The rugged metal DIN housing of the SSX/SST Safety Series Isolator and Splitter snaps securely onto G-type and Top Hat rails.
April 2015
Features• exida certified IEC 61508:2010. exida has certifiedtheSSX/SSTforuseinanSISuptoSIL3inmonitormode,whereonlytheinputcircuitispartofthesafetyfunction.Forsingleusemode,theSSX/SSTisapprovedforuseinanSISuptoSIL2.
• Comprehensive FMEDA certified safety data.Uponrequest,exida-certifiedFMEDAdataisprovidedtobeusedbyafunctionalsafetypractitionertodeterminetheSST’sandSSX’sapplicabilityinspecificsafety-relatedapplications.
• Valuable HART data not lost . BoththeSSXandSSTpasscriticalHARTdatatoassetmanagementsystems,programmingdevicesorhostsystems.
• Split signals between two locations. The4-WireSSTtakesinonesignalandgivesyoutwofullyisolatedoutputsthatcanbetakentotwoseparatereceivingdevices.Thisfacilitatesmaintenanceoneitheroutputloopwithoutlosingthesignalontheotheroutputloop.
• RFI/EMI Protection. Standard20V/mprotectionofferedtoprotectagainstharmfuleffectsofradiofrequencyandelectromagneticinterference.
• Transmitter excitation.The4-wireSSTiscapableofprovidinglooppowertoa2-wiretransmitterthatisconnectedtoitsinput.
2015MooreIndustries-International,Inc.
Description PartofMooreIndustries’FS Functional Safety Series,theexida® approved, SIL3capable2-wire(looppowered)SSXand4-wire(line/mainspowered)SSTSafetyIsolatorsandSplittersprovideisolationandsignalconversionforyourSIS(SafetyInstrumentedSystem)needs.TheseunitsprotectandenhanceloopsandalsopassvaluableHART® datafromthefieldtransmittertohostsystemsandvice-versa. Isolate your SIS fromyourBasicProcessControlSystemormonitoringsystemsodisconnectionsorfailurestothesesecondarysystemsdon’taffectyoursafetysystem.FMEDA(FailureModeEffectsandDiagnosticAnalysis)reportsareavailablewiththerequiredsafetydatatoensurethatriskreductionrequirementsaremet(SeeFigure1).
Protect your safety systemfromsurges,spikesandtransientsinthefield.With1500Vrmsisolatingcapability,theSSX/SSTprotectsyoursafetyI/Ocardsandsystemfromtherigorsofplantenvironments.
With built-in HART pass-through technology youcanrestassuredthatwhenyourloopsuseHARTtransmittersthatcriticalandvaluableHARTdiagnostic,process,andcalibrationinformationcanbereadoneithersideoftheSSX/SST.Mostallotherisolatorsblockand“stripoff”theHART signal.
Figure 1. The 2-wire SSX provides safety system isolation while still allowing valuable HART data to pass.
206-792-04D
HARTisaregisteredtrademarkoftheHARTCommunicationFoundation.
opto isolation
SSX
Logic Solver(e.g. Safety System
or DCS)
Monitor/Control System(e.g. DCS, or
Asset Management System)
24V
Certifications (See Page 2 for details)
Safety Series Isolator and Splitter SSX/SST
Page 2
2-Wire, Loop Powered SSXTheSSXisa2-wireisolator,drawingpowerfromtheoutputsideoftheloop.Typically,thisisfromasecondaryreceivingdevicesuchasaDCSorPLC.
Isolation for Safety Systems UsetheSSXtoisolateyourSISfromyourbasicprocesscontrolsystem.WhilepowerfortheSSXisderivedfromtheoutputsideoftheloop,disconnectionorlossofpowerwillnotaffecttheinputloop’ssignalintegrity.Thisallowsmaintenancetobeperformedonthenon-criticalsideoftheloop(SeeFigure2).
Isolate and Pass Critical HART Data WhenHARTdataisrequiredfordiagnostics,maintenanceorcalibrationtheSSXisabletoisolateandpassHARTdatafromthetransmittertothehostsystem(SeeFigure3).
Stop Ground Loop Noise and Convert Signals Differenceinpotentialbetweenagroundedtransmitterandagroundedreceivingdevicemayresultinunpredictablegroundloopproblemsthatcanleadtosignaldrift.TheSSXbreaksthegalvanicpathbetweenthefieldinstrumentandreceivingdeviceandevenconvertssignalswhenrequired(SeeFigure4).
Solve “Bucking” Power Supplies and Filter HART Whentwodevices(suchasa4-wireHARTtransmitterandaDCS)aretryingtosourcepowertothesameloop,theresultisanon-functioningloop.Whenneitherofthedevicescanbeeliminated,thesolutionisanSSX.Itcanoperatewithpoweredinputsfrombothsides,thusrestoringnormaloperationstotheloopwhilealsopassinganyHARTsignals.SometimesolderDCSandPLCinputcardshavetroublewithHARTsignals.WhenthisproblemarisesyoucanordertheSSXwithoptioncode-0HARTandtheSSXwillfiltertheHARTsignal(SeeFigure5).
Figure 3. The SSX passes HART data to asset management systems or other host control and monitoring systems.
Figure 2. The SSX provides isolation for your safety system and still allows maintenance on the output side of the loop.
Figure 5. The SSX solves bucking power supplies. Also, when used with the -0HART option, the SSX acts as a current isolator that stops a HART signal from reaching a PLC, DCS or other receiving device.
Figure 4. The SSX can also serve as a signal converter.
opto isolation
SSX
Logic Solver(e.g. Safety System
or DCS)
Monitor/Control System(e.g. DCS or Asset
Management System)
24V
24V
IN
IN
NON-ISOLATED TRANSMITTERRECEIVER
NON-ISOLATED4-WIRE
TRANSMITTERRECEIVERRECEIVER
+ +
– –
+24V+
– +IN
1-5VIsolated4-20mA
opto isolation
SSX
LOOPPOWERED
NON-ISOLATED TRANSMITTERRECEIVER
4-WIREHART
TRANSMITTERRECEIVERSIS or PLC
+
– –
+24V+
– +IN
Isolated4-20mA
opto isolation
SSX
4-20mA + HART
+24V
NON-ISOLATED TRANSMITTERRECEIVER
4-WIREHART
TRANSMITTERRECEIVERDCS orAsset
ManagementSystem
+ +
– –
+24V+
– +IN
4-20mA + HART 4-20mA + HART
opto isolation
LOOPPOWERED
SSX
Certifications
CE Conformant -EMCDirective2004/108/ECEN61326;LowVoltageDirective-2006/95/ECEN61010
exida Certified - IEC615082010FunctionalSafetyofElectrical/Electronic/ProgrammableElectronicSafety-RelatedSystems
FM Approvals (FM Global): Non-Incendive ClassI,Division2,GroupsA,B,CandDTemperatureClassT4,Tamb=-40°Cto+85°C
Page3
4-Wire Line/Mains Powered SST and SST SplitterTheSSTisa4-wireunitpoweredby24DC,117ACor230AC.Itisdesignedforapplicationswhereline/mainspowerisreadilyavailable,suchasthebackofapanelorinsideofacontrolroom.
HART Splitter: “Sharing” or “Splitting” Process Signals TheSSTSplittertakestheinputfromoneofyourprocesssignalsandcreatestwoidentical,completelyisolatedoutputstotwoseparatemonitoringorcontroldevices.Additionally,theSSTfunctionsasaHARTsplitterthatpassesvaluableHARTdatatooneorbothoftheSST’sindependentoutputs.ThisisespeciallyimportantwhenassetmanagementsystemsneedtomaintainadigitalHARTconnectionwithcriticalvalvesorinstrumentsfordiagnosticmonitoringorcalibrationrecordkeeping.ThisalsomakesitveryconvenientwhenusingHARThandhelds,modemsorprogrammingdevicestoconfigureremotefieldtransmittersfromcontrolrooms(SeeFigure6).
Power a 2-Wire Transmitter Withtheincluded-TXoption,theSSTprovides24Vpowertoa2-wire,output-looppoweredinstrument.Thiseliminatestheneedforanadditionalpowersupply(SeeFigure7).
Single- and Multiple-Unit Instrument Enclosures DesignedtomeetNEMA4XandIP66ratings,theR-BOXistheperfectsolutionforprotectingtheSST/SSXinfieldandcontrolroomapplications.Ruggedandversatile,itdeliversahighimpactstructureandresistancetoultravioletraysandchemicals.TheR-BOXmountsonapipe,panelorsurface,andcomesinavarietyofwidthstoeconomicallyaccommodateseveralSSTsorSSXs.Itfeaturesapre-installedmountingrail;customizableconduitentryoptions;aclearcoverandasecurelockingmechanism.Formoreinformation,seetheR-BOXField-MountEnclosuredatasheet(SeeFigure8).
Figure 6. The SST Splitter takes one process signal and delivers two completely isolated signal outputs. HART data can be passed to one or both outputs.
Figure 7. The standard -TX Transmitter Excitation of the SST allows it to supply loop power to a 2-wire transmitter.
Figure 8. Available in a variety of widths, our R-BOX field-mount instrument enclosure is designed to protect DIN-rail instruments in even the most rugged environments
SSTSplitter
+A +OUT
+
–A – OUT
–
opto isolation
+IN
–IN
AC OR DCPOWER
ISOLATED4-20mA w/ HART
+
B +OUT
–
B –OUT
4-20mA w/ HART
ISOLATED4-20mA w/ HART
4-WIREHART
TRANSMITTER
SIS
PLC
NON-ISOLATED
2-WIRE XMITTER
RECEIVERSST
ISOLATED4-20mA
–
+ +TX +
+IN
+OUT
–OUT –
opto isolation
NON-ISOLATED4-20mA
AC or DCPower
SafetySeriesIsolatorandSplitterSSX/SST
Page4
Accuracy:±0.1%ofspanStability:+/-0.2%ofreadingperyear Isolation: SSX:500VrmsbetweenInput,OutputandCase;SST:500VrmsBetweenInput,Output,CaseandPowerTested To: SSX:1500VrmsbetweenInput,OutputandCasefor1minute;SST:1500VrmsbetweenInput,Output,CaseandDCPowerfor1minute(2300VrmsfromACPowertoInput,OutputandCasefor1minute)Response Time (analog output):100msecmax.to99%ofoutput Input Resistance: 100 ohmsstandard;250ohmswith-IZ250optionInput Overrange Protection: 250%offullscaleRipple: <10mVmeasuredacrossa250ohmresistor
Performance
Adjustments
Weight
Burden:1Vmaximumforcurrent;1MohmminimumforvoltageLoad Effect:0.01%ofspanfrom0-100%ofratedoutput(currentonly)Power Supply: SST:24DC±10%;117AC50/60HZ,±10%;230AC50/60HZ,±10%;SSX:12-42DCPower Consumption:SST:Singlechannel:3wattsmax.;Dualoutputchannel:5wattsmax.Power Supply Rejection:Exceeds90dbforcurrentinputunits Load Capability: SSX: Vs–12Vdc
SST: 1000ohms SST-Splitter:600ohmsperchannel Output Current Limiting: 25mAtypical;30mAmax.Voltage Limit (for -EP only): 30Vdcmax.
Temperature Range: Operating:-40°Cto+85°C(-40°Fto+185°F);Storage:-40°Cto+85°C(-40°Fto+185°F)Temperature Effect: ±0.007%ofspan/°Ctypical;±0.015%ofspan/°Cmax Relative Humidity:5-95%non-condensing RFI/EMI Protection: Lessthan+/-0.1%ofspanerrorwhentestedat20V/m@20-1000MHzCommon Mode Rejection: Exceeds95dBat60Hzwithalimitof1500Vrms
Type:Frontpanelpots Span:±2% Zero:±2% SST:DC:12oz(340g),AC:17oz(482g) SST-Splitter: DC:15oz(425g),AC:20oz(567g) SSX: 8oz(227g)
Performance (continued)
Ambient Conditions
Specifications
Accessories: PartNumber700-702-36
FMEDA Report consistentwithIEC61508-2:2010providingtheinformationnecessarytodesignaSafetyInstrumentedSystem(OnecopyprovidedfreewitheachorderUponRequest)
Ordering Information
SST 4-wire, Line-(Mains)Powered, SafetyIsolatorandSplitter
Unit Input Output Power Options Housing
4-20MA4-20mAinto100ohmswithHARTdigitaldatasuperimposed1-5V* into1Mohm
4-20MA Isolated,4-20mAinto1000ohms(with24Vdc,117Vac, or230Vacpower); withHARTdigitaldatasuperimposed2X4-20MA into600ohmsperchannel(availablewith4-20mAinputonly);HARTdigitaldatasuperimposedonChannelAonly
24DC ±10%117AC 50/60HZ,±10%230AC 50/60HZ,±10%3wattsmaximumforsinglechannelmodels;5wattsmaximumfordualoutputchannelmodels
-IZ250**Increasestheinputresistanceto250ohms -EP***Externalpower,outputspoweredbyexternalsource(onlyavailableon2X4-20mAoutputmodels)-0HARTNoHARTsignalpass-through-2HART***HARTsignalpass-throughonbothchannels-RO***ReverseOutput(bothchannels)
DINUniversalDIN-stylehousingmountson32mmG-typerail(EN50035)oron35mmTopHatrail(EN50022FLBFlangebracketwithtop/bottommountingholes
*HART pass-through not available for 1-5V Input models**-IZ250 only available for 4-20mA Input models***-EP, -RO and -2HART only available for 2X4-20mA Output models
4-20MA4-20mAinto100ohmswithHARTdigitaldatasuperimposed1-5V*into1Mohm
4-20MA Isolated,4-20mAinto600ohms(with24Vdcpower);withHARTdigitaldatasuperimposed
12-42DC -IZ250**Increasestheinputresistanceto250ohms -0HARTNoHARTsignalpass-through
SSX 2-wire, Loop-Powered, SafetyIsolator
Unit Input Output Power Options Housing
When ordering, specify:Unit/Input/Output/Power/-Option[Housing]Model number examples:SST/4-20MA/2X4-20MA/24DC/-EP[DIN]SSX/4-20MA/4-20MA/12-42DC/-IZ250[DIN]
20mA
SafetySeriesIsolatorandSplitter SSX/SST
Page 5
Figure 10. Dimensions of the SST Isolator in its aluminum DIN-style housing
100mm(4.0 in)
119mm(4.7 in)
124mm(4.8 in)
131mm(5.1 in)
136mm(5.3 in)
CL
47mmREF.
53mm(2.1 in)REF.
(1.8 in)
REF.
REF.
35mm(1.4 in)
Figure 9. Dimensions of the SSX Isolator in its aluminum DIN-style housing
25mm(1.0 in)
100mm(3.9 in)
119mm(4.7 in)
124mm(4.8 in)
131mm(5.1 in)
136mm(5.3 in)
CL
47mmREF.
53mm(2.1 in)REF.
(1.8 in)
REF.
REF.
Safety Series Isolator and Splitter SSX/SST
Page 6
United States • [email protected]: (818) 894-7111 • FAX: (818) 891-2816
Australia • [email protected]: (02) 8536-7200 • FAX: (02) 9525-7296
Belgium • [email protected]: 03/448.10.18 • FAX: 03/440.17.97The Netherlands • [email protected]
Tel: (0)344-617971 • FAX: (0)344-615920
China • [email protected]: 86-21-62491499 • FAX: 86-21-62490635
United Kingdom • [email protected]: 01293 514488 • FAX: 01293 536852
Specificationsandinformationsubjecttochangewithoutnotice.
Figure 11. Dimensions of the SST Splitter in its aluminum DIN-style housing
100mm(3.9 in)
119mm(4.7 in)
124mm(4.8 in)
131mm(5.1 in)
136mm(5.3 in)
CL
47mmREF.
53mm(2.1 in)REF.
(1.8 in)
REF.
REF.
45mm(1.8in)
Figure 12. The SST Splitter and the SST and SSX Isolators mounted with the FLB flange bracket and the bracket’s dimensions.
23mm(0.9 in)
18mm(0.7 in)
9mm(0.4 in)
2 mm(0.1 in)
11mm(0.4 in)
143mm(5.6 in)
121mm(4.8in)
Ø6mm(Ø0.3 in)