first day class introduction,temp

Upload: kirankumar-reddy

Post on 14-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 First Day Class Introduction,Temp

    1/63

    FIELD INSTRUMENTS

  • 7/30/2019 First Day Class Introduction,Temp

    2/63

    INTRODUCTION:-

    Instrumentation is a field of sciencewhich deals with measurement of

    different parameters and controlling

    them.WHAT IS FIELD ?

    INDUSTRY :Systematic Economic Activity that

    could be related to Manufacture/Service/Trade

  • 7/30/2019 First Day Class Introduction,Temp

    3/63

    Various measurements generally in an industry

    Fluid pressure

    Fluid flow rate

    The temperature of an object

    Fluid volume stored in a vessel

    Chemical concentration

    Machine position, motion, or acceleration

    Physical dimension (s) of an object

    Count (inventory) of objects

    Electrical voltage, current, or resistance

  • 7/30/2019 First Day Class Introduction,Temp

    4/63

    Automation

    Automation is the process of operationof machines and systems without

    significant human intervention by

    technical equipment to achieves

    performance superior to manual

    operation.

    (Automation is basically the delegation of human control function

    to technical equipment for) Increasing Productivity

    Increasing Quality

    Reducing Cost

    Increasing Safety in working conditions

  • 7/30/2019 First Day Class Introduction,Temp

    5/63

  • 7/30/2019 First Day Class Introduction,Temp

    6/63

    Elements of automation

    Process -a sequence of actions that take place in a set up or a plant where wewant to control.

    Instrument- it is a physical means to determine the quantity orvariable

    Sensors Primary Sensing Element orPSE :-A device that directly senses the

    process variable and translates that sensed quantity into an analog

    representation (electrical voltage, current, resistance, mechanical

    force, motion, etc )

    Transmitter:A device that translates the signal produced by a primary sensingelement (PSE) into a standardized instrumentation signal such as 3-15 PSI air

    pressure, 4-20 mA DC current, 0 10 V DC , into Field bus digital signal packet,

    etc., which may then be conveyed to an indicating / controlling device, or both.

    transducer :- A device that converts one standardized instrumentationsignal into another standardized instrumentation signal, and/or performs somesort of processing on that signal, often referred to as a converterexample:- P/I

  • 7/30/2019 First Day Class Introduction,Temp

    7/63

    Controller-A device that receives a process variable (PV) signal from aprimary sensing element (PSE) or transmitter, compares that signal to the

    desired value for that process variable (called the set point), and calculates

    an appropriate output signal value to be sent to a final control element

    (FCE) such as an electric motor or control valve.

    Final control element-A device that receives the signal from acontroller to directly influence the process.( Examples: variable-speed electric

    motor, control valve, electric heater. )

  • 7/30/2019 First Day Class Introduction,Temp

    8/63

    Instrumentation terms and their definitions(Industrial measurement and control systems terms and standards)

    Process Variable

    Set poin t

    Lower- and Upper-range values

    Automat ic mode

    Manual mode Measur ing signal

    Control l ing signal

  • 7/30/2019 First Day Class Introduction,Temp

    9/63

    Process Variable (PV): The specific quantity we are

    measuring in a process. Examples:pressure, level,

    temperature, flow, electrical conductivity, Ph,position, speed, vibration.

    Set po in t (SP):The value at which we desire the

    process variable to be maintained at. In other words,

    the target value of the process variable.

  • 7/30/2019 First Day Class Introduction,Temp

    10/63

    Lower- and Upper-range values (LRV and URV):

    the values of process measurement deemed to be

    0% and 100% of a transmitters calibrated range.

    Example - if a temperature transmitter is calibrated to

    measure a temperature starting at 300 degrees

    Celsius and ending at 500 degrees Celsius- 300

    degrees would be the LRV and 500 degrees the

    URV.

    Relating 4 to 20 m A signals to instrument variables

  • 7/30/2019 First Day Class Introduction,Temp

    11/63

    Autom at ic mode:When the controller generates an

    output signal based on the relationship of process

    variable (PV) to the set point (SP).

    Manual mode:When the controllers decision-

    making ability is bypassed to let a human operator

    directly determine the output signal sent to the finalcontrol element.

  • 7/30/2019 First Day Class Introduction,Temp

    12/63

    CASE STUDY

  • 7/30/2019 First Day Class Introduction,Temp

    13/63

    CHEMICAL REACTOR TEMPERATURE CONTROL SYSTEM

  • 7/30/2019 First Day Class Introduction,Temp

    14/63

    A steam-heated jacket envelops the reactor vessel ,transfers heat from the steam into the chemical solutioninside. the temperature transmitter, located near the

    bottom of the vessel. The special connector (solid dots with lines in between

    sometimes referred to as a fieldbus ) is used to connectthe temperature transmitter (TT) with the temperature

    indicating controller (TIC). The TT send a digitalelectronic instrument signal using digital bits ofinformation rather than an analog signal (such as 4 to20 m A or 3 to 15 PSI).

    The controller / TIC send an analog signal of 4 to 20

    milliamps DC shown by dashed line a device labeled TYwhich is a transducer to convert the 4 to 20 mAelectronic signal into a 3 to 15 PSI pneumatic signalwhich then actuates the valve.

  • 7/30/2019 First Day Class Introduction,Temp

    15/63

    Various instruments used in an

    industry Fluid pressure- can be measured by using basic sensing

    elements such as bourdon tube , capsule, bellow , diaphragm

    made of metal such as berelium copper and phosphorus bronze

    , silicon diaphram .

    Fluid flow rate- can be measured by using basic sensing

    elements such as orifice plate , venture tube , pitot tube . The temperature of an object- can be measured by using basic

    sesnsing elements such as, RTD, thermocouple, thermister.

    Fluid volume/level stored in a vessel- can be measured by using

    float level,hydro static pressure measurement,by bubbler

    system, by displacer method,ultra sonic method

    Chemical concentration

    Machine position, motion, or acceleration-

    Physical dimension (s) of an object

    Count (inventory) of objects

  • 7/30/2019 First Day Class Introduction,Temp

    16/63

    TYPES OF SENSORS

    All the sensors can be classified in to two types

    based up on the type of signals they provide.1. Digital instruments/sensors - instruments which

    provide digital signals are called digitalinstruments. Digital signal are in the form of low

    /high voltage /0 /1.{ absence / presence ofvoltage }.

    2. Analog instruments/sensors- instruments whichprovide analog out put signal are called analog

    instruments . Analog signal vary in continuousfashion and take on infinite number of values inany given range. The industrial standardsignals are 4 to 20 milliamp DC,0-10 volt DC,3-15PSI .

  • 7/30/2019 First Day Class Introduction,Temp

    17/63

    SOURCING AND SINKING

    CIRCUITS

    switch sinks current in from the LED through itsoutput terminal, through its transistor, and down

    to ground

  • 7/30/2019 First Day Class Introduction,Temp

    18/63

    switch sources current from the positive supply

    terminal

    through its transistor and out to the LED through its

    output terminal

  • 7/30/2019 First Day Class Introduction,Temp

    19/63

    CLOSE LOOP OPEN LOOP CONTROL OF PROCESS

    OPEN LOOP CONTROL

  • 7/30/2019 First Day Class Introduction,Temp

    20/63

    OPEN LOOP CONTROL

    The control system where the output variable does not have

    any influence on the input variable is called open loop control.Fig-At constant applied pressure, the volumetric flow can be maintained

    by the position of the control valve. Here the output variable is

    "volumetric flow" and the input variable is "control valve setting" .if the

    applied pressure fluctuates, the volumetric flow will also fluctuate.

    In other words one or more input variables of a system act on a processvariable and causes the possible deviations . e.g. disturbances

    caused by other in put variable (pressure) are not compensated for in

    the open loop control process. Thus, the characteristic feature of

    open loop control is an open action flow .

  • 7/30/2019 First Day Class Introduction,Temp

    21/63

    CLOSE LOOP CONTROL

  • 7/30/2019 First Day Class Introduction,Temp

    22/63

    CLOSE LOOP CONTROL

    It is a process where the controlled variable is

    continuously monitored and compared with thereference variable. The input variable for the systemis influenced to adjust the output variable to thedesired value despite any disturbing influences. This

    feedback results in a closed-loop action. In other words in a closed loop control system, the

    variable to be controlled is continuously measuredand then compared with a predetermined value

    (reference variable ). If there is a difference betweenthese two variables, adjustments are being madeuntil the measured difference is eliminated and thecontrolled variable equals the reference variable.Hence, the characteristic feature of closed loopcontrol is a closed action flow

  • 7/30/2019 First Day Class Introduction,Temp

    23/63

    Measurement is a process of assigning a number to

    an attribute (or phenomenon) according to a rule or

    set of rules.(Or )

    (it is an act of comparison between the un known

    quantity and predefined standard)

    MEASUREMENT

  • 7/30/2019 First Day Class Introduction,Temp

    24/63

    METHODS OF MEASUREMENT

    1. Direct measurement: Un known quantity isdirectly compared against a standard.

    2. Ind irect measu rement:measuring something

    by measuring something else

  • 7/30/2019 First Day Class Introduction,Temp

    25/63

    ELEMENTS OF MEASURING SYSTEM

  • 7/30/2019 First Day Class Introduction,Temp

    26/63

  • 7/30/2019 First Day Class Introduction,Temp

    27/63

    MEASUREMENT SYSTEMA measuring system consist of

    Sensor / primary sensing element - to sense andmeasure the process variable by producingdisplacement , change in resistance)

    Variable conversion element to convertdisplacement , change in resistancetoanalogous form( in to a voltage .. Etc exwhenpressure changes a strain transducer converts the deformationof the diaphragm into an electrical resistance change.)

    Variable manipulation / processing element toprocess analog signal and feed the data for thepurpose of display/control. All elements may bein one box / separated.

  • 7/30/2019 First Day Class Introduction,Temp

    28/63

    ACTIVE AND PASSIVE INSTRUMENTS

    ACTIVE INSTRUMENTS:- those which does notneed external power supply for excitation.

    PASSIVE INSTRUMENTS:- those which needexternal power supply for excitation

  • 7/30/2019 First Day Class Introduction,Temp

    29/63

    DIGITAL SENSORS

    A discrete variable or measurement refers to a

    true-or-false condition. Thus, aDiscreteSensor is one that is able to indicatewhether the measured variable is

    above or below a specified set point. DiGITAL sensors typically take the form of

    Switches andare less sophisticated than so-calledcontinuous sensors

  • 7/30/2019 First Day Class Introduction,Temp

    30/63

    NORMAL status of a switch

    Normal means not being pressed Electrical switch contacts are typically classified

    as

    normally-open

    normally-closed

  • 7/30/2019 First Day Class Introduction,Temp

    31/63

    VARIOUS DISCRETE SENSORS AND THEIR NORMAL POSITION

    Hand switch: no one pressing the switch

    Limit switch: target not contacting the switch Proximity switch: target far away

    Pressure switch: low pressure (or even a

    vacuum)

    Level switch: low level (empty)

    Temperature switch: low temperature (cold)

    Flow switch: low flow rate (fluid stopped)

  • 7/30/2019 First Day Class Introduction,Temp

    32/63

    INSTRUMENTS

    Analog electronic instrument-An instrument can be classified as

    analog if it produces an analog signal standard to communicateinformation, even if the internal construction and design of the instrument

    may be mostly digital in nature.

    analog current signals-in modern industrial instrumentationsystems the 4 to 20 milliamp DC is an analog signal standard ,this electric

    current is used to proportionately represent measurements or commandsignals. 4 milliamp current value represents 0% of scale, a 20 milliamp current valuerepresents100% of scale, and any current value in between 4 and 20 milliamps

    represents a commensurate percentage in between 0% and 100%.

    Most of the industrial control systems use at least two different 4-20 mA

    signals: one to represent the process variable (PV) and one to represent the

    command signal to the final control element.

  • 7/30/2019 First Day Class Introduction,Temp

    33/63

    4-wire or self-poweredTransmitter connection to plc/controller

    Power source near to transmitter method :- 4-20 mA DC

    electric current signals are used to communicate processmeasurement information from transmitters to controllers. Thetransmitter has two terminals for the 4-20 mA signal wires to connect,and two more terminals to connect a power source. The current signalfrom the transmitter connects to the process variable input terminalsof the controller to complete the loop. BUT process controllers areunable to directly accept milliamp input signals, however acceptsvoltage signals. For this reason a precision resistor of 250 ohmsconnected across the input terminals of controller convert the 4-20 mAsignal into a standardized analog voltage signal of 1 to 5 volts andfurther this voltage is converted in digital by ADC which can be

    processed by the controllermicro processor. Some models of controller use different voltage ranges so require

    different precision resistor values.

  • 7/30/2019 First Day Class Introduction,Temp

    34/63

    POWER SOURCE NEAR TO CONTROLLER METHOD

    As shown in the fig same 4 wire transmitter is powered through additional

    wires in the cable from a power source located in the same panel as the

    controller.

    Disadvantages:1. requirement of two more conductors in the cable

    2. cable will be larger in diameter

    3. more expensive for a given length.

    4. Cables requires larger electrical conduit to fit in to

    5. all field wiring panels will have to contain more terminal blocks.

    6. Note :-this method of connection can be used If no suitable electrical power source exists at the

    transmitter location.

  • 7/30/2019 First Day Class Introduction,Temp

    35/63

    2-wire (Loop-powered) Transmitter Method

    In this method both electrical power to transmitter and 4 to 20 milliamps DC

    analog information are communicated over the same two wires so called loop

    powered.

    Loop powered 2-wire transmitters circuitry acts as a current regulator, limiting current in

    the series loop to 4 to 20 ma DC representing the process measurement.

    The current source in loop-powered transmitter actually behaves as an electrical load.

    Power source being 24 volts DC, the maximum voltage dropped across the

    controllers 250 ohm resistor being 5 volts DC, the transmitter should alwayshave at least 19 volts available at its terminals to operate, while regulating

    current to signal the process measurement.

  • 7/30/2019 First Day Class Introduction,Temp

    36/63

    The transmitter is designed with sensing, scaling, and output conditioningcircuitry inside and run on less then 4 mA of DC current, and at a modest

    terminal voltage.

    The transmitter circuitry uses a transistor to shunt (bypass) extra current when

    needed to make the total current indicative of the process measurement

    If the transmitters internal operating current is only 3.8 mA, and it must regulate

    loopcurrent at 16 mA to represent a condition of 75% process measurement, the

    transistor will bypass 12.2 mA of current.

  • 7/30/2019 First Day Class Introduction,Temp

    37/63

    ADVANCEMENT IN SENSOR TECHNOLOGY:-

    Olden days current-based industrial transmitters

    were using a current signal standard: 10 to 50milliamps DC and Loop power supplies for these

    transmitters ranged upwards of 90 volts to

    provide enough power.

    Safety concerns made the 10-50 mA standardunsuitable for some industrial installations, and

    advancement in technology reduced power

    consumption in modern industrial

    instrumentation systems to 4 - 20 milliamp DC asan analog signal standard , for nearly all types of

    process transmitters.

  • 7/30/2019 First Day Class Introduction,Temp

    38/63

    INTELLIGENT INSTRUMENTS

    In the past few years the development of

    measurement systems made intelligent devices inwhich the computational element (usually called a

    microcomputer or microprocessor) was integrated

    into the measurement system.

    SMART SENSORS:-Over years the size of intelligent instruments has

    gradually reduced and the functions performed

    have steadily increased.

    they included a microprocessor within the sensoritself, are usually called as smart sensors instead

    ofintelligent instruments.

  • 7/30/2019 First Day Class Introduction,Temp

    39/63

    Introduction to Temperaturemeasurement:-

    Thermal conductivity:the flow of heat from a hightemperature region to a low temperature region.

    Conduction :flow of heat in a material is transferred from one

    molecule to the next

    Convection :the transfer of heat due to motion of elevated

    temperature particles in a material (such as liquid and gases)

    Radiation :the emission of energy by electromagnetic waves thattravel at the speed of light through most materials that do not conduct

    electricity. Thermistors:a class of metal oxide (semiconductor material)

    which have a high negative temperature coefficient of resistance, but

    can also be positive .

  • 7/30/2019 First Day Class Introduction,Temp

    40/63

    BASICS ON ELECTRICITY .

    Resistance :It is the property of a substance to oppose theflow of electricity through it .it is measured in resistancevaries directly with length and inversely with cross section. It also

    depends up on material , temperature. R=.I /A Wheatstone bridge circuit :it is used to measure resistance and

    consist of four arms and operates upon null indication principle.attwo points an EMF is applied and at other two points a null

    indication instrument/ galvanometer is connected.

  • 7/30/2019 First Day Class Introduction,Temp

    41/63

    See beck effect:the voltage produced in a thermocouple isproportional to the temperature between the two junctions.

    Peltiereffect:if a current flows through a thermocouple one junction is

    heated (puts out energy) and the other junction is cooled (absorbs energy).

    Thermopile : a number of thermocouples connected in series, toincrease the sensitivity and accuracy by increasing the output voltage when

    measuring low temperature differences.

    Pyrometers are devices that measure temperature by

    sensing the heat radiatedfrom a hot body through a

    fixed lens that focuses the heat energy on to a

    thermopile;this is a noncontact device. Furnace

    temperatures, for instance, are normally measured

    through a small hole in the furnace wall. The distance

    from the source to thepyrometer can be fixed and the

    radiation should fill the field of view of the sensor

  • 7/30/2019 First Day Class Introduction,Temp

    42/63

    TEMPERATURE SWITCHES Bi-metal temperature switch - it is a bond of two dissimilar metals of

    equal sizes having different temperature expansion of coefficient .when

    subjected to temperature the bond bends. Temperature switches often use

    bimetallic strips as temperature sensing element, the motion of which actuates

    one or more switch contacts.

  • 7/30/2019 First Day Class Introduction,Temp

    43/63

    Temperature can be measured by using variousinstruments. they are Glass thermometer

    Bimetallic thermometers

    Pressure gauge /filled bulb thermometers

    RTD Thermistors

    Thermocouples/ Thermopiles

    Pyrometers

    Optical pyrometers

    M i l Thi i di t i l i di t Th ti

  • 7/30/2019 First Day Class Introduction,Temp

    44/63

    Mercury in glass-This gives direct visual indicator The operating range

    of the mercury thermometer is from 30 to 800F (35 to 450C)

  • 7/30/2019 First Day Class Introduction,Temp

    45/63

    Bi-metal temperature sensors:-

    This bending motion of bi metal can to drive a pointermechanism, activate an electromechanical switch, or

    perform any number of other mechanical tasks, making this

    a very simple and useful primary sensing element fortemperature.

  • 7/30/2019 First Day Class Introduction,Temp

    46/63

    CONTINUOUS TEMPERATURE MEASUREMENT

    Filled-bulb temperature sensors :-it works on the

    principle of expansion of fluid when temperature changes. Class I and Class V systems use a liquid fill fluid (class V is mercury),

    Class II, which uses a volatile liquid/vapor combination,

    Class III systems use a gas fill fluid, to generate a temperature-dependent fluid

    expansion.

    Th i t (th l i t )

  • 7/30/2019 First Day Class Introduction,Temp

    47/63

    Thermistors (thermal resistors) :-Theyare made of metallic oxides such as manganese ,nickel,cobalt ,

    copper, iron, uranium, which either increase in resistance with

    increasing temperature (a positive temperature coefficient) or

    decrease in resistance with increasing temperature (a negative

    temperature coefficient). They are in the form of beads ,rods,

    discs. They are suitable for measurement range from -60 to +15

    deg c. They are highly sensitive but non linear and detect very

    small change in temperature.

    Resistance Temperature Detectors (R T

  • 7/30/2019 First Day Class Introduction,Temp

    48/63

    Resistance Temperature Detectors (R T

    Ds):- It works on the principle of change in resistance of aconductor with change in temperature. RTD s are made of pure

    metal (usuallyplatinum or copper) which always increase in

    resistance with increasing temperature. (170 to 780C).

    100 and 1000 is a very common reference resistance for

    industrial RTDs.

    Analog electronic RTD instruments use operational amplifiers to

    convert the RTDs voltage drop into a standard instrument output

    signal, such as 4-20 mA DC. self-heating of RTD is removed bysending pulse current through them.

    Nickel = 0.00672 /oC Tungsten = 0.0045 /oC

    Silver = 0.0041 /oC Gold = 0.0040 /oC Platinum = 0.00392 /oC Copper = 0.0038 /oC

    RTD four-wire connection,

  • 7/30/2019 First Day Class Introduction,Temp

    49/63

    RTD three-wire connection

    ,

    RTD R i t l b d i Wh t t

  • 7/30/2019 First Day Class Introduction,Temp

    50/63

    RTD s Resistance can also be measured using a Wheatstone

    bridge, but are supplied from a constant current source. heating

    of the device is prevented by using a pulse technique. In this

    method the current is turned ON for say 10 ms every 10 s, and

    the sensor resistance is measured during this 10 ms time period. In this circuit, when the current flow in the meter is zero then the

    bridge is said to be in null balance. As the RTD temperature

    increases, the voltage read by the voltmeter increases. If a

    voltage transducer replaces the voltmeter, a 4-20 mA signal,

    which is proportional to the temperature range being monitored,can be generated.

  • 7/30/2019 First Day Class Introduction,Temp

    51/63

    THERMOCOUPLE:- it is an arrangement of two dissimilar

  • 7/30/2019 First Day Class Introduction,Temp

    52/63

    THERMOCOUPLE: it is an arrangement of two dissimilar

    metal wires joined to form two junctions by vacuum brazing

    , induction brazing ,and argon arc welding. One junction is

    called cold junction and other is called hot junction.

  • 7/30/2019 First Day Class Introduction,Temp

    53/63

  • 7/30/2019 First Day Class Introduction,Temp

    54/63

  • 7/30/2019 First Day Class Introduction,Temp

    55/63

    Type C

  • 7/30/2019 First Day Class Introduction,Temp

    56/63

    Type K (chromelalumel) is the most common general purpose

    thermocouple. It is inexpensive and available in a wide variety of probes.

    They are available in the 0 C to +1250 C range. Sensitivity is

    approximately 41 V/C.

    Type E (chrom elconstan tan ) has a h igh outp ut (68 V/C)which makes

    it well suited to cryogenic use. Additionally, it is non-magnetic.

    J typelimited range (40 to +750C). The Curie point of the iron (770 C)

    causes an abrupt change to the characteristic and it is this that provides the

    upper temperature limit. Type J thermocouples have a sensitivity of about55 V/C

    Type N (nici ron) thermoco uples are sui table for us e at high

    temperatures, exceeding 1200C, due to their stability and ability to resist

    high temperature oxidation. Sensitivity is about 39 V/C at 900 C, slightly

    lower than type K. Designed to be an improved type K, it is becoming more

    popular.

    Type B thermocouples use a platinum rhodium alloy

  • 7/30/2019 First Day Class Introduction,Temp

    57/63

    Type Bthermocouples use a platinumrhodium alloy

    for each conductor. One conductor contains 30%

    rhodium while the other conductor contains 6%

    rhodium. These thermocouples are suited for use atup to 1800 C. Type B thermocouples produce the

    same output at 0 C and 42 C, limiting their use

    below about 50 C.

    Type R thermocouples use a platinumrhodium alloy

    containing 13% rhodium for one conductor and pure

    platinum for the other conductor. Type R

    thermocouples are used up to 1600 C.

    Type S thermocouples are constructed using one wire of 90%

    Platinum and 10% Rhodium (the positive or "+" wire) and asecond wire of 100% platinum (the negative or "-" wire). Like

    type R, type S thermocouples are used up to 1600 C. In

    particular, type S is used as the standard of calibration for the

    melting point of gold (1064.43 C).

  • 7/30/2019 First Day Class Introduction,Temp

    58/63

    Type T (copperconstantan) thermocouples are suited formeasurements in the200 to 350C range. Often used as adifferential measurement since only copper wire touches the

    probes. Since both conductors are non-magnetic, there is noCurie point and thus no abrupt change in characteristics. TypeT thermocouples have a sensitivity of about 43 V/C.

    Type C (tungsten 5% rhenium tungsten 26% rhenium)

    thermocouples are suited for measurements in the 0 C to2320 C range. This thermocouple is well-suited for vacuumfurnaces at extremely high temperatures and must never beused in the presence of oxygen at temperatures above 260C.

    Application and selection of RTD and Thermocouple:-

    Thermocouples are extremely rugged and have fargreater temperature measurement ranges than

    thermistors, RTDs, and other primary sensing

    elements. However, if the application does not

    demand extreme ruggedness or large measurement

    INSTALLATION GUIDE LINES:

  • 7/30/2019 First Day Class Introduction,Temp

    59/63

    INSTALLATION GUIDE LINES:TEMPERATURE SENSOR ACCESSORIES

  • 7/30/2019 First Day Class Introduction,Temp

    60/63

    One of the most important accessories for any

    temperature-sensing element is a pressure-tight sheath

    known as a thermo well.

    This may be thought of as a thermally conductive

    protrusion into a process vessel or pipe that allows a

    temperature-sensitive instrument to detect process

    temperature without opening a hole in the vessel or pipe.

    Thermo wells are critically important for installationswherethe temperature element (RTD, thermocouple,

    thermometer, etc.) must be replaceable without de-

    pressurizing the process.

    Thermo wells may be made out of any material that is

    thermally conductive, pressure-tight, and not chemically

    reactive with the process.

  • 7/30/2019 First Day Class Introduction,Temp

    61/63

    If the temperature gauge is removed for service

    or replacement, the thermowell maintains

    pressure integrity of the pipe (no process fluidleaking out, and no air leaking in)

  • 7/30/2019 First Day Class Introduction,Temp

    62/63

    real (stainless steel) thermowelldevice where the temperature

    sensor is inserted

    RTD

    Pyrometers : pyrometer is a non contacting device that intercepts

  • 7/30/2019 First Day Class Introduction,Temp

    63/63

    Pyrometers :- pyrometer is a non-contacting device that interceptsand measures thermal radiation. This device can be used todetermine the temperature of an object's surface