eurocorr 2009 paper 8254[1]

Upload: david-vazquez-cacho

Post on 06-Apr-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    1/18

    1

    The Response of Galvanic Protection Current to Environmental Changes

    1Steven Holmes

    1

    Department of Civil & Building Engineering, Loughborough University, Leicestershire,LE11 3TU, UK, [email protected]

    ABSTRACT

    An observed favourable feature of galvanic anodes used in concrete repair is the variation of their

    current output in response to changing environmental conditions, such as concrete moisture content,

    chloride content and temperature. This means that the anodes provide more protective current to the

    steel reinforcement when the environment is aggressive and less current when it is more benign, thus

    conserving sacrificial anode life.

    Over the last two years, the current outputs of several hybrid anode systems installed in lab samples

    and on a bridge in a concrete repair application have been monitored with respect to changes in

    temperature, moisture and chloride content (variable concrete resistivity). The aim was to investigate

    the relative effects of these parameters on the protective current output.

    The results confirmed that both the laboratory and site applied anode systems are responsive to

    changes in concrete resistivity brought about by variations in temperature, moisture and chloride, with

    the latter two having the greater effect. On site, this is a distinct advantage for both conservation of

    anode life and protection in aggressive conditions.

    Keywords: Responsive behaviour; hybrid anode; variable resistivity.

    1.0 INTRODUCTION

    Galvanic cathodic protection has recently received much attention as a method of protecting

    steel in concrete. When attached to the steel, these anodes effectively suppress the corrosion

    reaction at the surface, with anodic dissolution being shifted to the installed anode.

    Traditional galvanic anodes are used in topical applications following patch repairs, where

    they are attached to the steel and immersed in the repair mortar or concrete. The aim of these

    anodes is to counteract the incipient anode effect which can see reinforcement corrosion in

    areas adjacent to the patch due to the residual chloride contained within it and the relocation

    of the corrosion reaction [1]. Problems arise when the use of high quality, low conductivity

    mortars limits the current thrown by the anodes, or gradual loss of anode material over time

    results in loss of protective current and new corrosion.

    A hybrid anode system [2,3] has been introduced which combines elements of both chlorideextraction/re-alkalisation and galvanic cathodic protection, in that, for a short period, a power

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    2/18

    2

    supply is used to drive a high current from the discrete sacrificial anode to re-passivate the

    steel and draw chloride to the anode. The same anode is then connected directly to the steel to

    provide maintenance free cathodic protection by means of a galvanic current.

    The impressed current (re-alkalisation) phase halts the corrosion at the steel surface by

    generating hydroxyl and neutralising the acid in the pit thus increasing the pH; whilst the

    galvanic phase sustains hydroxide production and maintains the high alkalinity (see Figure 1).

    Figure 1. The two stages of the hybrid anode system.

    When applied to patch repairs, this system, instead of being immersed in the repair mortar is

    placed in adjacent un-repaired concrete to counteract the anodic behaviour of the steel, with

    the number of anodes being tailored depending on amount of steel and size of the patch.

    As well as patch and topical repairs, the hybrid system can be applied to whole structures

    (bridges, car-parks, piers and industrial structures) to repair and protect against rebarcorrosion, using the same treatment methodology [4,5].

    1.1 Responsive Behaviour

    The current passed between an installed galvanic anode and the steel it is protecting very

    much depends on the resistivity of the concrete which separates them. The resistivity of the

    concrete can be influenced by the quality of the mix on casting (water to cement ratios,

    aeration, amount and size of aggregates, mixed in chlorides etc), features induced during

    service (cracking, and chloride diffusion during service) and environmental conditions

    (moisture content and temperature). Also, the distance between the anode and the steel will

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    3/18

    3

    determine the resistance to current flow due to the volume of concrete through which it must

    pass. Varying any of these conditions will have an effect on the resistance of the cell and in

    accordance with Ohms law the current passed will also change

    I = E/R

    Where I = Current (Amps); E = Potential (Volts); and R = Resistance (Ohms).

    This investigation has looked at the responsive behaviour of current output brought about by

    different temperature and moisture conditions as well as varying mixed-in chloride levels.

    Taking an electronic circuit approach, each of these factors can be seen as a variable resistor

    in an electrical circuit (see Figure 2), with the 3 variable resistances making up the total

    resistance of the concrete.

    Figure 2. The resistance of concrete in a galvanic cell, represented by the variable resistances

    of the contributing concrete conditions.

    Resistivity has been used by several authors to evaluate the risk of steel reinforcement

    corrosion [6,7,8,9] with these authors proposing relationships between measured concrete

    resistivity and active corrosion, as well as the chloride concentration threshold for concrete of

    different resistivities.

    These studies have focussed on the influence of concrete resistivity on steel corrosion rates,

    with respect to humidity/moisture, concrete structure and chloride concentrations. None of

    these papers discuss responsive current behaviour when considering galvanic cathodic

    protection, where concrete resistivity has a huge part to play in the effectiveness and

    longevity of the system. The benefits of responsive current behaviour include:

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    4/18

    4

    1. Increased anode lifetime in less aggressive environments (i.e., dry, cold, low chloride),meaning replacement of sacrificial systems can be delayed due to reduced metal

    dissolution.

    2. Increased protection in aggressive environments (i.e., hot, wet, high chloride),meaning that the protective current offered will increase where corrosion is more

    likely.

    The work presented charts the authors experience of responsive behaviour in the galvanic

    phase of the anode system over the last 2 years; taking results from both laboratory and site

    studies.

    2.0 EXPERIMENTAL

    2.1 Whiteadder Bridge Application

    773 days of current and temperature data has been recorded from a bridge over the

    Whiteadder River in Northumberland, UK. The bridge spans the river estuary and although it

    is fresh water, is affected by tidal fluctuations.

    The anodes were installed in the concrete cover in February 2007 during bridge maintenance

    and a variety of measurements have been taken over the subsequent 2 years. A data logger

    was used to collect galvanic current data at noon each day. This was calculated from the

    voltage drop measured across a 1 Ohm resistor. The temperature was measured using a Ttype thermocouple. Data was frequently downloaded from the logger using a GSM modem

    and software configuration.

    Galvanic current data was taken from 2 zones, each housing 25 anodes (5 rows of 5 anodes at

    400 mm centres) connected together with a wire, which was riveted to the steel in a break-out

    zone. These zones were located on a west-facing pier section, as can we seen in Figure 3.

    Following installation a waterproof coating was applied to pier.

    The galvanic current data presented follows a one week impressed current phase whereby a

    high current density is driven from the anode to re-passivate the corroding steel (Figure 1).

    Current, charge and residual life data can be found in Table 2.

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    5/18

    5

    Figure 3. Plan of the west-facing pier section housing the two anode zones

    2.2 Varying chloride blocks and environmental testing

    In a separate lab-based study, concrete samples were prepared in late December 2007. These

    were made with an 8:1 (all-in 20 mm aggregate:opc) mix, at a water to cement (w/c) ratio of

    0.6.

    The samples contained 0, 1, 2.5 or 5% chloride by weight of cement. NaCl (Sodium chloride)

    was used as the source of chloride and was hand-mixed into the water prior to its addition,

    ensuring complete dissolution. Mix details can be seen in Table 1.

    Upper Zone

    Lower Zone

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    6/18

    6

    Block

    Letter

    Cl % New/old Cement

    A 0 Old

    B 0 Old

    C 1 OldD 1 New

    E 2.5 Old

    F 2.5 New

    G 2.5 Old

    H 5 New

    I 5 New

    Table 1. Block concrete composition data.

    The concrete was cast in re-useable wooden moulds (dimensions 600 x 120 x 120 mm) with

    the 15 mm diameter mild steel reinforcing bar (rebar) being fed in from the centre at one end

    (Figure 4). The approximate surface area of the steel was 230 cm2.

    The samples were removed from the moulds between one and two days after casting and left

    to cure in the dry laboratory air (12-20C, ~50-70% Relative Humidity). After a period of six

    months had passed, a hole 30 mm diameter and ~90 mm deep was drilled into the block to

    house the anode which was 14.5 mm high and 17 mm in diameter (surface area 12.3 cm2).

    The steel had a surface area of 230 cm2.The anode was held in place with a lime mortar

    which was allowed to dry before treatment began.

    For 1 week a 12V power supply was used to deliver the impressed current phase of the

    treatment before the anode was connected to the steel galvanically by a rivet. Block F did not

    receive the impressed current treatment and the anode was connected to the steel galvanically

    throughout. Current readings were facilitated by recording the voltage drop across resistors of

    various sizes (depending on the chloride content of the block).

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    7/18

    7

    Figure 4. Test block schematic.

    Following the short term experiments detailed above, all of the blocks were placed outdoors

    throughout the winter/spring of 2008/2009. In May 2009, blocks B, E, D and H were placed

    indoors, leaving blocks A, C, F, G and I outdoors (i.e., one of each chloride concentration in

    either of the regimes). The blocks were thought to be fairly wet when this was done due to

    recent rainfall.

    Identical logger equipment was used to record the galvanic current by measuring the voltage

    drop across a resistor placed between the anode and steel on each block. The indoor and

    outdoor temperatures were also logged and rainfall/meteorological events noted so that the

    causes of major fluctuations could be identified. From these readings, the charge passed could

    be calculated and the residual life estimated (Table 2).

    2.2 Short-term wetting experiment

    Prior to the test, all nine blocks had been in laboratory air (~19C/~65% Relative humidity)

    for around 10 weeks, but were not thought to be excessively dry.

    A data-logger was used to record the voltage drop across a resistor connected between the

    anode and steel. The resistors varied between blocks due to the different amounts of current

    being passed. The temperature was also recorded using a thermocouple.

    40 ml of tap water was poured into the anode hole of each of the blocks and the current

    response measured over a ten day period. Only blocks B, D, G and H were logged to see the

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    8/18

    8

    effect of chloride content on the response, although all nine blocks were watered in this

    manner.

    3.0 RESULTS & DISCUSSION

    3.1 Whiteadder Bridge installation

    Upper and lower zone current data along with temperature readings for a 733 day period can

    be seen in Figure 5.

    Figure 5. Current and temperature data for the Whiteadder river bridge, beginning in late

    March 2007.

    0

    5

    10

    15

    20

    25

    30

    35

    40

    45

    0

    2

    4

    6

    8

    10

    12

    14

    16

    18

    0 100 200 300 400 500 600 700 800

    Airtemp(C)

    Current(mA)

    Time (days)

    Upper zone

    Lower zoneTemp

    River in flood

    causes highcurrent to protect

    the steel

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    9/18

    9

    Figure 6. Current and temperature data from a 5 day period.

    Figure 5 clearly shows the fluctuation of temperature on a monthly/seasonal basis. The

    current response to the changes in temperature can also be seen, but is better highlighted inFigure 6. The effect of different moisture contents on galvanic current can also be seen clearly

    in Figure 5; the bottom row of anodes on the lower zone were frequently under water and

    upward diffusion of water from the river ensured that the lower zone concrete had a

    consistently higher moisture content (and therefore lower resistance to current flow)

    throughout the year. The decay in both the upper and lower zone currents in the first ~200

    days can be explained by gradual drying after hydro-demolition and pressure washing during

    the repairs to the bridge deck.

    Figure 6 gives more detailed information about the effect of temperature on the resistance of

    the concrete. The secondary current peak seen on the lower zone, and less so on the upper

    zone is though to be a result of sunlight/shade effects due to the bridge geometry and the

    direction it faces.

    During the summer months the difference in current between the upper and lower zones is

    more pronounced, as the upper dries out more quickly due to the lesser influence of the river.

    This theory is backed up by the data from the winter months, which brings the current

    readings from the two zones much closer together, seemingly due to the upper zone becoming

    wetter.

    5

    10

    15

    20

    25

    30

    0

    0.5

    1

    1.5

    2

    2.5

    3

    3.5

    28/05/2009 29/05/2009 30/05/2009 31/05/2009 01/06/2009 02/06/2009

    Temperature(C)

    Current(mA)

    Date

    Upper Zone Lower zone Temperature

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    10/18

    10

    On September 9th

    2008, the river flooded. This can be seen by the large spike in protective

    galvanic current and the gradual drop as the flood subsided. The water rose high enough to

    significantly wet the concrete of the upper zone, reducing its resistance and increasing the

    current. It can be seen from Figure 7 that the lower zone recovered in a shorter period than the

    upper zone, probably due to the fact that the concrete held significant moisture prior to the

    flood. The upper zone concrete, as can be seen from the current prior to the flood, was drier

    than the lower at the time of the flood, so both the effect on its galvanic current and

    subsequent recovery after the flood subsided were more significant.

    Figure 7. Current and temperature data taken from the upper and lower zones around the time

    of a flood.

    From the logged currents, the charge passed per anode was calculated for both the upper and

    lower zones. From this data, residual anode life was calculated. This data can be found in

    Table 2.

    -10

    -5

    0

    5

    10

    15

    20

    0

    2

    4

    6

    8

    10

    12

    14

    16

    18

    03/09/2008 13/09/2008 23/09/2008 03/10/2008

    Temperature(C)

    Current(mA)

    Date

    Upper zone

    Lower zone

    Temperature

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    11/18

    11

    Calculation/Measurement Upper

    Zone

    Lower

    Zone

    Units

    Time 773 days

    Average Temperature 12.1 C

    Average current 0.62 2.71 mAAverage current per anode 0.03 0.11 mA

    Average charge per anode 1.17 7.71 kC

    Average charge per anode for 1 year 1.06 6.97 kC

    Charge left per anode after initial treatment 362.3 361.1 kC

    Calculated average anode life 340 50 years

    Steel surface area 2.05 1.92 m2

    Current density applied to steel 0.30 1.42 mA/m2

    Table 2. Relevant current and temperature data for the upper and lower zones

    Due to responsive behaviour, the residual life of the anodes in the lower zone is more than 6.5

    times less than that of the upper as the charge delivered is representative of metal dissolution.

    This shows that in aggressive environments the anodes will pass more protective current to

    the steel at the cost of their effective life, whereas in less aggressive environments, metal

    dissolution is minimal and life conserved. The results take into account an efficiency and

    utilisation factor of 0.85.

    3.2 Blocks with varying chloride content and environmental testing

    The current and temperature from the indoor and outdoor blocks was logged for a 29 day

    period in May and June 2009. The anode current density was then calculated using the

    original anode surface area and was, as a result, a conservative estimate. The differences

    between the indoor and outdoor temperatures can be seen in Figure 8 and the current densities

    with respect to temperature over the four weeks can be seen in Figures 9 and 10.

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    12/18

    12

    Figure 8. Temperatures indoors/outdoors.

    Figure 9. Current density/temperature plot for the outdoor blocks.

    0

    5

    10

    15

    20

    25

    30

    35

    40

    45

    22/05/2009 01/06/2009 11/06/2009 21/06/2009

    Temperature(C)

    Date

    Indoor

    Outdoor

    0

    5

    10

    15

    20

    25

    30

    35

    40

    0

    50

    100

    150

    200

    250

    300

    350

    400

    22/05/2009 01/06/2009 11/06/2009 21/06/2009

    Temperature(C)

    A

    nodeCurrentDensity(mA/m2)

    Date

    Block A

    Block F

    Block GBlock I

    Block C

    Temperature

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    13/18

    13

    Figure 10. Current density/temperature plot for the indoor blocks.

    It is clear from the results of the outdoor blocks in Figure 9 that the resistance of the concrete

    and therefore current delivered to the steel is heavily dependent on the amount of chloride inthe concrete mix. The purely galvanic 2.5% chloride Block F had the lowest current followed

    by the blocks with 1, 2.5 and 5% chloride that had received the impressed current phase.

    It is also clear from Figure 9 that the amount of chloride in the concrete determined the degree

    to which the current was affected by temperature fluctuations. Block F showed variations of

    up to ~20 mA/m2

    and Block I up to ~250 mA/m2.

    The moisture content of the blocks can be seen to have an effect between 6th

    and 9th

    June,

    where the current increases and then reaches a plateau despite a significant drop in

    temperature. The effect of moisture on concrete resistance is also highlighted in Figures 11 &

    12.

    From Figure 9 it is also apparent that the current generally peaks 1-3 hours after the peak

    temperature has been recorded. This effect is due to the anode being mortared into concrete

    which takes time to heat up in contrast to the thermocouple which reads an air temperature.

    Interestingly the peak currents in the indoor blocks did not generally occur until 3-5 hours

    after the maximum temperature was reached.

    The blocks kept indoors showed somewhat anomalous results, with the currents measured forBlock D being especially erratic. Blocks H and E produced similar current outputs throughout

    -60

    -40

    -20

    0

    20

    40

    60

    0

    10

    20

    30

    40

    50

    60

    70

    22/05/2009 01/06/2009 11/06/2009 21/06/2009

    Temperature(C)

    AnodeCurrentDensity(mA/m

    2)

    Date

    Block H

    Block D

    Block E

    Block B

    Temperature

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    14/18

    14

    the test period, despite having different chloride levels. The currents measured generally

    related well to the temperature indoors, although this would be expected without the influence

    of precipitation.

    What is not plainly evident from Figures 9 & 10 is the difference in magnitude of the current

    fluctuation, which is seemingly the result of increased moisture content in the outdoor blocks.

    Figures 11 & 12 represent two blocks with the same chloride content, one of which has been

    left outdoors. Assuming similar temperature trends (Figure 8), the very different current

    profile between 5th

    and 7th

    of June demonstrates the effect of rain and the resulting drop in

    concrete resistivity.

    Figure 11. Current of indoor/outdoor blocks, both containing 2.5% chloride by weight of

    cement.

    0

    20

    40

    60

    80

    100

    22/05/2009 01/06/2009 11/06/2009 21/06/2009

    AnodeCurrentDensity(,A/m2)

    Date

    Block E

    Block G

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    15/18

    15

    Figure 12. Current of indoor/outdoor blocks, both containing 0% chloride by weight of

    cement.

    3.3 Lab based moisture test

    The current response to the water addition for blocks with different chloride levels can be

    seen in Figure 13.

    0

    5

    10

    15

    20

    25

    22/05/2009 27/05/2009 01/06/2009 06/06/2009 11/06/2009 16/06/2009 21/06/2009

    AnodeCurrentDensity(mA/m2)

    Date

    Block B

    Block A

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    16/18

    16

    Figure 13. Current response to the addition of 40 ml tap water to the anode.

    All four blocks responded extremely quickly to the addition of the water, with the currentsspiking immediately. The nature of the rise in current and the time taken to reach a peak after

    the addition varied considerably with the chloride contents of the blocks.

    In general it can be seen that irrespective of chloride levels the anode responds to the

    increased moisture in the concrete, producing more protective current as the environment

    becomes more aggressive. As the water diffuses through the concrete/drains through the

    bottom of the block, the current drops off and eventually reaches a relatively stable state

    which continues to respond to changes in temperature.

    CONCLUSIONS

    The experiences gained over the last two years are summarised below:

    1. The hybrid anodes installed on the Whiteadder Bridge remain active after more than 2years, responding to changes in concrete resistivity brought about by temperature and

    moisture fluctuations as well as geometric effects.

    0

    5

    10

    15

    20

    25

    0

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    1.6

    1.8

    01/09/2008 03/09/2008 05/09/2008 07/09/2008 09/09/2008 11/09/2008

    Temperature(C)

    Current(mA)

    Date

    Block B

    Block D

    Block G

    Block H

    Temperature

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    17/18

    17

    2. The differences in concrete resistivity between the upper and lower zones haveresulted in a large difference in the charge passed. The result is that the anodes in the

    more aggressive lower zone have a predicted lifetime of 50 years and the upper zone

    340 years, which highlights the ability of the anode to preserve its life in benign

    environments and offer extra current when the environment demands it.

    3. Data from the indoor/outdoor samples highlights the responsive behaviour of theanodes to differing chloride levels in the concrete, with the anodes in the more

    aggressive environment (wet, high chloride, high temperature) delivering more current

    to the steel than the drier low chloride blocks. Increasing chloride also increased the

    degree to which the current was affected by temperature fluctuations

    4. This study has shown that the varying influences of moisture, temperature andchloride content on the resistivity of concrete result in a dynamic current response

    which can be measured over the course of a few seconds or a few years.

    REFERENCES

    [1] Broomfield, J.P., 1997, Corrosion of steel in concrete - Understanding, investigation

    and repair London; E & FN SPON.

    [2] Glass, G.K., et al, Hybrid Electrochemical Treatment in the Repair of Corrosion

    Damaged Concrete, Proceedings from: Concrete Platform 2007 Queens University,Belfast, 19

    th& 20

    thApril 2007.

    [3] Glass, G.K., Roberts, A.C., Davison, N., Hybrid corrosion protection for chloride

    contaminated concrete Proceedings of the Institute of Civil Engineers, Construction

    Materials, 161 (2008) p. 163-172.

    [4] Glass, G.K., Roberts, A.C., Davison, N., Hybrid Electrochemical Treatment in the

    Repair of Corrosion Damaged Concrete, Proceedings from: Concrete Platform

    2007 Queens University, Belfast, 19th

    & 20th

    April 2007.

    [5] Holmes, S.P., Repair of Corrosion Damaged Concrete Using a Two-Stage

    Electrochemical Treatment, Proceedings of Structural Faults and Repair 2008,

    Edinburgh.

    [6] Morris, W., Vico, A., Vazquez, Chloride induced corrosion of reinforcing steel

    evaluated by concrete resistivity measurements, Electrochimica Acta 49 (2004) p.

    4447-4453.

  • 8/3/2019 Eurocorr 2009 Paper 8254[1]

    18/18

    18

    [7] Morris, W., Vico, A., Vazquez, M., de Sanchez, S.R., Corrosion of reinforcing steel

    evaluated by means of concrete resistivity measurements, Corrosion Science 44

    (2002) p. 81-99.

    [8] Hunkeler, F., The resistivity of pore water solution a decisive parameter of rebar

    corrosion and repair methods, Construction and Building Materials 10 No. 5 (1996)

    p. 381-389.

    [9] Gonzalez, J.A., Lopez, W., Rodriguez., Effects of Moisture Availability on Corrosion

    Kinetics of Steel Embedded in Concrete Corrosion 49 No. 12 p 1004-1010.