fault.ppt
TRANSCRIPT
Bahir Dar University
Institute of Technology
School of Computing and Electrical Engineering
Eeng-5161: Power System II
Nov 2011
1. FAULT ANALYSIS1. 1 Introduction
● Fault (short circuit ) current calculation is an important part of power system (PS) design, which enable the system engineer to set relay protection and selection of various equipments such us circuit breaker, bus bar etc.
● Short circuit (SC) occur in PS when equipment insulation fails, due to:- system over voltages (lighting or switching); insulation contamination; other mechanical causes.● SC current may be (Isc)>>normal current Inom and if it is allowed to persists, may cause thermal and mechanical damage to equipments. It is therefore necessary to remove faulted sections of a system from service as soon as possible.
● commonly occurring types of fault are (Fig.1.1):- three phase, phase- to-phase, two-phase-to ground, and phase-to ground fault. From these phase-to ground is the most frequent and three-phase is the most sever.
a) Three-phase S.C (k (3))b) L-L-L, E (k (3E))
C) L-L. (k (2))
d) L-L, E (k (2E))
e) L-E (k (1))
f) L-E fault with fault impedance
Fig .1.1. Common types of fault or short circuit (S.C). L-Line, E-earth
or
Rf
● Current flowing to faulted place is termed fault current (If). The fault MVA is frequently used as a rating (the fault MVA = VLIf *10-6, where VL is the nominal line voltage of the faulted part). The fault MVA is often referred to as the fault level. ● fault current calculations can be divided into the
following two main types:
All three lines are short-circuited, when the network remains balanced electrically. For these calculations, normal single-phase equivalent circuits may be used as in ordinary network calculation;
Faults other than three-phase short circuits when the network is electrically unbalanced. To facilitate these calculations a special method for dealing with unbalance network is used, known as the method of symmetrical components.
● The main objects of fault analysis :
1. To determine maximum and minimum three-phase short circuit current;2. To determine the unsymmetrical fault current for single and double line to ground faults, and sometimes for open circuit faults;3. Investigations of operation of protective relays; 4. Determination of rated rupturing capacity of breakers;5. To determine fault-current distribution and bus bar-voltage levels during fault condition.
1.2 Symmetrical Fault Analysis
1.2.1 Series R-L circuit transient
● Closing switch SW(Fig.1.2) at t = 0 represent bolted three- phase short circuit.
Fig.1.2. Current-voltage wave forms in R-L circuit transient
Using KVL for the circuit,
α)tVsin(2Ri(t)dt
di(t) L t>0 (1.1)
Solution for (1.1) is
T
t
θ)esin(αθ)-αtsin(Z
V2(t)dc
i(t)ac
ii(t) A (1.2)
Whereθ)-αtsin(
ZV2(t)
aci T
t
θ)esin(αZ
V2(t)dc
i
Ω2(X)2R)2RZ 2 L(ω RωL1tanθ =
RX1tan
fL2X
ωLX
RLT Eq.(1.3)…(1.6)
The total fault current in (1.2), called the asymmetrical fault current (fig.1.2). iac(t) – called symmetrical or steady state fault current and sinusoid The dc offset current idc(t) decay exponentially with time constant T = L/R.
● The rms ac fault current is Iac = V/Z. The magnitude of the dc offset which depend on α, varies from 0 when α = θ to when α = (θ/2). For α = (θ - /2) maximum fault current is
T
t
e)2π-tsin(
ZV2i(t) A (1.7)
acI2
The RMS of i(t) is
Tt2
2e1I
2
Tt-
eac
I22ac
I2(t)dc
I2ac
I(t)rms
I ac
(1.8)
Eq.(1.8) can be written as
Irms() = K()Iac (1.9)
Where K() =
RX
4π
2e1
per unit (1.10)
t= t*f - is time in cycle. K() is called asymmetrical factor and t varies from 1 to 3 as it can be seen from (1.10).
1.2.2 Balanced fault calculation in power system
● The balanced three-phase fault in unloaded synchronous machine can be modelled by the series R-L circuit of fig.1.2, if time varying inductance L(t) or XL(t) is employed. Oscillogram of current in one of phase for 3-ph fault is in Fig.1.3.
Fig.1.3
● As we know from machine modelling there are three reactances Xd, Xd’’ and Xd’. There for different currents flow from time of occurrence of faults. These currents are: Sub-transient current which flow immediately after the occurrence of fault (1)
''d
X
gE
''I(0)Iac 'd
X
gE
'I d
X
gE
I I’’>I’>I(1) (2) (3)
Transient current which flow few cycle later the occurrence of fault (2)The sustained (steady state) fault current (3)
● The sub-transient current I’’ is initial symmetrical current which does not include dc components. To consider dc components some coefficient (value of 1.4 to 1.8)is used.
● For practical system a simplified fault current calculation procedure called E/X method is used. In this method the Thevenin theorem is applied. Then the fault current If is
If = Vf/Xth or If = I/Xth p.u.
Where Vf is pre-fault voltage at point of fault and its value is taken 1p.u.; I-normal load current. The three phase short- circuit volt-amperes
P.UXB
MVA
x.p.u
IL
V3
fI
LV3
MVAF
● The following assumption will be made in practical short circuit current calculations:
All generated voltages of synchronous machines are equal & in phase and represented by sub-transient reactances, hence no load is considered for fault calculation. Generally, load has negligible impact on the faulted phase.
Neglect resistance except at the lower voltage where resistance is larger.
All shunt reactance’s neglected (loads, charging & magnetizing reactances).
All mutual reactance’s neglected.
Induction motors are either neglected (<38kW) or represented as synchronous machines.
1.2.3 The bus impedance matrix for fault calculation
● For general network fault calculation Zbus is used. By definition,
1bus
Ybus
Z (1.11)
Zbus is symmetrical
Using Zbus, the sub-transient fault current can be calculated as:
kkZ
FV''
FkI (1.11)
Where, VF is pre-fault voltage at bus k, Zkk is self impedance of bus k.
The voltage at any bus n during fault can be calculated:
FV
kkZ
nkZ
1n
V
n = 1, 2 …N (1.12)
Where, Znk is transfer impedance between bus k and n.
The bus impedance equivalent circuit is shown in fig. 1.4.
Fig.1.4. Bus impedance equivalent circuit (rake equivalent)
1.3 Unsymmetrical Fault (short circuit)
1.3.1 Method of symmetrical component
● To solve problems in unsymmetrical conditions of power system, method of symmetrical component is used. Any unbalanced phasors of a three-phase system can be resolved in to three-balanced system of phasors. The balanced sets of components are:
+ve sequence ;- equal in magnitude and 120o phase displacement; a, b, c phase sequence as original phasers. This sequence is always representing by subscript 1 (Va1, Ia1 etc.)
-ve sequence ;– equal in magnitude and 120o phase displacement; a, c, b phase sequence and have subscript 2 (Va2,Ia2, etc)
Zero sequence components consisting of three phasors equal in magnitude and with zero phase displacement from each other and have subscript 0 (Va0,Ia0 etc) .● Each of the original unbalanced phasors is the sum of its components (Fig.1.5) and the original phasors expressed in terms of their components are:
c0V
c2V
c1V
cV
b0
Vb2
V b1
Vb
V a0
Va2
V a1
Va
V
(1.13)
Using operator a, which is rotating the phasor 120o anticlockwise.
a=1120o= –0.5+j0.866;a2=1240o= -0.5-j0.866 ;
a3= 1 3600= 100=1+jo.
Fig.1.5
Vb1= a2Va1; Vb2 = aVa2; Vb0 = Vao
Vc1 = aVa1; Vc2 = a2Va2; Vco = Vao (1.14)
Substituting in eq (1.13) yield;
a0V
a2Va
a1V
cV
a0
Va2
aV a1
Vb
V
a0V
a2V
a1V
aV
2
2
a
a(1.15)
By solving the eq (1.15) for sequence component:
cV
bVa
aV
31
a2V
c
Vb
aV a
V31
a1V
cV
bV
aV
31
a0V
2
2
a
a
(1.16)
Sequence components for other phases can be found byconsidering eq.(1.14.)●The above equation similarly works for current too.
In three-phase system the sum of line current equal to current through neutral In.
In the absence of neutral In = 0. For connected system I0=0.
In=Ia+Ib+IC ; Ia0=(1/3)In In=3Ia0
Zero- sequence network is always different depending on way of system grounding. Z0=Z1 for transformer; Z0=2-3.5Z1 for line and Z0 of generator is small. See fig.1.7, for zero sequence current flow through transformer.
1.3.3. Unsymmetrical fault on power system
● Sequence component voltage drop equation can be written as:
0Z
a0I - 0
a0V
2Z
a2I - 0
a2V
1Z
a1I -
fV
a1V
(1.17)
Ia1Vf
3Zn Zg0
z0
F
Va0
Va2
+F
-
Va1
-
+-
Where F is point of fault
I0
Fig.1.6. equivalent circuit for sequence impedance network
Fig.1.7 Zero sequence equivalent circuits of 3-phase transformer
Single Line- to- ground fault on a power system
For 1-E (K(1)), Ia1 = Ia2 = Ia0 = Ia/3
Then
0Z
2Z
1Z
fV
a1I
(1.18) c
a
b
With Zf
F3Z
0Z
2Z
1Z
fV
a1I
(1.19)
Finally fault current isa1
3I(1)a
I (1.20)
●It can be seen from eq.(1.19),that I = 0, when ZfYh. For ungrounded system no path exist for current flow. Sequence network connection is shown in fig.1.8.
Vf Z1
Z2 Z0
Fig.1.8. Sequence connection for single-line to ground fault
Ia1
- +
Ia1 Ia2Ia0
Line-to- Line fault on a power system
2Z
1Z
fV
a1I
(1.21)
Ia=0
Ib
Ic
With ZF ,
FZ
2Z
1Z
fV
a1I
(1.22)
The fault currents: Ia(2) =0 ;Ib(2) = -3 Ia1 ;Ic(2) = 3 Ia1
In most case Z1=Z2 ; (3)f
I2
3
12Z
fV3(2)
fI
Finally line-to-line fault current
(3)f
I 0.866 (2)f
I (1.23)
Fig.1.9. Sequence network connection for line-to-line fault
Z1Ia1 Ia2
Va1 Va2 Z2-
+Vf
- +
+ -
Double line to ground fault on a power system
Vb=Vc= 0; Ia=0
Va0 =1/3(Va+0+0) =Va1=Va2
2Z
0Z
2Z
0Z
1Z
fV
a1I
(1.24) IF
Ib
Ic
From eq.(1.24), the network sequence Z connection is in fig.1.10
Fig.1.10. Sequence network connection for double line-to-ground fault
+
Z1Ia1
Va1
Va2 Z2-
+Vf
-+
-
Z0 Va0
+
-
Ia0Ia2
1.3.4. Sequence bus impedance matrices
Single line-to-ground fault:
(1.25) F3Z
2kkZ
1kkZ
0-kkZ
fV
2kI
1kI
0kI
Line-to-line fault:
FZ
2kkZ
1kkZ
fV
2kI
1kI
(1.26)
00k
I (1.27)
Double line-to-ground fault:
F3Z
0kkZ
2kkZ
)F
3Z0kk
(Z2kk
Z
1kkZ
fV
1kI
(1.28)