gas applications.

    B. DIAMONDBACK Corrugated tubing may be installed in combination with other approved

    fuel gas piping materials using approved threaded couplings, unions, elbows, tees or

    terminations at the interface.

    DIAMONDBACK may be used like black iron pipe in low pressure gas piping systems

    (12 in w.c. (22.42 mmHg) or less). However, an elevated pressure system will allow the use of

    smaller tubing sizes. An elevated pressure system typically operates at 2-5 psi (13.79 - 34.48 kPa)

    gas pressure from the meter regulator to an intermediate line regulator/central distribution

    manifold. At that point, the pressure is reduced to a lower pressure (7 in w.c. (13.07 mmHg))

    Independent tubing runs, operated at low pressure, connect each appliance to the distributionmanifold.

    C. Using FIG. 2-1 as a guide, the elevated pressure system can be described as follows:

    An elevated pressure DIAMONDBACK system uses a distribution arrangement consisting of a

    shut-off valve, pressure regulator and multiport manifold.

    Gas is delivered to the housing unit or building at street pressure which is then reduced at the

    service regulator.

    The entire gas load is piped by a single line through an approved shut off valve, then through an

    approved line regulator where the pressure is reduced. At this point it enters a centrally located

    distribution manifold where the gas is distributed to each individual appliance (or small group of

    appliances) through independent DIAMONDBACK tubing lines.

    Thetubingisthenconnectedtoeachapplianceaccordingtolocalcodes(e.g.driplegs,exible

    appliance connector, hard piping).

    Any extra ports in the manifold are plugged until additional gas appliances are added. It is

    advisable to put a valve in the extra ports and then plug the valve outlet. This extra port can then

    be used for future expansion without turning off the existing system.

    D. The choice of system conguration is dependent on local piping restrictions, structural

    arrangement, availability of elevated pressure, and the total gas load.

    cHAPtEr 2.0: dEScriPtion oF SYStEM And coMPonEntS

  • 7/29/2019 flexible gas piping

    9/60

    5

    HArdwArE dEScriPtion

    This gas piping system using DIAMONDBACKcorrugated stainless steel tubing consists of the following

    components:

    DIAMONDBACKCorrugated Stainless Steel Tubing (CSST)

    Mechanical Joint Fittings

    Steel Indoor Termination Fittings

    Brass Outdoor Termination Fittings

    Mechanical Couplings

    Manifolds

    Striker Plates

    Gas Pressure Regulators (For Dual/Elevated Pressure System)

    Shut-Off Valves

    Black Iron Pipe, Fittings and Nipples (if selected)

    Strip Wound Metal Conduit

    Termination Brackets Manifold Brackets

    The tubing is jacketed with yellow polyethylene sleeve which provides ease of running through joists, studs

    and other building components. The jacket is marked at one foot intervals with the amount of tubing left on

    the reel, for quick measurement. The yellow color is the international designation for fuel gas.

    The regulator, for reducing pressure from Pounds Per Square Inch (PSI) to inches of water column is used

    in elevated pressure system installations over 12 in. w.c. (22.42 mmHg).

    Elevated pressure shut off ball valves are used in systems with supply gas pressures ranging from 2 ps

    (13.79 kPa) up to 5 psi (34.48kPa). Use only valves which comply with IAS U.S. Requirement 3-88 and/or

    CR 91-002. Valves complying with this requirement but not complying with ASME B16.33 and/or CGA 3.11

    shall not be installed outdoors.

    The Four-Port Manifold allows parallel installations with individual runs or home runs to each appliance.

    Protection devices (striker plates and spiral wound conduit) are used where DIAMONDBACK piping

    passes through studs, joists and other building materials and is restricted from moving to avoid nails, screws

    andotherpuncturethreats.Therearefourstrikerplatecongurationsmadefromspeciallyhardenedstee

    toresistpenetrationfromscrewsandpneumaticnailguns.Inaddition,spiralwoundsteeloppyconduitis

    available for use in areas where striker plates cannot be used.

    Fig. 2-1 Eevae Pesse Sysem Aaeme

    SHUT OFF VALVE

    PRESSURE REGULATOR REDUCING,

    SELF CONTAINED

    GAS METER

    DISTRIBUTION MANIFOLD

    KEY

    SERVICE REGULATOR

    STREET PRESSURE 2-5 PSIG

    APPROVED LINE REGULATOR

    2 PSIG TO 8 IN. W.C.

    APPLIANCE LINES

  • 7/29/2019 flexible gas piping

    10/60

    6

    O.D. I.D. JACKET O.D.

    DIAMONDBACK FLEXIBLE GAS

    TUBING

    Material: 300 Series Corrugated Stainless

    Steel with Polyethylene Jacket.

    Part No. 375DFT 500DFT 750 DFT 1000DFT 1250DFT

    Size 38 (10) 12 (13) 34 (19) 1 (25) 1 14 (32)

    EHD* 15 19 25 31 37

    Jacket O.D. (max.) .617 .781 1.050 1.346 1.606

    I.D. (nominal) 0.464 0.610 0.844 1.092 1.327

    O.D. (nominal) 0.585 0.748 1.023 1.307 1.582

    tuBing

    DIAMONDBACK ON REELS

    Material: 300 Series Corrugated Stainless Steel

    with Polyethylene Jacket. Packaged on Plywood

    Reels.

    Used to convey gas

    Part No. 375DFT 500DFT 750 DFT 1000DFT 1250DFT

    Size 38 (10) 12 (13) 34 (19) 1 (25) 1 14 (32)

    Reel Length250 ft.

    (76.20m)

    250 ft.

    (76.20m)

    250 ft.

    (76.20m)

    150 ft.

    (45.72m)

    125 ft.

    (38.10m)

    Weight30 lbs.

    (13.61kg)

    40 lbs.

    (18.14kg)

    58 lbs.

    (26.31kg)

    48 lbs.

    (21.77kg)

    70 lbs.

    (31.75kg)

    *EHD(EffectiveHydraulicDiameter):Arelativemeasureofowcapacity

  • 7/29/2019 flexible gas piping

    11/60

    7

    STRAIGHT FLANGE MOUNT TERMINATION

    FITTING

    Material: CA360 Brass Fitting

    Indoor: Black Iron Flange

    Outdoor: Brass Flange

    Usedforwall/oorterminationfor

    appliance connector

    SPLIT RING

    MALE ADAPTER

    FLANGE

    TUBING

    SEAL NUT WITH FLANG

    THREAD

    SEAL NUT WITH

    FLANGE THREAD

    MALE ADAPTER

    CA360 Brass Part Nos. 375DBFF 500DBFF 750DBFF 1000DBFF 1250DBFF

    Black Iron Part Nos. 375DFF 500DFF 750DFF 1000DFF 1250DFF

    Fitting Size 38 (10) 12 (13) 34 (19) 1 (25) 1 14 (32)

    Pipe Thread (NPT) 12 12 34 1 1 14

    Part No. 375DC 500DC 750DC 1000DC

    Fitting Size 38 (10) 12 (13) 34 (19) 1 (25)

    MECHANICAL COUPLING

    Material: CA360 Brass.

    Used to connect two

    DIAMONDBACKTM

    tubes of the same size.

    MALE ADAPTER

    SEAL NUT

    SPLIT RING

    TUBING

    MALE ADAPTER

    Part No. 375DMF 500DMF 750DMF 1000DMF 1250DMF

    Fitting Size 38 (10) 12 (13) 34 (19) 1 (25) 1 14 (32)

    Pipe Thread (NPT) 12 12 34 1 1 14

    STRAIGHT MECHANICAL JOINT

    FITTING

    Material: CA360 Brass.

    Used to connect DIAMONDBACK

    tubing to a manifold or gas outlet.

    FittingS

    SEAL NUT

    COUPLING BODY

    SPLIT RING

    TUBING

    SEAL NUT

    SEAL NUT

    COUPLING BODY

    SEAL NUT

  • 7/29/2019 flexible gas piping

    12/60

    8

    MULTIPORT MANIFOLDS

    Materials: Carbon Steel

    Used to route DIAMONDBACK tubing to

    multiple appliances.

    Part No. 500DSM 750DSM

    Outlet 4 Port 12 NPT Female 4 Port 1 NPT Female

    Inlet 34 NPT Female 114 NPT Female

    STUB-OUT FITTING

    Material: Black Iron.

    Used for the termination of gas line.

    Part No. 500DTF 500D90TF 750DTF

    Fitting Size 12 (13) 12 (13) 34 (13)

    Pipe Thread (NPT) 12 12 34

    5 SQ. 5 SQ. 2 34

    TEE FITTINGS

    Material: CA360 Brass.

    Used to connect three

    DIAMONDBACKTM

    tubes of the various sizes.

    Part No. DT555 DT7555 DT75575 DT17575 DT151 DT1751Run 1 Size 12 NPT 34 NPT 34 NPT 1 NPT 1 NPT 1 NPT

    Tap Size 12 NPT 12 NPT 12 NPT 34 NPT 12 NPT 34 NPT

    Run 2 Size 12 NPT 12 NPT 34 NPT 34 NPT 1 NPT 1 NPT

    SEAL NUT

    TUBING

    SPLIT RING

    TEE BODYTEE BODY

    RUN 2

    TAP

    RUN 1

  • 7/29/2019 flexible gas piping

    13/60

    9

    LINE PRESSURE REGULATOR

    0.5 psi - 2.0 psi (3.45 kPa - 13.79 kPa) Per ANSI Z21.80

    Materials: Cast Aluminum Housing Suitable

    For Outdoor Use.

    Used to control line pressure.

    * Must be vented outdoors.

    ELEVATED PRESSURE SHUT-OFF VALVES

    Materials: Brass Housing With Stainless Steel Ball.

    Used to close supply of fuel to an appliance.

    LINE PRESSURE REGULATOR w/ OPD

    2.0 psi - 5.0 psi (13.79 kPa - 34.48 kPa) Per ANSI Z21.80Materials: Cast Aluminum Housing Suitable

    For Outdoor Use.

    Used to control line pressure.

    Part No. 500DR3N 500DR3P 750DR5A ~

    Model No. 325-3L/Type90 325-3LP 325-5AL/Type95 325-7L*

    Port Size 12 x 12 NPT 12 x 12 NPT 34 x 34 NPT 1 14 x 1 14 NPT

    Vent Size 18 NPT 18 NPT 38 NPT 12 NPT

    Fuel Type Natural Gas Propane Gas Natural Gas Natural Gas

    Part No. 500DR3XN 750DR5XA

    Model No. 325-3L47 325-5AL48

    Port Size 12 x 12 NPT 34 x 34 NPT

    Vent Size 18 NPT 38 NPT

    Fuel Type Natural Gas Natural Gas

    Part No. 500DBV 750DBV

    Port Size 12 x 12 NPT 34 x 34 NPT

    Tubing Sizes 38 (10) & 12 (13) 34 (19)

  • 7/29/2019 flexible gas piping

    14/60

    10

    LARGE STRIKER PLATE

    PartNo.DSPX

    Materials: 16 Gauge Hardened Steel

    Size: 6 12 x 17 (165 x 432)

    Used to protect tubing from puncture at areas of

    support.

    FULL STRIKER PLATE

    Part No. DSPF

    Materials: 16 Gauge Hardened Steel

    Size: 3 12 x 11 12 (89 x 292)

    Used to protect tubing from puncture at areas of

    support.

    HALF STRIKER PLATE

    Part No. DSPH

    Materials: 16 Gauge Hardened Steel

    Size: 3 12 x 6 12 (89 x 165)

    Used to protect tubing from puncture at areas of

    support.

    QUARTER STRIKER PLATEPart No. DSPQ

    Materials: 16 Gauge Hardened Steel

    Size: 3 12 x 1 12 (89 x 38)

    Used to protect tubing from puncture at areas of

    support.

    StriKEr PlAtES

  • 7/29/2019 flexible gas piping

    15/60

    11

    FLOPPY STRIP WOUND CONDUIT

    Materials: Type RW Galvanized Steel.

    Used to protect tubing from puncture in area of

    support.

    TERMINATION OUTLET BRACKET

    Part No. DTMB

    Materials: 16 gauge galvanized steel.

    Usedformountingallangeadapterttingstostuds

    during rough installation.

    MANIFOLD MOUNT BRACKET

    Part No. DMB

    Materials: 16 gauge galvanized steel.

    Used for mounting manifolds to studs during rough

    installation.

    Part No. 375DFC 500DFC 750DFC 1000DFC 1250DFC

    Fits Sizes 38 (10) 12 (13) 34 (19) 1 (25) 1 14 (32)

    Length50 (15.24m)

    Roll

    50 (15.24m)

    Roll

    50 (15.24m)

    Roll

    25 (7.62m)

    Roll

    25 (7.62m)

    Roll

    Part No. 375DFC-1 500DFC-1 750DFC-1 1000DFC-1 1250DFC-1

    Fits Sizes 38 (10) 12 (13) 34 (19) 1 (25) 1 14 (32)

    Length 1 (3.05m) 1 (3.05m) 1 (3.05m) 1 (3.05m) 1 (3.05m)

  • 7/29/2019 flexible gas piping

    16/60

    12

    cHAPtEr 3.0: SYStEM conFigurAtionS & Sizing

    3.1 SYStEM conFigurAtionS

    seriesandparallellowpressuresystems

    APPLIANCE

    SHUTOFF

    VALVE

    PRESSURE

    REGULATORLINE

    SHUTOFF

    VALVE

    GAS

    DISTRIBUTION

    MANIFOLD

    LENGTH OF RUNS

    A = 10 FT. (3.05m)

    B = 10 FT. (3.05m)

    C = 15 FT. (4.57m)

    SUPPLY PRESSURE: 7 IN. W.C.

    (13.08 mmHg)

    ALLOWABLE DROP: 0.5 IN W.C.

    (.93 mmHg)

    WATER HEATER

    35 CFH

    FURNACE

    65 CFHLOW PRESSURE

    GAS METER

    100 CFH

    C A

    B

    0.5 PSI

    (3.45 kPa)

    GAS METER

    FURNACE

    80 CFH

    WATER HEATER

    40 CFH

    RANGE

    55 CFH

    DRYER

    30 CFH

    D

    A

    E

    C

    B

    LENGTH OF RUNS

    A = 10 FT. (3.05m)

    B = 20 FT. (6.10m)

    C = 10 FT. (3.05m)

    D = 40 FT. (12.19m)

    E = 10 FT. (3.05m)

    SUPPLY PRESSURE: 12 IN. W.C.

    (22.42 mmHg)

    ALLOWABLE DROP: 6 IN. W.C.

    (11.21 mmHg)

    FIG. 3-1 Key For Pictorial

    FIG. 3-2 EXAMPLE 1 - Low Pressure System, 7 in. w.c. (13.08mmHg), Series Arrangement

    FIG. 3-3 EXAMPLE 2 - Low Pressure System, 12 in. w.c. (22.42 mmHg) Parallel Arrangement

  • 7/29/2019 flexible gas piping

    17/60

    13

    duAl PrESSurE SYStEMS

    3.2 Sizing MEtHodS And ExAMPlES

    Thischapter includesexiblegaspipingsizingproceduresforboth lowpressureandelevatedpressure

    systems.Everypipingsystemintroducespressurelosstothefuelgasowingwithin.Theamountofloss

    dependsonthepipingsizeandtheow,expressedincubicfeetperhour(CFH),andconvertedtoBTUs

    The objective of the sizing exercise is to determine the allowed pressure loss or drop within the length of

    piping required.

    uSE oF Sizing tABlES

    Chapter 7 of this manual consists of fuel gas pipe sizing tables. These tables are required to determine the

    minimum size fuel gas pipe for each part of a fuel gas system. To use these tables you will need to know the

    supply gas pressure, the CFH requirement on the section of the system and the length, in feet, of the piping

    run.

    The tables are listed by the supply gas pressure and the allowable gas pressure drop. For example, the low

    pressure system call out a 7 in. w.c. (13.08 mmHg) supply pressure with a 0.5 in. w.c. (.93 mmHg) pressure

    drop.

    Findthecorrecttable.Onthetable,ndthecolumnwiththelengthinfeetofthegaspiperunyouare

    looking for. (If the length you are looking for is not on the list go to the next longer length.) Check the CFHratingsofthefuelgaspipeuntilyoundwhichonewillhandletheCFHrequirementatthedeterminedlength

    Match that CFH rating to the corresponding size of pipe.

    Chapter 3.2 of this manual gives examples of this procedure.

    Longest Run Method (Low/Medium Pressure Systems)-FIG. 3-2 and 3-3

    The low pressure series system (conventional arrangement) is sized in the same way as a conventional low

    pressure black iron pipe system using the sizing tables. This method is known as the longest run method

    Pressure drop in a low pressure system is usually limited to 0.5 in. w.c. (.93 mmHg) over the system. Medium

    pressure systems can have pressure drops of up to 6 in. w.c. (11.21 mmHg).

    2 PSI

    (13.79 kPa)

    GAS METER

    FURNACE

    80 CFH

    WATER HEATER

    40 CFH

    RANGE

    55 CFH

    DRYER

    30 CFH

    D

    A

    E

    C

    B

    LENGTH OF RUNS

    A = 100 FT. (30.48m)

    B = 15 FT. (4.57m)

    C = 10 FT. (3.05m)

    D = 25 FT. (7.62m)

    E = 20 FT. (6.10m)

    ELEVATED SUPPLY PRESSURE: 2 PSI (13.79 kPa)

    ALLOWABLE DROP UP TO REGULATOR: 1 PSI

    (6.90 kPa)

    LOW PRESSURE SUPPLY: 10 IN W.C. (18.68 mmHg)ALLOWABLE DROP REGULATOR TO APPL.: 3 IN. W.C.

    (5.60 mmHg)

    FIG. 3-4 EXAMPLE 3 - Elevated/Dual Pressure System, 2PSI (13.79 kPa), Parallel Arrangement

  • 7/29/2019 flexible gas piping

    18/60

    14

    Elevated/Dual Pressure Systems - FIG. 3-4

    Elevated pressure systems incorporate two operating pressures downstream of the gas utility meter set. The

    rstpressure,setbytheserviceregulatoratthemeter,isusually2psi(13.79kPa).Thispartofthesystemis

    sized separately and ends at the pounds-to-inches line regulator. The allowable pressure loss for this part of

    the system must be added to the effect of the regulator to determine the available pressure at the regulator

    outlet. Table 3-5 below shows pressure losses for maximum loads through the regulator.

    For a 2 psi (13.79 kPa) system, the proper drop is usually 1 psi (6.90 kPa) for this part of the system. This

    allows for the approximate 0.75 psi (5.17 kPa) regulator drop downstream and provides the 0.25 psi (1.72

    kPa) (6-7 in. w.c. (11.21 - 13.08 mmHg)) necessary for appliances. The regulator reduces the pressure frompounds per square inch to inches water column (in. w.c.). This part of the system is sized the same as a low

    pressure system, except that a special Table N-3 is used allowing 3 in. w.c. (5.60 mmHg) drop. These lines

    are typically sized for only one appliance load installed as a home-run from the manifold.

    NOTE: At 250 CFH gas ow the Maxitrol 325-3L or O.A.R.A. Type 90 regulator contributes 0.75 psi (5.17

    kPa) drop to the system (See Table 3-5). The low pressure part of the system downstream of the regulator

    requires the standard 0.25 psi (1.72 kPa) to power appliances. Deducting the 0.75 psi (5.17 kPa) drop for

    the regulator and the 0.25 psi (1.72 kPa) load for the appliances, the maximum allowable drop for the gas

    meter run is 1 psi (6.90 kPa).

    For example, start with 2 psi (13.79 kPa), 0.75 psi (5.17 kPa) drop for regulator and 0.25 psi (1.72 kPa) to

    run the appliances, this results in 1 psi (6.90 kPa) drop forSection A.

    Sizing ExAMPlES

    To size each of the following systems, determine the required size for each section and outlet. To size

    each section of the system, determine both the local gas load for all appliances and the maximum distance

    (longest run) in which a particular section delivers gas.

    Example 1 Low Pressure System, 7 in. w.c. (13.08 mmHg) Series Arrangement

    1. The system presented in FIG. 3-2 is typical of a single family installation in which there are a limited

    number of appliances located in one general area. The supply pressure is 7 in. w.c. (13.08 mmHg) and the

    allowable drop is 0.5 in. w.c. (.93 mmHg).

    2. To size Section A, determine the longest run (the longest run is the length from the meter to the

    furthest appliance) and total gas load for each appliance in cubic feet per hour (CFH), 1 CFH =

    1,000 BTU: Meter to Furnace = A + B = 10 + 10 = 20 ft. (3.05m + 3.05m = 6.10m)

    Meter to Water Heater = A + C = 10 + 15 = 25 ft. (3.05m + 4.57m = 7.62m)

    This is the longest run.

    Total load = Furnace + Water Heater = 65 + 35 = 100 CFH (100,000 BTU)

    Select Table N-1 (Page 44) 7 in. w.c. with 0.5 in. w.c. drop (13.08 mmHg with .93 mmHg

    Drop). Using the longest run method, select the column showing the measured length, or the

    next longest length if the table does not give the exact length. Referring to Table N-1, the column

    for 25 ft. (7.62m) of piping shows that sizes 3/8 (10) and 1/2 (13) are too small and the next

    available size is 3/4 (19) with a maximum capacity of 158 CFH. The correct size is 3/4 (19).

    Table 3-5Capacities and Pressure Drop Through Maxitrol/O.A.R.A Regulator

    Model 7 in. w.c.

    (13.08 mmHg)

    0.5 psi

    (3.45 kPa)

    0.75 psi

    (5.17 kPa)

    1 psi

    (6.90 kPa)

    Maxitrol 325-3L 145 CFH 204 CFH 250 CFH 289 CFH

    Maxitrol 325-5AL 338 CFH 476 CFH 583 CFH 673 CFH

    Maxitrol 325-7L 690 CFH 972 CFH 1191 CFH 1375 CFH

    O.A.R.A Type 90 155 CFH 220 CFH 280 CFH 310 CFH

    O.A.R.A Type 95 359 CFH 504 CFH 627 CFH 719 CFH

  • 7/29/2019 flexible gas piping

    19/60

    15

    3. To size Section B, determine the length of run from the Meter to the Furnace and the load delivered:

    Length = A + B = 10 + 10 = 20 ft. (3.05m + 3.05m = 6.10m), Load = 65 CFH (65,000 BTU)

    Table N-1 shows that size 1/2 (13) supplies 77 CFH.

    The correct size is 1/2 (13).

    4. To size Section C, determine the length of run from the Meter to the Water Heater and the load delivered:

    Length = A + C = 10 + 15 = 25 ft, (3.05m + 4.57m = 7.62m). Load = 35 CFH (35,000 BTU)

    Table N-1 shows that size 12 (13) is required, because size 38 (10) has a maximum capacity of 33CFH.

    The correct size is 12 (10).

    Example 2 Low Pressure System, 12 in. w.c. (22.42 mmHg) Parallel Arrangement.

    1. The system shown in FIG. 3-3 is typical of a single family installation with several appliances and medium

    loads. The appliances are installed apart instead of all together, and the arrangement chosen is parallel. The

    higher supply pressure of 12 in. w.c. (22.42 mmHg) allows a higher pressure drop, 6 in. w.c. (11.21 mmHg

    than is available with low pressure systems.

    2. To size Section A, determine the longest run from the Meter to the furthest appliance and the total load:

    Meter to Range = A + B = 10 + 20 = 30 ft. (3.05m + 6.10m = 9.15m)

    Meter to Water Heater = A + C = 10 + 10 = 20 ft. (3.05m + 3.05m = 6.10m)

    Meter to Furnace = A + E = 10 + 10 = 20 ft. (3.05m + 3.05m = 6.10m)

    Meter to Dryer = A + D = 10 + 40 = 50 ft. (3.05m + 12.19m = 15.24m) This is the longest run.

    Load = Dryer + Range + Water Heater + Furnace = 30 + 55 + 40 + 80 = 205 CFH (205,000 BTU)

    Select Table N-4 (Page 45) Low Pressure 12 in. w.c. (22.42 mmHg) with 6 in. w.c. (11.21 mmHgdrop). It shows that 12 (13) size is too small for 205 CFH at 50 ft (15.24m)., but size 34 (19) can

    handle 365 CFH.

    The correct size is 34 (19).

    3. To size Section B, determine the length of run from the Meter to the Range and the load delivered:

    Length = A + B = 10 + 20 = 30 ft. (3.05m + 6.10m = 9.15m), Load = 55 CFH (55,000 BTU)

    Table N-4 shows that size 38 (10) can handle 106 CFH at 30 feet (9.15m).

    The correct size is 38 (10).

    4. To size Section C, determine the length of run from the Meter to the Water Heater and the load delivered:

    Length = A + C = 10 + 10 = 20 ft. (3.05m + 3.05m = 6.10m), Load = 40 CFH (40,000 BTU)

    Table N-4 shows that size 38 (10) can handle 131 CFH at 20 feet (6.10m).

    The correct size is 38 (10).

    5. To size Section D, determine the length of run from the Meter to the Dryer and the load delivered:

    Length = A + D = 10 + 40 = 50 ft. (3.05m + 12.19m = 15.1m), Load = 30 CFH (30,000 BTU)

    Table N-4 shows that size 38 (10) can handle 82 CFH at 50 feet (15.1m).

    The correct size is 38 (10).

    6. To size Section E, determine the length of run from the Meter to the Furnace and the load delivered:

    Length = A + E = 10 + 10 = 20 ft. (3.05m + 3.05m = 6.10m), Load = 80 CFH (80,000 BTU)

    Table N-4 shows that size 38 (10) can handle 131 CFH at 20 feet (6.10m).

    The correct size is 38 (10).

    Example 3 Elevated Pressure System, 2 psi (13.79 kPa), Parallel Arrangement

    1. The system shown in FIG. 3-4 is adapted for multifamily or single family application with an extended

    100 ft. (30.48m), tubing run from the meter to the regulator. The 2 psi system is well adapted to handle the

    long runs required in multifamily buildings with centralized meter banks.

    2. To size Section A, determine the total gas load it will deliver:

    Load = Furnace + Water Heater + Dryer + Range = 80 + 40 + 30 + 55 = 205 CFH (205,000 BTU)

    Select Table N-5 (Page 46) Elevated Pressure 2 psi (13.79 kPa) with 1 psi (6.90 kPa) drop. This is the

    standard table chosen to stay within the Maxitrol 325-3L or O.A.R.A Type 90 regulator capacity.

    Length = 100 ft. (30.48m)

    Table N-5 shows that 38 (10) size is too small for 205 CFH, but 12 (13) can handle 249 CFH. The correct size is 12 (13).

  • 7/29/2019 flexible gas piping

    20/60

    16

    3. To size each of the other sections, select Table N-3 (Page 45) Regulator Outlet 10 in. w.c. (18.68 mmHg)

    with a drop of 3 in. w.c. (5.60 mmHg):

    Section B is 15 ft. (4.57m) with a 40 CFH load. The suitable size 38 (10) has 106 CFH capacity

    at 15 ft. (4.57m)

    Section C is 10 ft. (3.05m) with a 80 CFH load. The suitable size 38 (10) has 131 CFHcapacity

    at 10 ft. (3.05m).

    Section D is 25 ft. (7.62m) with a 30 CFH load. The suitable size 38 (10) has 82 CFH capacity

    at 25 ft. (7.62m)

    Section E is 20 ft. (6.10m) with a 55 CFH load. The suitable size 38 (10) has 92 CFH capacity

    at 20 ft. (6.10m)

    The correct size for all the above runs is 38 (10).

    ExAMPlE 4 - coMBinAtion diAMondBAcK cSSt SYStEM in conJunction witH otHEr APProVEd

    FuEl gAS PiPing MAtEriAlS

    FIG. 3-6 BLACK IRON PIPE AND CSST SYSTEMS

    METER

    FURNACE

    75 CFH

    WATER HEATER

    30 CFH

    FIREPLACE

    30CFH

    D

    A

    E

    C

    B

    LENGTH OF RUNS

    A = 40 FT. (12.19m)

    B = 50 FT. (15.24m)

    C = 30 FT. (9.14m)

    D = 20 FT. (6.10m)

    E = 20 FT. (6.10m)

    SUPPLY PRESSURE: 7 IN. W.C. (13.08mmHg)

    ALLOWABLE DROP: 0.5 IN. W.C. (.93 mmHg)

    CSST

    BLACK IRON PIPE

    Example 4 - Combination Black Iron Pipe and Diamondback CSST System

    1. When adding Diamondback to an existing black iron pipe system use the longest length method

    explained earlier in this chapter. In FIG. 3-6 the home has an existing supply line of one-inch black iron

    pipe. The supply pressure is 7 in. w.c. (13.08 mmHg) with an allowable drop of 0.5 in. w.c. (.93 mmHg).

    2. To size Section A. Determine the total load of the home (170 CFH) and the longest run, 90 ft. (27.43m).

    Table N-8 (Page 50) shows that 1 (25) dia. pipe has a capacity of 205 CFH at 90 ft. (27.43m) The 1 (25)

    dia. pipe (Section A) will handle the load.

    3. To size Section B.Determinetheloadofthereplace(30CFH)andthelengthoftherun,90ft.(27.43m)

    Table N-1 (Page 44) shows the suitable size Diamondback is 12 (13).

    4. To size Section C. Determine the load of the quick connect (35 CFH) and the length of the run., 70 ft.

    (21.34m) Table N-1 shows the suitable size Diamondback is 12 (13).

    NOTE: If the supply pressure was raised by the gas utility to 10 in. w.c. (18.68 mmHg) with allowable

    pressure drop of 3 in. w.c. (5.60 mmHg), Table N-3 (Page 45) shows Sections B & C could both be run

    with 38 (10) Diamondback CSST.

  • 7/29/2019 flexible gas piping

    21/60

    17

    cHAPtEr 4.0: inStAllAtion PrActicES

    4.1 gEnErAl inStAllAtion PrActicES

    codE coMPliAncE

    dESign liMitAtion

    DIAMONDBACK fuel gas systems shall not operate at pressures exceeding 5 psi (34.48 kPa). Thedesign operating pressures for the elevated pressure systems are 2-5 psi (13.79-34.48 kPa) from the mete

    to the pressure regulator, and 12 in. w.c. (22.42 mmHg) or less, from the pressure regulator to the inlet of

    the appliance regulator. The pressure regulator must be approved for operation for at least 5 psi (34.48 kPa)

    inlet pressure. On low pressure systems, less than 0.5 psi (3.45 kPa), where a pressure regulator is not

    necessary, the design operating pressure may be set by the local utility between 7 and 12 in. w.c. (13.08 and

    22.42 mmHg).

    PlAnning SYStEM dESign

    1. ConrmthatthelocalbuildingcodeauthorityhasacceptedtheuseofDIAMONDBACKCSST.

    2. Check with the local gas utility or supplier to determine the metered gas supply pressure.

    3. Prepare a dimensioned sketch of the installation showing the location of each appliance and

    possible piping routes.

    4. Determine the load demand for each appliance. This data is commonly found on the manufacturers

    nameplate on each gas appliance or is provided by the builder/contractor. Determine the type of

    pipinglayoutandDIAMONDBACKsizewhichbesttstheinstallation.

    Natural Gas Supply pressure in the USA and Canada is typically 6 to 7 in. w.c. (0.25 psi, 4 oz.

    or 1.72 kPa). Higher supply pressures 0.5 psi (14 in. w.c./3.45 kPa), 1 psi (28 in. w.c./6.90 kPa), and

    2 psi (56 in. w.c./13.79 kPa) will allow reduced tubing size in the CSST design plane. CSST can

    also be used in 5 psi (34.48 kPa) supply pressure systems which are normally restricted to

    commercial installations.

    Propane Gas (LPG - Liquid Petroleum Gas) Typical propane supply pressure for residentia

    buildings is 11 in. w.c. (20.55 mmHg) set at theregulator outside the building. Higher supply pressureswill allow reduced tubing size. Check with your propane supplier and local building code authority.

    Determine the total capacity for all appliances planned in the installation. The BTU equivalents for

    naturalgasorpropaneow(CFH)canbeobtainedfromthelocalgasutilityorpropanesupplier.Fo

    natural gas, one cubic foot per hour (1 CFH) is approximately 1,000 BTU per hour. For propane,

    one cubic foot per hour is approximately 2,500 BTU per hour. Check with the local utility for actua

    BTU content of the gas. The sizing tables in chapter 7 of this manual can be used for correctly

    sizing DiamondbackCSST.

    toolS For inStAllAtion

    Table 4-1

    General Tool ListTool Name Application

    Open End Wrench Forassemblyofttings

    Adjustable Wrench For gas outlet devices and manifold attachments

    Pipe Wrench Forattachmentsoftubingtottingsandmanifoldbody

    Screw Driver Formountingofterminationttingsandstrikerplates

    Hammer For fastening supports, striker and termination plates

    Drill For boring holes through wood or metal framing.

    Tubing Cutter To Cut CSST to Proper Length

    Utility Knife To Cut CSST Jacket to Proper Length

  • 7/29/2019 flexible gas piping

    22/60

    18

    PrEcAutionS

    Precautionsmustbetakentoensurethatanyexposedexiblepipingisnotdamagedorabusedduring

    building construction. All system hardware should be stored in a secure, dry location prior to installation.

    1. OnlycomponentsprovidedbyMetal-FaborspeciedaspartoftheDIAMONDBACKpipingsystem

    are to be used in the installation (black iron pipe is approved).

    DO NOT use DIAMONDBACK tubing or ttings with tubing or ttings of any other CSST

    manufacturerwhen installing a newsystem. IntermixingofCSST tubingand tting componentsbetween CSST manufacturers is prohibited in a new installation.

    2. Ends of the tubing are to be temporarily capped, plugged, or taped closed prior to installation and

    pulling through structure to prevent entrance of dirt, or other debris.

    3. Contact with sharp objects or harmful substances such as uxesusedforsolderingcoppertubesand

    acid based cleaners such as muriatic acid used for cleaning brickwork is to be avoided. Contact with

    any chemicals containing chlorides must be followed by thorough rinse and wipe dry.

    4. Unduestressorstrainonthetubingorttingsistobeavoided.

    Bending exiblegaspiping isone featurewhich contributes tothespeed ofinstallation.The

    recommended bend radius for general routing is 3 (76), multiple tight bends can restrict the gas

    owandincreasepressuredrop.Caremustbetakentoavoidsharpbends,stretching,kinkingor twisting of tubing. The tightest bend allowed for each size of DIAMONDBACK is shown in

    Table 4-2. Typical locations requiring tight bends are termination mount installations in hollow

    stud walls.

    Table 4-2

    Bending Radii

    Part No.Tubing

    Size

    Absolute

    Minimum

    Bend Radius

    Recommended

    Installed Bend

    Radius

    375DFT 38 (10) 1316 (21) 3 (76)

    500DFT 12 (13) 1 (25) 3 (76)

    750DFT 34 (19) 1 316 (30) 3 (76)

    1000DFT 1 (25) 1 1316 (46) 5 (76)

    1250DFT 1 14 (32) 2 38 (60) 6 (76)

    R

    TUBING ALONE

    MINIMUM BEND RADIUS

  • 7/29/2019 flexible gas piping

    23/60

    19

    HorizontAl runS And SuPPorting

    AllhorizontalrunsshallbesupportedasspeciedinTable 4-3 below.

    Tubing that runs parallel to the joists should be supported to the center of the vertical face at least

    3(76)fromtheoororceiling.(FIG. 4-14 on Page 25)

    Tubing that runs perpendicular to the joists should be supported, preferably routed through drilled

    holesinthejoistsorinsideanI-beamange.( FIG. 4-16 on Page 25)

    It is acceptable for CSST to lie directly on ceilings capable of supporting the CSST such as

    dropped ceilings and sheetrock.

    VErticAl runS And SuPPort

    The spacing between supports on vertical runs shall not exceed 10 ft. (3.05m)

    Unconcealed The tubing shall be supported in a workman like manner with piping straps

    tubing clips, bands, brackets or hangers suitable for the size and weight of the tubing. Standard

    support materials such as metal, plastic and wood are acceptable.

    Concealed It is recommended that concealed vertical tubing be as unconstrained as

    possible to avoid future puncture threats such as nails and screws.

    4.2 Fitting ASSEMBlY

    MAKing Fitting connEctionS to FlExiBlE gAS PiPing

    1. Cut tubing to length:

    Determine the proper length of the tubing and leave some extra in case it needs to be trimmed

    in the future. Use a standard tubing cutter equipped with a sharp (preferably hardened steel)

    cutting wheel. Whenever possible, cut a straight section of tubing that hasnt been bent too much.

    Remember that the DIAMONDBACK is much thinner and much harder than copper tubing.

    Cut through the polyethylene tubing jacket. The cut must be centered in a convolution (valley)

    between two corrugations. Use full, circular cutting strokes continuing in the same directions asstarting in. When the wheel has cut through the jacket and is in contact with the stainless steel it

    is important to slightly tighten the cutting wheel after a revolution or two for an even cut around

    thecircumference.Thetubingmayattenoutifthecutteristightenedtoofast.

    Taking a little time doing this procedure correctly can save time during later procedures.

    When the majority of the tubing has been severed the tubing cutter will not make anothe

    revolution correctly and a small portion of the DIAMONDBACK will remain attached. Remove

    the tubing cutter, gently open and close the tubing where the cut was made. Within seconds the

    remaining CSST still attached will sever. If the cut is too deformed it can easily be trimmed back

    an inch or so following the directions above.

    Table 4-3

    Horizontal or Inclined Runs Support Spacing

    Part No. Pipe Size Spacing of Supports

    375DFT 38 (10) 4 ft. (1.22m)

    500DFT 12 (13) 6 ft. (1.83m)

    750DFT 34 (19) 8 ft. (2.44m) USA, 6 ft. (1.83m) Canada

    1000DFT 1 (25) 8 ft. (2.44m) USA, 6 ft. (1.83m) Canada

    1250DFT 114 (32) 8 ft. (2.44m) USA, 6 ft. (1.83m) Canada

  • 7/29/2019 flexible gas piping

    24/60

    20

    2. Strip Jacket:

    Using a utility knife, strip the jacket back to the middle of the third convolution (valley) from the end

    of the tubing. The utility knife and the cut tubing ends are very sharp, Use caution when cutting

    the jacket and handling the tubing.

    3. Install Split Rings:

    Slide the seal nut over the end of the tubing, female side facing toward the tubing end. Place thesplitringsintherstconvolution(valley)attheendofthetubing.Ifthetubingroundnessdoesnt

    match the round of the split rings, gently squeeze the split rings together with pliers, this will round

    outthetubing.Thesplitringsmayhaveagapbetweenthem;thisisacceptablesincetheydonot

    form part of the seal. Pull the seal nut towards the end of the tubing and capture the split rings in

    the convolution. If the nut doesnt pass over the tubing, gently squeeze the split rings with pliers

    toroundoutthetubingorturnthesplitringsoverforacleaneredge.Ifthettingisreattached

    more than three times or the nut can not be pulled over the split rings then the split rings must be

    replaced.Packetsofsplitringsareavailableandtheremainingttingpartscanbereused.

    4. Wrench Fitting

    Place the male adapter into the seal nut and engage the threads. (Notice that the Diamondbackttingsaredesignedtoformaleakproofsealonthestainlesssteeltubingasthettingandseal

    nut are tightened.)Using theappropriate wrenches, tighten the ttinguntil themale adapter

    bottomsoutandtheresistancetotighteninggreatlyincreases.Thearehasnowbeencreated

    onthetubingend.(Removingthemaleadapterwillallowavisualconrmation.)

    NOTE:Ifthettingistobeconnectedtopipethread,threadthepipejointrst.Thentorquethe

    ttingtothetubingbytighteningthenut.

    ALSO: Whenatting isconnected toa termination outlet.First, slide the termination ange

    ontothetubing.Second,installandtorquetheterminationtting.Third,threadthetermination

    angeontotheterminationsealnut.Fourth,securelyfastentheterminationangetothedesired

    position.Alwayssecuretheterminationsealnuttotheterminationangetightlytoavoidfuture

    twisting of the CSST.

    5. Final Torque

    Tightensealnutandtting to the torquevaluesinTable 4-4 below. The actual seal is metal

    to metal (brass &stainless steel). If the tting cannotbemade to seal applying torqueper

    Table 4-4 below, Do Not Continue To Tighten The Assembly. Disassemble the assembly and

    inspectthesealingsurfaces.Cleanbothsealingsurfacesandreassemblethetting.Ifnecessary,

    thetubingcanbetrimmedandthettingreattached.

    Table 4-4

    Tube Part No. Pipe Size Fitting Part No. Required Torque375DFT 38 (10) 375DMF 45 ft-lb.

    500DFT 12 (13) 500DMF 50 ft-lb.

    750DFT 34 (19) 750DMF 60 ft-lb.

    1000DFT 1 (25) 1000DMF 70 ft-lb.

    1250DFT 114 (32) 1250DMFPre-Assemble: 60 ft-lb.

    Final: 80 ft-lb.

  • 7/29/2019 flexible gas piping

    25/60

    21

    4.3 routing

    run locAtion

    Runs can be located several places within the building. Depending on local building codes, DIAMONDBACK

    tubing can be routed:

    Beneath, through, and along side oor joists Consideration should be given to future

    constructionpossibilities.InunnishedbasementsitispreferredtorouteCSSTthroughratherthan

    below or beneath joists for the protection of the DIAMONDBACK. On top of ceiling joists in attic spaces Considered choice location in areas where slab-on-grade

    construction is prevalent.

    Inside wall cavities Preferred for vertical sections of piping rather than horizontal sections.

    Through conduit embedded in concrete oors and walls When runs must be buried or embedded

    in concrete DIAMONDBACKTM shall be routed within a non-metallic, watertight conduit which has an

    inside diameter at least 12 (13) larger than the outside diameter of tubing. No DIAMONDBACK

    joints are permitted within the conduit.

    To gas replaces DIAMONDBACK can be used to deliver gas directly to the valve of a gas

    replace.This isapproved indecorativeandheatgeneratinggasreplacesaswellasin allfue

    replacesutilizinggaslogsonly.Theyellowpolyethylenetubingjacketandrubbero-ring(ifsupplied)mustberemovedwhenDIAMONDBACKCSSTisroutedinsideofagasreplacerebox.

    DIAMONDBACKTM CSST must NOT be routed inside the rebox of a replace that can be used

    for burning solid fuel (i.e. wood or coal).

    Installation clearance holes for routing the piping through studs, joists, plates, etc. shall have a

    diameter12 (13) larger than the outside diameter of the piping. When a structural member must be

    drilled, conformance to building codes must be followed (See Table 4-5).

    BrAncHing

    Avoidbranchingifpossible.Thisminimizesthenumberofjointsinthesystem.Instead,install individual runs to each appliance outlet.

    Whenbranchingisnecessary,useastandardNPTClass150malleableirontee,theoutletsof

    whichcanbeconnectedtosuitablesizesofDIAMONDBACKttings.

    Table 4-5

    Installation Clearance Holes

    Tubing Size Drill Hole Size

    38 (10) 1 18 (29)

    12 (13) 1 38 (35)

    34 (19) 1 58 (41)

    1 (25) 1 78 (48)

    114 (32) 2 18 (54)

  • 7/29/2019 flexible gas piping

    26/60

    22

    BorEd HolES

    In locations where DIAMONDBACK is installed through bored holes in joists, rafters, or wood

    members, holes shall be bored so that the edge of the hole is not less than 2 (51) from the

    nearest edge of the wood member. Where this distance cannot be maintained at any point,

    the tubing shall be protected by a DIAMONDBACK striker plate of the appropriate length

    and width installed in accordance with the striker plate instructions in this manual. The

    diameter of the bored holes shall be a minimum of 12 (13) larger than the outside diameter

    ofthetubingjacketunlesstheholesizeisinconictwithlocalbuildingcodeswhichshallprevail. The size of the hole drilled through top plates, top frame members, and sole plates, to allow

    the vertical passage of the tubing, shall not exceed 12 of the width of the member. The hole should

    be bored through the center of the member (See FIG. 4-6 below).

    Where sole plates are cut for tubing, the width of the cut shall be 12 (13) larger than the

    outside diameter of the tubing jacket but not greater than 2 18 (54), and the tubing must be protected

    with a DIAMONDBACKTM striker plate of the appropriate length and width installed in accordance

    with this manual (See FIG. 4-6).

    Where a hole is to be bored in a joist, the hole should be located at the centerline, otherwise no

    closer than 2 (51 mm) from the nearest edge of the joist, and the hole diameter shall not exceed13 the depth of the joist (See FIG. 4-7 below).

    Where holes are to be bored in non-bearing vertical members of the wall framing, the size of such

    holes shall not be larger than 60 percent of the width of the member (See FIG. 4-8).

    Where holes are to be bored in load bearing vertical members of the wall framing, the size of such

    holes shall not be larger than 40 percent of the width of the member. Holes up to 60 percent

    of the members width are permitted if the members are doubled. No more than two

    successive double bored members are permitted (See FIG. 4-9 Page 22).

    D

    D/3MAX.TYP.

    2 (51) MIN.

    D/2

    2 (51)MIN.

    PREFERRED LOCATION

    2X4 W/2

    W

    TOP PLATE

    SOLE PLATE

    2 18(54)MAX.

    CUT WIDTH

    STUD

    2X4

    W/2MAX.TUBING HOLE

    FIG. 4-6 Holes and Cuts in Top and Sole Plates FIG. 4-7 Holes in Wood Joists

  • 7/29/2019 flexible gas piping

    27/60

    23

    1 12 (38)

    3 12 (89)

    58(16)

    MIN.

    2 18 16 MIN.

    HOLES UP TO 60%

    OF STUD WIDTH

    NON-BEARING WALL

    (I.E. 3.5 x 0.6 = 2.1)

    (I.E. 89mm x 0.6 = 53mm)

    2 x 4 1 12 (38)

    3 12 (89

    HOLES UP TO 40%

    OF STUD WIDTH

    BEARING WALL

    (I.E. 3.5 x 0.4 = 1.4)

    (I.E. 89mm x 0.4 = 36mm)

    2 x 4

    58 (16)

    MIN.

    1 38 (35)

    MIN.

    diAMondBAcK tHrougH MEtAl FrAMing - The installation instructions for metal framed

    structures are the same as wood framed structures with the following exception.

    When DIAMONDBACK CSST passes through metal members it shall be protected by one of the

    following methods:

    1. Bushings securely fastened in the opening of the metal member.

    2. Grommets securely fastened in the opening of the metal member.

    3. A minimum of four wraps of #10 mil. duct tape.

    The installer shall insure that no physical contact occurs between the metal member and the

    DIAMONDBACK tubing.

    guidElinES For inStAllAtion oF concEAlEd cSSt Fitting

    General Provisions

    It is not the intent of these guidelines to encourage the use of concealed tubing joints. Concealed

    jointsshouldbeavoided,andonlyusedwhentheinstallationofahiddenttingistheonlyreasonable solutiontoadifcultsituation.Likeblackironpipesystems,anyjointcanbeapotentialleaksite,and

    system designers and installers should strive to minimize the total number of joints in any piping system

    regardless of their location.

    These guidelines address known installation situations which typically require the use of a concealed

    tting.Theseguidelinesdonotsupersedelocalbuildingorplumbingcodes,butratherofferalternativeinstallation practices for consideration by the local authority having jurisdiction.

    Denitions

    TheNationalFuelGasCode2002(NFPA54)denesconcealedgaspipingasGaspipingthat,whenin placeinanishedbuilding,wouldrequireremovalofpermanentconstructiontogainaccesstothepiping.

    FIG. 4-8 Holes In Non-load Bearing Walls FIG. 4-9 Holes In Load Bearing Walls

  • 7/29/2019 flexible gas piping

    28/60

    24

    Subsection 3.4.6 stipulates a similar exception forReconnections.

    The American National Standard For Fuel Gas Piping Systems Using Corrugated Stainless Steel Tubing

    (CSST) ANSI/CSA LC-1 states under subsection 1.1.4 the following:

    Thisstandardincludescriteriatoestablishthesuitabilityofconcealedmechanicaltubettingsforuse

    with concealed gas piping.

    Exclusions

    Theterminationttingisnotaconcealedjoint,andtherefore,isnotaffectedbytheseguidelines.The

    terminationttingshallbeinstalledaccordingtotheinstructionsinthismanual.

    Manifold stations, which include the multiport manifold and pressure regulator, shall not be installedinaconcealedlocationregardlessofthequalicationsofthetubingttings.

    Fittings installed inside accessible enclosure boxes, for such items as quick connect gas outlets or

    replaceshut-offvalves,areexemptedfromtheseguidelines.

    ExAMPlES oF concEAlEd FittingS in nEw inStAllAtionS

    Fireplace Logs

    Theconnectiontoavalvecontrollinggasowtoa replaceappliancecanbehiddenwheninstalledasshown in FIG. 4-10.Theconcealedtubingttingcanbeinstalledbeneaththeoor,orhearth,orinsidethe

    brickworkofthereplace.Automaticorremotecontrolvalvesinstalledinsideahollowwallcavityadjacent

    tothereplaceshallrequiretheuseofanaccessibleenclosurebox.

    Multiple Gas Outlets

    When multiple gas outlets are supplied from a single run of CSST, each downstream outlet branch can

    beconnectedtothemainrunusingatee-typettingwhichcanbelocatedinaconcealedlocationas

    shown in FIG. 4-11.

    VALVE KEY

    BLUE FLAME

    GAS VALVE

    SUB-FLOOR

    CSST

    BLACK IRON PIPE

    STRIKER

    PLATE

    SILL PLATE ON

    FLOORING

    FINISHED CEILING

    IN BASEMENT TEE

    CSST

    FIG. 4-10 Fireplace Valve Installation FIG. 4-11 Multiple Outlets Along Main Tubing Run

    NFPA 54 goes on in subsection 3.4.2, Connection in Original Installations,todenethelimitationsand

    exceptionsontheuseofconcealedttings:

    When installinggaspiping that is tobe concealed,unions, tubing ttings, running threads, right

    and left couplings, bushings, swing joints, and compression couplings made by combinations of

    ttingsshallnotbeused.

    Exception No. 1: Jointing tubing by brazing shall be permitted.

    Exception No. 2: Fittings listed for use in concealed spaces that have been demonstrated to sustain,without leakage, any forces due to temperature expansion or contraction, vibration or fatigue based

    on their geographical location, or operation shall be permitted to be used.

  • 7/29/2019 flexible gas piping

    29/60

    25

    ExAMPlES oF concEAlEd FittingS in ModiFicAtionS to ExiSting inStAllAtionS.

    NewCeilingsinUnnishedRooms/Basements

    DIAMONDBACK ttings originally installed in accessible ceiling locations can be concealed

    at a later date in the event that a ceiling is installed. Precautions shall be taken to ensure

    that the newly concealed ttings and tubing are adequately protected from accidental puncture in

    accordance with Metal-Fabs instructions for the installation of protective devices.

    Extensions to Existing Tubing Runs

    A concealed tubing run may be modied to permit an extension of another appliance

    locationprovidedthereissufcientcapacitytosafelysupplybothappliancesatthesame time.Ifan

    accessiblelocationforthemodicationisnotavailable,theexistingtubingruncanbemodiedasshown

    in FIG. 4-12,whichwillresultinaconcealedttingbehindthewallboard.

    4.4 ProtEction

    Theexiblegaspipingmustbeadequatelyprotectedfrompuncture,shear,crushorotherphysicaldamage

    threats. The tubing shall be protected at points of support and when passing through structural members such

    as studs, joists and plates in accordance with this section. Protection is required whenever the tubing is

    concealed and constrained and within 3 (76) of a potential threat. If the tubing requires protection, the

    following measures should be taken.

    1. Install shielding devices, i.e. striker plates to protect the tubing from penetration by drill bits, nails

    screws, etc. (See FIG. 4-13) in those areas where the tubing will be concealed and will not be free to

    move and avoid such puncture threats.

    a. At support points and points of penetration less than 2 (51) away from any edge of astud, joist, plate, etc. shielding is required at the area of support and within 5 (127) of each side (if

    appropriate). Use a half striker or a full striker plate in these locations.

    b. At support points and points of penetration 2 (51) to 3 (76) from any edge of a stud, joist

    plate, etc. shielding is required throughout area of support. Use a quarter striker plate in these

    locations (See FIG. 4-15).

    c. Install oppy steel conduit in locations where striker plates are impractical such as

    termination outlets and stub outs, short tubing runs and where tubing is routed

    horizontally between studs (See FIG. 4-14).

    ALSO NOTE MINIMUM DISTANCES OF FLOPPY STEEL CONDUIT IN FIG.4-21 & 4-22

    TERMINATION

    FITTING

    TEE FITTING

    STRIKER

    PLATE

    MODIFIED INSTALLATIONEXISTINGINSTALLATION

    FIG. 4-12 Extension of Existing Tubing Run

  • 7/29/2019 flexible gas piping

    30/60

    26

    2. The best protection is to install the tubing in those out of the way areas where testing has shown no

    protection is necessary, for example:

    a. Where the tubing is supported more than 3 (76) from any outside edge of a stud, joist, plate, etc. or

    wall surface (See FIG. 4-16).

    b. Where any non-restrained tubing can be displaced from the direction of potential penetration at

    least 3 (76).

    c. When tubing is supported under the joists in basements or crawl spaces and is not concealed by

    wallboard or ceilings.

    5 (127)

    5 (127)

    5 (127)

    26 (660)

    NAIL

    (NON-RESTRAINED

    TUBING LENGTH SAFE

    FROM PUNCTURE)

    ADEQUATE DISTANCE

    FOR ESCAPE

    FULL STRIKER PLATE

    WALL

    TUBING

    HALF STRIKER PLATE

    PROTECTED AREA, LESS

    THAN 3 FT. (9.84m)

    INTERIOR

    WALLBOARD

    MOUNTING BLOCK

    TYPICAL WALL STUD

    (WOOD OR METAL)

    TERMINATION FITTING

    STRIPWOUND

    METAL CONDUIT

    STRIKER PLATES

    TUBING

    FIG. 4-13 Long Unsupported Tubing Runs, over 3 ft.

    (9.84m), Within an Interior Wall Partition

    FIG. 4-14 Short Unsupported Tubing Run, under 3 ft. (9.84m),

    From an Outlet Device Within a Wall Partition or

    Horizontal Run Between Studs

    3 (76) OR LESS

    FLOOR TUBING

    SUPPORT

    JOISTS

    QUARTER STRIKER PLATES

    FIG. 4-15 Shielding Required for Tubing Running Through

    Joists Within 3 of a Potential Nailing Surface

    FLOORTUBING

    WOODEN

    BLOCK

    G R E A T E R

    THAN 3 (76)

    SUPPORT

    JOISTS

    FIG. 4-16 No Shielding Required for Tubing Running Through

    Joists Greater Than 3 (76) From a Potential Nailing

    Surface

    GREATER

    THAN 3 (76)

  • 7/29/2019 flexible gas piping

    31/60

    27

    outdoor inStAllAtionS

    General Provisions

    The following additional instructions regard the use of DIAMONDBACK in systems in which

    portions of the piping are exposed to the outdoors as required to make connections to gas meters

    or gas appliances, which are attached to, mounted on, or located in close proximity to the building

    structure.

    Wherelocalcodeconictswiththismanual,localcodetakesprecedence.

    The external protective covering shall remain intact as much as practical for the given installation.

    Any portions of exposed stainless steel tubing shall be protected from the outdoor elements. Exposed

    tubingandttingconnectionshallbewrappedwithself-bondingsiliconetape.

    When installed along the side of a structure (between the ground and 6 ft. (1.83m) in an exposed

    condition, the DIAMONDBACK CSST tubing must be protected inside a conduit or installed in a

    location which will not subject it to crushing or puncture damage.

    DIAMONDBACK shall not be buried directly in the ground or directly embedded in concrete (e.g

    patio slabs, foundations and walkways). When burial or embedment is required, DIAMONDBACK

    shall be routed inside nonmetallic (e.g. PVC) conduit. The conduit shall be sealed at any exposed end

    to prevent water from entering.

    When installed in crawl spaces or underneath mobile homes, DIAMONDBACK shall be installed in

    accordance with Metal-Fabs standard installation instructions. No special precautions are required

    beneath the structure.

    When using a termination plate for an outdoor application, all four mounting fasteners shall be

    secured and tight.

    4.5 MEtEr HooK-uPS

    Meters which depend on the service and house piping for support shall not be directly connected

    outdoors with DIAMONDBACK. As shown in FIG. 4-17 & 4-18, steel pipe shall be used to connectthe meter outlet to the Outdoor Termination Fitting or Stub-Out on the exterior wall of the structure or

    to a transition from pipe to DIAMONDBACKTM located inside the structure.

    Meters which are independently supported with a bracket can be directly connected outdoors with

    DIAMONDBACK as shown in FIG. 4-19. If practical, direct connections shall include a 3 (76) to 6

    (152) loop of tubing to accommodate differential settling and meter movement.

    No mechanical protection is required for outdoor meter connections higher than 6 ft. (1.83m) Note

    Consult local code authority.

  • 7/29/2019 flexible gas piping

    32/60

    28

    NOTE: DIAMETER OF HOLE SHOULD BE AT LEAST12 (13) GREATER THAN O.D. OF TUBING AND

    SHOULD BE SLEEVED IN ACCORDANCE

    WITH LOCAL BUILDING CODE (IF APPLICABLE)

    NOTE: DIAMETER OF HOLE SHOULD BE AT LEAST 12 (13) GREATER THAN O.D. OF TUBING

    AND SHOULD BE SLEEVED IN ACCORDANCE WITH LOCAL BUILDING CODE

    (IF APPLICABLE)

    SEALANT

    3 - 6

    (76 - 152)

    RADIUS

    3 - 6

    (76 - 152)

    RADIUS

    SEALANT

    SEALANT

    FIG. 4-17 Meter Connection For Pipe Supported Meter

    FIG. 4-18 Pipe Supported Meter

    FIG. 4-19 Bracket Supported Meter

    HOUSE SERVICE

    REGULATOR

    SLEEVE

    (IF REQUIRED)

    SEALANT

    (TYPICAL)

    DIAMONDBACK

    TERMINATION FITTING

    OR STUB-OUT

    SERVICE LINE

    METER

    NOTE: DIAMETER OF HOLE SHOULD BE AT LEAST 12 (13) GREATER THAN O.D. OF TUBING

    AND SHOULD BE SLEEVED IN ACCORDANCE WITH LOCAL BUILDING CODE

    (IF APPLICABLE)

  • 7/29/2019 flexible gas piping

    33/60

    29

    4.6 APPliAncE connEctionS

    inStAllAtion oF tErMinAtion outlEt

    A DIAMONDBACKterminationoutletttingorstub-outttingshallbeinstalledandsecuredtothestructureatallCSSToutletsusedformovableappliancesandquick-disconnectdevices.Thettingsaredesignedto

    simplify the installation of gas connections for movable appliances and to minimize the need for concealed

    ttings.Thettingshallbesecurelyfastenedinplaceduringrough-in.Itmaybeattachedtoabracespanning

    betweenstudsforawalllocation,ordirectlytotheoor.Itmayalsobemountedwithaterminationoutlet

    bracket, which is nailed or screwed to the stud (See FIG. 4-20).

    APPliAncE connEctionS

    Movable appliance connections,suchasrangesanddryers,shallbemadeusingapprovedexible

    appliance connectors (See FIG. 4-21).

    Fixed appliance connections may be directly connected to the DIAMONDBACK tubing. When the

    xedapplianceislocatedinasecure,dedicatedspace,suchasabasement,attic,garageorutilitycloset

    theexiblepipingmaybedirectlyconnectedtotheapplianceshut-offvalvewithoutinstallationofaange

    ttingorexibleapplianceconnector(See FIG. 4-22).

    STRIPWOUND

    METAL CONDUIT

    NAIL OR SCREW

    WALL STUD

    TERMINATION

    OUTLET BRACKET

    BODY

    CAP

    NUT

    WALL STUD

    TERMINATION

    OUTLET BRACKET

    STRIPWOUND

    METAL CONDUIT

    GAS LINE TUBING

    NUT

    CAP

    BODY

    STRIPWOUND

    METAL CONDUIT

    JOIST

    FIG. 4-20 Termination Fitting Mounting Method

    TOP VIEW

    FLUSH WALL MOUNT

    FRONT VIEW

    FLUSH WALL MOUNT

    FLOOR MOUNT

  • 7/29/2019 flexible gas piping

    34/60

    30

    TYPICAL WALL STUD

    (WOOD OR METAL)

    EXTERIOR

    SHEATHING

    STRIPWOUND

    METAL HOSE

    TERMINATION OR

    STUB-OUT FITTING

    (CROSS BRACE

    MOUNTED)

    MOUNTING BLOCKCROSS BRACE

    6 (152)

    PROTECTED

    AREA

    INTERIOR

    WALLBOARD

    INTERIOR

    WALLBOARD

    TYPICAL WALL STUD

    (WOOD OR METAL)

    EXTERIOR

    SHEATHING

    STRIPWOUND

    METAL HOSE

    TERMINATION OR

    STUB-OUT FITTING

    (CROSS BRACE

    MOUNTED)

    MOUNTING BLOCK

    PROTECTED

    AREA, LESS THAN

    3 FT (.91m)

    STRIKER PLATES

    TYPICAL INSTALLATION FOR METER, BBQ GRILL, PAD MOUNTED EQUIPMENT

    FIG. 4-23 Standard Termination or Stub-Out Fitting Mounted On Outside Wall

    6 (152)

    PROTECTED

    AREA

    MOVABLE

    GAS

    APPLIANCE

    SHUT-OFF

    VALVE

    STRIPWOUND

    METAL HOSE

    CSST TUBING

    GAS CONNECTOR

    FIG. 4-21 Stainless Steel Gas Connector Connection to a

    Movable Gas Appliance

    4 (102)

    MIN.

    STRIPWOUND

    METAL HOSE

    WALL

    CSST TUBING

    WALL STUD

    TUBE

    CLAMP

    TUBING

    FITTING

    SHUT-OFF

    VALVE

    FIXED

    GAS

    APPLIANCE

    8 MIN. (203)

    LENGTH

    FIG. 4-22 Direct Tubing Connection to a Fixed Gas Appliance

    Shut Off Valve

  • 7/29/2019 flexible gas piping

    35/60

    31

    OUTDOOR

    WOODEN

    DECK

    CONNECTION OF CSST GRILL CONTROLS/SHUT

    OFF VALVE SHOULD BE IN ACCORDANCE WITH

    THE MANUFACTURERS INSTRUCTIONS.

    NOTE: DIAMETER OF HOLES SHOULD BE AT

    LEAST 12 (13) GREATER THAN O.D. OF TUBING

    AND SHOULD BE SLEEVED IN ACCORDANCE

    WITH LOCAL BUILDING CODE (IF APPLICABLE).

    NOTE: CSST SHOULD BE INSTALLED ONLY ON INSIDESURFACES OF JOISTS AT THE CENTERLINE.

    FIG. 4-24 BBQ Quick-Connect Outlet FIG. 4-25 Elevated Deck Direct Connection

    OUTSIDE WALL

    ENCLOSUREBOX*

    M.B. STURGIS

    QUICK CONNECT

    OUTLET

    STRIKER PLATES

    FLOOR

    JOIST

    SUBFLOOR

    STRIPWOUND

    METAL HOUSE

    INSIDE WALL

    *SEE MANUFACTURERS INSTRUCTIONS FOR ENCLOSUREBOXMOUNTINGANDQUICKCONNECTINSTALLATION

    Barbecue Grills

    Movable grills shall be connected using an approved outdoor appliance connector which shall be

    attachedtotheDIAMONDBACKsystemateitheraterminationorstub-outttingasshownin FIG

    4-23 or a quick-connect device, such as the M.B. Sturgis gas convenience outlet shown in FIG. 4-24

    The M.B. Sturgis gas convenience outlet shall be installed in accordance with the manufacturers

    instructions.

    Permanently mounted grills located on decks shall be connected to the DIAMONDBACK systemas shown in FIG. 4-25 and in accordance with Metal-Fabs instructions. The outdoor portion of the

    DIAMONDBACK shall be supported against the side of any of the inside deck joists. If the elevation

    of the deck is below the top of the foundation, any exposed DIAMONDBACK shall be protected

    using conduit.

    Lights

    Permanently mounted gas powered lights located on decks shall be connected to

    the DIAMONDBACK system the same as permanently mounted grills as shown in

    FIG. 4-25, and in accordance with the manufacturers instructions.

    Yard mounted gas powered lights shall be connected to the DIAMONDBACK system as shown

    in FIG. 4-26. All DIAMONDBACK installed below grade shall be protected by nonmetallic conduitExposed ends shall be sealed against water entry.

    Infrared Heaters

    Infrared heaters mounted from ceilings and from walls of structures shall be connected

    to the DIAMONDBACK system as shown in FIG. 4-27, and in accordance with

    Metal-Fabs instructions.

  • 7/29/2019 flexible gas piping

    36/60

    32

    Pad Mounted Equipment

    Gas appliances mounted on concrete pads or bricks, such as heat pumps, air conditioners, pool

    heaters and NGV refueling systems, shall be connected to the DIAMONDBACK system at a

    terminationorstub-outttingusingeitherrigidpipeoranapprovedoutdoorapplianceconnectoras

    shown in FIG. 4-24 & 4-28.

    Roof Top Equipment

    No special mechanical protection of the tubing is required for connections to roof top equipment.

    Wheneverpossible,roofpenetrationsshallincludeanoutdoorterminationorstub-outttingandshallbe located within 6 ft. (1.83m) of the equipment to be connected as shown in FIG. 4-29. Long runs

    of tubing shall be supported with nonmetallic blocks every 4 ft. (1.22m) along its outdoor length, and

    raised above the roof (as shown in FIG. 4-30) a distance determined by local code/practice.

    DIAMONDBACK run vertically up the internal or external side of a building to the roof shall be

    protected in accordance with the General provisions of this manual. See vertical run section of this

    manual.

    STANDARD ELBOW

    SHUT OFF VALVE

    GAS CONTROLS

    HEATER

    HANGING

    RODS

    CEILING JOIST

    HEATER

    GAS

    CONTROLS

    MOUNTING

    BRACKET

    WALL STUD

    EXTERIOR

    ATTIC

    SPACE

    ROOF

    A) CEILING MOUNT

    (PROTECTED AREA)

    B) WALL MOUNT

    (PROTECTED AREA)C) WALL MOUNTED

    OUTDOORS

    STANDARD TERMINATION OR

    STUB-OUT FITTING

    BBQ GRILL PEDESTAL

    OR GAS LAMP POST

    90 ELBOW

    MANUAL SHUT OFF VALVE

    SEAL AGAINST

    WATER ENTRY

    PROTECTION REQUIRED UP TO

    6 FT (1.83m) ABOVE GROUND

    SMALL GAP BETWEEN

    CONDUIT AND FITTING

    IS PERMITTED

    CONNECTION OF CSST TO EQUIPMENT GAS CONTROLS SHOULD BE IN

    ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS

    FIG. 4-26 Ground Level Buried Connection FIG. 4-27 Ceiling Or Wall Hung Infrared Heater Car Ports/Patios/

    Decks

  • 7/29/2019 flexible gas piping

    37/60

    33

    FIG. 4-30 Long Outdoor Connection To Mounted Equipment

    HUNG CEILING

    CSSTTUBING

    CLIP

    CONCRETE SLAB

    WATER PROOFING

    GAS

    APPLIANCESHUT OFF

    VALVE

    RIGID

    UP TO 6 FT.

    (1.83M)

    FIG. 4-28 Pad Mounted Gas Appliances FIG. 4-29 Short, 1-6 ft. (.30m-1.83m) Outdoor Connection To

    Roof Mounted Equipment

    CONCRETE PAD

    APPLIANCE

    CAP

    DRIP LEG

    STEEL PIPE OR APPROVED OUTDOOR

    APPLIANCE CONNECTOR

    SHUT OFF VALVE

    NOTE: DIAMETER OF HOLE SHOULD BE AT LEAST 12

    (13) GREATER THAN O.D. OF TUBING AND SHOULD

    BE SLEEVED IN ACCORDANCE WITH LOCAL

    BUILDING CODE (IF APPLICABLE).CSST

    PAD MOUNTED GAS APPLIANCE:

    - HEAT PUMP

    - AIR CONDITIONER

    - POOL HEATER

    - NGV REFUELING FOUNDATION WALL

    TERMINATION OR STUB-OUT

    WATER

    PROOFING

    GAS

    APPLIANCE*

    UNION

    SHUT OFF

    VALVE

    TYPICAL NONMETALLIC TUBING

    SUPPORT EVERY 4 FT (1.22m) TUBING

    ELEVATED** INCHES ABOVE ROOF

    CSSTTUBING

    CLIP

    SUSPENDED CEILING

    CONCRETE SLAB

    * WHENTHEEQUIPMENTMANUFACTURERREQUIRESTHEUSEOFAFLEXIBLECONNECTOR.

    ** HEIGHT OF ELEVATION BASED ON LOCAL PLUMBING/BUILDING REQUIREMENTS AND/OR WINTER ICE BUILDUP.

    4 FT (1.22m)

    TYP.

  • 7/29/2019 flexible gas piping

    38/60

    34

    CLAMP

    JOIST

    WALL

    STUD

    HANGERS

    4.7 MAniFold StAtionS

    inStAllAtion oF gAS diStriBution MAniFold ASSEMBlY

    Manifolds are installed where multiple tubing runs are made from a common location in a parallel

    arrangement.Themanifoldmaybemanufacturedfromaonepiece,blackironpipeorbrasscasting;oran

    all welded fabrication ofcarbon steel subcomponents or an assembly of approved, black iron pipe nipples

    and tees. Depending on the location and available space, different mounting arrangements are permitted.

    Amanifoldassemblymaybemountedonthesurfaceofaninteriorwall,betweenopenoor joists,inattic

    spaces, or within a partition wall inside a ventilated enclosure as shown in FIG. 4-34.

    The manifold assembly shall be installed in an accessible location where it can be inspected, maintained and

    serviced if repair or replacement is required. If manifold is located between wall studs behind an access door,

    then all penetrations by CSST shall be caulked or made gas resistant with grommets. Ventilation of manifold

    enclosure shall be into living area and not into wall space. Examples of manifold arrangements are shown in

    FIG. 4-31 through 4-33.

    TO APPLIANCE

    DIAMONDBACK

    FITTING

    PLUG (TEST PORT)

    UNION

    VENT LIMITER

    (MUST POINT UP)

    MINIMUM 10 PIPE DIAMETERS

    BEFORE CHANGING DIRECTIONS

    MAXTROL325-3L

    REGULATORDRIP LEG

    TEE (OPTIONAL)

    APPROVED VALVE

    DIAMONDBACK

    FITTING

    FROM GAS METER

    FIG. 4-31 Typical Regulator/Manifold Conguration When Using A Vent Limiter

    FIG. 4-33 Manifold Mounting MethodFIG. 4-32 Four-Port Manifold

  • 7/29/2019 flexible gas piping

    39/60

    35

    MAniFold And rEgulAtor StAtion

    The use of a central manifold and regulator station is recommended for elevated pressure systems which

    are typically installed in a parallel arrangement to take advantage of the capacity of the regulator, which is

    sufcient forseveralappliances.A four-portmanifold isavailablewith theDIAMONDBACKsystem,or

    the use of black iron pipe and tee fabricated manifolds is permitted with this system. The manifold/regulator

    station should be located near by the largest gas consuming appliances, typically the furnace or boiler and

    the water heater in order to allow short runs to these units. The manifold station may be contained in an

    enclosure box called a gas load center. Optional gas shut-off valves may be mounted on the manifold foeach appliance run (See FIG. 4-34).

    VENTILATED ENCLOSURE

    BOX

    REGULATOR

    CSST TUBING

    UNION

    SHUT-OFF VALVE

    FIG. 4-34 Gas Load Center

  • 7/29/2019 flexible gas piping

    40/60

    36

    4.8 PrESSurE rEgulAtorS

    rEgulAtorS For ElEVAtEd PrESSurE SYStEMS

    A tubing system used at gas pressures exceeding 0.5 psi (3.45 kPa) but serving appliances rated for 0.5

    psi (3.45 kPa) maximum, shall contain a pounds-to-inches regulator to limit the downstream pressure to no

    more than 0.5 psi (3.45 kPa). The regulator must incorporate a lock-up feature limiting downstream pressure

    to0.5psi(3.45kPa)undernoowconditions.Theregulatorshallcomplywiththeapplicableprovisionsof

    ANSI/Z21.80.

    Regulators used to reduce elevated system pressures for use by appliances must also conform to the

    following:

    1. Must be sized to supply the required appliance load (See Table 4-35 or 3-5).

    2. Must be equipped with an acceptable vent limiting device, supplied by the manufacturer, or be

    capable of being vented to the outdoors. The vent-limiting device can be used when the regulator is

    installed in a ventilated area. DIAMONDBACK ships all regulators with vent-limiters installed.

    3. Must be installed in accordance with manufacturers instructions. When a vent-limiter is used, the

    regulatormustbemountedinanuprightposition.Installtheregulatorproperlywithgasowingas

    indicated by the arrow on the casting.

    4. Must be installed in a fully accessible area with an approved shut-off valve ahead of regulator and a

    union provided to enable removal of regulator.

    5. For outdoor installations, remove the vent-limiter and mount regulator with the vent outlet pointing down

    to prevent the entrance of water.

    AdJuSting MAxitrol rEgulAtor

    The Maxitrol 325-3L, 325-5AL and O.A.R.A. Type 90, Type 95 pressure regulators are AGA/CGA Design

    Certiedfor2.0psig(13.79kPa)inletpressure.TheMaxitrol325-3L47and325-5AL48pressureregulators

    areAGA/CGADesignCertiedfor5.0psig(34.48kPa)inletpressure.Installations with a supply gas pressure

    exceeding 2 psi (13.79 kPa) require a tested and approved over pressure protection device for use with this

    regulator. The regulator shall comply with the applicable provisions of ANSI/Z21.80.

    The Maxitrol 325 pressure regulators capacity limits depend upon inlet pressure. Refer to FIG. 4-36A &

    4-36BforphysicalspecicationsfortheMaxitrol325seriespressureregulators.

    1. Regulators can be adjusted to deliver different outlet pressures within a limited range. The range is

    determined by the spring installed.

    2. Adjustment can be accomplished by rst removing the regulator seal cap to expose the

    adjusting screw on the top. Turning the screw clockwise will increase outlet pressure, turning it counter

    clockwise will decrease outlet pressure.

    3. If spring adjustment will not produce desired outlet pressure, check to make sure supply pressure is at

    least equal to desired outlet pressure plus pressure drop of the regulator. If supply pressure is

    adequate, consult factory if adjustment still cannot be made. Do not continue to turn regulator

    adjusting screw clockwise if outlet pressure readings do not continue to increase. This may

    result in over-ring due to loss of pressure control, should there be a subsequent increase in

    inlet pressure.

    Table 4-35

    Capacities and Pressure Drop Through Regulator

    Model 7 in. w.c. (13.08 mmHg) 0.5 psi (3.45 kPa) 0.75 psi (5.17 kPa) 1 psi (5.9 kPa)

    Maxitrol 325-3L 145 CFH 204 CFH 250 CFH 289 CFH

    Maxitrol 325-5AL 338 CFH 476 CFH 583 CFH 673 CFH

    Maxitrol 325-7L 690 CFH 972 CFH 1191 CFH 1375 CFH

    O.A.R.A Type 90 155CFH 220 CFH 280 CFH 310 CFH

    O.A.R.A. Type 95 359 CFH 504 CFH 627 CFH 719 CFH

  • 7/29/2019 flexible gas piping

    41/60

    37

    Spring Adjustment

    The 2 psi (13.79 kPa) system pounds-to-inches house line regulator can be adjusted with an outle

    pressure ranging between 7 and 11 in. w.c. (13.08 and 20.55 mmHg) The regulator must be adjusted

    according to the manufacturers recommended procedure. A pressure gauge mounted just downstream

    of the regulator can monitor the set pressure under various loads.

    The regulator is typically set when the system is operating at approximately 75 percent of maximum

    load.

    The average natural gas appliance is designed to operate at 3 to 4 in. w.c. (5.60 to 7.47 mmHg

    appliance manifold pressure, and a pressure difference of 1 to 2 in. w.c. (1.87 to 3.74 mmHg

    across the appliance regulator which will prevent slow regulator response. Therefore, the appliance

    regulator will operate best at 5 to 6 in. w.c. (9.34 to 11.21 mmHg) inlet pressure. In this case

    the 2 psi (13.79 kPa) system regulator should be reset to deliver approximately 8 to 10 in. w.c

    (14.94 to 18.68 mmHg) outlet pressure under load to allow for 3 in. w.c. (5.60 mmHg) pressure drop in

    the tubing. Regulators supplied by Metal-Fab are set for 7 in. w.c. (13.08 mmHg) output. Some appliances

    may have different inlet pressure requirements.

    AdJuSting MAxitrol/o.A.r.A. rEgulAtor

    rEgulAtor PErForMAncE

    Load Response

    A performance test should be conducted while operating all appliances at full load. This will test if

    adequate pressure is reaching each appliance under full-load conditions. To accomplish this, measure

    the line pressure at the appliance connection while operating the appliance.

    The inlet pressure for typical natural gas appliances should measure between 4 and 6 in.w.c. (7.47

    and 11.21 mmHg) under full-load conditions. If this pressure cannot be obtained a slight adjustment

    to the pounds-to-inches regulator may be necessary to increase the line pressure. (If the service

    regulator needs to be adjusted, call the gas utility.) Do not set any system regulator over the system

    design pressure, 2 or 5 psi (13.79 or 34.48 kPa).

    A

    BC

    PRESSURE ADJUSTMENT SCREW

    (UNDER SEAL CAP)

    MAXITROLMODEL325-3L

    O.A.R.A. TYPE 90

    PORTSIZE:1/2X1/2NPT

    VENT SIZE: 1/8 NPT

    MAXITROLMODEL325-5AL

    O.A.R.A. TYPE 95

    PORTSIZE:3/4X3/4NPT

    VENT SIZE: 3/8 NPT

    MODEL 325-7L

    PORTSIZE:11/4X11/4NPT

    VENT SIZE: 1/2 NPT

    (MUST BE VENTED OUTDOORS)

    FIG. 4-36A Maxitrol 325 Pressure Regulator

    O.A.R.A. Type 90/95 Pressure Regulator

  • 7/29/2019 flexible gas piping

    42/60

    38

    Model NumberSwing

    RadiusA B C

    325-3L/TYPE 90 3 (76) 3 12 (89) 4 14 (108) 3 78 (98)

    325-3LP 3 (76) 3 12 (89) 4 14 (108) 3 78 (98)

    325-5AL/TYPE 95 4 78 (124) 5 14 (133) 5 78 (149) 5 716 (138)

    325-7L 3 (