fire alarm installers manual

Upload: mlingerfelt65

Post on 07-Aug-2018

233 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/20/2019 Fire Alarm Installers Manual

    1/38

    Fire Alarm Installer’s

    Installation Guide

    For consistent, reliable installations

    c   2008 Daniel Larson

  • 8/20/2019 Fire Alarm Installers Manual

    2/38

  • 8/20/2019 Fire Alarm Installers Manual

    3/38

      - 2 -

    Table of Contents

    Section 1:

    Wall Mounted Back Boxes for; - Flush mounted devices

    Manual Pull StationsHorns and StrobesSpeakers and Strobes

    ModulesDuct Detector Test/Reset Switches or Alarm LED

    Annunciators

    Section 2:

    Back box conduit stub-ups for; - Flush mounted devices

    Horns, Horn/Strobes, Speakers, Speaker/Strobes

    Manual Pull Stations

    Section 3:

    Wall penetrations

    Sheet rock extended to the hard deckSheet rock to just above ceiling

    Fire rated walls

    Sleeves

    Section 4:

    Fastening to steel

    Steel beams, trusses, and columns

    Section 5:

    Ceiling Mounted Device Back Boxes

    T-Bar mounted back boxes

    Hard lid mounted back boxes

    Section 6:

    Fire Sprinkler Riser and OS&Y

    Riser and OS&Y

  • 8/20/2019 Fire Alarm Installers Manual

    4/38

      - 3 -

    Section 7:

    Cut-in Boxes

    Sheet rock extend to just above ceiling

    Sheet rock extends to deck

    Section 8:

    Wiring Methods (Securing to steel)

    Horizontal wire run on split trussPerpendicular wire run to mounted box

    90 degrees to horizontal wire run

    Securing to steel shelf or lip

    Section 9:

    Wiring Methods (Securing to wood)Horizontal wire runs

    Section 10:

    Wire protection

    Basic wire protection in metal raceway

    Section 11:

    Labeling circuits and terminations

    Section 12:

    Fire panel lay-outs

    Large systems w/voice

    Large systems Medium systems

    Smaller systems

    Section 13:

    Do’s and Don’ts

  • 8/20/2019 Fire Alarm Installers Manual

    5/38

    SECTION 1

    Wall Mounted Back Boxes for; Flush mounted devices

    Manual Pull Stations

    Specifications:

    Standard 4” X 4” - Steel Junction Box or 4” X 4” – Steel Junction Box w/ Bracket¾” knock-outs on boxesMount 48” to center A.F.F.

    Single Gang Mud Ring – extension varies

    Figure 1A - Illustrates the proper hardware for mounting the back boxes to either steel or wood

    studs.

    Figure 1A  

    Figure 1B: Illustrates the proper positioning and mounting of the back boxes to the 2”X 4” studs.

    The actual mounting height is 48” AFF to the center of the device, or the center of the

    mechanism.

    Figure 1B: CAD Symbols;  

    - 4 -

  • 8/20/2019 Fire Alarm Installers Manual

    6/38

    Horns and Strobes

    Specifications:Standard 4” X 4” - Steel Junction Box or 4” X 4” – Steel Junction Box w/ Bracket

    ¾” knock-outs on boxes

    Mount 84” to center A.F.FDouble Gang Mud Ring – extension varies

    Figure 1C - Illustrates the recommended hardware used to mount the Horns and Horn/Strobes.Both the Gentex and System Sensor products can also be mounted to 4” X 4” extension rings and

    single gang mud rings however; the double gang mud ring is our standard.

    Figure 1C:  

    . Figure 1D - Illustrates the proper positioning and mounting of the back boxes to the 2”X 4”studs. The mounting height is 84” AFF to the center of the device. NFPA allows for some

    variances depending on the notification appliance, for consistency we use 84” AFF as our

    standard

    Mount84” AFF Mount84” AFF

    Figure 1D:CAD Symbols; H/S H S  

    - 5 -

  • 8/20/2019 Fire Alarm Installers Manual

    7/38

     

    Speakers and Strobes

    Specifications:

    Standard 4” X 4” - Steel Junction Box or 4” X 4” – Steel Junction Box w/ Bracket

    ¾” knock-outs on boxesMount 84” to center A.F.F

    Extension Ring – 1 ½ ”or 2 ½” extension

    Figure 1E - Illustrates the hardware used to mount Speakers and Speaker/Strobes. The back of

    the speakers on both; the Gentex and System Sensor product, have a portion of the speaker that

     protrudes into the back box.

    Figure 1E  

    Figure 1F - Illustrates the proper positioning and mounting of the back boxes to the 2”X 4” studs.

    The mounting height is 84” AFF to the center of the device. NFPA allows for some variances

    depending on the notification appliance, for consistency we use 84” AFF as our standard

    Figure 1F CAD Symbols; SP/S SPS   S  

    - 6 -

  • 8/20/2019 Fire Alarm Installers Manual

    8/38

     

    Modules

    Specifications:

    Standard 4” X 4” - Steel Junction Box or 4” X 4” – Steel Junction Box w/ Bracket¾” knock-outs on boxes

    Mount 48” to center A.F.F (May vary – refer to plans)Extension Ring – 1 ½ ”or 2 ½” extension

    Figure 1G - Illustrates the proper hardware for mounting the back boxes to either steel or wood

    studs.

    Figure 1G  

    Figure 1H - Illustrates the proper positioning and mounting of the back boxes to the 2”X 4”

    studs. The actual mounting height is 48” AFF to the center of the device, this may vary, check

     plans.

    Figure 1H CAD Symbols; AIM  ARMM   C  

    - 7 -

  • 8/20/2019 Fire Alarm Installers Manual

    9/38

     

    Duct Detector Test/Reset Switches or Alarm LED

    Specifications:

    Standard 4” X 4” - Steel Junction Box or 4” X 4” – Steel Junction Box w/ Bracket¾” knock-outs on boxes

    Mount 48” to center A.F.F.Single Gang Mud Ring – extension varies

    Figure 1J - Illustrates the proper hardware for mounting the back boxes to either steel or wood

    studs.

    Figure 1J  

    Figure 1K - Illustrates the proper positioning and mounting of the back boxes to the 2”X 4”

    studs. The actual mounting height is 48” AFF to the center of the device, this may vary, check

     plans.

    Figure 1K CAD Symbols;   DT   DLDuct Test Duct LED  

    - 8 -

  • 8/20/2019 Fire Alarm Installers Manual

    10/38

     

    Annunciators Specifications:

    Standard 4” X 4” - Steel Junction Box or 4” X 4” – Steel Junction Box w/ Bracket

    ¾” knock-outs on boxesMount 50” to center A.F.F.

    Single Gang Mud Ring – extension varies(Note: The annuciators’ back box is supplied by the manufacture and can be flush or surfacemounted, using the manufactures trim-ring we surface mount to the flush assembly specified

     below.)

    Figure 1L - Illustrates the proper hardware for mounting the back boxes to either steel or woodstuds.

    Figure 1L  

    Figure 1M - Illustrates the proper positioning and mounting of the back boxes to the 2”X 4”

    studs. The actual mounting height is 50” AFF to the center of the device; this may vary, and

    check plans for special ADA regulations.

    Figure 1M CAD Symbols;   FAA Annunciator 

    50

    50

     

    - 9 -

  • 8/20/2019 Fire Alarm Installers Manual

    11/38

     

    SECTION 2

    Back box conduit stub-up assemblies

    Back boxes mounted at 84” AFF

    Specifications: Non- Fire Rated Walls, dropped ceiling (sheet rock does not extend to deck)Back box assemblies mounted at 84” AFF

    ¾” insulated box connectors

    ¾” EMT stubbed up no less than 4” above top of sheet rock¾” EMT bushing on end of stub-up

    Types of devices; Horns, Horn/Strobes, Strobes, Speakers, and Speaker/Strobes

    (Note: In some cases additional brackets may be required to secure the conduit.)

    Figure 2A – Illustrates the EMT stub-up assembly from the mounted device box to above the

    ceiling line. We established this standard for three main reasons; to protect our conductors and

     prevent ground faults caused by careless sheet-rockers, ease of replacing or adding conductors,we can still install our conductors after the sheetrock is in place.

    Above Ceiling

    EMT Bushing

    84” To Center AFF

    3/4” EMT Conduit

    3/4” EMT Insulated Connector  3/4” EMT Insulated Connector 

    secure w/ 3/4” single screw strapBracket mounted 1’ above JBox

    Finished Floor 

    secure w/ 3/4” single screw strapBracket mounted 1’ above JBox

    3/4” EMT Conduit

    EMT Bushing

    Figure 2A  

    (The type of mud rings will vary for the type of device being installed; a double gang is used in

    this illustration.)

    - 10 -

  • 8/20/2019 Fire Alarm Installers Manual

    12/38

     

    Back boxes mounted at 48” AFF

    Specifications: Non- Fire Rated Walls, dropped ceiling (sheet rock does not extend to deck)

    Back box assemblies mounted at 48” AFF¾” insulated box connectors¾” EMT stubbed up no less than 4” above top of sheet rock

    ¾” EMT bushing on end of stub-up

    Types of devices; Manual Pull Stations, Modules, and Duct Test Switches

    (Note: In some cases additional brackets may be required to secure the conduit.)

    Figure 2B – Illustrates the EMT stub-up assembly from the mounted device box to above the

    ceiling line. Again we established this standard for three main reasons; to protect our conductorsand prevent ground faults caused by careless sheet-rockers, ease of replacing or adding

    conductors, we can still install our conductors after the sheetrock is in place.

    Above Ceiling

    EMT Bushing

    48” To Center AFF

    3/4” EMT Conduit

    3/4” EMT Insulated Connector    3/4” EMT Insulated Connector 

    secure w/ 3/4” single screw strapBracket mounted 1’ above JBox

    Finished Floor 

    secure w/ 3/4” single screw strapBracket mounted 1’ above JBox

    3/4” EMT Conduit

    EMT Bushing

    Figure 2B  

    (The type of mud rings will vary for the type of device being installed; a double gang is used inthis illustration.)

    - 11 -

  • 8/20/2019 Fire Alarm Installers Manual

    13/38

     

    Perimeter Door Back boxes mounted at 48”and 84” AFF

    Specifications:

     Non- Fire Rated Walls, dropped ceiling (sheet rock does not extend to deck)Back box assemblies mounted at 48” and 84” AFF

    ¾” insulated box connectors¾” EMT stubbed up no less than 4” above top of sheet rock¾” EMT bushing on end of stub-up

    Types of devices; Manual Pull Stations, and Notification devices

    Figure 2C – Illustrates the EMT stub-up assembly from the mounted device box to above theceiling line. This configuration is usually used at perimeter door locations, where we have a

     Notification appliance mounted above a Manual Pull Station.

    Above Ceiling

    48” To Center AFF

    Finished Floor 

    84” To Center AFF

     

    - 12 -

  • 8/20/2019 Fire Alarm Installers Manual

    14/38

     

    SECTION 3

    Wall Penetrations

    Sheet rocked to deck:

    Drawing 99A

    5/8 ” Sheetrock

    Penetration

     

    In this illustration the sheet rock extends to the deck or roof, the penetration will be just abovethe ceiling. A 90 degree bend in the conduit will penetrate the sheet rock just above the ceiling.A conduit cap is place on the end of the conduit to protect the wire.

    - 13 -

  • 8/20/2019 Fire Alarm Installers Manual

    15/38

     

    Sheet rocked to just above ceiling:

    Drawing 99B

    5/8” Sheet rock

     

    In this illustration the sheet rock extends to just above the ceiling, the conduit will extend to just

    above the sheet rock. A conduit cap is placed on the end of the conduit to protect the wire.

    Always check the plans or check with the GC to make certain that the sheet rock will not extendto the deck.

    - 14 -

  • 8/20/2019 Fire Alarm Installers Manual

    16/38

    2 hr. rated fire wall- sheet rock to deck:

    2X 5/8” Sheet rock

    5/8” Sheet rock

    Drawing 99C  

    In this illustration one side of the wall is a 2 hr. rated fire wall, the sheet rock is 1 ¼” thick which

    extents to the deck. It also has a hard lid drop ceiling. The other side of the wall has 5/8” sheet

    rock to the deck, and has a T-bar drop ceiling. You will want to have the conduit penetrate on the

    T-bar ceiling side of the wall. This allow to easy access for the wire run.

    - 15 -

  • 8/20/2019 Fire Alarm Installers Manual

    17/38

    Horizontal wall penetrations:

    Drawing 99D  

    This illustration shows a couple of different wall penetrations, always use a sleeve. A sleeve is a

    short piece of conduit.

    - 16 -

  • 8/20/2019 Fire Alarm Installers Manual

    18/38

     

    SECTION 4

    Securing Back Boxes to Steel

    Fastening to steel

    Split Truss - Use 4” X 1/4”

    or #20 Toggle BoltsSteel Beams - Use Appropriate

    Beam Clamps

    “I” Column Round ColumnSecure channel-strut to column, secure boxes to channel-strut.  

    These illustrations show different ways to secure your boxes to steel columns, trusses, and

     beams.

    - 17 -

  • 8/20/2019 Fire Alarm Installers Manual

    19/38

    SECTION 5 

    Ceiling Mounted Back Boxes

    Horn/strobes, smoke and heat detectors, duct detector indicator LEDs.

    12 ga. support wire

    T-Bar Grid

    T-Bar Bracket

    4” X 4” Jbox

    3” O Mud ring

    4” X 4” Jbox3” O Mud ring

    2” X 4”Steel Studs

    24” Adjustable Bracket

    Drawing 112  

     Note: This procedure is the same for wood studs.

    These illustrations show how to secure your boxes to either T-bar or studs for the appropriateceiling type. As noted the studs can be either steel or wood.

    - 18 -

  • 8/20/2019 Fire Alarm Installers Manual

    20/38

     

    SECTION 6

    Fire Sprinkler Device Boxes

    Drawing 130

    Fire Sprinkler Riser

    Outside Stem and Yolk

    Weatherproof doublegang box

    Liquid tight 3/4”flex conduit

    Butterfly Valve

    Single gang box  Aluminum flex

    Water flow switch

    3/4” EMT

    Box Offset

    Box Offset

     

     Note: If the Fire sprinkler riser is outside, use weatherproof boxes and flex.

    These illustration show the basic raceway configurations for monitoring the fire sprinklersystem. Always make sure you flex to the device is positioned at the bottom of your box.

    - 19 -

  • 8/20/2019 Fire Alarm Installers Manual

    21/38

     

    SECTION 7

    Cut-in boxesSheet rock to just above ceiling:

    Drawing 200  

    In many cases it will be necessary to install a device in a finished wall; in this situation we willuse a “cut-in” box or “old work” box. We will use aluminum flex for our raceway. In the

    illustration above the sheet rock only extends above the ceiling line, making it easy to secure theflex to an adjustable bracket.

    - 20 -

  • 8/20/2019 Fire Alarm Installers Manual

    22/38

     

    Drawing 201  

    When the box is installed and secured in the wall we will trim and secure the flex to theadjustable bracket above the ceiling as shown in this illustration.

    Sheet rock up to deck:

    - 21 -

  • 8/20/2019 Fire Alarm Installers Manual

    23/38

     

    Drawing 202 

    In many cases the sheet rock will extend to the hard deck or ceiling, in this case we will need to

    use two cut-in boxes. The tricky part here is that we do not want to leave a large loop of flex in

    the wall. This means when we trim the flex for the second box we will be working very close tothe wall. Ideally we should not leave more than a 4” to 6” loop in the wall. The excess flex in the

    wall makes it tricky to pull the wire, but it can be done.

    - 22 -

  • 8/20/2019 Fire Alarm Installers Manual

    24/38

     

    Drawing 203  

    In this illustration we have trimmed our flex and installed our cut-in boxes in the wall.

    - 23 -

  • 8/20/2019 Fire Alarm Installers Manual

    25/38

     

    SECTION 8

    Wiring Methods (Securing to Steel)

    This section illustrates how to use tie wraps to secure your wire. These methods will eliminate

    ground faults caused by the insulation being worn or damaged on the metal beams, trusses, andcross members.

    In this illustration the fire cable is tie-wrapped to the tie-wrap going around the beam.

    Drawing 182

    Truss Tie Wrap

    Split Steel Truss

    Fire CableTie Wrap

      Never tie wrap the cable directly to any metal object, metal expand and constricts with the

    changes in temperature, this will eventually wear through the jacket of you cable creating groundfaults.

    - 24 -

  • 8/20/2019 Fire Alarm Installers Manual

    26/38

     

    The illustration below shows the wire run being directed down through the split truss where adevice box will be mounted. The wire is tied in such a manner as to be up off the metal edge.

    Drawing 183  

    Ground faults are very labor intensive and can be very costly, secure your wire runs properly.

    - 25 -

  • 8/20/2019 Fire Alarm Installers Manual

    27/38

     

    This illustration show how to create a 90 degree turn in your wire run. Notice that the wire doesnot touch the metal edge of the split beam.

    Fire Cable

    90 degree

    Beam Tie Wraps

    Cable Tie Wraps

    Drawing 184  

    The simple procedures shown in this section for tie wrapping your wire runs will save you time

    and ensure a quality installation.

    - 26 -

  • 8/20/2019 Fire Alarm Installers Manual

    28/38

     

    In this illustration we have a metal tray usually found in a building to support the walls and a perfect place to run your wire. Here we a showing how to secure your wire with clips, notice that

    we use two tie wraps, one around the clip and then one around the wire. The wire is not tied

    directly to the metal.

    Drawing 187  

    - 27 -

  • 8/20/2019 Fire Alarm Installers Manual

    29/38

     

    SECTION 9

    Wiring Methods (Securing to Wood)

    Large, Insulated

    Romex Staple

    J-Hook

     

    These illustrations show two acceptable ways of securing you wire runs to wood.

    - 28 -

  • 8/20/2019 Fire Alarm Installers Manual

    30/38

    SECTION 10

    Wire Protection

    Knock-out Bushing

    Knock-out Bushing

    Insulated Connector

    EMT Cap

    Connector Cap

    Non-insulated Connector

    Drawing 300 

    It is always important to protect you wire from sharp edges, in these example we are protectingour wire from our raceway. Each of the devices shown are inexpensive, easy to install, and will

    always be used.

    - 29 -

  • 8/20/2019 Fire Alarm Installers Manual

    31/38

     

    SECTION 11

    Labeling Circuits and TerminationsShrink wrapped labels

    Shrink-wrap

     

    In this illustration we are labeling the circuits. See table on page 32 for labeling codes.

    - 30 -

  • 8/20/2019 Fire Alarm Installers Manual

    32/38

     Nylon Labels

    Nylon Label

    O   -    S    

    L   C    

    -     1        

    -     2      

     

    In this illustration we are labeling the circuits. See table on page 32 for labeling codes.

    - 31 -

  • 8/20/2019 Fire Alarm Installers Manual

    33/38

     These tables are to establish consistency.

    Label Identification Codes:

    Code Code Code

    PNL Panel IDC Indicating Circuit H/S Horn and Strobe CombinationPS Power Booster SBS S Bus S Strobe Only

    VIP Voice Amplifier VBS Voice Bus SP/S Speaker and Strobe Combination

    NAC Notification Circuit XPNL Expander Panel SP Speaker Only

    SLC Signal Line Circuit Node Networked Panel ANN Annunciator  

    I IN O Out

    Device Labeling

    Sample: Device Label

    Circuit Device No.

    PS1-1-1 PS 1 1 1

    The sample above indicates a notification device on "Power Booster 1", "Circuit 1", and it is "Device 1".

    Sample: Device Label Circuit Device No.

    SLC-1-1 SLC 1 1

    The sample above indicates "Single Line Circuit 1", "Device 1". The Circuit ID. Is not used.

    Circuit Labeling

    Sample: Circuit Label

    Source Code Circuit

    I-NAC-1-PNL NAC 1

    O-NAC-1-2 NAC 1

    The sample above indicates the in and out circuits at a notification device. The "In" pair is from the Panel, Notification Circuit 1. The "Out" pair goes

    to Device 2.

    "I" In

    "O" Out

    In-Orgin / Out-Destination

    PNL

    2

    Output Orgin

    Output Orgin

    Description

    Input or Output

    Description

    Description Description Description

     

    BLACK BROWN DK. BLUE DK.PURPLE RED ORANGE LT. BLUE LT. PURPLE YELLOW WHITE

    The darker wire ina pair is the "Negative" ( - ), The lighter wire ina pair is the "Positive" ( + )

    Example: In a normal cable pair wehave a Black conductor ( - ) and a Red conductor ( + )

    DARK---------------------------------------------------------------------------------------------------------------------------------------------------------------------------LIGHT

    ( - ) ( + )

     

    - 32 -

  • 8/20/2019 Fire Alarm Installers Manual

    34/38

    SECTION 12

    Fire Alarm Panel Layouts

    Fire Alarm w/ Voice Evacuation

    Foot print - 8’ h X 6-1/2’w

    Gutter- 24” X 4” X 4”

    Drawing 80  

    - 33 -

  • 8/20/2019 Fire Alarm Installers Manual

    35/38

     

    Large Fire Alarm System

    Foot print - 8’ h X 4-1/2’w

    - 34 -

  • 8/20/2019 Fire Alarm Installers Manual

    36/38

     

    Medium Fire Alarm System

    Foot print- 8’ h X 4-1/2”w

    Drawing 82  

    - 35 -

  • 8/20/2019 Fire Alarm Installers Manual

    37/38

     

    Drawing 83 

    - 36 -

  • 8/20/2019 Fire Alarm Installers Manual

    38/38

    SECTION 13

    Don’ts

    1.   Never secure our wire runs to other trades hanging supports or conduit.

    2.   Never penetrate a wall with out a sleeve.

    3. 

     Never mount a device without a back box.4.   Never secure your wire runs directly to metal.5.   Never pull your wire into a box without the appropriate protection.

    6.   Never splice your wire runs in the field.

    7.   Never pull your wire runs on a diagonal.

    Do’s

    1.  For surface mounted devices, always run your conduit stub-up to above the ceiling or to

    the height of you horizontal run.

    2. 

    Always check the plans or with the GC for the thickness of the sheet rock being used.3.  Always use the appropriate mud rings on your boxes.

    4.  Always refer to the Fire plans before starting your project.