    FACILITY AUDIT(PRELIMINARY REPORT)

    "DATEPresented by:

    Client 1

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    2/48

    1/2/12

    p2

    MAJOR FINDINGS

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    3/48

    1/2/12

    p3

    MAJOR FINDINGS: SAFETY

    CONDITION Safety Issue: No catwalkprovision for Cooling Tower

    Personnel in accessing/

    inspecting the motor, belt,

    pillow block bearing, etc

    RECOMMENDATION Provide CatwalkRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    4/48

    1/2/12

    p4

    MAJOR FINDINGS: SAFETYCONDITION Obstruction of way to access AHU 1,

    2, 3, 4, 5 of Tenant Store 1RECOMMENDATION Provide proper space for right of way

    to access the AHU roomsRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    5/48

    1/2/12p5

    MAJOR FINDINGS: SAFETY

    CONDITION No signage for FE, provideeasy access.

    RECOMMENDATION Provide a signage which caneasily be seen and remove

    obstruction to FEInspect all PFE for possiblesimilar scenario

    RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    6/48

    1/2/12p6

    MAJOR FINDINGS: SAFETYCONDITION Exposed Wire in between

    merchandize fixture, posed

    Hazard to customer of Store

    A

    RECOMMENDATION Remove expose wire. Orrelocate

    RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    7/48

    1/2/12p8

    MAJOR FINDINGS: ACVSCONDITION Corroded pipes and support in

    Cooling Tower Area

    RECOMMENDATION Remove rust , then repaint.RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    8/48

    1/2/12p9

    MAJOR FINDINGS: ACVSCONDITION Corroded Motorize valve at CT 2

    RECOMMENDATION Check the condition if stillfunctioning or repaint

    RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    9/48

    1/2/12p10

    MAJOR FINDINGS: ROOFING

    CONDITION Flashing possible source of leaksdue to sealant integrity

    RECOMMENDATION Ask (roofing contractor) for theproper flashing termination.

    RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    10/48

    1/2/12p12

    MAJOR FINDINGS: ROOFINGCONDITION Ongoing rectification of leaks by

    Waterproofing ContractorRECOMMENDATION For flood testingRESPONSIBLE Waterproofing ContractorTARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    11/48

    1/2/12p13

    MAJOR FINDINGS: EXHAUST SYSTEM

    CONDITION Substandard KEF Manhole

    RECOMMENDATION Standardize the manhole (seeexample photo of correct

    installation of manhole)RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    12/48

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    13/48

    1/2/12p15

    MAJOR FINDINGS: INTERIORCONDITION Possible source of leaks

    RECOMMENDATION RectifyRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    14/48

    1/2/12p16

    MAJOR FINDINGS: INTERIORCONDITION Unleveled floor tiles

    Pop-up tiles at 2rd level Cyberpad

    RECOMMENDATION RectifyRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    15/48

    MINOR FINDINGS

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    16/48

    1/2/12p19

    FIRE PROTECTION

    CONDITION Broken Glass of FHC at 2nd floor

    south left wing entrance

    RECOMMENDATION Replace the broken glass forsafety

    RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    17/48

    1/2/12p20

    ROOFINGCONDITION Presence of Plastic at gutter:

    Extension bridge from mall to

    cyberpad

    RECOMMENDATION Remove or executehousekeeping of gutters

    RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    18/48

    1/2/12p22

    ROOFING

    CONDITION Roof flashing to walltermination: possible source

    of leaks

    RECOMMENDATION RectifyConsult waterproofingcontractor for correct

    solution.RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    19/48

    1/2/12p24

    VACSCONDITION Sign of corrosion of AHU

    support and valves at TenantStore 1

    RECOMMENDATION Remove the rust and installproper insulation.

    RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    20/48

    1/2/12p26

    VACSCONDITION Corrosion starting to build up at

    Chilled water pipeRECOMMENDATION Paint the pipes with anti-

    corrosive paintRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    21/48

    1/2/12p27

    ELECTRICAL SYSTEM

    CONDITION Expose Telephone Wire atTenant Store 2 EE Room

    RECOMMENDATION Rewiring/Provide properenclosure

    RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    22/48

    1/2/12p28

    ELECTRICAL SYSTEM

    CONDITION Corroded and Open Junction boxes

    at AHU rooms

    RECOMMENDATION Remove rust then repaint/ Cover allopen junction boxesInspect all areas for possible open

    junction boxRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    23/48

    1/2/12p30

    ELECTRICAL SYSTEMCONDITION Improper tagging of panel board

    at Tenant Store 1RECOMMENDATION Provide proper tagging and panel

    directoryRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    24/48

    1/2/12p31

    ELECTRICAL SYSTEM

    CONDITION Presence of danglingtelephone wire at the roof.

    RECOMMENDATION Remove / relocate thetelephone wire

    RESPONSIBLE TelcoTARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    25/48

    1/2/12p32

    ELECTRICAL SYSTEMCONDITION Presence of litters, tools and

    unwanted stocks at EE room ofTenant Store 1

    RECOMMENDATION Remove all unwanted materialsinside EE room

    RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    26/48

    1/2/12p33

    ELECTRICAL SYSTEMCONDITION Improper installation of MDF

    lines at MDF room with

    presence of stocks

    RECOMMENDATION Remove stocks/RewiringRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    27/48

    1/2/12p36

    EXTERIORCONDITION Sign of corrosion of Drop down

    banner frame

    RECOMMENDATION Remove the rust then RepaintRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    28/48

    1/2/12p37

    EXTERIORCONDITION 1.No floodlight at the top of Drop

    Down Banner2. All electrical lines are exposed

    RECOMMENDATION Install floodlight if still needed(seeeffect during night time)

    All electrical lines should be place

    inside a conduit for weather

    protection, short circuit and safety

    RESPONSIBLE

    TARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    29/48

    1/2/12p38

    EXTERIORCONDITION Gutter waterponding,

    presence of garbage andaccumulation of algae

    RECOMMENDATION Execute housekeeping of thecanopy

    RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    30/48

    1/2/12p39

    EXTERIORCONDITION Building cracks near pump room

    (scattered along exterior wall)

    RECOMMENDATION Rectify/Apply sealant or epoxyinjection

    RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    31/48

    1/2/12p41

    EXTERIOR

    CONDITION Damage EIFS at Cinema andnear Cooling Tower

    RECOMMENDATION RepairRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    32/48

    1/2/12p42

    EXTERIORCONDITION Presence of leak at canopy

    area at Store Entrance and

    Tenant Store 1

    RECOMMENDATION RectifyRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    33/48

    1/2/12p45

    INTERIOR

    CONDITION Damage walls near EE room

    going to CyberzoneRECOMMENDATION RepairRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    34/48

    1/2/12p48

    CPS - NonpotableCONDITION CPS pump #3: starting to

    accumulate dirt and corrosionPressure gauge: Glass cover

    not fixed

    RECOMMENDATION Repair/RectifyRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    35/48

    1/2/12p49

    EXHAUST SYSTEMCONDITION Corroded base, vibration isolator,

    bolts and nuts

    RECOMMENDATION Remove rust then repaintRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    36/48

    1/2/12p50

    EXHAUST SYSTEM

    CONDITION Damage Kitchen Air SupplyFan wire mesh

    RECOMMENDATION Rectify, design a wiremeshframe which can be easily

    detached.RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    37/48

    1/2/12p54

    OTHERSCONDITION 1. Open canal @ Tenant Store

    1

    2. Leak coming TS 1 area3. Open Floor Drain

    RECOMMENDATION Remove dirt from canal andrectify condition 2 and 3

    RESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    38/48

    1/2/12p56

    OTHERS

    CONDITION Presence of garbage, litters,molds, and dried algae at RoofDeck

    RECOMMENDATION HousekeepingRESPONSIBLETARGET DATE

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    39/48

    1/2/12p58

    OTHERSCONDITION Damage tiles at Garbage House

    RECOMMENDATION Rectify/Replace damage tilesRESPONSIBLETARGET DATE

    OTHER SYSTEMS

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    40/48

    1/2/12p60

    OTHER SYSTEMSSTP

    With live mosquito larvaeDetermined the consumption rate of chlorine per dayProper dozing of chlorineFREIGHT ELEVATOR 1 (T1 Store)With abnormal sound of door when open and close (DoorLimit switch on going observation)Slow down limit defective for quotation.FREIGHT ELEVATOR (Main)Operational

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    41/48

    PASSENGER ELEVATOR (Main)Operational no concernESCALATOR (Main)Escalator #2( going Down)

    Handrail Canvas (Partial Damage)Escalator #5 (going Up)

    Newel guide roller (Partial Damage Right Side)Escalator #3 (going Up)

    Temporary motor (service unit) Original Motor for rewiring since August 2011

    ESCALATOR (TS 1)Escalator #1 (going Up)

    Oil Leak at motor assembly for Quotation

    LIST OF DOWN EQUIPMENTS

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    42/48

    1/2/12p62

    LIST OF DOWN EQUIPMENTSCAPACITOR BANK 1 and 2

    Down since November 2012Already check by ContractorTarget Date: 2nd week of JANUARYCPS PUMP 2-POTABLE

    Down since 3rd week of September 2012Already check by ContractorTarget Date: 2nd week of JANUARY

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    43/48

    GOOD PRACTICES

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    44/48

    Proper enclosure of a standby Kitchen

    Exhaust

    P t i d H k i f AHU R

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    45/48

    Proper tagging and Housekeeping of AHU Rooms

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    46/48

    Proper Tagging of CB and Panel DirectoryGood Housekeeping

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    47/48

    Proper cover for DDC Panel Boards

  • 7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf

    48/48

    Final Report

    To Follow

    Prepared by