Environmental Systems 1
Danielle Morrison Judith Shoucair Lisa Martinez
Rome, Italy
Latitude: 41° 54‘ 0” N Longitude: 12° 30‘ 0” E
Rome, Italy
Latitude: 41° 54‘ 0” N Longitude: 12° 30‘ 0” E
Kitchen
Sleeping
Bathroom
Living Area
NSITE PLANScale:14" = 1'-0"
3'-4"
4'-4"
4'-10"2'-6" 3'-4"
3'-4"
3'-4"
4'
4'-4"
2'-8"3'-4"2'-10"2'-4"
SITE SECTIONScale:14" = 1'-0"
Kitchen
Sleeping
Bathroom
PLANScale:14" = 1'-0"
Living Area
SECTION B1" = 1'-0"
SECTION A1
Kitchen
Sleeping
Bathroom
Living Area
B
A
Scale:1/4"= 1'-0"
E ELEVATION
N ELEVATIONS ELEVATION
W ELEVATION
Scale: 3/16"= 1'-0"
SUN DIAGRAM (SUMMER SOLSTICE)
SUN DIAGRAM (WINTER SOLSTICE)
9:00 AM
2:00 PM
9:00 AM
2:00 PM
Scale: 3/16"= 1'-0"
N
Marble StuccoConcrete Concrete Ceramic Tiles
Ceramic Tiles
2x4 Wood Asphalt Shingles
1" Foam Board Insulation
FLOOR DETAILFoam Board InsulationLinoleum TileConcrete
WALL DETAILConcreteMarble StoccoFoam Board Insulation
ROOF DETAILFoam Board Insulation
Asphalt Shingles
R-VALUE5.4.5.8
R-VALUE.8125.4
R-VALUE5.4
.5
.44
1" Foam Board Insulation
2 x 4 Wood Studs 4.38Linoleum Tile
Solid Core Flush 3.7DOOR DETAIL R-VALUE
Double Insulating Glass 2.04WINDOW DETAIL R-VALUE
(1/2") air space
Windows: [(6 x 3') x 2 ] + (2 x 3') + (3 x 3')AREAS
Doors: 3 x (7 x 3')51 ft.sq.63 ft.sq.
DETAILScale: 1/2" = 1'-0"
THICKNESS1"
1/2"1'
1'2"1"
1/2"
2 1/4"
THICKNESS
THICKNESS
THICKNESS
THICKNESS
1"
Walls: [(17'-3" x 10') x 2] + [(15'-2" x 10') x 2] - 51 ft. sq. 596.5 ft.sq.
18.2
35.72
6.7
Batt Insulation
Batt Insulation 8" 25
U-VALUE.1492
U-VALUE.0549
U-VALUE.0279
.2703U-VALUE
.4902U-VALUE
TOTAL
JANUARY Dry Bulb: 50o F Interior Temperature: 65o F Difference: 15o F q (Wall) (.0549) (596.5ft2) (15) = 491.22Btu/h q (Roof) (.0279) (224ft2) (15) = 93.74 Btu/h q (Window) (.4902) (51ft2) (15) = 375.00 Btu/h q (Doors) (.2703) (63ft2) (15) = 255.43 Btu/h q (Total above ground) = 1,215.39 Btu/h
APRIL Dry Bulb: 60o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.2703) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h AUGUST Dry Bulb: 82o F Interior Temperature: 65o F Difference: 17o F q (Wall) (.0549) (596.5ft2) (17) = 556.71Btu/h q (Roof) (.0279) (224ft2) (17) = 106.24 Btu/h q (Window) (.4902) (51ft2) (17) = 425.00 Btu/h q (Doors) (.2703) (63ft2) (17) = 289.49 Btu/h q (Total above ground) = 1,377.44 Btu/h
OCTOBER Dry Bulb: 70o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.27033) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h
JANUARY Dry Bulb: 50o F Interior Temperature: 65o F Difference: 15o F q (Wall) (.0549) (596.5ft2) (15) = 491.22Btu/h q (Roof) (.0279) (224ft2) (15) = 93.74 Btu/h q (Window) (.4902) (51ft2) (15) = 375.00 Btu/h q (Doors) (.2703) (63ft2) (15) = 255.43 Btu/h q (Total above ground) = 1,215.39 Btu/h
APRIL Dry Bulb: 60o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.2703) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h AUGUST Dry Bulb: 82o F Interior Temperature: 65o F Difference: 17o F q (Wall) (.0549) (596.5ft2) (17) = 556.71Btu/h q (Roof) (.0279) (224ft2) (17) = 106.24 Btu/h q (Window) (.4902) (51ft2) (17) = 425.00 Btu/h q (Doors) (.2703) (63ft2) (17) = 289.49 Btu/h q (Total above ground) = 1,377.44 Btu/h
OCTOBER Dry Bulb: 70o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.27033) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h
JANUARY Dry Bulb: 50o F Interior Temperature: 65o F Difference: 15o F q (Wall) (.0549) (596.5ft2) (15) = 491.22Btu/h q (Roof) (.0279) (224ft2) (15) = 93.74 Btu/h q (Window) (.4902) (51ft2) (15) = 375.00 Btu/h q (Doors) (.2703) (63ft2) (15) = 255.43 Btu/h q (Total above ground) = 1,215.39 Btu/h
APRIL Dry Bulb: 60o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.2703) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h AUGUST Dry Bulb: 82o F Interior Temperature: 65o F Difference: 17o F q (Wall) (.0549) (596.5ft2) (17) = 556.71Btu/h q (Roof) (.0279) (224ft2) (17) = 106.24 Btu/h q (Window) (.4902) (51ft2) (17) = 425.00 Btu/h q (Doors) (.2703) (63ft2) (17) = 289.49 Btu/h q (Total above ground) = 1,377.44 Btu/h
OCTOBER Dry Bulb: 70o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.27033) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h
JANUARY Dry Bulb: 50o F Interior Temperature: 65o F Difference: 15o F q (Wall) (.0549) (596.5ft2) (15) = 491.22Btu/h q (Roof) (.0279) (224ft2) (15) = 93.74 Btu/h q (Window) (.4902) (51ft2) (15) = 375.00 Btu/h q (Doors) (.2703) (63ft2) (15) = 255.43 Btu/h q (Total above ground) = 1,215.39 Btu/h
APRIL Dry Bulb: 60o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.2703) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h AUGUST Dry Bulb: 82o F Interior Temperature: 65o F Difference: 17o F q (Wall) (.0549) (596.5ft2) (17) = 556.71Btu/h q (Roof) (.0279) (224ft2) (17) = 106.24 Btu/h q (Window) (.4902) (51ft2) (17) = 425.00 Btu/h q (Doors) (.2703) (63ft2) (17) = 289.49 Btu/h q (Total above ground) = 1,377.44 Btu/h
OCTOBER Dry Bulb: 70o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.27033) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h