FACILITY AUDIT(PRELIMINARY REPORT)
"DATEPresented by:
Client 1
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
2/48
1/2/12
p2
MAJOR FINDINGS
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
3/48
1/2/12
p3
MAJOR FINDINGS: SAFETY
CONDITION Safety Issue: No catwalkprovision for Cooling Tower
Personnel in accessing/
inspecting the motor, belt,
pillow block bearing, etc
RECOMMENDATION Provide CatwalkRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
4/48
1/2/12
p4
MAJOR FINDINGS: SAFETYCONDITION Obstruction of way to access AHU 1,
2, 3, 4, 5 of Tenant Store 1RECOMMENDATION Provide proper space for right of way
to access the AHU roomsRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
5/48
1/2/12p5
MAJOR FINDINGS: SAFETY
CONDITION No signage for FE, provideeasy access.
RECOMMENDATION Provide a signage which caneasily be seen and remove
obstruction to FEInspect all PFE for possiblesimilar scenario
RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
6/48
1/2/12p6
MAJOR FINDINGS: SAFETYCONDITION Exposed Wire in between
merchandize fixture, posed
Hazard to customer of Store
A
RECOMMENDATION Remove expose wire. Orrelocate
RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
7/48
1/2/12p8
MAJOR FINDINGS: ACVSCONDITION Corroded pipes and support in
Cooling Tower Area
RECOMMENDATION Remove rust , then repaint.RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
8/48
1/2/12p9
MAJOR FINDINGS: ACVSCONDITION Corroded Motorize valve at CT 2
RECOMMENDATION Check the condition if stillfunctioning or repaint
RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
9/48
1/2/12p10
MAJOR FINDINGS: ROOFING
CONDITION Flashing possible source of leaksdue to sealant integrity
RECOMMENDATION Ask (roofing contractor) for theproper flashing termination.
RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
10/48
1/2/12p12
MAJOR FINDINGS: ROOFINGCONDITION Ongoing rectification of leaks by
Waterproofing ContractorRECOMMENDATION For flood testingRESPONSIBLE Waterproofing ContractorTARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
11/48
1/2/12p13
MAJOR FINDINGS: EXHAUST SYSTEM
CONDITION Substandard KEF Manhole
RECOMMENDATION Standardize the manhole (seeexample photo of correct
installation of manhole)RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
12/48
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
13/48
1/2/12p15
MAJOR FINDINGS: INTERIORCONDITION Possible source of leaks
RECOMMENDATION RectifyRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
14/48
1/2/12p16
MAJOR FINDINGS: INTERIORCONDITION Unleveled floor tiles
Pop-up tiles at 2rd level Cyberpad
RECOMMENDATION RectifyRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
15/48
MINOR FINDINGS
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
16/48
1/2/12p19
FIRE PROTECTION
CONDITION Broken Glass of FHC at 2nd floor
south left wing entrance
RECOMMENDATION Replace the broken glass forsafety
RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
17/48
1/2/12p20
ROOFINGCONDITION Presence of Plastic at gutter:
Extension bridge from mall to
cyberpad
RECOMMENDATION Remove or executehousekeeping of gutters
RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
18/48
1/2/12p22
ROOFING
CONDITION Roof flashing to walltermination: possible source
of leaks
RECOMMENDATION RectifyConsult waterproofingcontractor for correct
solution.RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
19/48
1/2/12p24
VACSCONDITION Sign of corrosion of AHU
support and valves at TenantStore 1
RECOMMENDATION Remove the rust and installproper insulation.
RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
20/48
1/2/12p26
VACSCONDITION Corrosion starting to build up at
Chilled water pipeRECOMMENDATION Paint the pipes with anti-
corrosive paintRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
21/48
1/2/12p27
ELECTRICAL SYSTEM
CONDITION Expose Telephone Wire atTenant Store 2 EE Room
RECOMMENDATION Rewiring/Provide properenclosure
RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
22/48
1/2/12p28
ELECTRICAL SYSTEM
CONDITION Corroded and Open Junction boxes
at AHU rooms
RECOMMENDATION Remove rust then repaint/ Cover allopen junction boxesInspect all areas for possible open
junction boxRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
23/48
1/2/12p30
ELECTRICAL SYSTEMCONDITION Improper tagging of panel board
at Tenant Store 1RECOMMENDATION Provide proper tagging and panel
directoryRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
24/48
1/2/12p31
ELECTRICAL SYSTEM
CONDITION Presence of danglingtelephone wire at the roof.
RECOMMENDATION Remove / relocate thetelephone wire
RESPONSIBLE TelcoTARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
25/48
1/2/12p32
ELECTRICAL SYSTEMCONDITION Presence of litters, tools and
unwanted stocks at EE room ofTenant Store 1
RECOMMENDATION Remove all unwanted materialsinside EE room
RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
26/48
1/2/12p33
ELECTRICAL SYSTEMCONDITION Improper installation of MDF
lines at MDF room with
presence of stocks
RECOMMENDATION Remove stocks/RewiringRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
27/48
1/2/12p36
EXTERIORCONDITION Sign of corrosion of Drop down
banner frame
RECOMMENDATION Remove the rust then RepaintRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
28/48
1/2/12p37
EXTERIORCONDITION 1.No floodlight at the top of Drop
Down Banner2. All electrical lines are exposed
RECOMMENDATION Install floodlight if still needed(seeeffect during night time)
All electrical lines should be place
inside a conduit for weather
protection, short circuit and safety
RESPONSIBLE
TARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
29/48
1/2/12p38
EXTERIORCONDITION Gutter waterponding,
presence of garbage andaccumulation of algae
RECOMMENDATION Execute housekeeping of thecanopy
RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
30/48
1/2/12p39
EXTERIORCONDITION Building cracks near pump room
(scattered along exterior wall)
RECOMMENDATION Rectify/Apply sealant or epoxyinjection
RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
31/48
1/2/12p41
EXTERIOR
CONDITION Damage EIFS at Cinema andnear Cooling Tower
RECOMMENDATION RepairRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
32/48
1/2/12p42
EXTERIORCONDITION Presence of leak at canopy
area at Store Entrance and
Tenant Store 1
RECOMMENDATION RectifyRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
33/48
1/2/12p45
INTERIOR
CONDITION Damage walls near EE room
going to CyberzoneRECOMMENDATION RepairRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
34/48
1/2/12p48
CPS - NonpotableCONDITION CPS pump #3: starting to
accumulate dirt and corrosionPressure gauge: Glass cover
not fixed
RECOMMENDATION Repair/RectifyRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
35/48
1/2/12p49
EXHAUST SYSTEMCONDITION Corroded base, vibration isolator,
bolts and nuts
RECOMMENDATION Remove rust then repaintRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
36/48
1/2/12p50
EXHAUST SYSTEM
CONDITION Damage Kitchen Air SupplyFan wire mesh
RECOMMENDATION Rectify, design a wiremeshframe which can be easily
detached.RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
37/48
1/2/12p54
OTHERSCONDITION 1. Open canal @ Tenant Store
1
2. Leak coming TS 1 area3. Open Floor Drain
RECOMMENDATION Remove dirt from canal andrectify condition 2 and 3
RESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
38/48
1/2/12p56
OTHERS
CONDITION Presence of garbage, litters,molds, and dried algae at RoofDeck
RECOMMENDATION HousekeepingRESPONSIBLETARGET DATE
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
39/48
1/2/12p58
OTHERSCONDITION Damage tiles at Garbage House
RECOMMENDATION Rectify/Replace damage tilesRESPONSIBLETARGET DATE
OTHER SYSTEMS
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
40/48
1/2/12p60
OTHER SYSTEMSSTP
With live mosquito larvaeDetermined the consumption rate of chlorine per dayProper dozing of chlorineFREIGHT ELEVATOR 1 (T1 Store)With abnormal sound of door when open and close (DoorLimit switch on going observation)Slow down limit defective for quotation.FREIGHT ELEVATOR (Main)Operational
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
41/48
PASSENGER ELEVATOR (Main)Operational no concernESCALATOR (Main)Escalator #2( going Down)
Handrail Canvas (Partial Damage)Escalator #5 (going Up)
Newel guide roller (Partial Damage Right Side)Escalator #3 (going Up)
Temporary motor (service unit) Original Motor for rewiring since August 2011
ESCALATOR (TS 1)Escalator #1 (going Up)
Oil Leak at motor assembly for Quotation
LIST OF DOWN EQUIPMENTS
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
42/48
1/2/12p62
LIST OF DOWN EQUIPMENTSCAPACITOR BANK 1 and 2
Down since November 2012Already check by ContractorTarget Date: 2nd week of JANUARYCPS PUMP 2-POTABLE
Down since 3rd week of September 2012Already check by ContractorTarget Date: 2nd week of JANUARY
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
43/48
GOOD PRACTICES
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
44/48
Proper enclosure of a standby Kitchen
Exhaust
P t i d H k i f AHU R
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
45/48
Proper tagging and Housekeeping of AHU Rooms
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
46/48
Proper Tagging of CB and Panel DirectoryGood Housekeeping
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
47/48
Proper cover for DDC Panel Boards
-
7/30/2019 FACILITY AUDIT PRELIMINARY REPORT.pdf
48/48
Final Report
To Follow
Prepared by