Sub Head Description Amount TOWERS I Wiring Rs. 95,315,151 II Low Tension System Rs. 17,648,900 III Submains and Cables Rs. 26,661,955 IV Distribution System Rs. 63,541,127 V Earthing Rs. 2,275,757 VI Fixtures and Fittings Rs. 7,753,445 VII Lightning Protection Rs. 441,428 VIII Fire Detection & Alarm System Rs. 6,075,539 Rs. 219,713,302 PART - A -- INTERNAL ELECTRICAL WORK FOR TOWERS, BASEMENTS, EWS, CLUB & SHOPPING COMPLEX TOWERS AND BASEMENT SUMMARY OF COST OF INTERNAL ELECTRICAL WORKS PART-A TOTAL (PART - A) C/O TO PAGE-130 OF VOLUME-2 11/07/2011 66

Upload: naam9

Post on 20-Jul-2016

20 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Final Offer Electrical

Sub Head Description Amount

TOWERS

I WiringRs. 95,315,151

II Low Tension SystemRs. 17,648,900

III Submains and CablesRs. 26,661,955

IV Distribution SystemRs. 63,541,127

V EarthingRs. 2,275,757

VI Fixtures and FittingsRs. 7,753,445

VII Lightning ProtectionRs. 441,428

VIII Fire Detection & Alarm SystemRs. 6,075,539

Rs. 219,713,302

PART - A -- INTERNAL ELECTRICAL WORK FOR TOWERS, BASEMENTS, EWS, CLUB &

SHOPPING COMPLEX

TOWERS AND BASEMENT

SUMMARY OF COST OF INTERNAL ELECTRICAL WORKS

PART-A

TOTAL (PART - A) C/O TO PAGE-130 OF

VOLUME-2

11/07/2011 66

Page 2: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.PART - A -- INTERNAL ELECTRICAL WORK FOR TOWERS, BASEMENTS, EWS, CLUB & SHOPPING COMPLEX

PALM GARDEN GROUP HOUSING AT SECTOR 83, GURGAON

TENDER FOR INTERNAL ELECTRICAL WORKS

Sl

No.Description Unit

Qty suuply labour

SUB-HEAD - I (WIRING)

1 Wiring for primary light points for switch controlled points with 3 x 1.5 sq. mm PVC

insulated stranded copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick

PVC surface/concealed conduit including the cost of providing circuit wiring with 3 x 2.5

sq mm PVC insulated stranded copper conductor 1100 volt grade wires and including

cost of providing saddles etc for surface conduiting and/or cost of cutting and filling

chases for recessed conduiting and including the cost of providing and fixing a 6 amp 240

Volt grid plate mounted switch with moulded cover plate in 1.6 mm thick G.I box etc.

complete as per specifications and as per direction Project in-charge. nos 33,315 637 159

2 Wiring for primary light points for MCB controlled points with 3 x 2.5 sq. mm PVC

insulated stranded copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick

PVC surface/concealed conduit including cost of providing saddles etc for surface

conduiting and/or cost of cutting and filling chases for recessed conduiting etc. complete

as per specifications and as per direction of Project in-charge. (Cost of MCB shall be paid

in DB item) nos 1,087 1,063 266

3 Wiring for secondary light points with 3x1.5 sq. mm PVC insulated stranded copper

conductor 1100 Volt grade wires in surface/concealed 20/25 mm dia 2 mm thick PVC

conduit including cost of providing saddles etc for surface conduiting and/or cost of

cutting and filling chases for recessed conduiting etc. complete as per specification and

as per direction of Project in-charge. nos 6,650 383 96

4 Wiring for Two-way light points switch controlled with 1.5 sq. mm PVC insulated stranded

copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick PVC

surface/concealed conduit including the cost of providing circuit wiring with 2.5 sq mm

PVC insulated stranded copper conductor 1100 volt grade wires and including cost of

providing saddles etc for surface conduiting and/or cost of cutting and filling chases for

recessed conduiting and including the cost of providing and fixing two sets of 6 amp 240

Volt grid plate mounted switch with moulded cover plate in 1.6 mm thick G.I box and

including the cost of running 1.5 sq mm PVC insulated copper conductor wire for loop

earthing etc. complete as per specifications and as per direction of Project in-charge. nos 72 816 204

5 Wiring for Ceiling/bracket fan points with 3 x 1.5 sq. mm PVC insulated stranded copper

conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed

conduit including the cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated

stranded copper conductor 1100 volt grade wires and including cost of providing saddles

etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting

and including the cost of providing and fixing fan hook box, a 6 amp 240 volt single pole

grid plate mounted switch with moulded cover plate in a recessed 1.6 mm thick G.I box

with including cost of providing stepped electronic fan regulator as required etc. complete

as per specification and as per direction of Project in-charge.

nos 8,726 1,038 259

6 Wiring for Exhaust fan points with 3 x 1.5 sq. mm PVC insulated stranded copper

conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed

conduit including the cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated

stranded copper conductor 1100 volt grade wires and including cost of providing saddles

etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting

and including the cost of providing and fixing 5 pin 6 amp shuttered socket outlet a 6 amp

240 volt single pole grid plate mounted switch with moulded cover plate in a recessed

1.6 mm thick G.I box etc. complete as per specification and as per direction of Project

in-charge.( This shall include socket and plug top near fan & switch shall be put near

entrance to toilet/kitchen) nos 5,294 715 179

Page 3: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.7 Wiring for a 5 pin 240 volt 6 amp single phase and neutral switch socket outlet with 3 x

1.5 sq. mm PVC insulated stranded copper conductor 1100 Volt grade wires in 20/25

mm dia 2 mm thick PVC surface/concealed conduit including the cost of providing circuit

wiring with 3 x 2.5 sq mm PVC insulated stranded copper conductor 1100 volt grade

wires and including cost of providing saddles etc as required for surface conduiting and/or

cost of cutting and filling chases as required and providing and fixing of a combined 5 pin

240 volt 6 amp socket outlet with safety shutters and 6 amp 240 volt single pole grid plate

mounted switch with moulded cover plate in recessed 1.6 mm thick G.I box etc.

complete as per specification and as per direction of Project in-charge.

nos 17,842 808 202

8 Wiring as in Item 7 above looped from an adjacent 6 amp switch socket outlet as required

and providing and fixing of a modular type 5 pin 240 Volt 6 amp shuttered socket outlet

and a modular type 6 amp 240 Volt single pole switch in a recessed 1.6 mm thick G.I

boxes with internal wiring and moulded front plates as per approved sample complete as

per specification and as per direction of Project in-charge. nos 50 467 117

9 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket outlets (1 outlet

wired on 1 circuit) with 3 x 4.0 sq. mm PVC insulated stranded copper conductor 1100

volt grade wires in 20/25mm dia 2 mm thick PVC surface/concealed conduit including

cost of providing saddles etc as required for surface conduiting and/or cost of cutting and

filling chases as required and including providing and fixing of a 6 pin 240 volt 16 amp

socket outlet with safety shutters and 16 amp 240 volt single pole grid plate mounted

switch with moulded cover plate in a recessed 1.6 mm thick G.I boxes etc. complete as

per specification and as per direction of Project in-charge. nos 1,206 1,574 393

10 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket outlets (2 outlets

wired on 1 circuit) with PVC insulated stranded copper conductor 1100 volt grade wires, 3

x 4.0 sq mm upto the first outlet and 3 x 4.0 sq mm from first to the second outlet, in

20/25 mm dia 2 mm thick PVC surface/concealed conduit including cost of providing

saddles etc as required for surface conduiting and/or cost of cutting and filling chases and

including providing and fixing of two sets of 6 pin 240 volt 16 amp socket outlet with

safety shutters and 16 amp 240 volt single pole grid plate mounted switches with

moulded cover plate in a recessed 1.6 mm thick G.I box etc. complete and as per

direction of Project in-charge. 1,528 1,318 330

11 Wiring for 2 nos 6 pin 240 volt 20/20 amp looped single phase and neutral switch socket

(2 outlets wired on 1 circuit) with PVC insulated stranded copper conductor 1100 volt

grade wires, 3 x 4.0 sq mm upto the first outlet and 3 x 4.0 sq mm from first to the second

outlet, in 20/25 mm dia 2 mm thick PVC surface/concealed conduit including cost of

providing saddles etc as required for surface conduiting and/or cost of cutting and filling

chases and including providing and fixing of two sets of 6 pin 240 volt 20 amp socket

outlet with safety shutters and 20 amp 240 volt single pole grid plate mounted switches

with moulded cover plate in a recessed 1.6 mm thick G.I box etc. complete and as per

direction of Project in-charge.(Ist point for A/C & IInd for geyser)This shall include socket

& plug top near geyser and controlling switch at door. nos 4,190 1,574 393

12 Wiring for AC points with 3 x 4.0 sq. mm PVC insulated stranded copper conductor 1100

volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed conduit including

cost of providing saddles etc as required for surface conduiting and/or cost of cutting and

filling chases as required and including providing and fixing of a 6 pin 240 volt 20 amp

socket outlet with safety shutters with moulded cover plate in recessed 1.6 mm thick GI

box including providing and fixing a 20 amp single pole 240 volt 20 amp switch with

moulded cover plate in recessed 1.6 mm thick G.I box located separately as per

drawings/instructions for AC controls complete as per specification and as per direction of

Project in-charge.(one outlet on one circuit) nos 414 1,574 393

13 Point wiring for 20 amp single phase socket outlets with 3 x 4 sq mm PVC insulated 1100

volt grade stranded copper conductor wires in 20/25 mm dia 2 mm thick PVC recessed

and/or surface conduiting system including the cost of cutting/making good chases in

brick work and including the cost of supplying and fixing 20/25 amp 10 kA SP MCB,

industrial type metal clad outlet in recessed 1.6 mm thick G.I box, metal clad plug top etc.

complete as per specifications and as per direction of Project in-charge. nos 5 1,574 393

14 Wiring for bell push with 3 x 1.5 sq. mm PVC insulated stranded copper conductor 1100

volt grade wires in 20/25 mm dia 2 mm thick PVC surface/ concealed conduit including

cost of providing saddles etc as required for surface conduiting and/or cost of cutting and

filling chases as required and including providing and fixing a grid plate mounted 6 amp

240 volt Bell push with moulded cover plate in recessed zinc chromate passivated 1.6

mm thick GI box etc. complete as per specifications and as per direction of Project in-

charge. nos 1,206 706 177

15 Supplying and Laying of 2 mm thick PVC conduiting system recessed/surface including

cost of providing GI fish wire saddles, Bends (PVC), Junction Boxes (MS) etc. and/or cost

of cutting and filling chases for recessed conduiting complete with accessories as per

specifications and as per direction of Project in-charge.

Page 4: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.a) 25 mm m 189,000 39 10

b) 32 mm m 1,080 49 12

c) 40 mm m 1,080 61 15

d) 50 mm m 580 72 18

16 Supplying and fixing of the following MS Conduits including the cost of draw/junction

boxes with accessories as required and including the cost of GI fish wire etc. complete as

per specifications and as per direction of Project in-charge.

a) 25 mm dia 16 SWG m 30,080 106 26

b) 32 mm dia 16 SWG m 480 123 31

c) 38 mm dia 14 SWG m 480 143 36

d) 50 mm dia 14 SWG m 480 192 48

17 Supplying and drawing following sizes of PVC insulated copper conductor single core

stranded cables in existing surface / recessed conduits as per specifications and/or as

per direction of Project in-charge. as required.

a) 3 x 1.5 sq mm (P+N+E) m 4,500 64 16

b) 3 x 2.5 sq mm (P+N+E) m 3,000 106 26

c) 3 x 4.0 sq mm (P+N+E) m 1,600 145 36

d) 3 x 6.0 sq mm (P+N+E) m 400 170 42

18 Supply, installation, testing and commissioning of the following switches, sockets in

recessed 1.6 mm thick GI box with moulded cover plate, including internal connections,

complete as per specifications and/or as per direction of Project in-charge.

a) 6 amp switch with box and cover plate nos 443 98 24

b) 6 amp switch and 5 pin socket outlet with box and cover plate nos 443 174 44

c) 16 amp switch and 6 pin socket outlet with box and cover plate nos 60 332 83

TOTAL SUB-HEAD - I carried over to Summary

SUB-HEAD - II (LOW TENSION SYSTEM)

1 Wiring for telephone points with 4 pair 0.61 mm annealed tinned electrolytic copper

conductor PVC insulated unshielded twisted wire in 25 mm dia 2 mm thick PVC

surface/concealed conduit upto central point and including cost of providing saddles etc

for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and

including the cost of providing and fixing of a single telephone cord grid plate mounted

outlet unit (RJ-11) with moulded cover plate in recessed 1.6 mm thick GI box complete as

required for telephone/intercom system.. nos 5,473 638 159

2 Wiring for telephone points with 2 pair 0.61 mm annealed tinned electrolytic copper

conductor PVC insulated unshielded twisted wire in 25 mm dia 2 mm thick PVC

surface/concealed conduit upto central point and including cost of providing saddles etc

for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and

including the cost of providing and fixing of a single telephone cord grid plate mounted

outlet unit (RJ-11) with moulded cover plate in recessed 1.6 mm thick GI box complete as

required for telephone/intercom system. nos 20 595 149

3 Supply and fixing of the following sheet steel clad wall/recess/floor mounting telephone

tag block of Krone make constructed from 14 SWG sheet steel, finished with powder

coated paint, with hinged gasketted door and complete with adequately rated and sized

telephone terminal block to receive incoming and outgoing wires. The cost shall be

complete with fixing arrangements, foundations etc as required

a) 10 Pair nos 13 978 245

b) 20 Pair nos 4 1,234 308

c) 30 Pair nos 8 1,488 372

d) 50 Pair nos 95 3,403 851

e) 300 Pair nos 2 14,036 3,509

f) 400 Pair nos 11 15,737 3,934

4 Supply, laying clamped to wall with suitable clamps saddles and bolts/ in ground including

the cost of digging and back filling with sand and brick protection as required and testing

and commissioning of the following multi core 0.61 mm annealed tinned copper

conductor PVC insulated and PVC sheathed and overall PVC sheathed armoured

telephone cables including making terminal joints, complete as per specification and /or

as per direction of Project in-charge.

a) 10 Pair m 80 81 20

b) 20 Pair m 50 121 30

c) 30 Pair m 300 149 37

d) 50 Pair m 4,030 183 46

Page 5: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.5 Supply and fixing of co-axial outlets for TV with moulded cover plate in recessed zinc

chromate passivated MS boxes, including termination complete in all respects as per

specification and / or as per direction of Project in-charge.. nos 5,367 723 181

6 Supply and laying of coaxial cable RG-59 for Branch line in existing surface/concealed

conduits upto the central point complete in all respects as per specification and / or as

per direction of Project in-charge. m 155,750 28 7

7 Supply, erection and commissioning of 3 way / 4 way spliter for cable TV in MS enclosure

with 3 mm thick hylum sheet cover as required at site and /or as per direction of Project in-

charge. nos 934 851 213

8 Supply, erection and commissioning of 6 way tap off in MS enclosures with 3 mm thick

hylum sheet cover for cable TV as required at site and /or as per direction of Project in-

charge.. nos 149 1,361 340

TOTAL SUB-HEAD - II carried over to Summary

SUB-HEAD - III (SUBMAINS AND CABLES)

1 Wiring for Submains with PVC insulated stranded copper conductor 1100 volt grade wires

in surface/concealed conduit including cost of providing saddles, Bends (PVC), Junction

Boxes (MS) etc including the cost of cutting and filling chases as required and as per

specification and as per direction of Project in-charge.

a) 2 x 10 sq mm in PVC 25 mm dia 2 mm thick conduit m 6,850 200 50

b) 4 x 10 sq mm in PVC 32 mm dia 2 mm thick conduit m 81 396 99

c) 4 x 16 sq mm in PVC 40 mm dia 2 mm thick conduit m 405 455 114

1.1 Wiring for Submains with PVC insulated stranded copper conductor 1100 volt grade wires

in surface/concealed conduit including cost of providing saddles, Bends (PVC), Junction

Boxes (MS) etc including the cost of cutting and filling chases as required and as per

specification and as per direction of Project in-charge.

a) 2 x 10 sq mm in PVC 25 mm dia 2 mm thick conduit m 1,900 200 50

b) 4 x 10 sq mm in PVC 32 mm dia 2 mm thick conduit m 30,000 396 99

c) 4 x 16 sq mm in PVC 40 mm dia 2 mm thick conduit m 4,200 455 114

2 Supply and laying in cable Tray/clamped to wall with suitable clamps saddles and bolts/

in ground including the cost of digging and back filling with sand and brick protection as

required and including testing and commissioning of the following 1100 volt grade

armoured PVC/XLPE insulated and sheathed aluminium conductor armoured cable

complete as required. The costs shall include providing a gap of 1D between all the

cables being laid and properl clamping with cable clamps and ties. Prices shall include

providing and fixing of Identification tags for all cables and route markers for cables in

ground etc. as per specification and or as per direction of Project in-charge.

a) 3 -1/2 core 300 Sq mm XLPE m 1,000 553 138

b) 3 -1/2 core 240 Sq mm XLPE m 50 485 121

c) 3 -1/2 core 185 Sq mm XLPE m 100 404 101

d) 3 -1/2 core 70 Sq mm XLPE m 4,800 298 74

e) 3 -1/2 core 50 Sq mm XLPE m 600 260 65

f) 4 core 35 Sq mm XLPE m 100 234 58

g) 4 core 25 Sq mm XLPE m 200 187 47

h) 4 core 16 Sq mm XLPE m 1,200 136 34

i) 4 core 10 Sq mm XLPE m 7,000 106 27

j) 4 core 6 Sq mm XLPE m 100 76 19

k) 2 core 10 Sq mm XLPE m 1,000 81 20

3 Providing and fixing of Cable jointing of the following XLPE cables 1100 Volt grade

including cost of tinned copper heavy duty lugs, double compression glands, insulation

tape and all requisite material for completion of joints.

a) 3 -1/2 core 300 Sq mm XLPE nos 40 1,310 328

b) 3 -1/2 core 240 Sq mm XLPE nos 2 1,148 287

c) 3 -1/2 core 185 Sq mm XLPE nos 4 851 213

d) 3 -1/2 core 70 Sq mm XLPE nos 418 425 106

e) 3 -1/2 core 50 Sq mm XLPE nos 26 340 85

f) 4 core 35 Sq mm XLPE nos 2 298 74

g) 4 core 25 Sq mm XLPE nos 4 170 42

h) 4 core 16 Sq mm XLPE nos 66 128 32

i) 4 core 10 Sq mm XLPE nos 248 128 32

Page 6: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.j) 4 core 6 Sq mm XLPE nos 4 64 16

k) 2 core 10 Sq mm XLPE nos 50 85 21

4 Supply and fixing of 14 SWG sheet steel slotted cable trays as per approved design and

MS painted angle supports spaced 1000 mm apart throughout the length as specified,

including the cost of 1 meter MS threaded rod hangers duly painted, hooks, dash

fasteners etc. for suspension from ceiling etc. as per specification and/or as per direction

of Project in-charge.

a) 150 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS

rod hangers) m 50 319 80

b) 300 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS

rod hangers) m 100 383 96

c) 450 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS

rod hangers) m 300 425 106

d) 600 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS

rod hangers) m 100 553 138

5 Supply and fixing of additional length of MS rod hangers duly painted with 1 coat of primer

and 2 coats enamel paint for supporting the Cable Trays for extension of the supports as

in item no. 4 above. kg 1,010 72 18

6 Supply and fixing Ladder type cable trays with 100 mm vertical sides on both ends as per

approved design of the following sizes, including cost of providing and fixing of 15 x 30 x

15 mm MS channel supports spaced 250 mm apart throughout the length with necessary

fixing arrangements with angle iron supports etc. as per specification and /or as per

direction of Project in-charge. Rate shall include providing and applying paint 1 coat of

primer and 2 coats of enamel paint for all the MS material .

a) 900 mm m 80 1,234 308

b) 750 mm m 150 1,067 267

c) 600 mm m 150 974 243

d) 450 mm m 350 502 125

e) 300 mm m 650 442 111

f) 150 mm m 40 378 94

7 Providing and fixing Steel work welded in built up sections/ framed work including cutting,

fixing in position with fasteners, including a priming coat of primer and two coats of

approved synthetic enamel paint.

a) In grating, frames, ladders, brackets, similar works kg 530 72 18

8 Supply and laying of the following RCC Hume pipe NP-2 grade including excavation,

refilling including compaction of soil as required for cable entry including the cost of

sealing the ends as required complete in all respects, as per spacification and /or as per

direction of Project in-charge.

a) 150 mm dia m 680 298 74

b) 200 mm dia m 500 349 87

c) 300 mm dia m 500 408 102

9 Providing and making of manhole chamber with masonry bricks and plastering inside with

1:3:6 and fixing of Heavy duty frame and pre cast RCC cover as required.

a) 600 x 600 x 750 mm deep nos 34 3,615 904

b) 450 x 450 x 750 mm deep nos 34 3,020 755

TOTAL SUB-HEAD - III carried over to Summary

SUB-HEAD - IV (DISTRIBUTION SYSTEM)

1 Supply, erection, testing and commissioning of the following sheet steel clad wall recess

mounting dust and vermin proof distribution boards constructed from 18 SWG sheet steel

IP 42 construction, duly powder coated with hinged gasketted door and housing the

following complete with suitably rated PVC insulated copper busbars with

interconnections and neutral bar assembly, earthing terminals complete as approved by

Project Manager. Padlocking facility shall be provided on the door.

a) 12 WAY SPN

Page 7: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.1-40 amp DP MCB incoming with 32 amp ON position latched contactor and 24 hours

programe timer for operation of incoming and 12 no. 6/16/20 amps SP 10 kA MCB with

thermal magnetic protective releases out goings nos R/O 12,760 3,190

b) 12 WAY SPN

1-63 amp SPN 10 kA MCB with thermal magnetic protective releases incoming with 1-63

amp DP 30 mA ELCB incoming and 12 nos 6/16/20/25 amps SP 10 kA MCB with

thermal magnetic protective releases out goings. nos R/O 7,230 1,808

c) 6 WAY TPN (per phase isolation)-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3

single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 6 no.

6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings. nos R/O 5,529 1,382

d) 8 WAY TPN (per phase isolation)-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3

single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 8 no.

6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings. nos R/O 15,737 3,934

e) 8 WAY TPN with Timer on 2-phases-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with

1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming and 8 no. 6/16/20

amps SP 10 kA MCB with thermal magnetic protective releases out goings

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32

amp ON position latched contactor and 24 hours programe timer for operation of

incoming and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective

releases out goings nos R/O 21,265 5,316

f) 12 WAY TPN with Timer on 2-phases-Vertial DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with

1 single phase bank comprising of 1- 63 amp 30 mA DP ELCB incoming and 12 no.

6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32

amp ON position latched contactor and 24 hours programe timer for operation of

incoming and 12 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective

releases out goings nos R/O 27,220 6,805

g) Incomer DB for Penthouses-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 2 nos

63 amp SPN 10 kA MCB with thermal magnetic protective releases out goings. nos R/O 2,127 532

h) 8 Way VTPN

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 8 nos

6-32 amp 10 kA TP MCB with thermal magnetic protective releases out goings nos R/O 15,737 3,934

2 Design, manufacture, supplying, fixing, testing and commissioning of the following 2 mm

thick sheet steel enclosed, wall mounting, dust and vermin proof with IP 42 protection

triple pole and with 100% neutral Rising Mains with PVC insulated aluminium busbars

with a maximum current density of 1.0 amp per sq mm and suitable to withstand a

symmetrical fault level of 45 kA at 415 volts, complete with fire proof barriers at every

floor level, expansion joints, thrust pads to support weight of busbars, fully gasketed

covers, with arrangement to plug in tap off boxes as required and connecting chamber for

incoming isolator, powder coating, complete with fixing arrangements as required and

with 2 runs of aluminium strip for earthing as required .

a) 400 amps m R/O 8,506 2,127

3a Supplying, erection, testing and commissioning of Tap-Off Boxes with 125 amp TPN

MCCB (25 kA) and cable end boxes as required nos R/O 8,081 2,020

3b Supplying, erection, testing and commissioning of Tap-Off Boxes with 160 amp TPN

MCCB (25 kA) and cable end boxes as required nos R/O 8,932 2,233

4 Meter Boards Tap-Off Boxes

Page 8: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of

meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation

with reinforcement of suitable size angle iron, channels, T irons, flats wherever

necessary for large meter boards. Cable gland plates shall be provided at top and bottom

both and windows for meter reading, locking arrangement (pad-lock & seal) with wiring

upto KWH meter & meter to MCB shall be done by using adequately rated flexible single

core copper wire. The boards shall be treated with all anticorrosive process before

painting as per standards with final approved shade of powder coated as approved 2 nos.

earthing terminals shall be provided for 3 phase meter boards and to be connected with

the earthing by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for 415 V, 3

phase, 4 wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth

etc to match with site conditions.

An approval shall be taken for each panel before manufacturing. Galvanised hardwares

with zinc passivation shall be used in fabrication of boards.

a) 6 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

6 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 6 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 8 way

terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.nos R/O 55,291 13,823

b) 5 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

5 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 5 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 8 way

terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 52,739 13,185

c) 4 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

Page 9: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.4 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 4 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 6 way

terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 46,785 11,696

d) 3 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

3 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 3 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 6 way

terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 38,278 9,570

e) 2 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

2 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 2 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 4 way

terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 25,519 6,380

f) 9 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

9 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 9 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 12 way

terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 80,810 20,202

5 Dual Pre-Paid meter

Page 10: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.Design,supply ,installation testing and commissioning of BIS approved single phase dual

energy meter for recording dual electric supply from grid and DG with KWH & KVAH max

demand communication port,billing,storage facilities ,control panel for sensing supply

from DG sets, data transfer & receiving hub, AMR system. DLC with energy management

software with load manager system and recharge coupon generation software &

connecting accessories for prepaid system.

1 phase digital electronic energy meter (for tariff application) nos R/O 15,312 3,828

ALTERNATIVELY

1 Supply, erection, testing and commissioning of the following sheet steel clad wall recess

mounting dust and vermin proof distribution boards constructed from 18 SWG sheet steel

IP 42 construction, duly powder coated with hinged gasketted door and housing the

following complete with suitably rated PVC insulated copper busbars with

interconnections and neutral bar assembly, earthing terminals complete as approved by

Project Manager. Padlocking facility shall be provided on the door.

a) 12 WAY SPN

1-40 amp DP MCB incoming with 32 amp ON position latched contactor and 24 hours

programe timer for operation of incoming and 12 no. 6/16/20 amps SP 10 kA MCB with

thermal magnetic protective releases out goings nos 18 7,230 1,808

b) 12 WAY SPN

1-63 amp SPN 10 kA MCB with thermal magnetic protective releases incoming with 1-63

amp DP 30 mA ELCB incoming and 12 nos 6/16/20/25 amps SP 10 kA MCB with

thermal magnetic protective releases out goings.nos 20 6,635 1,659

c) 6 WAY TPN (per phase isolation)-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3

single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 6 no.

6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.

nos 1,098 12,334 3,084

d) 8 WAY TPN (per phase isolation)-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3

single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 8 no.

6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.

nos 5 15,737 3,934

e) 8 WAY TPN with Timer on 2-phases-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with

1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming and 8 no. 6/16/20

amps SP 10 kA MCB with thermal magnetic protective releases out goings

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32

amp ON position latched contactor and 24 hours programe timer for operation of

incoming and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective

releases out goings nos 35 18,714 4,679

f) 12 WAY TPN with Timer on 2-phases-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with

1 single phase bank comprising of 1- 63 amp 30 mA DP ELCB incoming and 12 no.

6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32

amp ON position latched contactor and 24 hours programe timer for operation of

incoming and 12 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective

releases out goings

nos 10 22,610 5,652

g) Incomer DB for Penthouses-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 2 nos

63 amp TPN 10 kA MCB with thermal magnetic protective releases out goings. nos 72 2,722 680

h) 8 Way VTPN-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 8 nos

6-32 amp 10 kA TP MCB with thermal magnetic protective releases out goings nos 2 14,631 3,658

Page 11: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.j) 8 WAY SPN

1-32 amp SPN MCB incoming and 8 nos 6/16/20 amps SP 10 kA MCB with thermal

magnetic protective releases out goings nos 1 5,529 1,382

k) 4 WAY SPN

1-32 amp SPN MCB incoming and 4 nos 6/16/20 amps SP 10 kA MCB with thermal

magnetic protective releases out goings nos 194 2,977 744

2 Design, manufacture, supplying, fixing, testing and commissioning of the following 2 mm

thick sheet steel enclosed, wall mounting, dust and vermin proof with IP 42 protection

triple pole and with 100% neutral Rising Mains with PVC insulated aluminium busbars

with a maximum current density of 1.0 amp per sq mm and suitable to withstand a

symmetrical fault level of 45 kA at 415 volts, complete with fire proof barriers at every

floor level, expansion joints, thrust pads to support weight of busbars, fully gasketed

covers, with arrangement to plug in tap off boxes as required and connecting chamber for

incoming isolator, powder coating, complete with fixing arrangements as required and

with 2 runs of aluminium strip for earthing as required .

a) 400 amps m 620 4,679 1,170

3a Supplying, erection, testing and commissioning of Tap-Off Boxes with 125 amp TPN

MCCB (25 kA) and cable end boxes as required nos 169 10,208 2,552

3b Supplying, erection, testing and commissioning of Tap-Off Boxes with 160 amp TPN

MCCB (25 kA) and cable end boxes as required nos 12 11,484 2,871

4 Meter Boards Tap-Off Boxes

Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of

meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation

with reinforcement of suitable size angle iron, channels, T irons, flats wherever

necessary for large meter boards. Cable gland plates shall be provided at top and bottom

both and windows for meter reading, locking arrangement (pad-lock & seal) with wiring

upto KWH meter & meter to MCB shall be done by using adequately rated flexible single

core copper wire. The boards shall be treated with all anticorrosive process before

painting as per standards with final approved shade of powder coated as approved 2 nos.

earthing terminals shall be provided for 3 phase meter boards and to be connected with

the earthing by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for 415 V, 3

phase, 4 wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth

etc to match with site conditions.

An approval shall be taken for each panel before manufacturing. Galvanised hardwares

with zinc passivation shall be used in fabrication of boards.

a) 6 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

6 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 6 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with

8 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 153 42,532 10,633

b) 5 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Page 12: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

5 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 5 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with

8 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 6 38,278 9,570

c) 4 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

4 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 4 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with

6 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.nos 8 34,025 8,506

d) 3 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

3 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 3 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with

6 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 4 25,519 6,380

e) 2 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

Page 13: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.2 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 2 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with

4 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 8 18,714 4,679

f) 9 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

9 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 9 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with

12 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 2 102,075 25,519

5 Dual Pre-Paid meter

Design,supply ,installation testing and commissioning of BIS approved three phase 4wire

dual energy meter for recording dual electric supply from grid and DG with KWH & KVAH

max demand communication port,billing,storage facilities ,control panel for sensing

supply from DG sets, data transfer & receiving hub, AMR system. DLC with energy

management software with load manager system and recharge coupon generation

software & connecting accessories for prepaid system.

3 phase digital electronic energy meter (for tariff application) nos 1,026 9,357 2,339

6 Design ,supply ,installation, testing and commissioning of required software to make the

kWH meter functional in coordination with kWH meter manufacturer and facility

mangement team for prepaid/postpaid tariff application system for dual resistor (

recording) KWH meter to effectively monitor/control the tariff as per individual site

condition complete with latest version of computer & printer etc as required. ( Integrated

with existing software installed) job 1 170,126 42,532

7 Design, manufacture, supply, installation, testing and commissioning of cubical type

electrical control panel comprising of necessary contactors.PLA relays terminals etc to

provide signaled DC supply to the dual source energy meters.( Integrated with existing

software installed) set 1 255,189 63,797

8 Design, manufacture, supplying, fixing in position, testing and commissioning of the

following rating Adopter Box for Rising Mains complete with interconnections as required.

The Adopter box shall be complete with voltmeter and ammeter with requisite CT's

a) 1-400 amp TPN switch isolator nos 24 11,909 2,977

9 Supplying and laying of following sizes 2 mm thick PVC conduit in recess/surface

including providing coupler, junction boxes complete as required from DG panel to all

meter boards ( to get 24V DC signal to energy meter to record consumotions ON DG

seperately)

a 25mm dia PVC conduit m 3,200 39 10

b 20 mm dia 2 mm thick PVC conduit from meter board to display unit in the apartment

m 31,000 33 8

c Supplying and laying of 2 x 2.5sq.mm PVC insulated copper wire m 3,500 81 20

9.1 Supplying and laying of 0.61 mm dia PVC insulated copper conductor wires in existing

conduit from Meter Board to freedom display units.

Three pair 0.61 mm dia (telephone wire) m 31,000 19 5

Page 14: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.10 Design, manufacture, supplying fixing in position, testing and commissioning of the

following front operated cubicle type, front access 2mm thick steel enclosed free

standing, dust and vermin proof, switchboard with IP42 protection with hinged and

lockable doors complete with interconnections, tinned copper crimping lugs, bonding to

earth and powder coating suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system,

and suitable for a fault level of 25 MVA symmetrical at 415 volts.

All switchboards shall have provision for entry of cables from the top or bottom as

required.

All live accessible parts shall be shrouded and all equipment shall be finger touch proof.

The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and

busbar supports shall be used. Padlocking facility shall be provided on all outgoing

feeders doors and switch handles shall be lockable in OFF position.The short circuit rating for MCCB's shall be Ics values

10.1 SWITCHBOARD - TOWER (1 TO 12)

INCOMINGS

2 nos 630 amp 4P Switch Isolator complete with

a) 3 nos Cast resin current transformers of 630/5 ratio Class 1.0 for metering

b) 1 no AVF digital meter (Ampere,Voltage Frequency)

c) 1 no. 3 phase 4 wire unbalanced load, Digital kWH CT operated meter alongwith CT’s

class 1.0 accuracy 10 VA Burden.

d) 1 set of RYB Phase indicating lamps (LED type)

e) Red / Green ON/OFF indicator (LED type)

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 800

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The main neutral busbar is to be of 50%

capacity.

BUS COUPLER

1 nos 630 amp 4P Switch Isolator complete

INTERLOCKING

The Incoming & Buscoupler shall be electrically & mechanically interlocked such that

incomers cannot be paralleled.

OUTGOING UNITS

LEFT HAND SECTION

1 no. 400 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

2 no. 160 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

1 no. 100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication.

1 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON

indication.

RIGHT HAND SECTION

1 no. 400 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

2 no. 160 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication.

Page 15: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 12 297,720 74,430

10.2 SWITCHBOARD - LIFTS-TOWER (1 TO 12)

INCOMINGS

1 no. 160 amp 4-P Changeover switch complete with

The incomers shall have the following indicating panel

a) 3 nos Cast resin current transformers of 160/5 ratio Class 1.0 for metering

b) 1 no AVF digital meter (Ampere,Voltage Frequency)

c) 1 set of RYB Phase indicating lamps (LED type)

d) Red / Green ON/OFF indicator (LED type)

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

OUTGOING UNITS

3 nos 100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

3 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication.

1 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON

indication.

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 12 127,595 31,899

10.3 SWITCHBOARD - BASEMENT VENTILATION

INCOMINGS

1 nos 160 amp TPN Switch Isolator complete with

The incomers shall have the following indicating panel

a) 3 nos Cast resin current transformers of 160/5 ratio Class 1.0 for metering

b) 1 no AVF digital meter (Ampere,Voltage Frequency)

c) 1 set of RYB Phase indicating lamps (LED type)

d) Red / Green ON/OFF indicator (LED type)

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

OUTGOING UNITS

8 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication.

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 12 144,607 36,152

11 Design manufacture, supply installation testing and commissioning of 1250 VA Inverter

system for a constant secondary voltage of 240 volts at 50 Hz, single phase, batteries

backup of minimum 4 hour duration including, batteries, battery chargers, rectifiers,

transformers, controls, protection and instruments etc complete as required. nos 12 26,369 6,592

Page 16: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.12 Design, manufacture, supplying fixing in position, testing and commissioning of the

following front operated cubicle type, front access 2mm thick steel enclosed free

standing, dust and vermin proof, switchboard with IP42 protection with hinged and

lockable doors complete with interconnections, tinned copper crimping lugs, bonding to

earth and powder coating suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system,

and suitable for a fault level of 25 MVA symmetrical at 415 volts.

All switchboards shall have provision for entry of cables from the top or bottom as

required.

All live accessible parts shall be shrouded and all equipment shall be finger touch proof.

The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and

busbar supports shall be used. Padlocking facility shall be provided on all outgoing

feeders doors and switch handles shall be lockable in OFF position.

The short circuit rating for MCCB's shall be Ics values

A. EWS MAIN PANEL

INCOMING

1 nos 400 amp TPN Switch Isolator complete with

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 400

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 50%

capacity.

INDICATING PANEL

The incomers shall have the following indicating panel

a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for metering

b) 1 no ammeter of 96 mm sq scaled 0-400 amps with 3 way and OFF selector switch

c) 1 no voltmeter of 96 mm sq scaled 0- 500 volts with 3 way & OFF selector switch

d) 1 set of three White phase indicating lamps

OUTGOING UNITS

11 nos.100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication.

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 1 127,595 31,899

B EWS COMMON PANEL

INCOMING

2 nos 100 amp 4P Switch Isolator complete with

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 100

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 100%

capacity.

INDICATING PANEL

The incomers shall have the following indicating panel

a) 3 nos Cast resin current transformers of 100/5 ratio Class 1.0 for metering

b) 1 no ammeter of 96 mm sq scaled 0-100 amps with 3 way and OFF selector switch

c) 1 no voltmeter of 96 mm sq scaled 0- 100 volts with 3 way & OFF selector switch

d) 1 set of three White phase indicating lamps

INTERLOCKING

Page 17: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.The Incoming shall be interlocked such that incomers cannot be paralleled.

OUTGOING UNITS

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication.

2 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON

indication.

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 1 119,088 29,772

E SWITCHBOARD - CLUB

INCOMING

1 nos 400 amp TPN Switch Isolator complete with

a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for metering

b) 1 no digital electronic ammeter 400 amps

c) 1 no digital electronic voltmeter 500 volts

d) 1 set of three White phase indicating lamps (LED type)

e) Red / Green ON/OFF indicator (LED type)

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 600

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 50%

capacity.

OUTGOING UNITS

2 nos 125 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with Digital Electronic Energy Meter with requisite CT suitable

for remote data logging

S

12 nos 63 amp 10 kA TPN MCB with thermal magnetic release complete with Digital

Electronic Energy Meter with requisite CT suitable for remote data logging

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 1 161,620 40,405

3 Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of

meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation

with reinforcement of suitable size angle iron, channels, T irons, flats wherever

necessary. Cable gland plates shall be provided at top and bottom both and windows for

meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH meter &

meter to MCB shall be done by using adequately rated flexible single core copper wire.

The boards shall be treated with all anticorrosive process before painting as per

standards with final approved shade of powder coated as approved, 2 nos. earthing

terminals shall be provided for 3 phase meter boards and to be connected with the

earthing of rising mains by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for

415 V, 3 phase, 4 wire, 50 Hz supply system. Boards shall be fabricated in length,

height, depth etc to match with site conditions.

The Meter Board shall be in Non-compartmentalized construction.

An approval shall be taken for each panel before manufacturing.

A SHOPPING METER BOARD

INCOMING

1 nos 100 amp TPN Switch Isolator complete with

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbar rated at 100 amp

having a maximum current density of 1 amp per sq. mm suitable to withstand

symmetrical fault level of 25 M.V.A at 415 volts .The neutral busbar is of 100% capacity.

Page 18: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.OUTGOING UNITS

1 no 63 amp TPN 10 kA MCB with thermal magnetic protective releases.

4 no 32 amp TPN 10 kA MCB with thermal magnetic protective releases.

14-32 amp SPN 10 kA MCB with thermal magnetic protective releases each with

provision for fixing of 32 A DHBVNL approved Single phase digital dual register prepaid

electronic energy meter.

The switchboard shall be complete with all interconnection, riser , internal wiring, labels

etc. complete as required. nos 1 72,303 18,076

B METER BOARD -EWS

INCOMING

1 nos 100 amp TPN Switch Isolator complete with

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbar rated at 100 amp

having a maximum current density of 1 amp per sq. mm suitable to withstand

symmetrical fault level of 25 M.V.A at 415 volts .The neutral busbar is of 100% capacity.

OUTGOING UNITS

2 no 32 amp TPN 10 kA MCB with thermal magnetic protective releases.

20-32 amp SPN 10 kA MCB with thermal magnetic protective releases each with

provision for fixing of 32 A DHBVNL approved Single phase digital dual register prepaid

electronic energy meter.

The switchboard shall be complete with all interconnection, riser , internal wiring, labels

etc. complete as required. nos 9 68,050 17,013

C Design,Supply installation testing & commissioning of BIS approved single phase dual

register energy meter for recording dual electric supply from grid and DG with kWH &

kWAh max demand communication port, billing storage facilities, control panel for

sensing supply from DG sets, data transfer & receiving hub,AMR system. DLC with

energy management software with load manager system & recharge coupon generation

software & connecting accessories for prepaid system.

single phase dual register digital electronic prepaid energy meter ( for tariff application)

nos 194 12,760 3,190

TOTAL SUB-HEAD - IV carried over to Summary

SUB HEAD V : EARTHING

1 Supplying and laying of the following earthing clamped to wall with suitable clamps

saddles and fixing bolts/ in ground/RCC slab along with submain conduit including the

cost of digging and back filling with sand and brick protection as required and complete

as required to comply with IS 3043:1987

a) 25 mm x 6 mm GI strip m 3,800 83 21

b) 8 SWG GI Wire m 102,200 7 2

c) 6 SWG GI Wire m 20,400 8 2

2 Supply and laying of the following GI pipe in ground including excavation, refilling as

required for earth strips etc. as required complete

a) 80 mm dia m 181 298 74

3 Providing and making earthpits including the cost of 600 mm x 600 mm x 6 mm GI plate

electrode 20 mm dia GI pipe, CI funnel with wiremesh charcoal, salt, all earth work,

masonry enclosure with CI frame & cover plate having locking arrangement complete as

per IS 3043:1987. nos 80 7,230 1,808

4 Providing and laying earth connections from earth electrode with 2 x 6 SWG GI wire in 25

mm dia. GI pipe from earth electrode as required as per specifications. m 181 128 32

TOTAL SUB HEAD V carried over to Summary

Page 19: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.SUB-HEAD -VI (FIXTURES AND FITTINGS)

1a Supply of the following light fixtures complete with housing, reflectors, all accessories i.e.

copper wound ballast, HPF condensors, starters, holders etc. complete as required

a) 1x18 W CFL recess mounting downlighter as approved including providing lamps and

other accessories (base Rate Rs 800/-) nos 780 927 232

b) 1x18 W CFL surface mounting downlighter as approved including providing lamps and

other accessories (base Rate Rs 600/-) nos 3,693 681 170

c) 1x28 W T5 lamp surface mounting box type fixture as approved including providing lamps

and other accessories (base Rate Rs 800/-) nos 790 1,084 271

d) 1x11 W CFL lamp surface mounting bulk head fixture as approved including providing

lamps and other accessories (base Rate Rs 450/-) nos 530 564 141

e) 1x11 W CFL lamp surface mounting wall bracket fixture as approved including providing

lamps and other accessories (base Rate Rs 450/-) nos 24 468 117

f) 2x28 W T5 lamp pendat mounting box type fixture as approved including providing

downrods, lamps and other accessories (base Rate Rs 1200/-) nos 970 1,276 319

1b Receiving, assembling, erection, connecting, testing and commissioning of the following

light fixtures complete with housing, reflectors, all accessories i.e. copper wound ballast,

HPF condensors, starters, holders etc. complete as required

a) 1x18 W CFL recess mounting downlighter as approved including providing lamps and

other accessories nos 780 64 16

b) 1x18 W CFL surface mounting downlighter as approved including providing lamps and

other accessories nos 3,693 64 16

c) 1x28 W T5 lamp surface mounting box type fixture as approved including providing lamps

and other accessories nos 790 64 16

d) 1x11 W CFL lamp surface mounting bulk head fixture as approved including providing

lamps and other accessories nos 530 64 16

e) 1x11 W CFL lamp surface mounting wall bracket fixture as approved including providing

lamps and other accessories nos 24 64 16

f) 2x28 W T5 lamp pendat mounting box type fixture as approved including providing

downrods, lamps and other accessories nos 970 64 16

2 Supply, fixing, testing and commissioning of 240 Volt single phase ceiling fans of 1200

mm Sweep including supply of 19 mm heavy gauge GI down rod of length as required

complete. nos 17 1,488 372

3 Supply, fixing, testing and commissioning of 240 Volt single phase heavy duty Exhaust

Fans 300 mm dia complete with all accessories as required and with 6 amp 3 pin plug top

as required. nos 17 1,531 383

4 Receiving, storing, transportation at site, unpacking, assembling, fixing, testing and

commissioning of 240 Volt single phase Buzzer as required complete. nos 1,206 64 16

TOTAL SUB-HEAD - VI carried over to Summary

SUB HEAD VII : LIGHTNING PROTECTION

1 Air Terminal & Accessories

Supplying, Erection & commissioning of External Lightning Wide Area Protection System

based on pro-active Early Streamer Emission (ESE) Technology type SATELIT-3-60.

Device shall emit electromagnetic impulse in the form of a controlled emission of

streamers into the air 60 microseconds earlier than naturally formed streamers & polarise

the tip with a voltage between 35 kV & 45 kV . Device confirming to NFC17-102 or UNE

21186 standards. The device shall be mounted at least 5 meter clear to the highest point

by Support Mast of 50mm dia Schedule 80 MS Pipe duly galvanized with minimum 85

micron zinc coating with foundation to suite Mast with concrete to cover 300mmX300mm

floor area & upto 600mm height complete as required sets 3 8,932 2,233

2 Low Impedance high voltage down conductor & accessories

Supply, installation, testing & commissioning of down conductor. The Down conductor

shall be of 25X3mm GI strip/Tape. They should be fixed to the structure by means of 2

fasteners every 1.0 meters horizontally & 0.5 meter vertically, It should then run down

the elevation pole and take the shortest direct route down the outside of the building to

the earth termination network, avoiding any sharp corners, thereby providing a low

impedance path from the air terminal to its earth termination system. m 300 95 24

3 Lightning Discharge Counter

Page 20: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.Supply, installation, testing & commissioning of Lightning Discharge Counter. The

lightning event counter suitable for 1.0KA - 100KA . Counter housed in weather proof

IP67 enclosure with fixing clamps, etc. sets 3 21,265 5,316

4 Maintenance Free Earthing

Supply, Installation, Testing & Commissioning of long life, Maintenance Free Electrolytic

Earthing System Earth pit should consists of 3 nos. 1.2 meters long 14mm dia MS Rod

moleculerly bonded with 250 micron copper coating and treated with 10 kgs of Terec+,

The earthing pit shall be provided with suitable sturdy Test Well for observation. The

Earth Pit shall be covered with 25mm thick gravel/ tiles The Installation procedures

should be followed as instructed by the Earth Electrode Supplier)

nos 6 15,312 3,828

5 Supplying fixing, testing and commissioning of LED Aviation lights, complete as per

Wipro Cat WAN 20001 or Bajaj Cat BJAOL-1, complete with flasher etc as required

nos 3 6,380 1,595

6 Supplying, fixing, testing and commissioning of photochromatic switch for automatic

ON/OFF of Aviation light as required. nos 3 5,529 1,382

7 Wiring for aviation light with 3 core 2.5 sq.mm XLPe insulated PVC sheathed copper

conductor armoured cable from M/C room DB to aviation light. m 200 132 33

8 Supply and fixing GI strip 25 mm x 6 mm along outside wall/ columns as vertical

conductors with suitable GI fasteners, brass fixing screws, copper clamps & saddles

complete as required. m 50 83 21

9 Supply and fixing GI strip 25 mm x 6 mm along roof as horizontal conductors with

suitable GI fasteners, brass fixing screws, copper clamps & saddles complete as

required. m 200 83 21

10 Supply and laying in ground of GI strip 32 mm x 6 mm for connecting to the GI earth

plate at one end and vertical conductor strip at the other end including the cost of digging

and back filling complete m 30 179 45

11 Providing and making earthpits including the cost of 600 mm x 600 mm x 6 mm GI plate

electrode 50 mm dia GI pipe, CI funnel with wiremesh charcoal, salt, all earth work,

masonry enclosure with CI frame & cover plate having locking arrangement complete as

per IS 3043:1987. nos 2 7,230 1,808

12 Supplying and laying in ground of GI strip 32 mm x 6 mm for interconnecting the various

Lightning arrestor earth pits, including the cost of digging and back filling, complete as

required. m 200 115 29

13 Supply and fixing testing joints made of 25 mm x 6 mm thick GI strip 125 mm long with 4

Nos. GI bolts, nuts, check nuts and spring washers complete as required. nos 2 166 41

14 Providing and fixing Lightning Conductor Finials made of 25 mm dia 300 mm long GI tube

having a single prong at the top with 85 mm dia 6 mm thick GI base plate complete as

required. nos 1 1,531 383

15 Supply and fixing of DMC/SMC insulator complete with GI clamps, Nut Bolts supports

wherever is required. nos 30 485 121

TOTAL SUB-HEAD - VII carried over to Summary

SUB-HEAD -VIII (FIRE DETECTION & ALARM SYSTEM)

1 Supply, installation, testing and commissioning of wall or ceiling mounted 240 Volt AC

illuminated Signs having on its front a white perspex sheet with the letters 'FIRE EXIT'

painted in red including the cost of in-built rechargeable batteries suitable for 30 minute

operation and including the cost of accessories for surface or recessed or ceiling

suspended mounting complete as required. nos 514 1,849 462

2 Supply installation testing and commissioning of dust and vermin proof Manual call boxes

with push button to initiate audio visual alarm with breakable glass cover as per detailed

specifications complete with a steel chain including the cost of accessories for surface

mounted as required nos 514 554 139

Page 21: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.3 Supply installation test and commissioning of the following 8 ohm size speaker-cum-

hooter units with line matching transformer suitable for broadcast of speech and alarm

siren complete as required suitable for recessed/surface mounting complete with

enclosure as approved by Project Manager and as required. nos 211 740 185

4 Supply, installation, testing and commissioning of wall recess mounting 24 zone

microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential

free contacts as per detailed specifications with alarms, controls and indications as per

detailed specifications and with an integral power supply unit and complete with a suitably

rated set of batteries and trickle charged from 240 volt AC mains supply, including the

cost of mounting accessories as required, complete. nos 10 62,873 15,718

4 Supply, installation, testing and commissioning of wall recess mounting 16 zone

microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential

free contacts as per detailed specifications with alarms, controls and indications as per

detailed specifications and with an integral power supply unit and complete with a suitably

rated set of batteries and trickle charged from 240 volt AC mains supply, including the

cost of mounting accessories as required, complete. nos 2 55,476 13,869

5 Supply, installation, testing and commissioning of wall recess mounting 15 zone

microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential

free contacts as per detailed specifications with alarms, controls and indications as per

detailed specifications and with an integral power supply unit and complete with a suitably

rated set of batteries and trickle charged from 240 volt AC mains supply, including the

cost of mounting accessories as required, complete. nos 1 51,777 12,944

6 Supply, installation, testing and commissioning of wall recess mounting 10 zone

microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential

free contacts as per detailed specifications with alarms, controls and indications as per

detailed specifications and with an integral power supply unit and complete with a suitably

rated set of batteries and trickle charged from 240 volt AC mains supply, including the

cost of mounting accessories as required, complete. nos 1 48,079 12,020

7 Wiring with 2 core 1.5 Sqmm standard copper conductor FRLS 660/1100 volts grade

wires in existing concealed/surface MS conduit etc. as per specification and as required

including the cost of crimped termination's. m 36,500 40 10

8 Supply and laying control cabling with copper conductor PVC insulated and PVC

sheathed armoured Control cables in existing pipes/conduits or on existing tray including

the cost of making connections, complete etc. etc. as per specification and as required

as below:

a) 10 core 2.5 sq mm m 5,100 229 57

TOTAL SUB-HEAD -VIII carried over to Summary

Page 22: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

PALM GARDEN GROUP HOUSING AT SECTOR 83, GURGAON

TENDER FOR INTERNAL ELECTRICAL WORKS

supply

amount

Labour

Amount rate Amount

21,232,316 5,308,079 797 26,540,395

1,155,594 288,899 1,328.88 1,444,493

2,548,918 637,230 479.12 3,186,148

58,774 14,694 1,020.39 73,468

9,055,773 2,263,943 1,297.24 11,319,716

3,785,549 946,387 893.83 4,731,936

Page 23: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

14,419,476 3,604,869 1,010.22 18,024,345

23,368 5,842 584.21 29,211

1,898,080 474,520 1,967.33 2,372,600

2,013,953 503,488 1,647.54 2,517,441

6,594,490 1,648,623 1,967.33 8,243,113

651,580 162,895 1,967.33 814,475

7,869 1,967 1,967.33 9,837

851,465 212,866 882.53 1,064,331

-

Page 24: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.7,346,808 1,836,702 48.59 9,183,510

52,721 13,180 61.02 65,902

66,390 16,597 76.84 82,987

41,946 10,486 90.40 52,432

-

3,181,501 795,375 132.21 3,976,877

59,013 14,753 153.68 73,766

68,559 17,140 178.54 85,699

91,991 22,998 239.56 114,989

-

288,828 72,207 80.23 361,035

317,304 79,326 132.21 396,630

231,424 57,856 180.80 289,280

67,981 16,995 212.44 84,976

-

43,251 10,813 122.04 54,064

77,291 19,323 218.09 96,614

19,906 4,977 414.71 24,883

76,252,121 19,063,030 20,151 95,315,151

3,489,636 872,409 797.01 4,362,044

11,906 2,977 744.13 14,883

-

12,718 3,180 1,222.90 15,898

4,935 1,234 1,542.08 6,168

11,906 2,977 1,860.33 14,883

323,245 80,811 4,253.23 404,057

28,071 7,018 17,544.58 35,089

173,107 43,277 19,671.20 216,383

-

6,473 1,618 101.14 8,091

6,050 1,512 151.24 7,562

44,759 11,190 186.50 55,949

735,874 183,968 228.25 919,842

Page 25: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

3,880,201 970,050 903.72 4,850,252

4,392,898 1,098,224 35.26 5,491,122

794,503 198,626 1,063.31 993,129

202,839 50,710 1,701.67 253,548

14,119,120 3,529,780 52,007 17,648,900

1,367,777 341,944 249.59 1,709,722

32,046 8,012 494.54 40,058

184,279 46,070 568.76 230,349

-

379,383 94,846 249.59 474,229

11,869,068 2,967,267 494.54 14,836,335

1,911,043 477,761 568.76 2,388,804

-

552,995 138,249 691.24 691,244

24,235 6,059 605.88 30,294

40,380 10,095 504.75 50,475

1,428,725 357,181 372.06 1,785,906

155,880 38,970 324.75 194,850

23,382 5,845 292.27 29,227

37,411 9,353 233.82 46,764

163,002 40,751 169.79 203,753

743,034 185,758 132.68 928,792

7,645 1,911 95.56 9,556

80,908 20,227 101.14 101,135

-

52,405 13,101 1,637.64 65,506

2,297 574 1,435.37 2,871

3,403 851 1,063.31 4,253

177,785 44,446 531.65 222,231

8,839 2,210 424.95 11,049

595 149 372.06 744

680 170 212.47 850

8,426 2,107 159.59 10,533

31,663 7,916 159.59 39,578

Page 26: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.255 64 79.79 319

4,268 1,067 106.71 5,335

-

15,959 3,990 398.97 19,948

38,302 9,575 478.77 47,877

127,597 31,899 531.65 159,496

55,299 13,825 691.24 69,124

72,724 18,181 90.00 90,905

-

98,693 24,673 1,542.08 123,366

160,108 40,027 1,334.24 200,135

146,079 36,520 1,217.33 182,599

175,621 43,905 627.22 219,526

287,560 71,890 553.00 359,450

15,113 3,778 472.27 18,891

-

38,162 9,540 90.00 47,702

-

202,403 50,601 372.06 253,003

174,436 43,609 436.09 218,045

204,128 51,032 510.32 255,160

-

122,906 30,726 4,518.60 153,632

102,665 25,666 3,774.46 128,332

21,329,564 5,332,391 29,971 26,661,955

Page 27: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

15,949.62

-

9,038.12

-

6,911.50

-

19,671.20

-

-

-

26,581.77

-

-

-

34,024.93

-

2,658.27

-

19,671.20

-

10,633.09

10,101.43

11,164.74

-

Page 28: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

-

-

-

-

-

-

-

-

69,114.10

-

-

-

-

-

-

65,924.18

-

-

-

-

-

-

Page 29: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

58,481.01

-

-

-

-

-

-

47,847.94

-

-

-

-

-

-

31,898.32

-

-

-

-

-

-

101,012.41

-

Page 30: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

-

19,139.54

-

-

-

130,149 32,537 9,038.12 162,686

-

132,704 33,176 8,293.99 165,880

-

13,543,144 3,385,786 15,417.97 16,928,930

-

78,685 19,671 19,671.20 98,356

-

-

-

654,998 163,749 23,392.77 818,747

-

-

-

226,097 56,524 28,262.10 282,621

-

195,978 48,995 3,402.40 244,973

-

29,262 7,315 18,288.71 36,577

Page 31: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.-

5,529 1,382 6,911.50 6,911

-

577,589 144,397 3,721.58 721,986

-

2,900,703 725,176 5,848.19 3,625,878

1,725,111 431,278 12,759.70 2,156,389

137,805 34,451 14,354.66 172,256

-

-

-

-

-

-

-

-

-

6,507,332 1,626,833 53,164.48 8,134,165

-

-

-

-

Page 32: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

-

-

229,670 57,418 47,847.94 287,088

-

-

-

-

-

-

272,201 68,050 42,531.39 340,251

-

-

-

-

-

-

102,075 25,519 31,898.32 127,593

-

-

-

-

-

-

Page 33: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

149,714 37,428 23,392.77 187,142

-

-

-

-

-

-

204,151 51,038 127,594.19 255,188

-

-

9,600,399 2,400,100 11,696.39 12,000,499

170,126 42,532 212,657.91 212,658

255,189 63,797 318,985.93 318,986

-

285,817 71,454 14,886.31 357,272

-

123,523 30,881 48.25 154,403

1,012,507 253,127 40.83 1,265,634

283,178 70,795 101.14 353,973

-

575,333 143,833 23.20 719,166

Page 34: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Page 35: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.3,572,644 893,161 372,150.40 4,465,805

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1,531,137 382,784 159,493.43 1,913,921

-

-

-

-

-

-

-

-

-

-

-

-

1,735,283 433,821 180,758.66 2,169,104

316,432 79,108 32,961.63 395,540

Page 36: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

127,595 31,899 159,493.43 159,493

-

-

-

-

-

-

-

-

-

-

-

-

Page 37: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.-

-

-

-

119,088 29,772 148,860.35 148,860

-

-

-

-

-

-

-

-

-

-

-

-

-

161,620 40,405 202,024.82 202,025

-

-

-

-

-

-

-

-

Page 38: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.-

-

-

-

72,303 18,076 90,379.33 90,379

-

-

-

-

-

-

-

-

612,452 153,113 85,062.80 765,565

-

2,475,381 618,845 15,949.62 3,094,227

50,832,902 12,708,225 2,501,366 63,541,127

315,901 78,975 103.91 394,876

682,753 170,688 8.35 853,442

166,528 41,632 10.20 208,160

-

53,875 13,469 372.06 67,344

578,440 144,610 9,038.12 723,050

23,109 5,777 159.59 28,886

1,820,605 455,151 9,692 2,275,757

Page 39: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

723,136 180,784 1,158.87 903,920

2,513,702 628,426 850.83 3,142,128

856,521 214,130 1,355.25 1,070,651

298,947 74,737 705.06 373,684

11,223 2,806 584.54 14,029

1,237,690 309,422 1,594.96 1,547,112

-

49,789 12,447 79.79 62,236

235,730 58,932 79.79 294,662

50,427 12,607 79.79 63,034

33,831 8,458 79.79 42,288

1,532 383 79.79 1,915

61,916 15,479 79.79 77,396

25,300 6,325 1,860.33 31,626

26,032 6,508 1,914.14 32,540

76,981 19,245 79.79 96,226

6,202,756 1,550,689 10,583 7,753,445

26,795 6,699 11,164.74 33,494

-

28,503 7,126 118.76 35,629

-

Page 40: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

63,796 15,949 26,581.77 79,745

-

91,870 22,967 19,139.54 114,837

19,140 4,785 7,974.81 23,924

16,588 4,147 6,911.50 20,734

26,426 6,606 165.16 33,032

4,157 1,039 103.91 5,196

16,626 4,157 103.91 20,783

5,367 1,342 223.62 6,708

14,461 3,615 9,038.12 18,076

23,010 5,753 143.82 28,763

331 83 206.91 414

1,531 383 1,914.14 1,914

14,541 3,635 605.88 18,177

353,142 88,286 84,397 441,428

950,505 237,626 2,311.54 1,188,131

284,987 71,247 693.06 356,234

Page 41: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

156,074 39,019 924.61 195,093

628,726 157,181 78,590.72 785,907

110,951 27,738 69,344.56 138,689

51,777 12,944 64,721.48 64,721

48,079 12,020 60,099.22 60,099

1,460,733 365,183 50.03 1,825,916

-

1,168,598 292,150 286.42 1,460,748

4,860,431 1,215,108 277,022 6,075,539

Page 42: Final Offer Electrical

Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.

Page 43: Final Offer Electrical

PART - B -ANCILLIARY AREAS (NURSERY & PRIMARY SCHOOL)

Sub

Head

Description Amount

TOWERS

I WiringRs. #REF!

II Low Tension SystemRs. #REF!

III Submains and CablesRs. #REF!

IV Distribution SystemRs. #REF!

V EarthingRs. #REF!

VI Fixtures and FittingsRs. #REF!

VII Lightning ProtectionRs. #REF!

VIII Fire Detection & Alarm SystemRs. #REF!

Rs. #REF!

PALM GARDEN GROUP HOUSING AT SECTOR 83, GURGAON

SUMMARY OF COST

TENDER FOR INTERNAL ELECTRICAL WORKS

TOTAL (PART - B) C/O TO PAGE-130 OF

VOLUME-2

Prepared by Pradeep Kumar K.N. 7/16/2014 Page 97

Page 44: Final Offer Electrical

Prepared by Pradeep Kumar K.N. 7/16/2014 Page 98

Page 45: Final Offer Electrical

Internal Electrification BOQ for Nursery Primary School.PART - B -ANCILLIARY AREAS (NURSERY & PRIMARY SCHOOL)

PALM GARDEN GROUP HOUSING AT SECTOR 83, GURGAON

TENDER FOR INTERNAL ELECTRICAL WORKS

Sl No. Description Unit QTY labour labour

rate amount

SUB-HEAD - I (WIRING)

1 Wiring for primary light points for switch controlled points with 3 x 1.5 sq.

mm PVC insulated stranded copper conductor 1100 Volt grade wires in

20/25 mm dia 2 mm thick PVC surface/concealed conduit including the

cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated

stranded copper conductor 1100 volt grade wires and including cost of

providing saddles etc for surface conduiting and/or cost of cutting and

filling chases for recessed conduiting and including the cost of providing

and fixing a 6 amp 240 Volt grid plate mounted switch with moulded

cover plate in 1.6 mm thick G.I box etc. complete as per specifications

and as per direction Project in-charge.nos 110 198 21,782

0 0

2 Wiring for primary light points for MCB controlled points with 3 x 2.5 sq.

mm PVC insulated stranded copper conductor 1100 Volt grade wires in

20/25 mm dia 2 mm thick PVC surface/concealed conduit including cost

of providing saddles etc for surface conduiting and/or cost of cutting and

filling chases for recessed conduiting etc. complete as per specifications

and as per direction of Project in-charge. (Cost of MCB shall be paid in

DB item) nos 10 119 1,189

0 0

3 Wiring for secondary light points with 3x1.5 sq. mm PVC insulated

stranded copper conductor 1100 Volt grade wires in surface/concealed

20/25 mm dia 2 mm thick PVC conduit including cost of providing

saddles etc for surface conduiting and/or cost of cutting and filling

chases for recessed conduiting etc. complete as per specification and

as per direction of Project in-charge. nos 300 222 66,597

0 0

4 Wiring for Ceiling/bracket fan points with 3 x 1.5 sq. mm PVC insulated

stranded copper conductor 1100 volt grade wires in 20/25 mm dia 2 mm

thick PVC surface/concealed conduit including the cost of providing

circuit wiring with 3 x 2.5 sq mm PVC insulated stranded copper

conductor 1100 volt grade wires and including cost of providing saddles

etc for surface conduiting and/or cost of cutting and filling chases for

recessed conduiting and including the cost of providing and fixing fan

hook box, a 6 amp 240 volt single pole grid plate mounted switch with

moulded cover plate in a recessed 1.6 mm thick G.I box with including

cost of providing stepped electronic fan regulator as required etc.

complete as per specification and as per direction of Project in-charge.nos 168 489 82,102

0 0

5 Wiring for Exhaust fan points with 3 x 1.5 sq. mm PVC insulated

stranded copper conductor 1100 volt grade wires in 20/25 mm dia 2 mm

thick PVC surface/concealed conduit including the cost of providing

circuit wiring with 3 x 2.5 sq mm PVC insulated stranded copper

conductor 1100 volt grade wires and including cost of providing saddles

etc for surface conduiting and/or cost of cutting and filling chases for

recessed conduiting and including the cost of providing and fixing 5 pin

6 amp shuttered socket outlet a 6 amp 240 volt single pole grid plate

mounted switch with moulded cover plate in a recessed 1.6 mm thick

G.I box etc. complete as per specification and as per direction of

Project in-charge.( This shall include socket and plug top near fan &

switch shall be put near entrance to toilet/kitchen)nos 18 0 0

0 0

6 Wiring for a 5 pin 240 volt 6 amp single phase and neutral switch socket

outlet with 3 x 1.5 sq. mm PVC insulated stranded copper conductor

1100 Volt grade wires in 20/25 mm dia 2 mm thick PVC

surface/concealed conduit including the cost of providing circuit wiring

with 3 x 2.5 sq mm PVC insulated stranded copper conductor 1100 volt

grade wires and including cost of providing saddles etc as required for

surface conduiting and/or cost of cutting and filling chases as required

and providing and fixing of a combined 5 pin 240 volt 6 amp socket

outlet with safety shutters and 6 amp 240 volt single pole grid plate

mounted switch with moulded cover plate in recessed 1.6 mm thick G.I

box etc. complete as per specification and as per direction of Project in-

charge.nos 65 12 779

0 0

7 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket

outlets (1 outlet wired on 1 circuit) with 3 x 4.0 sq. mm PVC insulated

stranded copper conductor 1100 volt grade wires in 20/25mm dia 2 mm

thick PVC surface/concealed conduit including cost of providing saddles

etc as required for surface conduiting and/or cost of cutting and filling

chases as required and including providing and fixing of a 6 pin 240 volt

16 amp socket outlet with safety shutters and 16 amp 240 volt single

pole grid plate mounted switch with moulded cover plate in a recessed

1.6 mm thick G.I boxes etc. complete as per specification and as per

direction of Project in-charge.

nos 25 19 478

0 0

Page 46: Final Offer Electrical

Internal Electrification BOQ for Nursery Primary School.Sl No. Description Unit QTY labour labour

8 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket

outlets (2 outlets wired on 1 circuit) with PVC insulated stranded copper

conductor 1100 volt grade wires, 3 x 4.0 sq mm upto the first outlet and

3 x 4.0 sq mm from first to the second outlet, in 20/25 mm dia 2 mm

thick PVC surface/concealed conduit including cost of providing saddles

etc as required for surface conduiting and/or cost of cutting and filling

chases and including providing and fixing of two sets of 6 pin 240 volt

16 amp socket outlet with safety shutters and 16 amp 240 volt single

pole grid plate mounted switches with moulded cover plate in a

recessed 1.6 mm thick G.I box etc. complete and as per direction of

Project in-charge. nos 10 0 0

0 0

9 Wiring for bell push with 3 x 1.5 sq. mm PVC insulated stranded copper

conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC

surface/ concealed conduit including cost of providing saddles etc as

required for surface conduiting and/or cost of cutting and filling chases

as required and including providing and fixing a grid plate mounted 6

amp 240 volt Bell push with1.6 mm thick GI boxes provided with

minimum 3mm thick plastic/hylam sheets with beveled edges fitted to

the box with countersunk carmium plated screws and including the cost

of running 1.5 sq mm PVC insulated copper conductor wire for loop

earthing etc. complete as per specifications and as required, complete

as required. nos 38 0

0 0

10 Supplying and Laying of 2 mm thick PVC conduiting system

recessed/surface including cost of providing GI fish wire saddles, Bends

(PVC), Junction Boxes (MS) etc. and/or cost of cutting and filling

chases for recessed conduiting complete with accessories as per

specifications and as per direction of Project in-charge. 59 0

0 0

a) 25 mm m 5,500 12 64,636

b) 32 mm m 20 15 298

c) 40 mm m 20 19 375

d) 50 mm m 20 22 438

0 0

11 Supplying and fixing of the following MS Conduits including the cost of

draw/junction boxes with accessories as required and including the cost

of GI fish wire etc. complete as per specifications and as per direction of

Project in-charge. 0 0

0 0

a) 25 mm dia 16 SWG m 20 32 646

b) 32 mm dia 16 SWG m 20 38 750

c) 38 mm dia 14 SWG m 20 44 872

d) 50 mm dia 14 SWG m 20 58 1,166

0 0

TOTAL SUB-HEAD I carried over to Summary 0 242,111

0 0

0 0

Note: The rate shall include the following 0 0

0 0

a) All junction boxes shall be covered with PVC cover. 0 0

b) All fan boxes shall be covered with 3 mm thick hylum sheet 0 0

c) All lights/ceiling fans / exhaust fans points shall be terminated

with PVC connectors. 0 0

0 0

0 0

SUB HEAD II - LOW TENSION SYSTEM 0 0

0 0

1 Wiring for telephone points with 4 pair 0.61 mm annealed tinned

electrolytic copper conductor PVC insulated unshielded twisted wire in

25 mm dia PVC surface/concealed conduit upto central point and

including cost of providing saddles etc for surface conduiting and/or cost

of cutting and filling chases for recessed conduiting and including the

cost of providing and fixing of a single telephone cord grid plate

mounted outlet unit (RJ-11) with moulded cover plate in recessed 1.6

mm thick GI box complete as required for telephone/intercom system..

nos 10 198 1,980

0 0

2 Supply and fixing of the following sheet steel clad wall/recess/floor

mounting telephone tag block of Krone make constructed from 14 SWG

sheet steel, finished with powder coated paint, with hinged gasketted

door and complete with adequately rated and sized telephone terminal

block to receive incoming and outgoing wires. The cost shall be

complete with fixing arrangements, foundations etc as required304 0

0 0

a) 5/10 Pair nos 2 0 0

b) 20 Pair nos 0 0

c) 50 Pair nos 0 0

d) 400 Pair nos 57 0

0 0

3 Supply, laying clamped to wall with suitable clamps saddles and bolts/ in

ground including the cost of digging and back filling with sand and brick

protection as required and testing and commissioning of the following

multi core 0.61 mm annealed tinned copper conductor PVC insulated

and PVC sheathed and overall PVC sheathed armoured telephone

cables including making terminal joints, complete as per specification

and /or as per direction of Project in-charge. 9 0

0 0

a) 50 pair m 15 423 6,342

Page 47: Final Offer Electrical

Internal Electrification BOQ for Nursery Primary School.Sl No. Description Unit QTY labour labour

0 0

4 Supply and fixing of co-axial outlets for TV with moulded cover plate in

recessed 1.6 mm thick GI boxes, including termination complete in all

respects as per specification and / or as per direction of Project in-

charge.. nos 2 29 58

0 0

5 Supply and laying of coaxial cable RG-59 for Branch line in existing

surface/concealed conduits upto the central point complete in all

respects as per specification and / or as per direction of Project in-

charge.m 250 9 2,147

0 0

6 Supply, erection and commissioning of 3 way / 4 way spliter for cable TV

in MS enclosure with 3 mm thick hylum sheet cover as required at site

and /or as per direction of Project in-charge. nos 1 259 259

0 0

7 Supply, erection and commissioning of 6 way tap off in MS enclosures

with 3 mm thick hylum sheet cover for cable TV as required at site and

/or as per direction of Project in-charge.. nos 1 414 414

0 0

8 Steel work welded in built up sections/ framed work including cutting,

fixing in position with fasteners and applying a priming coat of primer

and two coats of approved synthetic enamel paint. 0 0

0 0

a) In grating, frames, ladders, brackets, similar works kgs 5 28 142

0 0

TOTAL SUB-HEAD II carried over to Summary 0 11,343

0 0

0 0

SUB HEAD III - SUBMAINS AND CABLES 0 0

0 0

1 Wiring for Submains with PVC insulated stranded copper conductor

1100 volt grade wires in surface/concealed conduit including cost of

providing saddles, Bends (PVC), Junction Boxes (MS) etc as required

and/or the cost of cutting and filling chases as required and including

cost of PVC insulated copper wires and making suitable end

connections complete in all respects as per specification and /or as per

direction of Project in-charge. 0 0

0 0

a) 2 x 6 sq mm PVC 25 mm dia 2 mm thick conduit m 150 62 9,301

b) 2 x 10 sq mm PVC 25 mm dia 2 mm thick conduit m 20 123 2,457

c) 4 x 16 sq mm PVC 40 mm dia 2 mm thick conduit m 150 141 21,196

0 0

2 Supply and laying in cable Tray/clamped to wall with suitable clamps

saddles and bolts/ in ground including the cost of digging and back filling

with sand and brick protection as required and including testing and

commissioning of the following 1100 volt grade armoured PVC/XLPE

insulated and sheathed aluminium conductor armoured cable complete

as required. The costs shall include providing a gap of 1D between all

the cables being laid and properl clamping with cable clamps and ties.

Prices shall include providing and fixing of Identification tags for all

cables and route markers for cables in ground etc. as per specification

and or as per direction of Project in-charge.

92 0

0 0

a) 3.5 core 70 Sq mm PVCA/XLPE m 100 42 4,219

b) 4 core 25 Sq mm PVCA/XLPE m 19 0 0

c) 4 core 16 Sq mm PVCA/XLPE m 38 132 5,019

0 0

3 Providing and fixing of Cable jointing of the following XLPE cables 1100

Volt grade including cost of tinned copper heavy duty lugs, double

compression glands, insulation tape and all requisite material for

completion of joints. 40 0

0 0

a) 3.5 core 70 Sq mm PVCA/XLPE nos 3 119 357

b) 4 core 25 Sq mm PVCA/XLPE nos 1 22 22

c) 4 core 16 Sq mm PVCA/XLPE nos 2 0 0

0 0

4 Supply and fixing of 14 SWG sheet steel slotted cable trays as per

approved design and MS painted angle supports spaced 1000 mm

apart throughout the length as specified, including the cost of 1 meter

MS threaded rod hangers duly painted, hooks, dash fasteners etc. for

suspension from ceiling etc. as per specification and/or as per direction

of Project in-charge. 0 0

0 0

a) 300 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and

10 mm dia MS rod hangers) m 15 0 0

0 0

5 Supply and fixing of additional length of MS rod hangers duly painted

with 2 coats of spray paint for supporting the Cable Trays, complete for

extension of the supports as in 4 above. The rate shall be

proportionately applicable to the length of rod actually required. kg 10 938 9,378

0 0

Page 48: Final Offer Electrical

Internal Electrification BOQ for Nursery Primary School.Sl No. Description Unit QTY labour labour

6 Supply and fixing Ladder type cable trays with 100 mm vertical sides on

both ends as per approved design of the following sizes, including cost

of providing and fixing of 15 x 30 x 15 mm MS channel supports spaced

250 mm apart throughout the length with necessary fixing arrangements

with angle iron supports etc. as per specification and /or as per direction

of Project in-charge. Rate shall include providing and applying paint 1

coat of primer and 2 coats of enamel paint for all the MS material .2 0

0 0

a) 150 mm m 10 115 1,150

0 0

7 Supply and laying of the following RCC Hume pipe including excavation,

refilling including compaction of soil as required for cable entry including

the cost of sealing the ends as required complete

0 0

0 0

a) 150 mm dia m 37 91 3,353

0 0

8 Providing and making of manhole chamber with masonry bricks and

plastering inside with 1:3:6 and fixing of Heavy duty frame and pre cast

RCC cover as required. 0 0

0 0

a) 600 x 600 x 750 mm deep nos 2 1,101 2,201

b) 450 x 450 x 750 mm deep nos 2 919 1,839

0 0

9 Supplying and laying of following earthing GI wire in slab/wall along with

Submain pipe from meter panel to distribution boards including

connections at both end with tinned copper lugs with tinned washers

etc. as required and as per specifications. 0 0

a) 1 x 8 SWG GI wire m 2,000 2 4,068

0 0

TOTAL SUB HEAD III carried over to Summary 0 64,561

0 0

0 0

SUB HEAD IV - DISTRIBUTION SYSTEM 0 0

0 0

1 Supply, erection, testing and commissioning of the following sheet steel

clad wall recess mounting dust and vermin proof distribution boards

constructed from 18 SWG sheet steel IP 42 construction, duly powder

coated with hinged gasketted door and housing the following complete

with suitably rated PVC insulated copper busbars with interconnections

and neutral bar assembly, earthing terminals complete as approved by

Project Manager. Padlocking facility shall be provided on the door.0 0

0 0

a) 8 WAY SPN 0 0

1-32 amp SPN MCB incoming and 8 nos 6/16/20 amps SP 10 kA MCB

with thermal magnetic protective releases out goings nos 0 0

0 0

b) 4 WAY SPN 0 0

1-32 amp SPN MCB incoming and 4 nos 6/16/20 amps SP 10 kA MCB

with thermal magnetic protective releases out goings nos 0 0

0 0

c) 12 WAY SPN 0 0

1-63 amp SPN 10 kA MCB with thermal magnetic protective releases

incoming with 1-63 amp DP 30 mA ELCB incoming and 12 nos

6/16/20/25 amps SP 10 kA MCB with thermal magnetic protective

releases out goings. nos 3 2,245 6,736

0 0

d) 8 WAY TPN (per phase isolation)-Vertical DB 0 0

1-40 amp TPN 10 kA MCB with thermal magnetic protective releases

incoming with 3 single phase banks each comprising of 1-40 amp 30 mA

DP ELCB incoming and 6 no. 6/16/20/32 amps SP 10 kA MCB with

thermal magnetic protective releases out goings. nos 3 4,887 14,662

0 0

e) 8 WAY TPN with Timer on 2-phases-Vertical DB 0 0

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases

incoming with 0 0

1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming

and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic

protective releases out goings 0 0

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB

incoming with 32 amp ON position latched contactor and 24 hours

programe timer for operation of incoming and 8 no. 6/16/20 amps SP 10

kA MCB with thermal magnetic protective releases out goings nos 0 0

0 0

2 Design, manufacture, supplying fixing in position, testing and

commissioning of the following front operated cubicle type, front access

2mm thick steel enclosed free standing, dust and vermin proof,

switchboard with IP42 protection with hinged and lockable doors

complete with interconnections, tinned copper crimping lugs, bonding to

earth and powder coating suitable for use at 415 volts, 3 phase 4 wire

50 Hertz system, and suitable for a fault level of 25 MVA symmetrical at

415 volts. 0 0

0 0

All switchboards shall have provision for entry of cables from the top or

bottom as required. 0 0

0 0

Page 49: Final Offer Electrical

Internal Electrification BOQ for Nursery Primary School.Sl No. Description Unit QTY labour labour

All live accessible parts shall be shrouded and all equipment shall be

finger touch proof. The Busbars insulation shall be with heat shrinkable

sleeves. SMC/DMC shrouds and busbar supports shall be used.

Padlocking facility shall be provided on all outgoing feeders doors and

switch handles shall be lockable in OFF position.

0 0

0 0

The short circuit rating for MCCB's shall be Ics values 0 0

0 0

A. EWS MAIN PANEL 0 0

0 0

INCOMING 0 0

0 0

1 nos 400 amp TPN Switch Isolator complete with 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbars

rated at 400 amps having a maximum current density of 1.0 amp per sq

mm suitable to with stand symmetrical fault level of 25 M.V.A. at 415

volts. The neutral busbar is to be of 50% capacity.0 0

0 0

INDICATING PANEL 0 0

0 0

The incomers shall have the following indicating panel 0 0

a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for

metering 0 0

b) 1 no ammeter of 96 mm sq scaled 0-400 amps with 3 way and OFF

selector switch 0 0

c) 1 no voltmeter of 96 mm sq scaled 0- 500 volts with 3 way & OFF

selector switch 0 0

d) 1 set of three White phase indicating lamps 0 0

0 0

OUTGOING UNITS 0 0

0 0

11 nos.100 amp 25 kA TPN MCCB with overcurrent bimetallic release

and short circuit magnetic release complete with ON/OFF indicating

lamps 0 0

0 0

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective

releases with ON indication. 0 0

0 0

The Switchboard shall be complete with all interconnections, risers,

internal wiring, labels etc complete as required nos 0 0

0 0

B EWS COMMON PANEL 0 0

0 0

INCOMING 0 0

0 0

2 nos 100 amp 4P Switch Isolator complete with 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbars

rated at 100 amps having a maximum current density of 1.0 amp per sq

mm suitable to with stand symmetrical fault level of 25 M.V.A. at 415

volts. The neutral busbar is to be of 100% capacity.

0 0

0 0

INDICATING PANEL 0 0

0 0

The incomers shall have the following indicating panel 0 0

a) 3 nos Cast resin current transformers of 100/5 ratio Class 1.0 for

metering 0 0

b) 1 no ammeter of 96 mm sq scaled 0-100 amps with 3 way and OFF

selector switch 0 0

c) 1 no voltmeter of 96 mm sq scaled 0- 100 volts with 3 way & OFF

selector switch 0 0

d) 1 set of three White phase indicating lamps 0 0

0 0

INTERLOCKING 0 0

0 0

The Incoming shall be interlocked such that incomers cannot be

paralleled. 0 0

0 0

OUTGOING UNITS 0 0

0 0

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective

releases with ON indication. 0 0

0 0

2 nos 63 amp 10 KA SPN MCB with thermal magnetic protective

releases with ON indication. 0 0

0 0

The Switchboard shall be complete with all interconnections, risers,

internal wiring, labels etc complete as required nos 0 0

Page 50: Final Offer Electrical

Internal Electrification BOQ for Nursery Primary School.Sl No. Description Unit QTY labour labour

0 0

C NURSERY SCHOOL MAIN PANEL 0 0

0 0

INCOMING 0 0

0 0

1 nos 100 amp TPN Switch Isolator complete with 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbars

rated at 100 amps having a maximum current density of 1.0 amp per sq

mm suitable to with stand symmetrical fault level of 25 M.V.A. at 415

volts. The neutral busbar is to be of 100% capacity.

0 0

0 0

INDICATING PANEL 0 0

0 0

The incomers shall have the following indicating panel 0 0

a) 3 nos Cast resin current transformers of 100/5 ratio Class 1.0 for

metering 0 0

b) 1 no ammeter of 96 mm sq scaled 0-100 amps with 3 way and OFF

selector switch 0 0

c) 1 no voltmeter of 96 mm sq scaled 0- 100 volts with 3 way & OFF

selector switch 0 0

d) 1 set of three White phase indicating lamps 0 0

0 0

OUTGOING UNITS 0 0

0 0

2 nos 63 amp 10 KA TPN MCB with thermal magnetic protective

releases with ON indication. 0 0

0 0

6 nos 32 amp 10 KA SPN MCB with thermal magnetic protective

releases with ON indication. 0 0

0 0

The Switchboard shall be complete with all interconnections, risers,

internal wiring, labels etc complete as required nos 1 35,663 35,663

0 0

D PRIMARY SCHOOL MAIN PANEL 0 0

0 0

INCOMING 0 0

0 0

1 nos 125 amp TPN Switch Isolator complete with 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbars

rated at 200 amps having a maximum current density of 1.0 amp per sq

mm suitable to with stand symmetrical fault level of 25 M.V.A. at 415

volts. The neutral busbar is to be of 100% capacity. 0 0

0 0

INDICATING PANEL 0 0

0 0

The incomers shall have the following indicating panel 0 0

a) 3 nos Cast resin current transformers of 200/5 ratio Class 1.0 for

metering 0 0

b) 1 no ammeter of 96 mm sq scaled 0-200 amps with 3 way and OFF

selector switch 0 0

c) 1 no voltmeter of 96 mm sq scaled 0- 200 volts with 3 way & OFF

selector switch 0 0

d) 1 set of three White phase indicating lamps 0 0

0 0

OUTGOING UNITS 0 0

0 0

2 nos 63 amp 10 KA TPN MCB with thermal magnetic protective

releases with ON indication. 0 0

0 0

5 nos 40 amp 10 KA TPN MCB with thermal magnetic protective

releases with ON indication. 0 0

0 0

2 nos 32 amp 10 KA SPN MCB with thermal magnetic protective

releases with ON indication. 0 0

0 0

The Switchboard shall be complete with all interconnections, risers,

internal wiring, labels etc complete as required nos 1 42,267 42,267

0 0

E SWITCHBOARD - CLUB 0 0

0 0

INCOMING 0 0

0 0

1 nos 400 amp TPN Switch Isolator complete with 0 0

0 0

a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for

metering 0 0

b) 1 no digital electronic ammeter 400 amps 0 0

Page 51: Final Offer Electrical

Internal Electrification BOQ for Nursery Primary School.Sl No. Description Unit QTY labour labour

c) 1 no digital electronic voltmeter 500 volts 0 0

d) 1 set of three White phase indicating lamps (LED type) 0 0

e) Red / Green ON/OFF indicator (LED type) 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbars

rated at 600 amps having a maximum current density of 1 amp per sq

mm suitable to with stand symmetrical fault level of 25 M.V.A. at 415

volts. The neutral busbar is to be of 50% capacity.

0 0

0 0

OUTGOING UNITS 0 0

0 0

2 nos 125 amp 25 kA TPN MCCB with overcurrent bimetallic release

and short circuit magnetic release complete with Digital Electronic

Energy Meter with requisite CT suitable for remote data logging

0 0

0 0

12 nos 63 amp 10 kA TPN MCB with thermal magnetic release

complete with Digital Electronic Energy Meter with requisite CT suitable

for remote data logging 0 0

0 0

The Switchboard shall be complete with all interconnections, risers,

internal wiring, labels etc complete as required nos 0 0

0 0

3 Design, fabrication, assembling, wiring & supply, installation, testing &

commissioning of meter boards fabricated out of 14 gauge CRCA

painted sheet steel in cubicle formation with reinforcement of suitable

size angle iron, channels, T irons, flats wherever necessary. Cable

gland plates shall be provided at top and bottom both and windows for

meter reading, locking arrangement (pad-lock & seal) with wiring upto

KWH meter & meter to MCB shall be done by using adequately rated

flexible single core copper wire. The boards shall be treated with all

anticorrosive process before painting as per standards with final

approved shade of powder coated as approved, 2 nos. earthing

terminals shall be provided for 3 phase meter boards and to be

connected with the earthing of rising mains by 2 nos. 25 X 6 mm GI

strips. The boards shall be suitable for 415 V, 3 phase, 4 wire, 50 Hz

supply system. Boards shall be fabricated in length, height, depth etc to

match with site conditions. 0 0

0 0

The Meter Board shall be in Non-compartmentalized construction. 0 0

0 0

An approval shall be taken for each panel before manufacturing. 0 0

0 0

A SHOPPING METER BOARD 0 0

0 0

INCOMING 0 0

0 0

1 nos 100 amp TPN Switch Isolator complete with 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbar

rated at 100 amp having a maximum current density of 1 amp per sq.

mm suitable to withstand symmetrical fault level of 25 M.V.A at 415

volts .The neutral busbar is of 100% capacity. 0 0

0 0

OUTGOING UNITS 0 0

0 0

1 no 63 amp TPN 10 kA MCB with thermal magnetic protective

releases. 0 0

0 0

4 no 32 amp TPN 10 kA MCB with thermal magnetic protective

releases. 0 0

0 0

14-32 amp SPN 10 kA MCB with thermal magnetic protective releases

each with provision for fixing of 32 A DHBVNL approved Single phase

digital dual register prepaid electronic energy meter. 0 0

0 0

The switchboard shall be complete with all interconnection, riser ,

internal wiring, labels etc. complete as required.

nos 0 0

0 0

B METER BOARD -EWS 0 0

0 0

INCOMING 0 0

0 0

1 nos 100 amp TPN Switch Isolator complete with 0 0

0 0

BUSBAR 0 0

0 0

Page 52: Final Offer Electrical

Internal Electrification BOQ for Nursery Primary School.Sl No. Description Unit QTY labour labour

Electrolytic high conductivity aluminium three phase and neutral busbar

rated at 100 amp having a maximum current density of 1 amp per sq.

mm suitable to withstand symmetrical fault level of 25 M.V.A at 415

volts .The neutral busbar is of 100% capacity.

0 0

0 0

OUTGOING UNITS 0 0

0 0

2 no 32 amp TPN 10 kA MCB with thermal magnetic protective

releases. 0 0

0 0

20-32 amp SPN 10 kA MCB with thermal magnetic protective releases

each with provision for fixing of 32 A DHBVNL approved Single phase

digital dual register prepaid electronic energy meter. 0 0

0 0

The switchboard shall be complete with all interconnection, riser ,

internal wiring, labels etc. complete as required. nos 0 0

0 0

C Design,Supply installation testing & commissioning of BIS approved

single phase dual register energy meter for recording dual electric

supply from grid and DG with kWH & kWAh max demand

communication port, billing storage facilities, control panel for sensing

supply from DG sets, data transfer & receiving hub,AMR system. DLC

with energy management software with load manager system &

recharge coupon generation software & connecting accessories for

prepaid system. 0 0

single phase dual register digital electronic prepaid energy meter ( for

tariff application) nos 0 0

0 0

TOTAL SUB HEAD IV carried over to Summary 0 99,329

0 0

SUB HEAD V : EARTHING 0 0

0 0

1 Providing and making earthpits including the cost of 600 mm x 600 mm

x 6 mm GI plate electrode 20 mm dia GI pipe, CI funnel with wiremesh

charcoal, salt, all earth work, masonry enclosure with CI frame & cover

plate having locking arrangement complete as per IS 3043:1987.

nos 4 2,245 8,982

0 0

2 Supplying and laying of the following earthing clamped to wall with

suitable clamps saddles and fixing bolts/ in ground including the cost of

digging and back filling with sand and brick protection as required and

complete as required to comply with IS 3043:1987 0 0

0 0

a) 25 mm x 6 mm GI strip m 500 26 12,909

b) 8 SWG GI Wire m 1,500 2 3,112

0 0

3 Supply and laying of the following GI pipe in ground including

excavation, refilling as required for earth strips etc. as required complete

0 0

0 0

a) 80 mm dia m 20 92 1,849

0 0

4 Providing and laying earth connections from earth electrode with 2 x 6

SWG GI wire in 25 mm dia. GI pipe from earth electrode as required as

per specifications. m 20 40 793

0 0

TOTAL SUB HEAD V carried over to Summary 0 27,645

0 0

0 0

SUB HEAD VI : FIXTURES AND FITTINGS 0 0

0 0

1a Supply of the following light fixtures complete with housing, reflectors, all

accessories i.e. copper wound ballast, HPF condensors, starters,

holders etc. complete as required 0 0

0 0

a) 1x18 W CFL recess mounting downlighter as approved including

providing lamps and other accessories (base Rate Rs 800/-) nos 60 288 17,275

b) 1x18 W CFL surface mounting downlighter as approved including

providing lamps and other accessories (base Rate Rs 600/-) nos 100 211 21,139

c) 1x28 W T5 lamp surface mounting box type fixture as approved

including providing lamps and other accessories (base Rate Rs 800/-)

nos 260 330 85,827

0 0

1b Receiving, assembling, erection, connecting, testing and commissioning

of the following light fixtures complete with housing, reflectors, all

accessories i.e. copper wound ballast, HPF condensors, starters,

holders etc. complete as required 0 0

0 0

a) 1x18 W CFL recess mounting downlighter as approved including

providing lamps and other accessories nos 60 20 1,189

b) 1x18 W CFL surface mounting downlighter as approved including

providing lamps and other accessories nos 100 20 1,982

c) 1x28 W T5 lamp surface mounting box type fixture as approved

including providing lamps and other accessories nos 260 20 5,154

0 0

Page 53: Final Offer Electrical

Internal Electrification BOQ for Nursery Primary School.Sl No. Description Unit QTY labour labour

2 Supply, fixing, testing and commissioning of 240 Volt single phase

ceiling fans of 1200 mm Sweep including supply of 19 mm heavy gauge

GI down rod of length as required complete. nos 5 462 2,311

0 0

3 Supply, fixing, testing and commissioning of 240 Volt single phase

Heavy duty Exhaust Fans 300 mm dia complete with all accessories as

required and with 6 amp 3 pin plug top as required. nos 5 476 2,378

0 0

4 Supply, fixing, testing and commissioning of 240 Volt single phase

Buzzer as required complete. nos 0 0

0 0

TOTAL SUB-HEAD VI carried over to Summary 0 137,256

0 0

0 0

SUB HEAD VII : LIGHTNING PROTECTION 0 0

0 0

1 Supply and fixing GI strip 25 mm x 6 mm along outside wall/

columns as vertical conductors with suitable GI fasteners, brass fixing

screws, copper clamps & saddles complete as required. m 25 26 645

0 0

2 Supply and fixing GI strip 25 mm x 6 mm along roof as horizontal

conductors with suitable GI fasteners, brass fixing screws, copper

clamps & saddles complete as required. m 80 26 2,065

0 0

3 Supply and laying in ground of GI strip 32 mm x 6 mm for connecting to

the GI earth plate at one end and vertical conductor strip at the other

end including the cost of digging and back filling complete

m 15 56 833

0 0

4 Providing and making earthpits including the cost of 600 mm x 600 mm

x 6 mm GI plate electrode 50 mm dia GI pipe, CI funnel with wiremesh

charcoal, salt, all earth work, masonry enclosure with CI frame & cover

plate having locking arrangement complete as per IS 3043:1987.

nos 2 2,245 4,491

0 0

5 Supplying and laying in ground of GI strip 32 mm x 6 mm for

interconnecting the various Lightning arrestor earth pits, including the

cost of digging and back filling, complete as required. m 49 36 1,751

0 0

6 Supply and fixing testing joints made of 25 mm x 6 mm thick GI strip 125

mm long with 4 Nos. GI bolts, nuts, check nuts and spring washers

complete as required. nos 2 51 103

0 0

7 Providing and fixing Lightning Conductor Finials made of 25 mm dia 300

mm long GI tube having a single prong at the top with 85 mm dia 6 mm

thick GI base plate complete as required. nos 1 476 476

0 0

8 Supply and fixing of DMC/SMC insulator complete with GI clamps, Nut

Bolts supports wherever is required. nos 12 151 1,806

0 0

TOTAL SUB HEAD VII carried over to Summary 0 12,171

0 0

0 0

SUB-HEAD -VIII (FIRE DETECTION & ALARM SYSTEM) 0 0

0 0

0 0

1 Supply, installation, testing and commissioning of wall or ceiling

mounted 240 Volt AC illuminated Signs having on its front a white

perspex sheet with the letters 'FIRE EXIT' painted in red including the

cost of in-built rechargeable batteries suitable for 30 minute operation

and including the cost of accessories for surface or recessed or ceiling

suspended mounting complete as required. nos 0 0

0 0

2 Supply installation testing and commissioning of dust and vermin proof

Manual call boxes with push button to initiate audio visual alarm with

breakable glass cover as per detailed specifications complete with a

steel chain including the cost of accessories for surface mounted as

required nos 0 0

0 0

3 Supply installation test and commissioning of the following 8 ohm size

speaker-cum-hooter units with line matching transformer suitable for

broadcast of speech and alarm siren complete as required suitable for

recessed/surface mounting complete with enclosure as approved by

Project Manager and as required. nos 0 0

0 0

4 Supply, installation, testing and commissioning of wall recess mounting

10 zone microprocessor based Conventional Fire Control Panel with PA

amplifier and 5 potential free contacts as per detailed specifications with

alarms, controls and indications as per detailed specifications and with

an integral power supply unit and complete with a suitably rated set of

batteries and trickle charged from 240 volt AC mains supply, including

the cost of mounting accessories as required, complete.

nos 0 0

0 0

Page 54: Final Offer Electrical

Internal Electrification BOQ for Nursery Primary School.Sl No. Description Unit QTY labour labour

5 Wiring with 2 core 1.5 Sqmm standard copper conductor FRLS

660/1100 volts grade wires in existing concealed/surface MS conduit

etc. as per specification and as required including the cost of crimped

termination's. m 0 0

0 0

6 Supply and laying control cabling with copper conductor PVC

insulated and PVC sheathed armoured Control cables in existing

pipes/conduits or on existing tray including the cost of making

connections, complete etc. etc. as per specification and as required as

below: 0 0

0 0

a) 10 core 2.5 sq mm m 0 0

TOTAL SUB-HEAD -VIII carried over to Summary -

594,415.74

Page 55: Final Offer Electrical

PART - A -- INTERNAL ELECTRICAL WORK FOR TOWERS, BASEMENTS, EWS, CLUB & SHOPPING COMPLEX

PALM GARDEN GROUP HOUSING AT SECTOR 83, GURGAON

TENDER FOR INTERNAL ELECTRICAL WORKS

Sl

No.Description Unit

Qty labour Labour Amount

SUB-HEAD - I (WIRING)

1 Wiring for primary light points for switch controlled points with 3 x 1.5 sq. mm PVC

insulated stranded copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick

PVC surface/concealed conduit including the cost of providing circuit wiring with 3 x 2.5 sq

mm PVC insulated stranded copper conductor 1100 volt grade wires and including cost of

providing saddles etc for surface conduiting and/or cost of cutting and filling chases for

recessed conduiting and including the cost of providing and fixing a 6 amp 240 Volt grid

plate mounted switch with moulded cover plate in 1.6 mm thick G.I box etc. complete as

per specifications and as per direction Project in-charge. nos 33,315 145 4,830,675

0 0

2 Wiring for primary light points for MCB controlled points with 3 x 2.5 sq. mm PVC insulated

stranded copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick PVC

surface/concealed conduit including cost of providing saddles etc for surface conduiting

and/or cost of cutting and filling chases for recessed conduiting etc. complete as per

specifications and as per direction of Project in-charge. (Cost of MCB shall be paid in DB

item) nos 1,087 145 157,615

0 0

3 Wiring for secondary light points with 3x1.5 sq. mm PVC insulated stranded copper

conductor 1100 Volt grade wires in surface/concealed 20/25 mm dia 2 mm thick PVC

conduit including cost of providing saddles etc for surface conduiting and/or cost of cutting

and filling chases for recessed conduiting etc. complete as per specification and as per

direction of Project in-charge. nos 6,650 125 831,250

0 0

Page 56: Final Offer Electrical

4 Wiring for Two-way light points switch controlled with 1.5 sq. mm PVC insulated stranded

copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick PVC

surface/concealed conduit including the cost of providing circuit wiring with 2.5 sq mm

PVC insulated stranded copper conductor 1100 volt grade wires and including cost of

providing saddles etc for surface conduiting and/or cost of cutting and filling chases for

recessed conduiting and including the cost of providing and fixing two sets of 6 amp 240

Volt grid plate mounted switch with moulded cover plate in 1.6 mm thick G.I box and

including the cost of running 1.5 sq mm PVC insulated copper conductor wire for loop

earthing etc. complete as per specifications and as per direction of Project in-charge. nos 72 145 10,440

0 0

5 Wiring for Ceiling/bracket fan points with 3 x 1.5 sq. mm PVC insulated stranded copper

conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed

conduit including the cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated

stranded copper conductor 1100 volt grade wires and including cost of providing saddles

etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting

and including the cost of providing and fixing fan hook box, a 6 amp 240 volt single pole

grid plate mounted switch with moulded cover plate in a recessed 1.6 mm thick G.I box

with including cost of providing stepped electronic fan regulator as required etc. complete

as per specification and as per direction of Project in-charge.

nos 8,726 145 1,265,270

0 0

6 Wiring for Exhaust fan points with 3 x 1.5 sq. mm PVC insulated stranded copper

conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed

conduit including the cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated

stranded copper conductor 1100 volt grade wires and including cost of providing saddles

etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting

and including the cost of providing and fixing 5 pin 6 amp shuttered socket outlet a 6 amp

240 volt single pole grid plate mounted switch with moulded cover plate in a recessed 1.6

mm thick G.I box etc. complete as per specification and as per direction of Project in-

charge.( This shall include socket and plug top near fan & switch shall be put near

entrance to toilet/kitchen) nos 5,294 145 767,630

0 0

7 Wiring for a 5 pin 240 volt 6 amp single phase and neutral switch socket outlet with 3 x 1.5

sq. mm PVC insulated stranded copper conductor 1100 Volt grade wires in 20/25 mm dia

2 mm thick PVC surface/concealed conduit including the cost of providing circuit wiring

with 3 x 2.5 sq mm PVC insulated stranded copper conductor 1100 volt grade wires and

including cost of providing saddles etc as required for surface conduiting and/or cost of

cutting and filling chases as required and providing and fixing of a combined 5 pin 240 volt

6 amp socket outlet with safety shutters and 6 amp 240 volt single pole grid plate mounted

switch with moulded cover plate in recessed 1.6 mm thick G.I box etc. complete as per

specification and as per direction of Project in-charge.

nos 17,842 160 2,854,720

0 0

Page 57: Final Offer Electrical

8 Wiring as in Item 7 above looped from an adjacent 6 amp switch socket outlet as required

and providing and fixing of a modular type 5 pin 240 Volt 6 amp shuttered socket outlet

and a modular type 6 amp 240 Volt single pole switch in a recessed 1.6 mm thick G.I

boxes with internal wiring and moulded front plates as per approved sample complete as

per specification and as per direction of Project in-charge. nos 50 114 5,7000 0

9 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket outlets (1 outlet

wired on 1 circuit) with 3 x 4.0 sq. mm PVC insulated stranded copper conductor 1100 volt

grade wires in 20/25mm dia 2 mm thick PVC surface/concealed conduit including cost of

providing saddles etc as required for surface conduiting and/or cost of cutting and filling

chases as required and including providing and fixing of a 6 pin 240 volt 16 amp socket

outlet with safety shutters and 16 amp 240 volt single pole grid plate mounted switch with

moulded cover plate in a recessed 1.6 mm thick G.I boxes etc. complete as per

specification and as per direction of Project in-charge. nos 1,206 200 241,2000 0

10 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket outlets (2 outlets

wired on 1 circuit) with PVC insulated stranded copper conductor 1100 volt grade wires, 3

x 4.0 sq mm upto the first outlet and 3 x 4.0 sq mm from first to the second outlet, in 20/25

mm dia 2 mm thick PVC surface/concealed conduit including cost of providing saddles etc

as required for surface conduiting and/or cost of cutting and filling chases and including

providing and fixing of two sets of 6 pin 240 volt 16 amp socket outlet with safety shutters

and 16 amp 240 volt single pole grid plate mounted switches with moulded cover plate in

a recessed 1.6 mm thick G.I box etc. complete and as per direction of Project in-charge.

1,528 200 305,600

0 0

11 Wiring for 2 nos 6 pin 240 volt 20/20 amp looped single phase and neutral switch socket

(2 outlets wired on 1 circuit) with PVC insulated stranded copper conductor 1100 volt

grade wires, 3 x 4.0 sq mm upto the first outlet and 3 x 4.0 sq mm from first to the second

outlet, in 20/25 mm dia 2 mm thick PVC surface/concealed conduit including cost of

providing saddles etc as required for surface conduiting and/or cost of cutting and filling

chases and including providing and fixing of two sets of 6 pin 240 volt 20 amp socket

outlet with safety shutters and 20 amp 240 volt single pole grid plate mounted switches

with moulded cover plate in a recessed 1.6 mm thick G.I box etc. complete and as per

direction of Project in-charge.(Ist point for A/C & IInd for geyser)This shall include socket

& plug top near geyser and controlling switch at door. nos 4,190 200 838,000

0 0

7 Wiring for AC points with 3 x 4.0 sq. mm PVC insulated stranded copper conductor 1100

volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed conduit including

cost of providing saddles etc as required for surface conduiting and/or cost of cutting and

filling chases as required and including providing and fixing of a 6 pin 240 volt 20 amp

socket outlet with safety shutters with moulded cover plate in recessed 1.6 mm thick GI

box including providing and fixing a 20 amp single pole 240 volt 20 amp switch with

moulded cover plate in recessed 1.6 mm thick G.I box located separately as per

drawings/instructions for AC controls complete as per specification and as per direction of

Project in-charge.(one outlet on one circuit) nos 414 225 93,150

0 0

Page 58: Final Offer Electrical

13 Point wiring for 20 amp single phase socket outlets with 3 x 4 sq mm PVC insulated 1100

volt grade stranded copper conductor wires in 20/25 mm dia 2 mm thick PVC recessed

and/or surface conduiting system including the cost of cutting/making good chases in brick

work and including the cost of supplying and fixing 20/25 amp 10 kA SP MCB, industrial

type metal clad outlet in recessed 1.6 mm thick G.I box, metal clad plug top etc. complete

as per specifications and as per direction of Project in-charge. nos 5 275 1,3750 0

14 Wiring for bell push with 3 x 1.5 sq. mm PVC insulated stranded copper conductor 1100

volt grade wires in 20/25 mm dia 2 mm thick PVC surface/ concealed conduit including

cost of providing saddles etc as required for surface conduiting and/or cost of cutting and

filling chases as required and including providing and fixing a grid plate mounted 6 amp

240 volt Bell push with moulded cover plate in recessed zinc chromate passivated 1.6 mm

thick GI box etc. complete as per specifications and as per direction of Project in-charge.

nos 1,206 135 162,8100 0

15 Supplying and Laying of 2 mm thick PVC conduiting system recessed/surface including

cost of providing GI fish wire saddles, Bends (PVC), Junction Boxes (MS) etc. and/or cost

of cutting and filling chases for recessed conduiting complete with accessories as per

specifications and as per direction of Project in-charge. 0 0

a) 25 mm m 189,000 18 3,402,000

b) 32 mm m 1,080 19 20,520

c) 40 mm m 1,080 19 20,520

d) 50 mm m 580 21 12,1800 0

16 Supplying and fixing of the following MS Conduits including the cost of draw/junction

boxes with accessories as required and including the cost of GI fish wire etc. complete as

per specifications and as per direction of Project in-charge. 0 0

a) 25 mm dia 16 SWG m 30,080 31 932,480

b) 32 mm dia 16 SWG m 480 37 17,760

c) 38 mm dia 14 SWG m 480 43 20,640

d) 50 mm dia 14 SWG m 480 57 27,360

17 Supplying and drawing following sizes of PVC insulated copper conductor single core

stranded cables in existing surface / recessed conduits as per specifications and/or as per

direction of Project in-charge. as required.

a) 3 x 1.5 sq mm (P+N+E) m 4,500 30 135,000

b) 3 x 2.5 sq mm (P+N+E) m 3,000 25 75,000

c) 3 x 4.0 sq mm (P+N+E) m 1,600 24 38,400

d) 3 x 6.0 sq mm (P+N+E) m 400 30 12,000

0 0

18 Supply, installation, testing and commissioning of the following switches, sockets in

recessed 1.6 mm thick GI box with moulded cover plate, including internal connections,

complete as per specifications and/or as per direction of Project in-charge. 0 0

0 0

a) 6 amp switch with box and cover plate nos 443 24 10,632

b) 6 amp switch and 5 pin socket outlet with box and cover plate nos 443 24 10,632

c) 16 amp switch and 6 pin socket outlet with box and cover plate nos 60 24 1,440

0 0

Page 59: Final Offer Electrical

TOTAL SUB-HEAD - I carried over to Summary 0 17,101,999

0 0

SUB-HEAD - II (LOW TENSION SYSTEM) 0 0

0 0

1 Wiring for telephone points with 4 pair 0.61 mm annealed tinned electrolytic copper

conductor PVC insulated unshielded twisted wire in 25 mm dia 2 mm thick PVC

surface/concealed conduit upto central point and including cost of providing saddles etc

for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and

including the cost of providing and fixing of a single telephone cord grid plate mounted

outlet unit (RJ-11) with moulded cover plate in recessed 1.6 mm thick GI box complete as

required for telephone/intercom system.. nos 5,473 145 793,585

0 0

2 Wiring for telephone points with 2 pair 0.61 mm annealed tinned electrolytic copper

conductor PVC insulated unshielded twisted wire in 25 mm dia 2 mm thick PVC

surface/concealed conduit upto central point and including cost of providing saddles etc

for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and

including the cost of providing and fixing of a single telephone cord grid plate mounted

outlet unit (RJ-11) with moulded cover plate in recessed 1.6 mm thick GI box complete as

required for telephone/intercom system. nos 20 114 2,280

0 0

3 Supply and fixing of the following sheet steel clad wall/recess/floor mounting telephone tag

block of Krone make constructed from 14 SWG sheet steel, finished with powder coated

paint, with hinged gasketted door and complete with adequately rated and sized telephone

terminal block to receive incoming and outgoing wires. The cost shall be complete with

fixing arrangements, foundations etc as required 0 0

0 0

a) 10 Pair nos 13 178 2,314

b) 20 Pair nos 4 237 948

c) 30 Pair nos 8 474 3,792

d) 50 Pair nos 95 474 45,030

e) 300 Pair nos 2 3,557 7,114

f) 400 Pair nos 11 4,743 52,173

0 0

4 Supply, laying clamped to wall with suitable clamps saddles and bolts/ in ground including

the cost of digging and back filling with sand and brick protection as required and testing

and commissioning of the following multi core 0.61 mm annealed tinned copper conductor

PVC insulated and PVC sheathed and overall PVC sheathed armoured telephone cables

including making terminal joints, complete as per specification and /or as per direction of

Project in-charge. 0 0

0 0

a) 10 Pair m 80 7 560

b) 20 Pair m 50 11 550

c) 30 Pair m 300 24 7,200

d) 50 Pair m 4,030 36 145,080

0 0

Page 60: Final Offer Electrical

5 Supply and fixing of co-axial outlets for TV with moulded cover plate in recessed zinc

chromate passivated MS boxes, including termination complete in all respects as per

specification and / or as per direction of Project in-charge.. nos 5,367 60 322,020

0 0

6 Supply and laying of coaxial cable RG-59 for Branch line in existing surface/concealed

conduits upto the central point complete in all respects as per specification and / or as per

direction of Project in-charge. m 155,750 5 778,750

0 0

7 Supply, erection and commissioning of 3 way / 4 way spliter for cable TV in MS enclosure

with 3 mm thick hylum sheet cover as required at site and /or as per direction of Project in-

charge. nos 934 60 56,040

0 0

8 Supply, erection and commissioning of 6 way tap off in MS enclosures with 3 mm thick

hylum sheet cover for cable TV as required at site and /or as per direction of Project in-

charge.. nos 149 237 35,313

0 0

TOTAL SUB-HEAD - II carried over to Summary 0 2,252,749

0 0

SUB-HEAD - III (SUBMAINS AND CABLES) 0 0

0 0

1 Wiring for Submains with PVC insulated stranded copper conductor 1100 volt grade wires

in surface/concealed conduit including cost of providing saddles, Bends (PVC), Junction

Boxes (MS) etc including the cost of cutting and filling chases as required and as per

specification and as per direction of Project in-charge. 0 0

0 0

a) 2 x 10 sq mm in PVC 25 mm dia 2 mm thick conduit m 6,850 24 164,400

b) 4 x 10 sq mm in PVC 32 mm dia 2 mm thick conduit m 81 53 4,293

c) 4 x 16 sq mm in PVC 40 mm dia 2 mm thick conduit m 405 65 26,325

0 0

0 0

1.1 Wiring for Submains with PVC insulated stranded copper conductor 1100 volt grade wires

in surface/concealed conduit including cost of providing saddles, Bends (PVC), Junction

Boxes (MS) etc including the cost of cutting and filling chases as required and as per

specification and as per direction of Project in-charge. 0 0

0 0

a) 2 x 10 sq mm in PVC 25 mm dia 2 mm thick conduit m 1,900 24 45,600

b) 4 x 10 sq mm in PVC 32 mm dia 2 mm thick conduit m 30,000 53 1,590,000

c) 4 x 16 sq mm in PVC 40 mm dia 2 mm thick conduit m 4,200 65 273,000

0 0

0 0

Page 61: Final Offer Electrical

2 Supply and laying in cable Tray/clamped to wall with suitable clamps saddles and bolts/ in

ground including the cost of digging and back filling with sand and brick protection as

required and including testing and commissioning of the following 1100 volt grade

armoured PVC/XLPE insulated and sheathed aluminium conductor armoured cable

complete as required. The costs shall include providing a gap of 1D between all the cables

being laid and properl clamping with cable clamps and ties. Prices shall include providing

and fixing of Identification tags for all cables and route markers for cables in ground etc.

as per specification and or as per direction of Project in-charge. 0 0

0 0

a) 3 -1/2 core 300 Sq mm XLPE m 1,000 36 36,000

b) 3 -1/2 core 240 Sq mm XLPE m 50 36 1,800

c) 3 -1/2 core 185 Sq mm XLPE m 100 36 3,600

d) 3 -1/2 core 70 Sq mm XLPE m 4,800 36 172,800

e) 3 -1/2 core 50 Sq mm XLPE m 600 77 46,200

f) 4 core 35 Sq mm XLPE m 100 36 3,600

g) 4 core 25 Sq mm XLPE m 200 30 6,000

h) 4 core 16 Sq mm XLPE m 1,200 24 28,800

i) 4 core 10 Sq mm XLPE m 7,000 24 168,000

j) 4 core 6 Sq mm XLPE m 100 24 2,400

k) 2 core 10 Sq mm XLPE m 1,000 24 24,000

0 0

3 Providing and fixing of Cable jointing of the following XLPE cables 1100 Volt grade

including cost of tinned copper heavy duty lugs, double compression glands, insulation

tape and all requisite material for completion of joints.0 0

0 0

a) 3 -1/2 core 300 Sq mm XLPE nos 40 237 9,480

b) 3 -1/2 core 240 Sq mm XLPE nos 2 237 474

c) 3 -1/2 core 185 Sq mm XLPE nos 4 177 708

d) 3 -1/2 core 70 Sq mm XLPE nos 418 60 25,080

e) 3 -1/2 core 50 Sq mm XLPE nos 26 60 1,560

f) 4 core 35 Sq mm XLPE nos 2 60 120

g) 4 core 25 Sq mm XLPE nos 4 24 96

h) 4 core 16 Sq mm XLPE nos 66 24 1,584

i) 4 core 10 Sq mm XLPE nos 248 24 5,952

j) 4 core 6 Sq mm XLPE nos 4 12 48

k) 2 core 10 Sq mm XLPE nos 50 12 600

0 0

4 Supply and fixing of 14 SWG sheet steel slotted cable trays as per approved design and

MS painted angle supports spaced 1000 mm apart throughout the length as specified,

including the cost of 1 meter MS threaded rod hangers duly painted, hooks, dash

fasteners etc. for suspension from ceiling etc. as per specification and/or as per direction

of Project in-charge. 0 0

0 0

a) 150 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS

rod hangers) m 50 30 1,500

Page 62: Final Offer Electrical

0 0

b) 300 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS

rod hangers) m 100 30 3,000

0 0

c) 450 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS

rod hangers) m 300 30 9,000

0 0

d) 600 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS

rod hangers) m 100 41 4,100

0 0

0 0

5 Supply and fixing of additional length of MS rod hangers duly painted with 1 coat of primer

and 2 coats enamel paint for supporting the Cable Trays for extension of the supports as

in item no. 4 above. kg 1,010 21 21,210

0 0

6 Supply and fixing Ladder type cable trays with 100 mm vertical sides on both ends as per

approved design of the following sizes, including cost of providing and fixing of 15 x 30 x

15 mm MS channel supports spaced 250 mm apart throughout the length with necessary

fixing arrangements with angle iron supports etc. as per specification and /or as per

direction of Project in-charge. Rate shall include providing and applying paint 1 coat of

primer and 2 coats of enamel paint for all the MS material .0 0

0 0

a) 900 mm m 80 280 22,400

b) 750 mm m 150 280 42,000

c) 600 mm m 150 280 42,000

d) 450 mm m 350 230 80,500

e) 300 mm m 650 230 149,500

f) 150 mm m 40 207 8,280

0 0

7 Providing and fixing Steel work welded in built up sections/ framed work including cutting,

fixing in position with fasteners, including a priming coat of primer and two coats of

approved synthetic enamel paint. 0 0

0 0

a) In grating, frames, ladders, brackets, similar works kg 530 21 11,130

0 0

8 Supply and laying of the following RCC Hume pipe NP-2 grade including excavation,

refilling including compaction of soil as required for cable entry including the cost of

sealing the ends as required complete in all respects, as per spacification and /or as per

direction of Project in-charge. 0 0

0 0

a) 150 mm dia m 680 71 48,280

b) 200 mm dia m 500 95 47,500

c) 300 mm dia m 500 142 71,000

0 0

Page 63: Final Offer Electrical

9 Providing and making of manhole chamber with masonry bricks and plastering inside with

1:3:6 and fixing of Heavy duty frame and pre cast RCC cover as required. 0 0

0 0

a) 600 x 600 x 750 mm deep nos 34 711 24,174

b) 450 x 450 x 750 mm deep nos 34 533 18,122

0 0

TOTAL SUB-HEAD - III carried over to Summary 0 3,246,216

0 0

SUB-HEAD - IV (DISTRIBUTION SYSTEM) 0 0

0 0

1 Supply, erection, testing and commissioning of the following sheet steel clad wall recess

mounting dust and vermin proof distribution boards constructed from 18 SWG sheet steel

IP 42 construction, duly powder coated with hinged gasketted door and housing the

following complete with suitably rated PVC insulated copper busbars with interconnections

and neutral bar assembly, earthing terminals complete as approved by Project Manager.

Padlocking facility shall be provided on the door. 0 0

0 0

a) 12 WAY SPN 0 0

1-40 amp DP MCB incoming with 32 amp ON position latched contactor and 24 hours

programe timer for operation of incoming and 12 no. 6/16/20 amps SP 10 kA MCB with

thermal magnetic protective releases out goings nos R/O 3,782

0

b) 12 WAY SPN 0

1-63 amp SPN 10 kA MCB with thermal magnetic protective releases incoming with 1-63

amp DP 30 mA ELCB incoming and 12 nos 6/16/20/25 amps SP 10 kA MCB with thermal

magnetic protective releases out goings. nos R/O 2,143

0

c) 6 WAY TPN (per phase isolation)-Vertical DB 0

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3

single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 6 no.

6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings. nos R/O 1,639

0

d) 8 WAY TPN (per phase isolation)-Vertical DB 0

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3

single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 8 no.

6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings. nos R/O 4,665

0

e) 8 WAY TPN with Timer on 2-phases-Vertical DB 0

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 0

1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming and 8 no. 6/16/20

amps SP 10 kA MCB with thermal magnetic protective releases out goings 0

0

Page 64: Final Offer Electrical

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32

amp ON position latched contactor and 24 hours programe timer for operation of incoming

and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out

goings nos R/O 6,304

0 0

f) 12 WAY TPN with Timer on 2-phases-Vertial DB 0 0

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 0 0

1 single phase bank comprising of 1- 63 amp 30 mA DP ELCB incoming and 12 no.

6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings

0 0

0 0

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32

amp ON position latched contactor and 24 hours programe timer for operation of incoming

and 12 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out

goings nos R/O 8,069

0

g) Incomer DB for Penthouses-Vertical DB 0

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 2 nos

63 amp SPN 10 kA MCB with thermal magnetic protective releases out goings. nos R/O 630

h) 8 Way VTPN 0

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 8 nos

6-32 amp 10 kA TP MCB with thermal magnetic protective releases out goings nos R/O 4,665

0

2 Design, manufacture, supplying, fixing, testing and commissioning of the following 2 mm

thick sheet steel enclosed, wall mounting, dust and vermin proof with IP 42 protection

triple pole and with 100% neutral Rising Mains with PVC insulated aluminium busbars

with a maximum current density of 1.0 amp per sq mm and suitable to withstand a

symmetrical fault level of 45 kA at 415 volts, complete with fire proof barriers at every floor

level, expansion joints, thrust pads to support weight of busbars, fully gasketed covers,

with arrangement to plug in tap off boxes as required and connecting chamber for

incoming isolator, powder coating, complete with fixing arrangements as required and with

2 runs of aluminium strip for earthing as required . 0

0

a) 400 amps m R/O 2,522

0

3a Supplying, erection, testing and commissioning of Tap-Off Boxes with 125 amp TPN

MCCB (25 kA) and cable end boxes as required nos R/O 2,395

0

3b Supplying, erection, testing and commissioning of Tap-Off Boxes with 160 amp TPN

MCCB (25 kA) and cable end boxes as required nos R/O 2,648

0 0

4 Meter Boards Tap-Off Boxes 0 0

0 0

Page 65: Final Offer Electrical

Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of

meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation

with reinforcement of suitable size angle iron, channels, T irons, flats wherever necessary

for large meter boards. Cable gland plates shall be provided at top and bottom both and

windows for meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH

meter & meter to MCB shall be done by using adequately rated flexible single core

copper wire. The boards shall be treated with all anticorrosive process before painting as

per standards with final approved shade of powder coated as approved 2 nos. earthing

terminals shall be provided for 3 phase meter boards and to be connected with the

earthing by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for 415 V, 3 phase, 4

wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth etc to

match with site conditions. 0 0

0 0

An approval shall be taken for each panel before manufacturing. Galvanised hardwares

with zinc passivation shall be used in fabrication of boards. 0 0

0 0

a) 6 WAY 0 0

0 0

Incomer 0 0

Provision for direct cable connection to busbars 0 0

0 0

Bus Bars 0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity. 0 0

0 0

Outgoings 0 0

6 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 6 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 8 way terminal

block to connect 2 x 2.5 sq.mm control wire including control wiring.nos R/O 16,389

0 0

b) 5 WAY 0 0

0 0

Incomer 0 0

Provision for direct cable connection to busbars 0 0

0 0

Bus Bars 0 0

Page 66: Final Offer Electrical

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity. 0 0

0 0

Outgoings 0 0

5 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 5 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 8 way terminal

block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 15,633

0 0

c) 4 WAY 0 0

0 0

Incomer 0 0

Provision for direct cable connection to busbars 0 0

0 0

Bus Bars 0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity. 0 0

0 0

Outgoings 0 0

4 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 4 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 6 way terminal

block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 13,868

0 0

d) 3 WAY 0 0

0 0

Incomer 0 0

Provision for direct cable connection to busbars 0 0

0 0

Bus Bars 0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity. 0 0

Page 67: Final Offer Electrical

0 0

Outgoings 0 0

3 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 3 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 6 way terminal

block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 11,346

0

e) 2 WAY 0

0

Incomer 0

Provision for direct cable connection to busbars 0

0

Bus Bars 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity. 0

0

Outgoings 0

2 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 2 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 4 way terminal

block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 7,564

0 0

f) 9 WAY 0 0

0 0

Incomer 0 0

Provision for direct cable connection to busbars 0 0

0 0

Bus Bars 0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity. 0 0

0 0

Outgoings 0 0

Page 68: Final Offer Electrical

9 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 9 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 12 way

terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 23,954

0

5 Dual Pre-Paid meter 0

0

Design,supply ,installation testing and commissioning of BIS approved single phase dual

energy meter for recording dual electric supply from grid and DG with KWH & KVAH max

demand communication port,billing,storage facilities ,control panel for sensing supply from

DG sets, data transfer & receiving hub, AMR system. DLC with energy management

software with load manager system and recharge coupon generation software &

connecting accessories for prepaid system. 0

1 phase digital electronic energy meter (for tariff application) nos R/O 4,539

0 0

0 0

0 0

ALTERNATIVELY 0 0

0 0

1 Supply, erection, testing and commissioning of the following sheet steel clad wall recess

mounting dust and vermin proof distribution boards constructed from 18 SWG sheet steel

IP 42 construction, duly powder coated with hinged gasketted door and housing the

following complete with suitably rated PVC insulated copper busbars with interconnections

and neutral bar assembly, earthing terminals complete as approved by Project Manager.

Padlocking facility shall be provided on the door. 0 0

0 0

a) 12 WAY SPN 0 0

1-40 amp DP MCB incoming with 32 amp ON position latched contactor and 24 hours

programe timer for operation of incoming and 12 no. 6/16/20 amps SP 10 kA MCB with

thermal magnetic protective releases out goings nos 18 711 12,798

0 0

b) 12 WAY SPN 0 0

1-63 amp SPN 10 kA MCB with thermal magnetic protective releases incoming with 1-63

amp DP 30 mA ELCB incoming and 12 nos 6/16/20/25 amps SP 10 kA MCB with thermal

magnetic protective releases out goings.nos 20 711 14,220

0 0

c) 6 WAY TPN (per phase isolation)-Vertical DB 0 0

Page 69: Final Offer Electrical

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3

single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 6 no.

6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.

nos 1,098 900 988,200

0 0

d) 8 WAY TPN (per phase isolation)-Vertical DB 0 0

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3

single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 8 no.

6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.

nos 5 1,200 6,000

0 0

e) 8 WAY TPN with Timer on 2-phases-Vertical DB 0 0

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 0 0

1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming and 8 no. 6/16/20

amps SP 10 kA MCB with thermal magnetic protective releases out goings

0 0

0 0

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32

amp ON position latched contactor and 24 hours programe timer for operation of incoming

and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out

goings nos 35 5,547 194,145

0 0

f) 12 WAY TPN with Timer on 2-phases-Vertical DB 0 0

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 0 0

1 single phase bank comprising of 1- 63 amp 30 mA DP ELCB incoming and 12 no.

6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings 0 0

0 0

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32

amp ON position latched contactor and 24 hours programe timer for operation of incoming

and 12 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out

goings

nos 10 1,779 17,790

0 0

g) Incomer DB for Penthouses-Vertical DB 0 0

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 2 nos

63 amp TPN 10 kA MCB with thermal magnetic protective releases out goings. nos 72 949 68,328

h) 8 Way VTPN-Vertical DB 0 0

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 8 nos

6-32 amp 10 kA TP MCB with thermal magnetic protective releases out goings nos 2 1,186 2,372

0 0

j) 8 WAY SPN 0 0

Page 70: Final Offer Electrical

1-32 amp SPN MCB incoming and 8 nos 6/16/20 amps SP 10 kA MCB with thermal

magnetic protective releases out goings nos 1 593 593

0 0

k) 4 WAY SPN 0 0

1-32 amp SPN MCB incoming and 4 nos 6/16/20 amps SP 10 kA MCB with thermal

magnetic protective releases out goings nos 194 474 91,956

0 0

2 Design, manufacture, supplying, fixing, testing and commissioning of the following 2 mm

thick sheet steel enclosed, wall mounting, dust and vermin proof with IP 42 protection

triple pole and with 100% neutral Rising Mains with PVC insulated aluminium busbars

with a maximum current density of 1.0 amp per sq mm and suitable to withstand a

symmetrical fault level of 45 kA at 415 volts, complete with fire proof barriers at every floor

level, expansion joints, thrust pads to support weight of busbars, fully gasketed covers,

with arrangement to plug in tap off boxes as required and connecting chamber for

incoming isolator, powder coating, complete with fixing arrangements as required and with

2 runs of aluminium strip for earthing as required . 0 0

0 0

a) 400 amps m 620 896 555,520

0 0

3a Supplying, erection, testing and commissioning of Tap-Off Boxes with 125 amp TPN

MCCB (25 kA) and cable end boxes as required nos 169 1,186 200,434

0 0

3b Supplying, erection, testing and commissioning of Tap-Off Boxes with 160 amp TPN

MCCB (25 kA) and cable end boxes as required nos 12 1,779 21,348

0 0

4 Meter Boards Tap-Off Boxes 0 0

0 0

Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of

meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation

with reinforcement of suitable size angle iron, channels, T irons, flats wherever necessary

for large meter boards. Cable gland plates shall be provided at top and bottom both and

windows for meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH

meter & meter to MCB shall be done by using adequately rated flexible single core

copper wire. The boards shall be treated with all anticorrosive process before painting as

per standards with final approved shade of powder coated as approved 2 nos. earthing

terminals shall be provided for 3 phase meter boards and to be connected with the

earthing by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for 415 V, 3 phase, 4

wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth etc to

match with site conditions. 0 0

0 0

An approval shall be taken for each panel before manufacturing. Galvanised hardwares

with zinc passivation shall be used in fabrication of boards. 0 0

0 0

a) 6 WAY 0 0

0 0

Incomer 0 0

Page 71: Final Offer Electrical

Provision for direct cable connection to busbars 0 0

0 0

Bus Bars 0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity. 0 0

0 0

Outgoings 0 0

6 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 6 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with 8

way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 153 4,150 634,950

0 0

b) 5 WAY 0 0

0 0

Incomer 0 0

Provision for direct cable connection to busbars 0 0

0 0

Bus Bars 0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity. 0 0

0 0

Outgoings 0 0

5 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 5 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with 8

way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 6 4,150 24,900

0 0

c) 4 WAY 0 0

0 0

Incomer 0 0

Provision for direct cable connection to busbars 0 0

0 0

Bus Bars 0 0

Page 72: Final Offer Electrical

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity. 0 0

0 0

Outgoings 0 0

4 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 4 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with 6

way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.nos 8 3,794 30,352

0 0

d) 3 WAY 0 0

0 0

Incomer 0 0

Provision for direct cable connection to busbars 0 0

0 0

Bus Bars 0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity. 0 0

0 0

Outgoings 0 0

3 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 3 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with 6

way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 4 2,964 11,856

0 0

e) 2 WAY 0 0

0 0

Incomer 0 0

Provision for direct cable connection to busbars 0 0

0 0

Bus Bars 0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity. 0 0

Page 73: Final Offer Electrical

0 0

Outgoings 0 0

2 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 2 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with 4

way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 8 2,371 18,968

0 0

f) 9 WAY 0 0

0 0

Incomer 0 0

Provision for direct cable connection to busbars 0 0

0 0

Bus Bars 0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity. 0 0

0 0

Outgoings 0 0

9 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 9 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with

12 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.nos 2 9,486 18,972

0 0

5 Dual Pre-Paid meter 0 0

0 0

Design,supply ,installation testing and commissioning of BIS approved three phase 4wire

dual energy meter for recording dual electric supply from grid and DG with KWH & KVAH

max demand communication port,billing,storage facilities ,control panel for sensing supply

from DG sets, data transfer & receiving hub, AMR system. DLC with energy management

software with load manager system and recharge coupon generation software &

connecting accessories for prepaid system. 0 0

0 0

3 phase digital electronic energy meter (for tariff application) nos 1,026 474 486,324

0 0

Page 74: Final Offer Electrical

6 Design ,supply ,installation, testing and commissioning of required software to make the

kWH meter functional in coordination with kWH meter manufacturer and facility

mangement team for prepaid/postpaid tariff application system for dual resistor (

recording) KWH meter to effectively monitor/control the tariff as per individual site

condition complete with latest version of computer & printer etc as required. ( Integrated

with existing software installed) job 1 0 0

0 0

7 Design, manufacture, supply, installation, testing and commissioning of cubical type

electrical control panel comprising of necessary contactors.PLA relays terminals etc to

provide signaled DC supply to the dual source energy meters.( Integrated with existing

software installed) set 1 3,557 3,557

0 0

8 Design, manufacture, supplying, fixing in position, testing and commissioning of the

following rating Adopter Box for Rising Mains complete with interconnections as required.

The Adopter box shall be complete with voltmeter and ammeter with requisite CT's

0 0

0 0

a) 1-400 amp TPN switch isolator nos 24 1,897 45,528

0 0

9 Supplying and laying of following sizes 2 mm thick PVC conduit in recess/surface including

providing coupler, junction boxes complete as required from DG panel to all meter boards

( to get 24V DC signal to energy meter to record consumotions ON DG seperately)

0 0

0 0

a 25mm dia PVC conduit m 3,200 12 38,400

b 20 mm dia 2 mm thick PVC conduit from meter board to display unit in the apartment

m 31,000 10 310,000

c Supplying and laying of 2 x 2.5sq.mm PVC insulated copper wire m 3,500 12 42,000

0 0

9.1 Supplying and laying of 0.61 mm dia PVC insulated copper conductor wires in existing

conduit from Meter Board to freedom display units. 0 0

Three pair 0.61 mm dia (telephone wire) m 31,000 5 155,000

0 0

10 Design, manufacture, supplying fixing in position, testing and commissioning of the

following front operated cubicle type, front access 2mm thick steel enclosed free standing,

dust and vermin proof, switchboard with IP42 protection with hinged and lockable doors

complete with interconnections, tinned copper crimping lugs, bonding to earth and powder

coating suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system, and suitable for a

fault level of 25 MVA symmetrical at 415 volts. 0 0

All switchboards shall have provision for entry of cables from the top or bottom as

required. 0 0

All live accessible parts shall be shrouded and all equipment shall be finger touch proof.

The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and

busbar supports shall be used. Padlocking facility shall be provided on all outgoing

feeders doors and switch handles shall be lockable in OFF position. 0 0

The short circuit rating for MCCB's shall be Ics values 0 0

Page 75: Final Offer Electrical

0 0

10.1 SWITCHBOARD - TOWER (1 TO 12) 0 0

0 0

INCOMINGS 0 0

0 0

2 nos 630 amp 4P Switch Isolator complete with 0 0

0 0

a) 3 nos Cast resin current transformers of 630/5 ratio Class 1.0 for metering 0 0

b) 1 no AVF digital meter (Ampere,Voltage Frequency) 0 0

c) 1 no. 3 phase 4 wire unbalanced load, Digital kWH CT operated meter alongwith CT’s

class 1.0 accuracy 10 VA Burden. 0 0

d) 1 set of RYB Phase indicating lamps (LED type) 0 0

e) Red / Green ON/OFF indicator (LED type) 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 800

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The main neutral busbar is to be of 50%

capacity.

0 0

0 0

BUS COUPLER 0 0

0 0

1 nos 630 amp 4P Switch Isolator complete 0 0

0 0

INTERLOCKING 0 0

0 0

The Incoming & Buscoupler shall be electrically & mechanically interlocked such that

incomers cannot be paralleled. 0 0

0 0

OUTGOING UNITS 0 0

0 0

LEFT HAND SECTION 0 0

0 0

1 no. 400 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps 0 0

0 0

2 no. 160 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps 0 0

0 0

1 no. 100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps 0 0

0 0

Page 76: Final Offer Electrical

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication. 0 0

0 0

1 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON

indication. 0 0

0 0

RIGHT HAND SECTION 0 0

0 0

1 no. 400 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps 0 0

0 0

2 no. 160 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps 0 0

0 0

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication. 0 0

0 0

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 12 3,500 42,000

0 0

10.2 SWITCHBOARD - LIFTS-TOWER (1 TO 12) 0 0

0 0

INCOMINGS 0 0

0 0

1 no. 160 amp 4-P Changeover switch complete with 0 0

0 0

The incomers shall have the following indicating panel 0 0

0 0

a) 3 nos Cast resin current transformers of 160/5 ratio Class 1.0 for metering 0 0

b) 1 no AVF digital meter (Ampere,Voltage Frequency) 0 0

c) 1 set of RYB Phase indicating lamps (LED type) 0 0

d) Red / Green ON/OFF indicator (LED type) 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100% 0 0

0 0

OUTGOING UNITS 0 0

0 0

3 nos 100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps 0 0

0 0

Page 77: Final Offer Electrical

3 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication. 0 0

0 0

1 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON

indication. 0 0

0 0

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 12 4,743 56,916

0 0

10.3 SWITCHBOARD - BASEMENT VENTILATION 0 0

0 0

INCOMINGS 0 0

0 0

1 nos 160 amp TPN Switch Isolator complete with 0 0

0 0

The incomers shall have the following indicating panel 0 0

0 0

a) 3 nos Cast resin current transformers of 160/5 ratio Class 1.0 for metering 0 0

b) 1 no AVF digital meter (Ampere,Voltage Frequency) 0 0

c) 1 set of RYB Phase indicating lamps (LED type) 0 0

d) Red / Green ON/OFF indicator (LED type) 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

0 0

0 0

OUTGOING UNITS 0 0

0 0

8 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication. 0 0

0 0

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 12 4,743 56,916

0 0

11 Design manufacture, supply installation testing and commissioning of 1250 VA Inverter

system for a constant secondary voltage of 240 volts at 50 Hz, single phase, batteries

backup of minimum 4 hour duration including, batteries, battery chargers, rectifiers,

transformers, controls, protection and instruments etc complete as required. nos 12 7,817 93,804

0 0

Page 78: Final Offer Electrical

12 Design, manufacture, supplying fixing in position, testing and commissioning of the

following front operated cubicle type, front access 2mm thick steel enclosed free standing,

dust and vermin proof, switchboard with IP42 protection with hinged and lockable doors

complete with interconnections, tinned copper crimping lugs, bonding to earth and powder

coating suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system, and suitable for a

fault level of 25 MVA symmetrical at 415 volts.

0 0

0 0

All switchboards shall have provision for entry of cables from the top or bottom as

required. 0 0

0 0

All live accessible parts shall be shrouded and all equipment shall be finger touch proof.

The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and

busbar supports shall be used. Padlocking facility shall be provided on all outgoing

feeders doors and switch handles shall be lockable in OFF position. 0 0

0 0

The short circuit rating for MCCB's shall be Ics values 0 0

0 0

A. EWS MAIN PANEL 0 0

0 0

INCOMING 0 0

0 0

1 nos 400 amp TPN Switch Isolator complete with 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 400

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 50%

capacity.0 0

0 0

INDICATING PANEL 0 0

0 0

The incomers shall have the following indicating panel 0 0

a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for metering 0 0

b) 1 no ammeter of 96 mm sq scaled 0-400 amps with 3 way and OFF selector switch 0 0

c) 1 no voltmeter of 96 mm sq scaled 0- 500 volts with 3 way & OFF selector switch 0 0

d) 1 set of three White phase indicating lamps 0 0

0 0

OUTGOING UNITS 0 0

0 0

11 nos.100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps 0 0

Page 79: Final Offer Electrical

0 0

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication. 0 0

0 0

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 1 37,822 37,822

0 0

B EWS COMMON PANEL 0 0

0 0

INCOMING 0 0

0 0

2 nos 100 amp 4P Switch Isolator complete with 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 100

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 100%

capacity.

0 0

0 0

INDICATING PANEL 0 0

0 0

The incomers shall have the following indicating panel 0 0

a) 3 nos Cast resin current transformers of 100/5 ratio Class 1.0 for metering 0 0

b) 1 no ammeter of 96 mm sq scaled 0-100 amps with 3 way and OFF selector switch 0 0

c) 1 no voltmeter of 96 mm sq scaled 0- 100 volts with 3 way & OFF selector switch 0 0

d) 1 set of three White phase indicating lamps 0 0

0 0

INTERLOCKING 0 0

0 0

The Incoming shall be interlocked such that incomers cannot be paralleled. 0 0

0 0

OUTGOING UNITS 0 0

0 0

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication. 0 0

0 0

2 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON

indication. 0 0

0 0

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 1 4,742 4,742

0 0

E SWITCHBOARD - CLUB 0 0

0 0

Page 80: Final Offer Electrical

INCOMING 0 0

0 0

1 nos 400 amp TPN Switch Isolator complete with 0 0

0 0

a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for metering 0 0

b) 1 no digital electronic ammeter 400 amps 0 0

c) 1 no digital electronic voltmeter 500 volts 0 0

d) 1 set of three White phase indicating lamps (LED type) 0 0

e) Red / Green ON/OFF indicator (LED type) 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 600

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 50%

capacity. 0 0

0 0

OUTGOING UNITS 0 0

0 0

2 nos 125 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with Digital Electronic Energy Meter with requisite CT suitable

for remote data logging 0 0

S 0 0

12 nos 63 amp 10 kA TPN MCB with thermal magnetic release complete with Digital

Electronic Energy Meter with requisite CT suitable for remote data logging 0 0

0 0

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 1 2,371 2,371

0 0

3 Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of

meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation

with reinforcement of suitable size angle iron, channels, T irons, flats wherever

necessary. Cable gland plates shall be provided at top and bottom both and windows for

meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH meter &

meter to MCB shall be done by using adequately rated flexible single core copper wire.

The boards shall be treated with all anticorrosive process before painting as per

standards with final approved shade of powder coated as approved, 2 nos. earthing

terminals shall be provided for 3 phase meter boards and to be connected with the

earthing of rising mains by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for

415 V, 3 phase, 4 wire, 50 Hz supply system. Boards shall be fabricated in length, height,

depth etc to match with site conditions. 0 0

0 0

The Meter Board shall be in Non-compartmentalized construction. 0 0

0 0

An approval shall be taken for each panel before manufacturing. 0 0

Page 81: Final Offer Electrical

0 0

A SHOPPING METER BOARD 0 0

0 0

INCOMING 0 0

0 0

1 nos 100 amp TPN Switch Isolator complete with 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbar rated at 100 amp

having a maximum current density of 1 amp per sq. mm suitable to withstand symmetrical

fault level of 25 M.V.A at 415 volts .The neutral busbar is of 100% capacity.

0 0

0 0

OUTGOING UNITS 0 0

0 0

1 no 63 amp TPN 10 kA MCB with thermal magnetic protective releases. 0 0

0 0

4 no 32 amp TPN 10 kA MCB with thermal magnetic protective releases. 0 0

0 0

14-32 amp SPN 10 kA MCB with thermal magnetic protective releases each with provision

for fixing of 32 A DHBVNL approved Single phase digital dual register prepaid electronic

energy meter. 0 0

0 0

The switchboard shall be complete with all interconnection, riser , internal wiring, labels

etc. complete as required. nos 1 1,186 1,186

0 0

B METER BOARD -EWS 0 0

0 0

INCOMING 0 0

0 0

1 nos 100 amp TPN Switch Isolator complete with 0 0

0 0

BUSBAR 0 0

0 0

Electrolytic high conductivity aluminium three phase and neutral busbar rated at 100 amp

having a maximum current density of 1 amp per sq. mm suitable to withstand symmetrical

fault level of 25 M.V.A at 415 volts .The neutral busbar is of 100% capacity.

0 0

0 0

OUTGOING UNITS 0 0

0 0

2 no 32 amp TPN 10 kA MCB with thermal magnetic protective releases. 0 0

0 0

Page 82: Final Offer Electrical

20-32 amp SPN 10 kA MCB with thermal magnetic protective releases each with provision

for fixing of 32 A DHBVNL approved Single phase digital dual register prepaid electronic

energy meter. 0 0

0 0

The switchboard shall be complete with all interconnection, riser , internal wiring, labels

etc. complete as required. nos 9 1,186 10,674

0 0

C Design,Supply installation testing & commissioning of BIS approved single phase dual

register energy meter for recording dual electric supply from grid and DG with kWH &

kWAh max demand communication port, billing storage facilities, control panel for

sensing supply from DG sets, data transfer & receiving hub,AMR system. DLC with

energy management software with load manager system & recharge coupon generation

software & connecting accessories for prepaid system. 0 0

single phase dual register digital electronic prepaid energy meter ( for tariff application)

nos 194 1,186 230,084

0 0

0 0

TOTAL SUB-HEAD - IV carried over to Summary 0 4,531,026

0 0

SUB HEAD V : EARTHING 0 0

0 0

1 Supplying and laying of the following earthing clamped to wall with suitable clamps

saddles and fixing bolts/ in ground/RCC slab along with submain conduit including the cost

of digging and back filling with sand and brick protection as required and complete as

required to comply with IS 3043:1987 0 0

0 0

a) 25 mm x 6 mm GI strip m 3,800 18 68,400

b) 8 SWG GI Wire m 102,200 2 170,688

c) 6 SWG GI Wire m 20,400 3 61,200

0 0

2 Supply and laying of the following GI pipe in ground including excavation, refilling as

required for earth strips etc. as required complete 0 0

0 0

a) 80 mm dia m 181 60 10,860

0 0

3 Providing and making earthpits including the cost of 600 mm x 600 mm x 6 mm GI plate

electrode 20 mm dia GI pipe, CI funnel with wiremesh charcoal, salt, all earth work,

masonry enclosure with CI frame & cover plate having locking arrangement complete as

per IS 3043:1987. nos 80 2,964 237,120

0 0

4 Providing and laying earth connections from earth electrode with 2 x 6 SWG GI wire in 25

mm dia. GI pipe from earth electrode as required as per specifications. m 181 24 4,344

0 0

TOTAL SUB HEAD V carried over to Summary 0 552,612

0 0

SUB-HEAD -VI (FIXTURES AND FITTINGS) 0 0

Page 83: Final Offer Electrical

0 0

1a Supply of the following light fixtures complete with housing, reflectors, all accessories i.e.

copper wound ballast, HPF condensors, starters, holders etc. complete as required

0 0

0 0

a) 1x18 W CFL recess mounting downlighter as approved including providing lamps and

other accessories (base Rate Rs 800/-) nos 780 274 213,720

b) 1x18 W CFL surface mounting downlighter as approved including providing lamps and

other accessories (base Rate Rs 600/-) nos 3,693 201 742,293

c) 1x28 W T5 lamp surface mounting box type fixture as approved including providing lamps

and other accessories (base Rate Rs 800/-) nos 790 321 253,590

d) 1x11 W CFL lamp surface mounting bulk head fixture as approved including providing

lamps and other accessories (base Rate Rs 450/-) nos 530 167 88,510

e) 1x11 W CFL lamp surface mounting wall bracket fixture as approved including providing

lamps and other accessories (base Rate Rs 450/-) nos 24 139 3,336

f) 2x28 W T5 lamp pendat mounting box type fixture as approved including providing

downrods, lamps and other accessories (base Rate Rs 1200/-) nos 970 378 366,660

0 0

1b Receiving, assembling, erection, connecting, testing and commissioning of the following

light fixtures complete with housing, reflectors, all accessories i.e. copper wound ballast,

HPF condensors, starters, holders etc. complete as required

0 0

0 0

a) 1x18 W CFL recess mounting downlighter as approved including providing lamps and

other accessories nos 780 60 46,800

b) 1x18 W CFL surface mounting downlighter as approved including providing lamps and

other accessories nos 3,693 60 221,580

c) 1x28 W T5 lamp surface mounting box type fixture as approved including providing lamps

and other accessories nos 790 60 47,400

d) 1x11 W CFL lamp surface mounting bulk head fixture as approved including providing

lamps and other accessories nos 530 60 31,800

e) 1x11 W CFL lamp surface mounting wall bracket fixture as approved including providing

lamps and other accessories nos 24 60 1,440

f) 2x28 W T5 lamp pendat mounting box type fixture as approved including providing

downrods, lamps and other accessories nos 970 60 58,200

0 0

2 Supply, fixing, testing and commissioning of 240 Volt single phase ceiling fans of 1200

mm Sweep including supply of 19 mm heavy gauge GI down rod of length as required

complete. nos 17 83 1,411

0 0

3 Supply, fixing, testing and commissioning of 240 Volt single phase heavy duty Exhaust

Fans 300 mm dia complete with all accessories as required and with 6 amp 3 pin plug top

as required. nos 17 83 1,411

0 0

Page 84: Final Offer Electrical

4 Receiving, storing, transportation at site, unpacking, assembling, fixing, testing and

commissioning of 240 Volt single phase Buzzer as required complete. nos 1,206 60 72,360

0 0

TOTAL SUB-HEAD - VI carried over to Summary 0 2,150,511

0 0

SUB HEAD VII : LIGHTNING PROTECTION 0 0

0 0

1 Air Terminal & Accessories 0 0

Supplying, Erection & commissioning of External Lightning Wide Area Protection System

based on pro-active Early Streamer Emission (ESE) Technology type SATELIT-3-60.

Device shall emit electromagnetic impulse in the form of a controlled emission of

streamers into the air 60 microseconds earlier than naturally formed streamers & polarise

the tip with a voltage between 35 kV & 45 kV . Device confirming to NFC17-102 or UNE

21186 standards. The device shall be mounted at least 5 meter clear to the highest point

by Support Mast of 50mm dia Schedule 80 MS Pipe duly galvanized with minimum 85

micron zinc coating with foundation to suite Mast with concrete to cover 300mmX300mm

floor area & upto 600mm height complete as required sets 3 1,779 5,337

0 0

2 Low Impedance high voltage down conductor & accessories 0 0

Supply, installation, testing & commissioning of down conductor. The Down conductor

shall be of 25X3mm GI strip/Tape. They should be fixed to the structure by means of 2

fasteners every 1.0 meters horizontally & 0.5 meter vertically, It should then run down the

elevation pole and take the shortest direct route down the outside of the building to the

earth termination network, avoiding any sharp corners, thereby providing a low impedance

path from the air terminal to its earth termination system. m 300 12 3,600

0 0

3 Lightning Discharge Counter 0 0

Supply, installation, testing & commissioning of Lightning Discharge Counter. The

lightning event counter suitable for 1.0KA - 100KA . Counter housed in weather proof

IP67 enclosure with fixing clamps, etc. sets 3 237 711

0 0

4 Maintenance Free Earthing 0 0

Supply, Installation, Testing & Commissioning of long life, Maintenance Free Electrolytic

Earthing System Earth pit should consists of 3 nos. 1.2 meters long 14mm dia MS Rod

moleculerly bonded with 250 micron copper coating and treated with 10 kgs of Terec+,

The earthing pit shall be provided with suitable sturdy Test Well for observation. The Earth

Pit shall be covered with 25mm thick gravel/ tiles The Installation procedures should be

followed as instructed by the Earth Electrode Supplier)

nos 6 1,067 6,402

0 0

5 Supplying fixing, testing and commissioning of LED Aviation lights, complete as per Wipro

Cat WAN 20001 or Bajaj Cat BJAOL-1, complete with flasher etc as required

nos 3 1,186 3,558

0 0

Page 85: Final Offer Electrical

6 Supplying, fixing, testing and commissioning of photochromatic switch for automatic

ON/OFF of Aviation light as required. nos 3 119 357

0 0

7 Wiring for aviation light with 3 core 2.5 sq.mm XLPe insulated PVC sheathed copper

conductor armoured cable from M/C room DB to aviation light. m 200 30 6,000

0 0

8 Supply and fixing GI strip 25 mm x 6 mm along outside wall/ columns as vertical

conductors with suitable GI fasteners, brass fixing screws, copper clamps & saddles

complete as required. m 50 12 600

0 0

9 Supply and fixing GI strip 25 mm x 6 mm along roof as horizontal conductors with

suitable GI fasteners, brass fixing screws, copper clamps & saddles complete as required.

m 200 12 2,400

0 0

10 Supply and laying in ground of GI strip 32 mm x 6 mm for connecting to the GI earth plate

at one end and vertical conductor strip at the other end including the cost of digging and

back filling complete m 30 18 540

0 0

11 Providing and making earthpits including the cost of 600 mm x 600 mm x 6 mm GI plate

electrode 50 mm dia GI pipe, CI funnel with wiremesh charcoal, salt, all earth work,

masonry enclosure with CI frame & cover plate having locking arrangement complete as

per IS 3043:1987. nos 2 2,964 5,928

0 0

12 Supplying and laying in ground of GI strip 32 mm x 6 mm for interconnecting the various

Lightning arrestor earth pits, including the cost of digging and back filling, complete as

required. m 200 18 3,600

0 0

13 Supply and fixing testing joints made of 25 mm x 6 mm thick GI strip 125 mm long with 4

Nos. GI bolts, nuts, check nuts and spring washers complete as required. nos 2 12 24

0 0

14 Providing and fixing Lightning Conductor Finials made of 25 mm dia 300 mm long GI tube

having a single prong at the top with 85 mm dia 6 mm thick GI base plate complete as

required. nos 1 119 119

0 0

15 Supply and fixing of DMC/SMC insulator complete with GI clamps, Nut Bolts supports

wherever is required. nos 30 119 3,570

0 0

0 0

TOTAL SUB-HEAD - VII carried over to Summary 0 42,746

0 0

SUB-HEAD -VIII (FIRE DETECTION & ALARM SYSTEM) 0 0

0 0

Page 86: Final Offer Electrical

1 Supply, installation, testing and commissioning of wall or ceiling mounted 240 Volt AC

illuminated Signs having on its front a white perspex sheet with the letters 'FIRE EXIT'

painted in red including the cost of in-built rechargeable batteries suitable for 30 minute

operation and including the cost of accessories for surface or recessed or ceiling

suspended mounting complete as required. nos 514 42 21,588

0 0

2 Supply installation testing and commissioning of dust and vermin proof Manual call boxes

with push button to initiate audio visual alarm with breakable glass cover as per detailed

specifications complete with a steel chain including the cost of accessories for surface

mounted as required nos 514 42 21,588

0 0 0

3 Supply installation test and commissioning of the following 8 ohm size speaker-cum-

hooter units with line matching transformer suitable for broadcast of speech and alarm

siren complete as required suitable for recessed/surface mounting complete with

enclosure as approved by Project Manager and as required. nos 211 42 8,862

0 0

4 Supply, installation, testing and commissioning of wall recess mounting 24 zone

microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential

free contacts as per detailed specifications with alarms, controls and indications as per

detailed specifications and with an integral power supply unit and complete with a suitably

rated set of batteries and trickle charged from 240 volt AC mains supply, including the cost

of mounting accessories as required, complete. nos 10 2,371 23,710

0 0

4 Supply, installation, testing and commissioning of wall recess mounting 16 zone

microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential

free contacts as per detailed specifications with alarms, controls and indications as per

detailed specifications and with an integral power supply unit and complete with a suitably

rated set of batteries and trickle charged from 240 volt AC mains supply, including the cost

of mounting accessories as required, complete. nos 2 2,371 4,742

0 0

5 Supply, installation, testing and commissioning of wall recess mounting 15 zone

microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential

free contacts as per detailed specifications with alarms, controls and indications as per

detailed specifications and with an integral power supply unit and complete with a suitably

rated set of batteries and trickle charged from 240 volt AC mains supply, including the

cost of mounting accessories as required, complete. nos 1 2,371 2,371

0 0

6 Supply, installation, testing and commissioning of wall recess mounting 10 zone

microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential

free contacts as per detailed specifications with alarms, controls and indications as per

detailed specifications and with an integral power supply unit and complete with a suitably

rated set of batteries and trickle charged from 240 volt AC mains supply, including the cost

of mounting accessories as required, complete. nos 1 2,371 2,371

0 0

Page 87: Final Offer Electrical

7 Wiring with 2 core 1.5 Sqmm standard copper conductor FRLS 660/1100 volts grade

wires in existing concealed/surface MS conduit etc. as per specification and as required

including the cost of crimped termination's. m 36,500 12 438,000

0 0

8 Supply and laying control cabling with copper conductor PVC insulated and PVC

sheathed armoured Control cables in existing pipes/conduits or on existing tray including

the cost of making connections, complete etc. etc. as per specification and as required as

below: 0 0

0 0

a) 10 core 2.5 sq mm m 5,100 36 183,600

TOTAL SUB-HEAD -VIII carried over to Summary 706,832

Total30,584,691.31

Page 88: Final Offer Electrical

PART - A -- INTERNAL ELECTRICAL WORK FOR TOWERS, BASEMENTS, EWS, CLUB & SHOPPING COMPLEX

PALM GARDEN GROUP HOUSING AT SECTOR 83, GURGAON

TENDER FOR INTERNAL ELECTRICAL WORKS

Sl

No.Description Unit

Qty labour Labour Amount

SUB-HEAD - I (WIRING)

1 Wiring for primary light points for switch controlled points with 3 x 1.5 sq. mm PVC

insulated stranded copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick

PVC surface/concealed conduit including the cost of providing circuit wiring with 3 x 2.5 sq

mm PVC insulated stranded copper conductor 1100 volt grade wires and including cost of

providing saddles etc for surface conduiting and/or cost of cutting and filling chases for

recessed conduiting and including the cost of providing and fixing a 6 amp 240 Volt grid

plate mounted switch with moulded cover plate in 1.6 mm thick G.I box etc. complete as

per specifications and as per direction Project in-charge.

nos 33,315 109 3,623,006

2 Wiring for primary light points for MCB controlled points with 3 x 2.5 sq. mm PVC insulated

stranded copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick PVC

surface/concealed conduit including cost of providing saddles etc for surface conduiting

and/or cost of cutting and filling chases for recessed conduiting etc. complete as per

specifications and as per direction of Project in-charge. (Cost of MCB shall be paid in DB

item) nos 1,087 109 118,211

3 Wiring for secondary light points with 3x1.5 sq. mm PVC insulated stranded copper

conductor 1100 Volt grade wires in surface/concealed 20/25 mm dia 2 mm thick PVC

conduit including cost of providing saddles etc for surface conduiting and/or cost of cutting

and filling chases for recessed conduiting etc. complete as per specification and as per

direction of Project in-charge. nos 6,650 94 623,438

4 Wiring for Two-way light points switch controlled with 1.5 sq. mm PVC insulated stranded

copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick PVC

surface/concealed conduit including the cost of providing circuit wiring with 2.5 sq mm

PVC insulated stranded copper conductor 1100 volt grade wires and including cost of

providing saddles etc for surface conduiting and/or cost of cutting and filling chases for

recessed conduiting and including the cost of providing and fixing two sets of 6 amp 240

Volt grid plate mounted switch with moulded cover plate in 1.6 mm thick G.I box and

including the cost of running 1.5 sq mm PVC insulated copper conductor wire for loop

earthing etc. complete as per specifications and as per direction of Project in-charge.

nos 72 109 7,830

5 Wiring for Ceiling/bracket fan points with 3 x 1.5 sq. mm PVC insulated stranded copper

conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed

conduit including the cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated

stranded copper conductor 1100 volt grade wires and including cost of providing saddles

etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting

and including the cost of providing and fixing fan hook box, a 6 amp 240 volt single pole

grid plate mounted switch with moulded cover plate in a recessed 1.6 mm thick G.I box

with including cost of providing stepped electronic fan regulator as required etc. complete

as per specification and as per direction of Project in-charge.

nos 8,726 109 948,953

6 Wiring for Exhaust fan points with 3 x 1.5 sq. mm PVC insulated stranded copper

conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed

conduit including the cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated

stranded copper conductor 1100 volt grade wires and including cost of providing saddles

etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting

and including the cost of providing and fixing 5 pin 6 amp shuttered socket outlet a 6 amp

240 volt single pole grid plate mounted switch with moulded cover plate in a recessed 1.6

mm thick G.I box etc. complete as per specification and as per direction of Project in-

charge.( This shall include socket and plug top near fan & switch shall be put near

entrance to toilet/kitchen) nos 5,294 109 575,723

Page 89: Final Offer Electrical

7 Wiring for a 5 pin 240 volt 6 amp single phase and neutral switch socket outlet with 3 x 1.5

sq. mm PVC insulated stranded copper conductor 1100 Volt grade wires in 20/25 mm dia

2 mm thick PVC surface/concealed conduit including the cost of providing circuit wiring

with 3 x 2.5 sq mm PVC insulated stranded copper conductor 1100 volt grade wires and

including cost of providing saddles etc as required for surface conduiting and/or cost of

cutting and filling chases as required and providing and fixing of a combined 5 pin 240 volt

6 amp socket outlet with safety shutters and 6 amp 240 volt single pole grid plate mounted

switch with moulded cover plate in recessed 1.6 mm thick G.I box etc. complete as per

specification and as per direction of Project in-charge.

nos 17,842 120 2,141,040

8 Wiring as in Item 7 above looped from an adjacent 6 amp switch socket outlet as required

and providing and fixing of a modular type 5 pin 240 Volt 6 amp shuttered socket outlet

and a modular type 6 amp 240 Volt single pole switch in a recessed 1.6 mm thick G.I

boxes with internal wiring and moulded front plates as per approved sample complete as

per specification and as per direction of Project in-charge.

nos 50 86 4,275

9 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket outlets (1 outlet

wired on 1 circuit) with 3 x 4.0 sq. mm PVC insulated stranded copper conductor 1100 volt

grade wires in 20/25mm dia 2 mm thick PVC surface/concealed conduit including cost of

providing saddles etc as required for surface conduiting and/or cost of cutting and filling

chases as required and including providing and fixing of a 6 pin 240 volt 16 amp socket

outlet with safety shutters and 16 amp 240 volt single pole grid plate mounted switch with

moulded cover plate in a recessed 1.6 mm thick G.I boxes etc. complete as per

specification and as per direction of Project in-charge.

nos 1,206 150 180,900

10 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket outlets (2 outlets

wired on 1 circuit) with PVC insulated stranded copper conductor 1100 volt grade wires, 3

x 4.0 sq mm upto the first outlet and 3 x 4.0 sq mm from first to the second outlet, in 20/25

mm dia 2 mm thick PVC surface/concealed conduit including cost of providing saddles etc

as required for surface conduiting and/or cost of cutting and filling chases and including

providing and fixing of two sets of 6 pin 240 volt 16 amp socket outlet with safety shutters

and 16 amp 240 volt single pole grid plate mounted switches with moulded cover plate in a

recessed 1.6 mm thick G.I box etc. complete and as per direction of Project in-charge.

1,528 150 229,200

11 Wiring for 2 nos 6 pin 240 volt 20/20 amp looped single phase and neutral switch socket

(2 outlets wired on 1 circuit) with PVC insulated stranded copper conductor 1100 volt

grade wires, 3 x 4.0 sq mm upto the first outlet and 3 x 4.0 sq mm from first to the second

outlet, in 20/25 mm dia 2 mm thick PVC surface/concealed conduit including cost of

providing saddles etc as required for surface conduiting and/or cost of cutting and filling

chases and including providing and fixing of two sets of 6 pin 240 volt 20 amp socket

outlet with safety shutters and 20 amp 240 volt single pole grid plate mounted switches

with moulded cover plate in a recessed 1.6 mm thick G.I box etc. complete and as per

direction of Project in-charge.(Ist point for A/C & IInd for geyser)This shall include socket

& plug top near geyser and controlling switch at door.

nos 4,190 150 628,500

7 Wiring for AC points with 3 x 4.0 sq. mm PVC insulated stranded copper conductor 1100

volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed conduit including cost

of providing saddles etc as required for surface conduiting and/or cost of cutting and filling

chases as required and including providing and fixing of a 6 pin 240 volt 20 amp socket

outlet with safety shutters with moulded cover plate in recessed 1.6 mm thick GI box

including providing and fixing a 20 amp single pole 240 volt 20 amp switch with moulded

cover plate in recessed 1.6 mm thick G.I box located separately as per

drawings/instructions for AC controls complete as per specification and as per direction of

Project in-charge.(one outlet on one circuit) nos 414 169 69,863

13 Point wiring for 20 amp single phase socket outlets with 3 x 4 sq mm PVC insulated 1100

volt grade stranded copper conductor wires in 20/25 mm dia 2 mm thick PVC recessed

and/or surface conduiting system including the cost of cutting/making good chases in brick

work and including the cost of supplying and fixing 20/25 amp 10 kA SP MCB, industrial

type metal clad outlet in recessed 1.6 mm thick G.I box, metal clad plug top etc. complete

as per specifications and as per direction of Project in-charge.

nos 5 206 1,031

14 Wiring for bell push with 3 x 1.5 sq. mm PVC insulated stranded copper conductor 1100

volt grade wires in 20/25 mm dia 2 mm thick PVC surface/ concealed conduit including

cost of providing saddles etc as required for surface conduiting and/or cost of cutting and

filling chases as required and including providing and fixing a grid plate mounted 6 amp

240 volt Bell push with moulded cover plate in recessed zinc chromate passivated 1.6 mm

thick GI box etc. complete as per specifications and as per direction of Project in-charge.

nos 1,206 101 122,108

Page 90: Final Offer Electrical

15 Supplying and Laying of 2 mm thick PVC conduiting system recessed/surface including

cost of providing GI fish wire saddles, Bends (PVC), Junction Boxes (MS) etc. and/or cost

of cutting and filling chases for recessed conduiting complete with accessories as per

specifications and as per direction of Project in-charge.

a) 25 mm m 189,000 14 2,551,500

b) 32 mm m 1,080 14 15,390

c) 40 mm m 1,080 14 15,390

d) 50 mm m 580 16 9,135

16 Supplying and fixing of the following MS Conduits including the cost of draw/junction boxes

with accessories as required and including the cost of GI fish wire etc. complete as per

specifications and as per direction of Project in-charge.

a) 25 mm dia 16 SWG m 30,080 23 699,360

b) 32 mm dia 16 SWG m 480 28 13,320

c) 38 mm dia 14 SWG m 480 32 15,480

d) 50 mm dia 14 SWG m 480 43 20,520

17 Supplying and drawing following sizes of PVC insulated copper conductor single core

stranded cables in existing surface / recessed conduits as per specifications and/or as per

direction of Project in-charge. as required.

a) 3 x 1.5 sq mm (P+N+E) m 4,500 23 101,250

b) 3 x 2.5 sq mm (P+N+E) m 3,000 19 56,250

c) 3 x 4.0 sq mm (P+N+E) m 1,600 18 28,800

d) 3 x 6.0 sq mm (P+N+E) m 400 23 9,000

18 Supply, installation, testing and commissioning of the following switches, sockets in

recessed 1.6 mm thick GI box with moulded cover plate, including internal connections,

complete as per specifications and/or as per direction of Project in-charge.

a) 6 amp switch with box and cover plate nos 443 18 7,974

b) 6 amp switch and 5 pin socket outlet with box and cover plate nos 443 18 7,974

c) 16 amp switch and 6 pin socket outlet with box and cover plate nos 60 18 1,080

TOTAL SUB-HEAD - I carried over to Summary 12,826,499

SUB-HEAD - II (LOW TENSION SYSTEM)

1 Wiring for telephone points with 4 pair 0.61 mm annealed tinned electrolytic copper

conductor PVC insulated unshielded twisted wire in 25 mm dia 2 mm thick PVC

surface/concealed conduit upto central point and including cost of providing saddles etc for

surface conduiting and/or cost of cutting and filling chases for recessed conduiting and

including the cost of providing and fixing of a single telephone cord grid plate mounted

outlet unit (RJ-11) with moulded cover plate in recessed 1.6 mm thick GI box complete as

required for telephone/intercom system.. nos 5,473 109 595,189

2 Wiring for telephone points with 2 pair 0.61 mm annealed tinned electrolytic copper

conductor PVC insulated unshielded twisted wire in 25 mm dia 2 mm thick PVC

surface/concealed conduit upto central point and including cost of providing saddles etc for

surface conduiting and/or cost of cutting and filling chases for recessed conduiting and

including the cost of providing and fixing of a single telephone cord grid plate mounted

outlet unit (RJ-11) with moulded cover plate in recessed 1.6 mm thick GI box complete as

required for telephone/intercom system. nos 20 86 1,710

3 Supply and fixing of the following sheet steel clad wall/recess/floor mounting telephone tag

block of Krone make constructed from 14 SWG sheet steel, finished with powder coated

paint, with hinged gasketted door and complete with adequately rated and sized telephone

terminal block to receive incoming and outgoing wires. The cost shall be complete with

fixing arrangements, foundations etc as required

a) 10 Pair nos 13 134 1,736

b) 20 Pair nos 4 178 711

c) 30 Pair nos 8 356 2,844

d) 50 Pair nos 95 356 33,773

e) 300 Pair nos 2 2,668 5,336

f) 400 Pair nos 11 3,557 39,130

4 Supply, laying clamped to wall with suitable clamps saddles and bolts/ in ground including

the cost of digging and back filling with sand and brick protection as required and testing

and commissioning of the following multi core 0.61 mm annealed tinned copper conductor

PVC insulated and PVC sheathed and overall PVC sheathed armoured telephone cables

including making terminal joints, complete as per specification and /or as per direction of

Project in-charge.

a) 10 Pair m 80 5 420

b) 20 Pair m 50 8 413

Page 91: Final Offer Electrical

c) 30 Pair m 300 18 5,400

d) 50 Pair m 4,030 27 108,810

5 Supply and fixing of co-axial outlets for TV with moulded cover plate in recessed zinc

chromate passivated MS boxes, including termination complete in all respects as per

specification and / or as per direction of Project in-charge.. nos 5,367 45 241,515

6 Supply and laying of coaxial cable RG-59 for Branch line in existing surface/concealed

conduits upto the central point complete in all respects as per specification and / or as per

direction of Project in-charge. m 155,750 4 584,063

7 Supply, erection and commissioning of 3 way / 4 way spliter for cable TV in MS enclosure

with 3 mm thick hylum sheet cover as required at site and /or as per direction of Project in-

charge. nos 934 45 42,030

8 Supply, erection and commissioning of 6 way tap off in MS enclosures with 3 mm thick

hylum sheet cover for cable TV as required at site and /or as per direction of Project in-

charge.. nos 149 178 26,485

TOTAL SUB-HEAD - II carried over to Summary 1,689,562

SUB-HEAD - III (SUBMAINS AND CABLES)

1 Wiring for Submains with PVC insulated stranded copper conductor 1100 volt grade wires

in surface/concealed conduit including cost of providing saddles, Bends (PVC), Junction

Boxes (MS) etc including the cost of cutting and filling chases as required and as per

specification and as per direction of Project in-charge.

a) 2 x 10 sq mm in PVC 25 mm dia 2 mm thick conduit m 6,850 18 123,300

b) 4 x 10 sq mm in PVC 32 mm dia 2 mm thick conduit m 81 40 3,220

c) 4 x 16 sq mm in PVC 40 mm dia 2 mm thick conduit m 405 49 19,744

1.1 Wiring for Submains with PVC insulated stranded copper conductor 1100 volt grade wires

in surface/concealed conduit including cost of providing saddles, Bends (PVC), Junction

Boxes (MS) etc including the cost of cutting and filling chases as required and as per

specification and as per direction of Project in-charge.

a) 2 x 10 sq mm in PVC 25 mm dia 2 mm thick conduit m 1,900 18 34,200

b) 4 x 10 sq mm in PVC 32 mm dia 2 mm thick conduit m 30,000 40 1,192,500

c) 4 x 16 sq mm in PVC 40 mm dia 2 mm thick conduit m 4,200 49 204,750

2 Supply and laying in cable Tray/clamped to wall with suitable clamps saddles and bolts/ in

ground including the cost of digging and back filling with sand and brick protection as

required and including testing and commissioning of the following 1100 volt grade

armoured PVC/XLPE insulated and sheathed aluminium conductor armoured cable

complete as required. The costs shall include providing a gap of 1D between all the cables

being laid and properl clamping with cable clamps and ties. Prices shall include providing

and fixing of Identification tags for all cables and route markers for cables in ground etc.

as per specification and or as per direction of Project in-charge.

a) 3 -1/2 core 300 Sq mm XLPE m 1,000 27 27,000

b) 3 -1/2 core 240 Sq mm XLPE m 50 27 1,350

c) 3 -1/2 core 185 Sq mm XLPE m 100 27 2,700

d) 3 -1/2 core 70 Sq mm XLPE m 4,800 27 129,600

e) 3 -1/2 core 50 Sq mm XLPE m 600 58 34,650

f) 4 core 35 Sq mm XLPE m 100 27 2,700

g) 4 core 25 Sq mm XLPE m 200 23 4,500

h) 4 core 16 Sq mm XLPE m 1,200 18 21,600

i) 4 core 10 Sq mm XLPE m 7,000 18 126,000

j) 4 core 6 Sq mm XLPE m 100 18 1,800

k) 2 core 10 Sq mm XLPE m 1,000 18 18,000

3 Providing and fixing of Cable jointing of the following XLPE cables 1100 Volt grade

including cost of tinned copper heavy duty lugs, double compression glands, insulation

tape and all requisite material for completion of joints.

a) 3 -1/2 core 300 Sq mm XLPE nos 40 178 7,110

b) 3 -1/2 core 240 Sq mm XLPE nos 2 178 356

c) 3 -1/2 core 185 Sq mm XLPE nos 4 133 531

d) 3 -1/2 core 70 Sq mm XLPE nos 418 45 18,810

e) 3 -1/2 core 50 Sq mm XLPE nos 26 45 1,170

f) 4 core 35 Sq mm XLPE nos 2 45 90

g) 4 core 25 Sq mm XLPE nos 4 18 72

Page 92: Final Offer Electrical

h) 4 core 16 Sq mm XLPE nos 66 18 1,188

i) 4 core 10 Sq mm XLPE nos 248 18 4,464

j) 4 core 6 Sq mm XLPE nos 4 9 36

k) 2 core 10 Sq mm XLPE nos 50 9 450

4 Supply and fixing of 14 SWG sheet steel slotted cable trays as per approved design and

MS painted angle supports spaced 1000 mm apart throughout the length as specified,

including the cost of 1 meter MS threaded rod hangers duly painted, hooks, dash

fasteners etc. for suspension from ceiling etc. as per specification and/or as per direction

of Project in-charge.

a) 150 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS

rod hangers) m 50 23 1,125

b) 300 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS

rod hangers) m 100 23 2,250

c) 450 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS

rod hangers) m 300 23 6,750

d) 600 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS

rod hangers) m 100 31 3,075

5 Supply and fixing of additional length of MS rod hangers duly painted with 1 coat of primer

and 2 coats enamel paint for supporting the Cable Trays for extension of the supports as

in item no. 4 above. kg 1,010 16 15,908

6 Supply and fixing Ladder type cable trays with 100 mm vertical sides on both ends as per

approved design of the following sizes, including cost of providing and fixing of 15 x 30 x

15 mm MS channel supports spaced 250 mm apart throughout the length with necessary

fixing arrangements with angle iron supports etc. as per specification and /or as per

direction of Project in-charge. Rate shall include providing and applying paint 1 coat of

primer and 2 coats of enamel paint for all the MS material .

a) 900 mm m 80 210 16,800

b) 750 mm m 150 210 31,500

c) 600 mm m 150 210 31,500

d) 450 mm m 350 173 60,375

e) 300 mm m 650 173 112,125

f) 150 mm m 40 155 6,210

7 Providing and fixing Steel work welded in built up sections/ framed work including cutting,

fixing in position with fasteners, including a priming coat of primer and two coats of

approved synthetic enamel paint.

a) In grating, frames, ladders, brackets, similar works kg 530 16 8,348

8 Supply and laying of the following RCC Hume pipe NP-2 grade including excavation,

refilling including compaction of soil as required for cable entry including the cost of sealing

the ends as required complete in all respects, as per spacification and /or as per direction

of Project in-charge.

a) 150 mm dia m 680 53 36,210

b) 200 mm dia m 500 71 35,625

c) 300 mm dia m 500 107 53,250

9 Providing and making of manhole chamber with masonry bricks and plastering inside with

1:3:6 and fixing of Heavy duty frame and pre cast RCC cover as required.

a) 600 x 600 x 750 mm deep nos 34 533 18,131

b) 450 x 450 x 750 mm deep nos 34 400 13,592

TOTAL SUB-HEAD - III carried over to Summary 2,434,662

SUB-HEAD - IV (DISTRIBUTION SYSTEM)

1 Supply, erection, testing and commissioning of the following sheet steel clad wall recess

mounting dust and vermin proof distribution boards constructed from 18 SWG sheet steel

IP 42 construction, duly powder coated with hinged gasketted door and housing the

following complete with suitably rated PVC insulated copper busbars with interconnections

and neutral bar assembly, earthing terminals complete as approved by Project Manager.

Padlocking facility shall be provided on the door.

a) 12 WAY SPN

Page 93: Final Offer Electrical

1-40 amp DP MCB incoming with 32 amp ON position latched contactor and 24 hours

programe timer for operation of incoming and 12 no. 6/16/20 amps SP 10 kA MCB with

thermal magnetic protective releases out goings nos R/O 2,837 0

b) 12 WAY SPN

1-63 amp SPN 10 kA MCB with thermal magnetic protective releases incoming with 1-63

amp DP 30 mA ELCB incoming and 12 nos 6/16/20/25 amps SP 10 kA MCB with thermal

magnetic protective releases out goings. nos R/O 1,607 0

c) 6 WAY TPN (per phase isolation)-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3

single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 6 no.

6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.

nos R/O 1,229 #VALUE!

d) 8 WAY TPN (per phase isolation)-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3

single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 8 no.

6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.

nos R/O 3,499 #VALUE!

e) 8 WAY TPN with Timer on 2-phases-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with

1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming and 8 no. 6/16/20

amps SP 10 kA MCB with thermal magnetic protective releases out goings

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32

amp ON position latched contactor and 24 hours programe timer for operation of incoming

and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out

goings nos R/O 4,728 0

f) 12 WAY TPN with Timer on 2-phases-Vertial DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with

1 single phase bank comprising of 1- 63 amp 30 mA DP ELCB incoming and 12 no.

6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32

amp ON position latched contactor and 24 hours programe timer for operation of incoming

and 12 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out

goings nos R/O 6,052 0

g) Incomer DB for Penthouses-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 2 nos

63 amp SPN 10 kA MCB with thermal magnetic protective releases out goings.

nos R/O 473 0

h) 8 Way VTPN

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 8 nos

6-32 amp 10 kA TP MCB with thermal magnetic protective releases out goings nos R/O 3,499 0

2 Design, manufacture, supplying, fixing, testing and commissioning of the following 2 mm

thick sheet steel enclosed, wall mounting, dust and vermin proof with IP 42 protection

triple pole and with 100% neutral Rising Mains with PVC insulated aluminium busbars

with a maximum current density of 1.0 amp per sq mm and suitable to withstand a

symmetrical fault level of 45 kA at 415 volts, complete with fire proof barriers at every floor

level, expansion joints, thrust pads to support weight of busbars, fully gasketed covers,

with arrangement to plug in tap off boxes as required and connecting chamber for

incoming isolator, powder coating, complete with fixing arrangements as required and with

2 runs of aluminium strip for earthing as required .

a) 400 amps m R/O 1,892 0

3a Supplying, erection, testing and commissioning of Tap-Off Boxes with 125 amp TPN

MCCB (25 kA) and cable end boxes as required nos R/O 1,796 0

3b Supplying, erection, testing and commissioning of Tap-Off Boxes with 160 amp TPN

MCCB (25 kA) and cable end boxes as required nos R/O 1,986 0

4 Meter Boards Tap-Off Boxes

Page 94: Final Offer Electrical

Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of

meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation

with reinforcement of suitable size angle iron, channels, T irons, flats wherever necessary

for large meter boards. Cable gland plates shall be provided at top and bottom both and

windows for meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH

meter & meter to MCB shall be done by using adequately rated flexible single core

copper wire. The boards shall be treated with all anticorrosive process before painting as

per standards with final approved shade of powder coated as approved 2 nos. earthing

terminals shall be provided for 3 phase meter boards and to be connected with the

earthing by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for 415 V, 3 phase, 4

wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth etc to

match with site conditions.

An approval shall be taken for each panel before manufacturing. Galvanised hardwares

with zinc passivation shall be used in fabrication of boards.

a) 6 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

6 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 6 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 8 way terminal

block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 12,292 0

b) 5 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

5 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 5 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 8 way terminal

block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 11,725

c) 4 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

Page 95: Final Offer Electrical

4 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 4 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 6 way terminal

block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 10,401

d) 3 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

3 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 3 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 6 way terminal

block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 8,510

e) 2 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

2 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 2 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 4 way terminal

block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 5,673

f) 9 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

9 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 9 nos 63A(10kA) SPN MCB and

provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register

electronic energy meter (projection mounted & for tariff application) for recording dual

electric supply from grid and DG complete with control and internal wiring for the same.

Dual meter shall also have facility for pre-paid measurement complete with 12 way

terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos R/O 17,966

5 Dual Pre-Paid meter

Page 96: Final Offer Electrical

Design,supply ,installation testing and commissioning of BIS approved single phase dual

energy meter for recording dual electric supply from grid and DG with KWH & KVAH max

demand communication port,billing,storage facilities ,control panel for sensing supply from

DG sets, data transfer & receiving hub, AMR system. DLC with energy management

software with load manager system and recharge coupon generation software &

connecting accessories for prepaid system.

1 phase digital electronic energy meter (for tariff application) nos R/O 3,404

ALTERNATIVELY

1 Supply, erection, testing and commissioning of the following sheet steel clad wall recess

mounting dust and vermin proof distribution boards constructed from 18 SWG sheet steel

IP 42 construction, duly powder coated with hinged gasketted door and housing the

following complete with suitably rated PVC insulated copper busbars with interconnections

and neutral bar assembly, earthing terminals complete as approved by Project Manager.

Padlocking facility shall be provided on the door.

a) 12 WAY SPN

1-40 amp DP MCB incoming with 32 amp ON position latched contactor and 24 hours

programe timer for operation of incoming and 12 no. 6/16/20 amps SP 10 kA MCB with

thermal magnetic protective releases out goings nos 18 533 9,599

b) 12 WAY SPN

1-63 amp SPN 10 kA MCB with thermal magnetic protective releases incoming with 1-63

amp DP 30 mA ELCB incoming and 12 nos 6/16/20/25 amps SP 10 kA MCB with thermal

magnetic protective releases out goings. nos 20 533 10,665

c) 6 WAY TPN (per phase isolation)-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3

single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 6 no.

6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.

nos 1,098 675 741,150

d) 8 WAY TPN (per phase isolation)-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3

single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 8 no.

6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.

nos 5 900 4,500

e) 8 WAY TPN with Timer on 2-phases-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with

1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming and 8 no. 6/16/20

amps SP 10 kA MCB with thermal magnetic protective releases out goings

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32

amp ON position latched contactor and 24 hours programe timer for operation of incoming

and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out

goings nos 35 4,160 145,609

f) 12 WAY TPN with Timer on 2-phases-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with

1 single phase bank comprising of 1- 63 amp 30 mA DP ELCB incoming and 12 no.

6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings

2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32

amp ON position latched contactor and 24 hours programe timer for operation of incoming

and 12 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out

goings nos 10 1,334 13,343

g) Incomer DB for Penthouses-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 2 nos

63 amp TPN 10 kA MCB with thermal magnetic protective releases out goings.

nos 72 712 51,246

h) 8 Way VTPN-Vertical DB

1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 8 nos

6-32 amp 10 kA TP MCB with thermal magnetic protective releases out goings nos 2 890 1,779

j) 8 WAY SPN

1-32 amp SPN MCB incoming and 8 nos 6/16/20 amps SP 10 kA MCB with thermal

magnetic protective releases out goings nos 1 445 445

k) 4 WAY SPN

1-32 amp SPN MCB incoming and 4 nos 6/16/20 amps SP 10 kA MCB with thermal

magnetic protective releases out goings nos 194 356 68,967

Page 97: Final Offer Electrical

2 Design, manufacture, supplying, fixing, testing and commissioning of the following 2 mm

thick sheet steel enclosed, wall mounting, dust and vermin proof with IP 42 protection

triple pole and with 100% neutral Rising Mains with PVC insulated aluminium busbars

with a maximum current density of 1.0 amp per sq mm and suitable to withstand a

symmetrical fault level of 45 kA at 415 volts, complete with fire proof barriers at every floor

level, expansion joints, thrust pads to support weight of busbars, fully gasketed covers,

with arrangement to plug in tap off boxes as required and connecting chamber for

incoming isolator, powder coating, complete with fixing arrangements as required and with

2 runs of aluminium strip for earthing as required .

a) 400 amps m 620 672 416,640

3a Supplying, erection, testing and commissioning of Tap-Off Boxes with 125 amp TPN

MCCB (25 kA) and cable end boxes as required nos 169 890 150,326

3b Supplying, erection, testing and commissioning of Tap-Off Boxes with 160 amp TPN

MCCB (25 kA) and cable end boxes as required nos 12 1,334 16,011

4 Meter Boards Tap-Off Boxes

Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of

meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation

with reinforcement of suitable size angle iron, channels, T irons, flats wherever necessary

for large meter boards. Cable gland plates shall be provided at top and bottom both and

windows for meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH

meter & meter to MCB shall be done by using adequately rated flexible single core

copper wire. The boards shall be treated with all anticorrosive process before painting as

per standards with final approved shade of powder coated as approved 2 nos. earthing

terminals shall be provided for 3 phase meter boards and to be connected with the

earthing by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for 415 V, 3 phase, 4

wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth etc to

match with site conditions.

An approval shall be taken for each panel before manufacturing. Galvanised hardwares

with zinc passivation shall be used in fabrication of boards.

a) 6 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

6 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 6 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with 8

way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 153 3,113 476,213

b) 5 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

Page 98: Final Offer Electrical

5 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 5 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with 8

way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 6 3,113 18,675

c) 4 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

4 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 4 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with 6

way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 8 2,846 22,764

d) 3 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

3 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 3 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with 6

way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 4 2,223 8,892

e) 2 WAY

Incomer

Provision for direct cable connection to busbars

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

2 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 2 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with 4

way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 8 1,778 14,226

f) 9 WAY

Incomer

Provision for direct cable connection to busbars

Page 99: Final Offer Electrical

Bus Bars

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

capacity.

Outgoings

9 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet

sealing & locking arrangement complete with supply of 9 nos 63A(10kA) FP MCB and

provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load

digital electronic dual KWH enegy meters (projection mounted & for tariff application) for

recording dual electric supply from grid and DG complete with control and internal wiring

for the same. Dual meter shall also have facility for pre-paid measurement complete with

12 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.

nos 2 7,115 14,229

5 Dual Pre-Paid meter

Design,supply ,installation testing and commissioning of BIS approved three phase 4wire

dual energy meter for recording dual electric supply from grid and DG with KWH & KVAH

max demand communication port,billing,storage facilities ,control panel for sensing supply

from DG sets, data transfer & receiving hub, AMR system. DLC with energy management

software with load manager system and recharge coupon generation software &

connecting accessories for prepaid system.

3 phase digital electronic energy meter (for tariff application) nos 1,026 356 364,743

6 Design ,supply ,installation, testing and commissioning of required software to make the

kWH meter functional in coordination with kWH meter manufacturer and facility

mangement team for prepaid/postpaid tariff application system for dual resistor (

recording) KWH meter to effectively monitor/control the tariff as per individual site

condition complete with latest version of computer & printer etc as required. ( Integrated

with existing software installed) job 1

7 Design, manufacture, supply, installation, testing and commissioning of cubical type

electrical control panel comprising of necessary contactors.PLA relays terminals etc to

provide signaled DC supply to the dual source energy meters.( Integrated with existing

software installed) set 1 2,668 2,668

8 Design, manufacture, supplying, fixing in position, testing and commissioning of the

following rating Adopter Box for Rising Mains complete with interconnections as required.

The Adopter box shall be complete with voltmeter and ammeter with requisite CT's

a) 1-400 amp TPN switch isolator nos 24 1,423 34,146

9 Supplying and laying of following sizes 2 mm thick PVC conduit in recess/surface including

providing coupler, junction boxes complete as required from DG panel to all meter boards

( to get 24V DC signal to energy meter to record consumotions ON DG seperately)

a 25mm dia PVC conduit m 3,200 9 28,800

b 20 mm dia 2 mm thick PVC conduit from meter board to display unit in the apartment

m 31,000 8 232,500

c Supplying and laying of 2 x 2.5sq.mm PVC insulated copper wire m 3,500 9 31,500

9.1 Supplying and laying of 0.61 mm dia PVC insulated copper conductor wires in existing

conduit from Meter Board to freedom display units.

Three pair 0.61 mm dia (telephone wire) m 31,000 4 116,250

10 Design, manufacture, supplying fixing in position, testing and commissioning of the

following front operated cubicle type, front access 2mm thick steel enclosed free standing,

dust and vermin proof, switchboard with IP42 protection with hinged and lockable doors

complete with interconnections, tinned copper crimping lugs, bonding to earth and powder

coating suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system, and suitable for a

fault level of 25 MVA symmetrical at 415 volts.

All switchboards shall have provision for entry of cables from the top or bottom as

required.

All live accessible parts shall be shrouded and all equipment shall be finger touch proof.

The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and

busbar supports shall be used. Padlocking facility shall be provided on all outgoing feeders

doors and switch handles shall be lockable in OFF position.

The short circuit rating for MCCB's shall be Ics values

10.1 SWITCHBOARD - TOWER (1 TO 12)

Page 100: Final Offer Electrical

INCOMINGS

2 nos 630 amp 4P Switch Isolator complete with

a) 3 nos Cast resin current transformers of 630/5 ratio Class 1.0 for metering

b) 1 no AVF digital meter (Ampere,Voltage Frequency)

c) 1 no. 3 phase 4 wire unbalanced load, Digital kWH CT operated meter alongwith CT’s

class 1.0 accuracy 10 VA Burden.

d) 1 set of RYB Phase indicating lamps (LED type)

e) Red / Green ON/OFF indicator (LED type)

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 800

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The main neutral busbar is to be of 50%

capacity.

BUS COUPLER

1 nos 630 amp 4P Switch Isolator complete

INTERLOCKING

The Incoming & Buscoupler shall be electrically & mechanically interlocked such that

incomers cannot be paralleled.

OUTGOING UNITS

LEFT HAND SECTION

1 no. 400 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

2 no. 160 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

1 no. 100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication.

1 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON

indication.

RIGHT HAND SECTION

1 no. 400 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

2 no. 160 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication.

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 12 2,625 31,500

10.2 SWITCHBOARD - LIFTS-TOWER (1 TO 12)

INCOMINGS

1 no. 160 amp 4-P Changeover switch complete with

The incomers shall have the following indicating panel

a) 3 nos Cast resin current transformers of 160/5 ratio Class 1.0 for metering

b) 1 no AVF digital meter (Ampere,Voltage Frequency)

c) 1 set of RYB Phase indicating lamps (LED type)

d) Red / Green ON/OFF indicator (LED type)

BUSBAR

Page 101: Final Offer Electrical

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

OUTGOING UNITS

3 nos 100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

3 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication.

1 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON

indication.

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 12 3,557 42,687

10.3 SWITCHBOARD - BASEMENT VENTILATION

INCOMINGS

1 nos 160 amp TPN Switch Isolator complete with

The incomers shall have the following indicating panel

a) 3 nos Cast resin current transformers of 160/5 ratio Class 1.0 for metering

b) 1 no AVF digital meter (Ampere,Voltage Frequency)

c) 1 set of RYB Phase indicating lamps (LED type)

d) Red / Green ON/OFF indicator (LED type)

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

OUTGOING UNITS

8 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication.

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 12 3,557 42,687

11 Design manufacture, supply installation testing and commissioning of 1250 VA Inverter

system for a constant secondary voltage of 240 volts at 50 Hz, single phase, batteries

backup of minimum 4 hour duration including, batteries, battery chargers, rectifiers,

transformers, controls, protection and instruments etc complete as required.

nos 12 5,863 70,353

12 Design, manufacture, supplying fixing in position, testing and commissioning of the

following front operated cubicle type, front access 2mm thick steel enclosed free standing,

dust and vermin proof, switchboard with IP42 protection with hinged and lockable doors

complete with interconnections, tinned copper crimping lugs, bonding to earth and powder

coating suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system, and suitable for a

fault level of 25 MVA symmetrical at 415 volts.

All switchboards shall have provision for entry of cables from the top or bottom as

required.

All live accessible parts shall be shrouded and all equipment shall be finger touch proof.

The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and

busbar supports shall be used. Padlocking facility shall be provided on all outgoing feeders

doors and switch handles shall be lockable in OFF position.

The short circuit rating for MCCB's shall be Ics values

A. EWS MAIN PANEL

INCOMING

1 nos 400 amp TPN Switch Isolator complete with

Page 102: Final Offer Electrical

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 400

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 50%

capacity.

INDICATING PANEL

The incomers shall have the following indicating panel

a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for metering

b) 1 no ammeter of 96 mm sq scaled 0-400 amps with 3 way and OFF selector switch

c) 1 no voltmeter of 96 mm sq scaled 0- 500 volts with 3 way & OFF selector switch

d) 1 set of three White phase indicating lamps

OUTGOING UNITS

11 nos.100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with ON/OFF indicating lamps

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication.

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 1 28,367 28,367

B EWS COMMON PANEL

INCOMING

2 nos 100 amp 4P Switch Isolator complete with

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 100

amps having a maximum current density of 1.0 amp per sq mm suitable to with stand

symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 100%

capacity.

INDICATING PANEL

The incomers shall have the following indicating panel

a) 3 nos Cast resin current transformers of 100/5 ratio Class 1.0 for metering

b) 1 no ammeter of 96 mm sq scaled 0-100 amps with 3 way and OFF selector switch

c) 1 no voltmeter of 96 mm sq scaled 0- 100 volts with 3 way & OFF selector switch

d) 1 set of three White phase indicating lamps

INTERLOCKING

The Incoming shall be interlocked such that incomers cannot be paralleled.

OUTGOING UNITS

4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON

indication.

2 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON

indication.

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 1 3,557 3,557

E SWITCHBOARD - CLUB

INCOMING

1 nos 400 amp TPN Switch Isolator complete with

a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for metering

b) 1 no digital electronic ammeter 400 amps

c) 1 no digital electronic voltmeter 500 volts

d) 1 set of three White phase indicating lamps (LED type)

e) Red / Green ON/OFF indicator (LED type)

BUSBAR

Page 103: Final Offer Electrical

Electrolytic high conductivity aluminium three phase and neutral busbars rated at 600

amps having a maximum current density of 1 amp per sq mm suitable to with stand

symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 50%

capacity.

OUTGOING UNITS

2 nos 125 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit

magnetic release complete with Digital Electronic Energy Meter with requisite CT suitable

for remote data logging

S

12 nos 63 amp 10 kA TPN MCB with thermal magnetic release complete with Digital

Electronic Energy Meter with requisite CT suitable for remote data logging

The Switchboard shall be complete with all interconnections, risers, internal wiring, labels

etc complete as required nos 1 1,778 1,778

3 Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of

meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation

with reinforcement of suitable size angle iron, channels, T irons, flats wherever

necessary. Cable gland plates shall be provided at top and bottom both and windows for

meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH meter &

meter to MCB shall be done by using adequately rated flexible single core copper wire.

The boards shall be treated with all anticorrosive process before painting as per

standards with final approved shade of powder coated as approved, 2 nos. earthing

terminals shall be provided for 3 phase meter boards and to be connected with the

earthing of rising mains by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for

415 V, 3 phase, 4 wire, 50 Hz supply system. Boards shall be fabricated in length, height,

depth etc to match with site conditions.

The Meter Board shall be in Non-compartmentalized construction.

An approval shall be taken for each panel before manufacturing.

A SHOPPING METER BOARD

INCOMING

1 nos 100 amp TPN Switch Isolator complete with

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbar rated at 100 amp

having a maximum current density of 1 amp per sq. mm suitable to withstand symmetrical

fault level of 25 M.V.A at 415 volts .The neutral busbar is of 100% capacity.

OUTGOING UNITS

1 no 63 amp TPN 10 kA MCB with thermal magnetic protective releases.

4 no 32 amp TPN 10 kA MCB with thermal magnetic protective releases.

14-32 amp SPN 10 kA MCB with thermal magnetic protective releases each with provision

for fixing of 32 A DHBVNL approved Single phase digital dual register prepaid electronic

energy meter.

The switchboard shall be complete with all interconnection, riser , internal wiring, labels

etc. complete as required. nos 1 890 890

B METER BOARD -EWS

INCOMING

1 nos 100 amp TPN Switch Isolator complete with

BUSBAR

Electrolytic high conductivity aluminium three phase and neutral busbar rated at 100 amp

having a maximum current density of 1 amp per sq. mm suitable to withstand symmetrical

fault level of 25 M.V.A at 415 volts .The neutral busbar is of 100% capacity.

OUTGOING UNITS

Page 104: Final Offer Electrical

2 no 32 amp TPN 10 kA MCB with thermal magnetic protective releases.

20-32 amp SPN 10 kA MCB with thermal magnetic protective releases each with provision

for fixing of 32 A DHBVNL approved Single phase digital dual register prepaid electronic

energy meter.

The switchboard shall be complete with all interconnection, riser , internal wiring, labels

etc. complete as required. nos 9 890 8,006

C Design,Supply installation testing & commissioning of BIS approved single phase dual

register energy meter for recording dual electric supply from grid and DG with kWH &

kWAh max demand communication port, billing storage facilities, control panel for sensing

supply from DG sets, data transfer & receiving hub,AMR system. DLC with energy

management software with load manager system & recharge coupon generation software

& connecting accessories for prepaid system.

single phase dual register digital electronic prepaid energy meter ( for tariff application)

nos 194 890 172,563

TOTAL SUB-HEAD - IV carried over to Summary 3,398,270

SUB HEAD V : EARTHING

1 Supplying and laying of the following earthing clamped to wall with suitable clamps saddles

and fixing bolts/ in ground/RCC slab along with submain conduit including the cost of

digging and back filling with sand and brick protection as required and complete as

required to comply with IS 3043:1987

a) 25 mm x 6 mm GI strip m 3,800 14 51,300

b) 8 SWG GI Wire m 102,200 1 128,016

c) 6 SWG GI Wire m 20,400 2 45,900

2 Supply and laying of the following GI pipe in ground including excavation, refilling as

required for earth strips etc. as required complete

a) 80 mm dia m 181 45 8,145

3 Providing and making earthpits including the cost of 600 mm x 600 mm x 6 mm GI plate

electrode 20 mm dia GI pipe, CI funnel with wiremesh charcoal, salt, all earth work,

masonry enclosure with CI frame & cover plate having locking arrangement complete as

per IS 3043:1987. nos 80 2,223 177,840

4 Providing and laying earth connections from earth electrode with 2 x 6 SWG GI wire in 25

mm dia. GI pipe from earth electrode as required as per specifications. m 181 18 3,258

TOTAL SUB HEAD V carried over to Summary 414,459

SUB-HEAD -VI (FIXTURES AND FITTINGS)

1a Supply of the following light fixtures complete with housing, reflectors, all accessories i.e.

copper wound ballast, HPF condensors, starters, holders etc. complete as required

a) 1x18 W CFL recess mounting downlighter as approved including providing lamps and

other accessories (base Rate Rs 800/-) Nos. 780 206 160,290

b) 1x18 W CFL surface mounting downlighter as approved including providing lamps and

other accessories (base Rate Rs 600/-) Nos. 3,693 151 556,720

c) 1x28 W T5 lamp surface mounting box type fixture as approved including providing lamps

and other accessories (base Rate Rs 800/-) Nos. 790 241 190,193

d) 1x11 W CFL lamp surface mounting bulk head fixture as approved including providing

lamps and other accessories (base Rate Rs 450/-) Nos. 530 125 66,383

e) 1x11 W CFL lamp surface mounting wall bracket fixture as approved including providing

lamps and other accessories (base Rate Rs 450/-) Nos. 24 104 2,502

f) 2x28 W T5 lamp pendat mounting box type fixture as approved including providing

downrods, lamps and other accessories (base Rate Rs 1200/-) Nos. 970 284 274,995

1b Receiving, assembling, erection, connecting, testing and commissioning of the following

light fixtures complete with housing, reflectors, all accessories i.e. copper wound ballast,

HPF condensors, starters, holders etc. complete as required

a) 1x18 W CFL recess mounting downlighter as approved including providing lamps and

other accessories Nos. 780 45 35,100

b) 1x18 W CFL surface mounting downlighter as approved including providing lamps and

other accessories Nos. 3,693 45 166,185

c) 1x28 W T5 lamp surface mounting box type fixture as approved including providing lamps

and other accessories Nos. 790 45 35,550

Page 105: Final Offer Electrical

d) 1x11 W CFL lamp surface mounting bulk head fixture as approved including providing

lamps and other accessories Nos. 530 45 23,850

e) 1x11 W CFL lamp surface mounting wall bracket fixture as approved including providing

lamps and other accessories Nos. 24 45 1,080

f) 2x28 W T5 lamp pendat mounting box type fixture as approved including providing

downrods, lamps and other accessories Nos. 970 45 43,650

2 Supply, fixing, testing and commissioning of 240 Volt single phase ceiling fans of 1200 mm

Sweep including supply of 19 mm heavy gauge GI down rod of length as required

complete. Nos. 17 62 1,058

3 Supply, fixing, testing and commissioning of 240 Volt single phase heavy duty Exhaust

Fans 300 mm dia complete with all accessories as required and with 6 amp 3 pin plug top

as required. Nos. 17 62 1,058

4 Receiving, storing, transportation at site, unpacking, assembling, fixing, testing and

commissioning of 240 Volt single phase Buzzer as required complete. Nos. 1,206 45 54,270

TOTAL SUB-HEAD - VI carried over to Summary

SUB HEAD VII : LIGHTNING PROTECTION

1 Air Terminal & Accessories

Supplying, Erection & commissioning of External Lightning Wide Area Protection System

based on pro-active Early Streamer Emission (ESE) Technology type SATELIT-3-60.

Device shall emit electromagnetic impulse in the form of a controlled emission of

streamers into the air 60 microseconds earlier than naturally formed streamers & polarise

the tip with a voltage between 35 kV & 45 kV . Device confirming to NFC17-102 or UNE

21186 standards. The device shall be mounted at least 5 meter clear to the highest point

by Support Mast of 50mm dia Schedule 80 MS Pipe duly galvanized with minimum 85

micron zinc coating with foundation to suite Mast with concrete to cover 300mmX300mm

floor area & upto 600mm height complete as required

Sets 3 1,334 4,003

2 Low Impedance high voltage down conductor & accessories

Supply, installation, testing & commissioning of down conductor. The Down conductor

shall be of 25X3mm GI strip/Tape. They should be fixed to the structure by means of 2

fasteners every 1.0 meters horizontally & 0.5 meter vertically, It should then run down the

elevation pole and take the shortest direct route down the outside of the building to the

earth termination network, avoiding any sharp corners, thereby providing a low impedance

path from the air terminal to its earth termination system. M 300 9 2,700

3 Lightning Discharge Counter

Supply, installation, testing & commissioning of Lightning Discharge Counter. The

lightning event counter suitable for 1.0KA - 100KA . Counter housed in weather proof

IP67 enclosure with fixing clamps, etc. Sets 3 178 533

4 Maintenance Free Earthing

Supply, Installation, Testing & Commissioning of long life, Maintenance Free Electrolytic

Earthing System Earth pit should consists of 3 nos. 1.2 meters long 14mm dia MS Rod

moleculerly bonded with 250 micron copper coating and treated with 10 kgs of Terec+,

The earthing pit shall be provided with suitable sturdy Test Well for observation. The Earth

Pit shall be covered with 25mm thick gravel/ tiles The Installation procedures should be

followed as instructed by the Earth Electrode Supplier)

Nos. 6 800 4,802

5 Supplying fixing, testing and commissioning of LED Aviation lights, complete as per Wipro

Cat WAN 20001 or Bajaj Cat BJAOL-1, complete with flasher etc as required Nos. 3 890 2,669

6 Supplying, fixing, testing and commissioning of photochromatic switch for automatic

ON/OFF of Aviation light as required. Nos. 3 89 268

7 Wiring for aviation light with 3 core 2.5 sq.mm XLPe insulated PVC sheathed copper

conductor armoured cable from M/C room DB to aviation light. M 200 23 4,500

8 Supply and fixing GI strip 25 mm x 6 mm along outside wall/ columns as vertical

conductors with suitable GI fasteners, brass fixing screws, copper clamps & saddles

complete as required. M 50 9 450

9 Supply and fixing GI strip 25 mm x 6 mm along roof as horizontal conductors with

suitable GI fasteners, brass fixing screws, copper clamps & saddles complete as required.

M 200 9 1,800

10 Supply and laying in ground of GI strip 32 mm x 6 mm for connecting to the GI earth plate

at one end and vertical conductor strip at the other end including the cost of digging and

back filling complete M 30 14 405

Page 106: Final Offer Electrical

11 Providing and making earthpits including the cost of 600 mm x 600 mm x 6 mm GI plate

electrode 50 mm dia GI pipe, CI funnel with wiremesh charcoal, salt, all earth work,

masonry enclosure with CI frame & cover plate having locking arrangement complete as

per IS 3043:1987. Nos 2 2,223 4,446

12 Supplying and laying in ground of GI strip 32 mm x 6 mm for interconnecting the various

Lightning arrestor earth pits, including the cost of digging and back filling, complete as

required. M 200 14 2,700

13 Supply and fixing testing joints made of 25 mm x 6 mm thick GI strip 125 mm long with 4

Nos. GI bolts, nuts, check nuts and spring washers complete as required. Nos 2 9 18

14 Providing and fixing Lightning Conductor Finials made of 25 mm dia 300 mm long GI tube

having a single prong at the top with 85 mm dia 6 mm thick GI base plate complete as

required. Nos 1 89 89

15 Supply and fixing of DMC/SMC insulator complete with GI clamps, Nut Bolts supports

wherever is required. Nos 30 89 2,678

TOTAL SUB-HEAD - VII carried over to Summary 32,060

SUB-HEAD -VIII (FIRE DETECTION & ALARM SYSTEM)

1 Supply, installation, testing and commissioning of wall or ceiling mounted 240 Volt AC

illuminated Signs having on its front a white perspex sheet with the letters 'FIRE EXIT'

painted in red including the cost of in-built rechargeable batteries suitable for 30 minute

operation and including the cost of accessories for surface or recessed or ceiling

suspended mounting complete as required. Nos 514 32 16,191

2 Supply installation testing and commissioning of dust and vermin proof Manual call boxes

with push button to initiate audio visual alarm with breakable glass cover as per detailed

specifications complete with a steel chain including the cost of accessories for surface

mounted as required Nos 514 32 16,191

3 Supply installation test and commissioning of the following 8 ohm size speaker-cum-hooter

units with line matching transformer suitable for broadcast of speech and alarm siren

complete as required suitable for recessed/surface mounting complete with enclosure as

approved by Project Manager and as required. Nos 211 32 6,647

4 Supply, installation, testing and commissioning of wall recess mounting 24 zone

microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential

free contacts as per detailed specifications with alarms, controls and indications as per

detailed specifications and with an integral power supply unit and complete with a suitably

rated set of batteries and trickle charged from 240 volt AC mains supply, including the cost

of mounting accessories as required, complete. Nos 10 1,778 17,783

4 Supply, installation, testing and commissioning of wall recess mounting 16 zone

microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential

free contacts as per detailed specifications with alarms, controls and indications as per

detailed specifications and with an integral power supply unit and complete with a suitably

rated set of batteries and trickle charged from 240 volt AC mains supply, including the cost

of mounting accessories as required, complete. Nos 2 1,778 3,557

5 Supply, installation, testing and commissioning of wall recess mounting 15 zone

microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential

free contacts as per detailed specifications with alarms, controls and indications as per

detailed specifications and with an integral power supply unit and complete with a suitably

rated set of batteries and trickle charged from 240 volt AC mains supply, including the

cost of mounting accessories as required, complete. Nos 1 1,778 1,778

6 Supply, installation, testing and commissioning of wall recess mounting 10 zone

microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential

free contacts as per detailed specifications with alarms, controls and indications as per

detailed specifications and with an integral power supply unit and complete with a suitably

rated set of batteries and trickle charged from 240 volt AC mains supply, including the cost

of mounting accessories as required, complete. Nos. 1 1,778 1,778

7 Wiring with 2 core 1.5 Sqmm standard copper conductor FRLS 660/1100 volts grade

wires in existing concealed/surface MS conduit etc. as per specification and as required

including the cost of crimped termination's. M 36,500 9 328,500

Page 107: Final Offer Electrical

8 Supply and laying control cabling with copper conductor PVC insulated and PVC

sheathed armoured Control cables in existing pipes/conduits or on existing tray including

the cost of making connections, complete etc. etc. as per specification and as required as

below:

a) 10 core 2.5 sq mm M 5,100 27 137,700

TOTAL SUB-HEAD -VIII carried over to Summary 530,124

n