first day class introduction,temp
TRANSCRIPT
-
7/30/2019 First Day Class Introduction,Temp
1/63
FIELD INSTRUMENTS
-
7/30/2019 First Day Class Introduction,Temp
2/63
INTRODUCTION:-
Instrumentation is a field of sciencewhich deals with measurement of
different parameters and controlling
them.WHAT IS FIELD ?
INDUSTRY :Systematic Economic Activity that
could be related to Manufacture/Service/Trade
-
7/30/2019 First Day Class Introduction,Temp
3/63
Various measurements generally in an industry
Fluid pressure
Fluid flow rate
The temperature of an object
Fluid volume stored in a vessel
Chemical concentration
Machine position, motion, or acceleration
Physical dimension (s) of an object
Count (inventory) of objects
Electrical voltage, current, or resistance
-
7/30/2019 First Day Class Introduction,Temp
4/63
Automation
Automation is the process of operationof machines and systems without
significant human intervention by
technical equipment to achieves
performance superior to manual
operation.
(Automation is basically the delegation of human control function
to technical equipment for) Increasing Productivity
Increasing Quality
Reducing Cost
Increasing Safety in working conditions
-
7/30/2019 First Day Class Introduction,Temp
5/63
-
7/30/2019 First Day Class Introduction,Temp
6/63
Elements of automation
Process -a sequence of actions that take place in a set up or a plant where wewant to control.
Instrument- it is a physical means to determine the quantity orvariable
Sensors Primary Sensing Element orPSE :-A device that directly senses the
process variable and translates that sensed quantity into an analog
representation (electrical voltage, current, resistance, mechanical
force, motion, etc )
Transmitter:A device that translates the signal produced by a primary sensingelement (PSE) into a standardized instrumentation signal such as 3-15 PSI air
pressure, 4-20 mA DC current, 0 10 V DC , into Field bus digital signal packet,
etc., which may then be conveyed to an indicating / controlling device, or both.
transducer :- A device that converts one standardized instrumentationsignal into another standardized instrumentation signal, and/or performs somesort of processing on that signal, often referred to as a converterexample:- P/I
-
7/30/2019 First Day Class Introduction,Temp
7/63
Controller-A device that receives a process variable (PV) signal from aprimary sensing element (PSE) or transmitter, compares that signal to the
desired value for that process variable (called the set point), and calculates
an appropriate output signal value to be sent to a final control element
(FCE) such as an electric motor or control valve.
Final control element-A device that receives the signal from acontroller to directly influence the process.( Examples: variable-speed electric
motor, control valve, electric heater. )
-
7/30/2019 First Day Class Introduction,Temp
8/63
Instrumentation terms and their definitions(Industrial measurement and control systems terms and standards)
Process Variable
Set poin t
Lower- and Upper-range values
Automat ic mode
Manual mode Measur ing signal
Control l ing signal
-
7/30/2019 First Day Class Introduction,Temp
9/63
Process Variable (PV): The specific quantity we are
measuring in a process. Examples:pressure, level,
temperature, flow, electrical conductivity, Ph,position, speed, vibration.
Set po in t (SP):The value at which we desire the
process variable to be maintained at. In other words,
the target value of the process variable.
-
7/30/2019 First Day Class Introduction,Temp
10/63
Lower- and Upper-range values (LRV and URV):
the values of process measurement deemed to be
0% and 100% of a transmitters calibrated range.
Example - if a temperature transmitter is calibrated to
measure a temperature starting at 300 degrees
Celsius and ending at 500 degrees Celsius- 300
degrees would be the LRV and 500 degrees the
URV.
Relating 4 to 20 m A signals to instrument variables
-
7/30/2019 First Day Class Introduction,Temp
11/63
Autom at ic mode:When the controller generates an
output signal based on the relationship of process
variable (PV) to the set point (SP).
Manual mode:When the controllers decision-
making ability is bypassed to let a human operator
directly determine the output signal sent to the finalcontrol element.
-
7/30/2019 First Day Class Introduction,Temp
12/63
CASE STUDY
-
7/30/2019 First Day Class Introduction,Temp
13/63
CHEMICAL REACTOR TEMPERATURE CONTROL SYSTEM
-
7/30/2019 First Day Class Introduction,Temp
14/63
A steam-heated jacket envelops the reactor vessel ,transfers heat from the steam into the chemical solutioninside. the temperature transmitter, located near the
bottom of the vessel. The special connector (solid dots with lines in between
sometimes referred to as a fieldbus ) is used to connectthe temperature transmitter (TT) with the temperature
indicating controller (TIC). The TT send a digitalelectronic instrument signal using digital bits ofinformation rather than an analog signal (such as 4 to20 m A or 3 to 15 PSI).
The controller / TIC send an analog signal of 4 to 20
milliamps DC shown by dashed line a device labeled TYwhich is a transducer to convert the 4 to 20 mAelectronic signal into a 3 to 15 PSI pneumatic signalwhich then actuates the valve.
-
7/30/2019 First Day Class Introduction,Temp
15/63
Various instruments used in an
industry Fluid pressure- can be measured by using basic sensing
elements such as bourdon tube , capsule, bellow , diaphragm
made of metal such as berelium copper and phosphorus bronze
, silicon diaphram .
Fluid flow rate- can be measured by using basic sensing
elements such as orifice plate , venture tube , pitot tube . The temperature of an object- can be measured by using basic
sesnsing elements such as, RTD, thermocouple, thermister.
Fluid volume/level stored in a vessel- can be measured by using
float level,hydro static pressure measurement,by bubbler
system, by displacer method,ultra sonic method
Chemical concentration
Machine position, motion, or acceleration-
Physical dimension (s) of an object
Count (inventory) of objects
-
7/30/2019 First Day Class Introduction,Temp
16/63
TYPES OF SENSORS
All the sensors can be classified in to two types
based up on the type of signals they provide.1. Digital instruments/sensors - instruments which
provide digital signals are called digitalinstruments. Digital signal are in the form of low
/high voltage /0 /1.{ absence / presence ofvoltage }.
2. Analog instruments/sensors- instruments whichprovide analog out put signal are called analog
instruments . Analog signal vary in continuousfashion and take on infinite number of values inany given range. The industrial standardsignals are 4 to 20 milliamp DC,0-10 volt DC,3-15PSI .
-
7/30/2019 First Day Class Introduction,Temp
17/63
SOURCING AND SINKING
CIRCUITS
switch sinks current in from the LED through itsoutput terminal, through its transistor, and down
to ground
-
7/30/2019 First Day Class Introduction,Temp
18/63
switch sources current from the positive supply
terminal
through its transistor and out to the LED through its
output terminal
-
7/30/2019 First Day Class Introduction,Temp
19/63
CLOSE LOOP OPEN LOOP CONTROL OF PROCESS
OPEN LOOP CONTROL
-
7/30/2019 First Day Class Introduction,Temp
20/63
OPEN LOOP CONTROL
The control system where the output variable does not have
any influence on the input variable is called open loop control.Fig-At constant applied pressure, the volumetric flow can be maintained
by the position of the control valve. Here the output variable is
"volumetric flow" and the input variable is "control valve setting" .if the
applied pressure fluctuates, the volumetric flow will also fluctuate.
In other words one or more input variables of a system act on a processvariable and causes the possible deviations . e.g. disturbances
caused by other in put variable (pressure) are not compensated for in
the open loop control process. Thus, the characteristic feature of
open loop control is an open action flow .
-
7/30/2019 First Day Class Introduction,Temp
21/63
CLOSE LOOP CONTROL
-
7/30/2019 First Day Class Introduction,Temp
22/63
CLOSE LOOP CONTROL
It is a process where the controlled variable is
continuously monitored and compared with thereference variable. The input variable for the systemis influenced to adjust the output variable to thedesired value despite any disturbing influences. This
feedback results in a closed-loop action. In other words in a closed loop control system, the
variable to be controlled is continuously measuredand then compared with a predetermined value
(reference variable ). If there is a difference betweenthese two variables, adjustments are being madeuntil the measured difference is eliminated and thecontrolled variable equals the reference variable.Hence, the characteristic feature of closed loopcontrol is a closed action flow
-
7/30/2019 First Day Class Introduction,Temp
23/63
Measurement is a process of assigning a number to
an attribute (or phenomenon) according to a rule or
set of rules.(Or )
(it is an act of comparison between the un known
quantity and predefined standard)
MEASUREMENT
-
7/30/2019 First Day Class Introduction,Temp
24/63
METHODS OF MEASUREMENT
1. Direct measurement: Un known quantity isdirectly compared against a standard.
2. Ind irect measu rement:measuring something
by measuring something else
-
7/30/2019 First Day Class Introduction,Temp
25/63
ELEMENTS OF MEASURING SYSTEM
-
7/30/2019 First Day Class Introduction,Temp
26/63
-
7/30/2019 First Day Class Introduction,Temp
27/63
MEASUREMENT SYSTEMA measuring system consist of
Sensor / primary sensing element - to sense andmeasure the process variable by producingdisplacement , change in resistance)
Variable conversion element to convertdisplacement , change in resistancetoanalogous form( in to a voltage .. Etc exwhenpressure changes a strain transducer converts the deformationof the diaphragm into an electrical resistance change.)
Variable manipulation / processing element toprocess analog signal and feed the data for thepurpose of display/control. All elements may bein one box / separated.
-
7/30/2019 First Day Class Introduction,Temp
28/63
ACTIVE AND PASSIVE INSTRUMENTS
ACTIVE INSTRUMENTS:- those which does notneed external power supply for excitation.
PASSIVE INSTRUMENTS:- those which needexternal power supply for excitation
-
7/30/2019 First Day Class Introduction,Temp
29/63
DIGITAL SENSORS
A discrete variable or measurement refers to a
true-or-false condition. Thus, aDiscreteSensor is one that is able to indicatewhether the measured variable is
above or below a specified set point. DiGITAL sensors typically take the form of
Switches andare less sophisticated than so-calledcontinuous sensors
-
7/30/2019 First Day Class Introduction,Temp
30/63
NORMAL status of a switch
Normal means not being pressed Electrical switch contacts are typically classified
as
normally-open
normally-closed
-
7/30/2019 First Day Class Introduction,Temp
31/63
VARIOUS DISCRETE SENSORS AND THEIR NORMAL POSITION
Hand switch: no one pressing the switch
Limit switch: target not contacting the switch Proximity switch: target far away
Pressure switch: low pressure (or even a
vacuum)
Level switch: low level (empty)
Temperature switch: low temperature (cold)
Flow switch: low flow rate (fluid stopped)
-
7/30/2019 First Day Class Introduction,Temp
32/63
INSTRUMENTS
Analog electronic instrument-An instrument can be classified as
analog if it produces an analog signal standard to communicateinformation, even if the internal construction and design of the instrument
may be mostly digital in nature.
analog current signals-in modern industrial instrumentationsystems the 4 to 20 milliamp DC is an analog signal standard ,this electric
current is used to proportionately represent measurements or commandsignals. 4 milliamp current value represents 0% of scale, a 20 milliamp current valuerepresents100% of scale, and any current value in between 4 and 20 milliamps
represents a commensurate percentage in between 0% and 100%.
Most of the industrial control systems use at least two different 4-20 mA
signals: one to represent the process variable (PV) and one to represent the
command signal to the final control element.
-
7/30/2019 First Day Class Introduction,Temp
33/63
4-wire or self-poweredTransmitter connection to plc/controller
Power source near to transmitter method :- 4-20 mA DC
electric current signals are used to communicate processmeasurement information from transmitters to controllers. Thetransmitter has two terminals for the 4-20 mA signal wires to connect,and two more terminals to connect a power source. The current signalfrom the transmitter connects to the process variable input terminalsof the controller to complete the loop. BUT process controllers areunable to directly accept milliamp input signals, however acceptsvoltage signals. For this reason a precision resistor of 250 ohmsconnected across the input terminals of controller convert the 4-20 mAsignal into a standardized analog voltage signal of 1 to 5 volts andfurther this voltage is converted in digital by ADC which can be
processed by the controllermicro processor. Some models of controller use different voltage ranges so require
different precision resistor values.
-
7/30/2019 First Day Class Introduction,Temp
34/63
POWER SOURCE NEAR TO CONTROLLER METHOD
As shown in the fig same 4 wire transmitter is powered through additional
wires in the cable from a power source located in the same panel as the
controller.
Disadvantages:1. requirement of two more conductors in the cable
2. cable will be larger in diameter
3. more expensive for a given length.
4. Cables requires larger electrical conduit to fit in to
5. all field wiring panels will have to contain more terminal blocks.
6. Note :-this method of connection can be used If no suitable electrical power source exists at the
transmitter location.
-
7/30/2019 First Day Class Introduction,Temp
35/63
2-wire (Loop-powered) Transmitter Method
In this method both electrical power to transmitter and 4 to 20 milliamps DC
analog information are communicated over the same two wires so called loop
powered.
Loop powered 2-wire transmitters circuitry acts as a current regulator, limiting current in
the series loop to 4 to 20 ma DC representing the process measurement.
The current source in loop-powered transmitter actually behaves as an electrical load.
Power source being 24 volts DC, the maximum voltage dropped across the
controllers 250 ohm resistor being 5 volts DC, the transmitter should alwayshave at least 19 volts available at its terminals to operate, while regulating
current to signal the process measurement.
-
7/30/2019 First Day Class Introduction,Temp
36/63
The transmitter is designed with sensing, scaling, and output conditioningcircuitry inside and run on less then 4 mA of DC current, and at a modest
terminal voltage.
The transmitter circuitry uses a transistor to shunt (bypass) extra current when
needed to make the total current indicative of the process measurement
If the transmitters internal operating current is only 3.8 mA, and it must regulate
loopcurrent at 16 mA to represent a condition of 75% process measurement, the
transistor will bypass 12.2 mA of current.
-
7/30/2019 First Day Class Introduction,Temp
37/63
ADVANCEMENT IN SENSOR TECHNOLOGY:-
Olden days current-based industrial transmitters
were using a current signal standard: 10 to 50milliamps DC and Loop power supplies for these
transmitters ranged upwards of 90 volts to
provide enough power.
Safety concerns made the 10-50 mA standardunsuitable for some industrial installations, and
advancement in technology reduced power
consumption in modern industrial
instrumentation systems to 4 - 20 milliamp DC asan analog signal standard , for nearly all types of
process transmitters.
-
7/30/2019 First Day Class Introduction,Temp
38/63
INTELLIGENT INSTRUMENTS
In the past few years the development of
measurement systems made intelligent devices inwhich the computational element (usually called a
microcomputer or microprocessor) was integrated
into the measurement system.
SMART SENSORS:-Over years the size of intelligent instruments has
gradually reduced and the functions performed
have steadily increased.
they included a microprocessor within the sensoritself, are usually called as smart sensors instead
ofintelligent instruments.
-
7/30/2019 First Day Class Introduction,Temp
39/63
Introduction to Temperaturemeasurement:-
Thermal conductivity:the flow of heat from a hightemperature region to a low temperature region.
Conduction :flow of heat in a material is transferred from one
molecule to the next
Convection :the transfer of heat due to motion of elevated
temperature particles in a material (such as liquid and gases)
Radiation :the emission of energy by electromagnetic waves thattravel at the speed of light through most materials that do not conduct
electricity. Thermistors:a class of metal oxide (semiconductor material)
which have a high negative temperature coefficient of resistance, but
can also be positive .
-
7/30/2019 First Day Class Introduction,Temp
40/63
BASICS ON ELECTRICITY .
Resistance :It is the property of a substance to oppose theflow of electricity through it .it is measured in resistancevaries directly with length and inversely with cross section. It also
depends up on material , temperature. R=.I /A Wheatstone bridge circuit :it is used to measure resistance and
consist of four arms and operates upon null indication principle.attwo points an EMF is applied and at other two points a null
indication instrument/ galvanometer is connected.
-
7/30/2019 First Day Class Introduction,Temp
41/63
See beck effect:the voltage produced in a thermocouple isproportional to the temperature between the two junctions.
Peltiereffect:if a current flows through a thermocouple one junction is
heated (puts out energy) and the other junction is cooled (absorbs energy).
Thermopile : a number of thermocouples connected in series, toincrease the sensitivity and accuracy by increasing the output voltage when
measuring low temperature differences.
Pyrometers are devices that measure temperature by
sensing the heat radiatedfrom a hot body through a
fixed lens that focuses the heat energy on to a
thermopile;this is a noncontact device. Furnace
temperatures, for instance, are normally measured
through a small hole in the furnace wall. The distance
from the source to thepyrometer can be fixed and the
radiation should fill the field of view of the sensor
-
7/30/2019 First Day Class Introduction,Temp
42/63
TEMPERATURE SWITCHES Bi-metal temperature switch - it is a bond of two dissimilar metals of
equal sizes having different temperature expansion of coefficient .when
subjected to temperature the bond bends. Temperature switches often use
bimetallic strips as temperature sensing element, the motion of which actuates
one or more switch contacts.
-
7/30/2019 First Day Class Introduction,Temp
43/63
Temperature can be measured by using variousinstruments. they are Glass thermometer
Bimetallic thermometers
Pressure gauge /filled bulb thermometers
RTD Thermistors
Thermocouples/ Thermopiles
Pyrometers
Optical pyrometers
M i l Thi i di t i l i di t Th ti
-
7/30/2019 First Day Class Introduction,Temp
44/63
Mercury in glass-This gives direct visual indicator The operating range
of the mercury thermometer is from 30 to 800F (35 to 450C)
-
7/30/2019 First Day Class Introduction,Temp
45/63
Bi-metal temperature sensors:-
This bending motion of bi metal can to drive a pointermechanism, activate an electromechanical switch, or
perform any number of other mechanical tasks, making this
a very simple and useful primary sensing element fortemperature.
-
7/30/2019 First Day Class Introduction,Temp
46/63
CONTINUOUS TEMPERATURE MEASUREMENT
Filled-bulb temperature sensors :-it works on the
principle of expansion of fluid when temperature changes. Class I and Class V systems use a liquid fill fluid (class V is mercury),
Class II, which uses a volatile liquid/vapor combination,
Class III systems use a gas fill fluid, to generate a temperature-dependent fluid
expansion.
Th i t (th l i t )
-
7/30/2019 First Day Class Introduction,Temp
47/63
Thermistors (thermal resistors) :-Theyare made of metallic oxides such as manganese ,nickel,cobalt ,
copper, iron, uranium, which either increase in resistance with
increasing temperature (a positive temperature coefficient) or
decrease in resistance with increasing temperature (a negative
temperature coefficient). They are in the form of beads ,rods,
discs. They are suitable for measurement range from -60 to +15
deg c. They are highly sensitive but non linear and detect very
small change in temperature.
Resistance Temperature Detectors (R T
-
7/30/2019 First Day Class Introduction,Temp
48/63
Resistance Temperature Detectors (R T
Ds):- It works on the principle of change in resistance of aconductor with change in temperature. RTD s are made of pure
metal (usuallyplatinum or copper) which always increase in
resistance with increasing temperature. (170 to 780C).
100 and 1000 is a very common reference resistance for
industrial RTDs.
Analog electronic RTD instruments use operational amplifiers to
convert the RTDs voltage drop into a standard instrument output
signal, such as 4-20 mA DC. self-heating of RTD is removed bysending pulse current through them.
Nickel = 0.00672 /oC Tungsten = 0.0045 /oC
Silver = 0.0041 /oC Gold = 0.0040 /oC Platinum = 0.00392 /oC Copper = 0.0038 /oC
RTD four-wire connection,
-
7/30/2019 First Day Class Introduction,Temp
49/63
RTD three-wire connection
,
RTD R i t l b d i Wh t t
-
7/30/2019 First Day Class Introduction,Temp
50/63
RTD s Resistance can also be measured using a Wheatstone
bridge, but are supplied from a constant current source. heating
of the device is prevented by using a pulse technique. In this
method the current is turned ON for say 10 ms every 10 s, and
the sensor resistance is measured during this 10 ms time period. In this circuit, when the current flow in the meter is zero then the
bridge is said to be in null balance. As the RTD temperature
increases, the voltage read by the voltmeter increases. If a
voltage transducer replaces the voltmeter, a 4-20 mA signal,
which is proportional to the temperature range being monitored,can be generated.
-
7/30/2019 First Day Class Introduction,Temp
51/63
THERMOCOUPLE:- it is an arrangement of two dissimilar
-
7/30/2019 First Day Class Introduction,Temp
52/63
THERMOCOUPLE: it is an arrangement of two dissimilar
metal wires joined to form two junctions by vacuum brazing
, induction brazing ,and argon arc welding. One junction is
called cold junction and other is called hot junction.
-
7/30/2019 First Day Class Introduction,Temp
53/63
-
7/30/2019 First Day Class Introduction,Temp
54/63
-
7/30/2019 First Day Class Introduction,Temp
55/63
Type C
-
7/30/2019 First Day Class Introduction,Temp
56/63
Type K (chromelalumel) is the most common general purpose
thermocouple. It is inexpensive and available in a wide variety of probes.
They are available in the 0 C to +1250 C range. Sensitivity is
approximately 41 V/C.
Type E (chrom elconstan tan ) has a h igh outp ut (68 V/C)which makes
it well suited to cryogenic use. Additionally, it is non-magnetic.
J typelimited range (40 to +750C). The Curie point of the iron (770 C)
causes an abrupt change to the characteristic and it is this that provides the
upper temperature limit. Type J thermocouples have a sensitivity of about55 V/C
Type N (nici ron) thermoco uples are sui table for us e at high
temperatures, exceeding 1200C, due to their stability and ability to resist
high temperature oxidation. Sensitivity is about 39 V/C at 900 C, slightly
lower than type K. Designed to be an improved type K, it is becoming more
popular.
Type B thermocouples use a platinum rhodium alloy
-
7/30/2019 First Day Class Introduction,Temp
57/63
Type Bthermocouples use a platinumrhodium alloy
for each conductor. One conductor contains 30%
rhodium while the other conductor contains 6%
rhodium. These thermocouples are suited for use atup to 1800 C. Type B thermocouples produce the
same output at 0 C and 42 C, limiting their use
below about 50 C.
Type R thermocouples use a platinumrhodium alloy
containing 13% rhodium for one conductor and pure
platinum for the other conductor. Type R
thermocouples are used up to 1600 C.
Type S thermocouples are constructed using one wire of 90%
Platinum and 10% Rhodium (the positive or "+" wire) and asecond wire of 100% platinum (the negative or "-" wire). Like
type R, type S thermocouples are used up to 1600 C. In
particular, type S is used as the standard of calibration for the
melting point of gold (1064.43 C).
-
7/30/2019 First Day Class Introduction,Temp
58/63
Type T (copperconstantan) thermocouples are suited formeasurements in the200 to 350C range. Often used as adifferential measurement since only copper wire touches the
probes. Since both conductors are non-magnetic, there is noCurie point and thus no abrupt change in characteristics. TypeT thermocouples have a sensitivity of about 43 V/C.
Type C (tungsten 5% rhenium tungsten 26% rhenium)
thermocouples are suited for measurements in the 0 C to2320 C range. This thermocouple is well-suited for vacuumfurnaces at extremely high temperatures and must never beused in the presence of oxygen at temperatures above 260C.
Application and selection of RTD and Thermocouple:-
Thermocouples are extremely rugged and have fargreater temperature measurement ranges than
thermistors, RTDs, and other primary sensing
elements. However, if the application does not
demand extreme ruggedness or large measurement
INSTALLATION GUIDE LINES:
-
7/30/2019 First Day Class Introduction,Temp
59/63
INSTALLATION GUIDE LINES:TEMPERATURE SENSOR ACCESSORIES
-
7/30/2019 First Day Class Introduction,Temp
60/63
One of the most important accessories for any
temperature-sensing element is a pressure-tight sheath
known as a thermo well.
This may be thought of as a thermally conductive
protrusion into a process vessel or pipe that allows a
temperature-sensitive instrument to detect process
temperature without opening a hole in the vessel or pipe.
Thermo wells are critically important for installationswherethe temperature element (RTD, thermocouple,
thermometer, etc.) must be replaceable without de-
pressurizing the process.
Thermo wells may be made out of any material that is
thermally conductive, pressure-tight, and not chemically
reactive with the process.
-
7/30/2019 First Day Class Introduction,Temp
61/63
If the temperature gauge is removed for service
or replacement, the thermowell maintains
pressure integrity of the pipe (no process fluidleaking out, and no air leaking in)
-
7/30/2019 First Day Class Introduction,Temp
62/63
real (stainless steel) thermowelldevice where the temperature
sensor is inserted
RTD
Pyrometers : pyrometer is a non contacting device that intercepts
-
7/30/2019 First Day Class Introduction,Temp
63/63
Pyrometers :- pyrometer is a non-contacting device that interceptsand measures thermal radiation. This device can be used todetermine the temperature of an object's surface