ENHANCED PERFORMANCE THROUGH OPTIMIZED MASONRY LINTELS
Presented by Scott W. Walkowicz, P.E.For the Indiana/Kentucky Structural Masonry Coalition
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 1
ALL SEASONS BUILDING MATERIALS
A REGISTERED INDIANA PDH PROVIDER
INDIANA/KENTUCKY STRUCTURAL MASONRY COALITION
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 2
This presentation is protected by U.S. and International copyright laws. Reproduction, distribution, display and use of the presentation without permission of the speaker is prohibited.© Walkowicz Consulting Engineers, LLC
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 3
THIS PRESENTATION IS INTENDED FOR THE USE OF INDUSTRY PROFESSIONALS WHO ARE COMPETENT TO EVALUATE THE SIGNIFICANCE AND LIMITATIONS OF THE INFORMATION PROVIDED HEREIN. THIS PUBLICATION SHOULD NOT BE USED AS THE SOLE GUIDE FOR MASONRY DESIGN AND CONSTRUCTION, AND WCE AND MISMC DISCLAIMS ANY AND ALL LEGAL RESPONSIBILITY FOR THE CONSEQUENCES OF APPLYING THE INFORMATION.
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 4
To have gained insight into masonry lintel detailing performance benefitsTo demonstrate masonry lintel structural performance benefitsTo illustrate structural design approachesTo recognize the overall building improvements gained through the use of masonry lintels
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 5
Steel lintels can add 6-8 weeks… to as much as 12 weeks delayWith Masonry Lintels:◦Differential movement eliminated◦Detailing dramatically better (flashing and steel infill)◦ Thermal bridging reduced◦ Control joints reduced (see Structural Performance…)◦Wide cavity options
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 6
Steel lintels can add 6-8 weeks… to as much as 12 weeks delay
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 7
Steel lintels cause delays…◦add 6-8 weeks…◦to as much as 12 weeks delay
Detailing / Review / ?Revision? / Fabrication / Galvanizing
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 8
Detailing dramatically better (flashing and steel infill)Thermal bridging reduced
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 9
Figure Credits: Masonry Institute of Michigan
Different Example Details
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 10
Figure Credits: International Masonry Institute
Detailing dramatically better (flashing and steel infill)Thermal bridging reduced
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 11
Figure Credit: Masonry Institute of Michigan Figure Credit: GMB
Detailing dramatically better (flashing and steel infill)Thermal bridging reduced
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 12
Figure Credit: Masonry Institute of Michigan
Detailing dramatically better (flashing and steel infill)Thermal bridging reduced
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 13
Detailing dramatically better (flashing and steel infill)
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 14
Detailing dramatically better (flashing and steel infill)
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 15
Detailing dramatically better (flashing and steel infill)
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 16
Use masonry modules for length, height and position!
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 17
Use masonry modules for length, height and position!
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 18
Detailing dramatically better (flashing and steel infill)Thermal bridging reduced eliminated…Works for wide cavities
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 19
Figure Credits: Masonry Institute of Michigan
Proprietary or project specific engineered outrigger angleThermal bridging reduced minimized…Works for wide cavities…
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 20
Figure Credits: FERO
(Shelf angle detail)
Proprietary or project specific engineered outrigger angleThermal bridging reduced minimized…Works for wide cavities…
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 21
Figure Credits: Halfen(Shelf angle detail) Halfen FK4 Brickwork Support System
Control joints better placed for better wall structural performance◦Greater effective ‘pier’ width◦Masonry wall or wall-frame performance
Span large openingsEasier to achieve lower deflectionHandle torsion and shear better with less complicationDeep beam optionDoubly Reinforced
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 22
Control joints better placed for better wall structural performance◦Reduced number of joints◦Reduced length of joints◦Better jamb reinforcement
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 23
Figure Credit: GMB
Control joints better placed for better wall structural performance
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 24
Figure Credit: Masonry Institute of Michigan
Figure Credit: International Masonry Institute
Control joints better placed for better wall structural performance
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 25
Control joints better placed for better wall structural performance
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 26
(See NCMA TEK 10-3 re. eliminating CJ’s)
Span large openingsEasier to achieve lower deflection
◦ 7 cs. CMU = 0.145”◦W16x36 = 0.376”
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 27
Figure Credit: DeMattia
Figure Credit: DeMattia
24’-8”40’-0”
Span large openingsEasier to achieve lower deflection
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 28
48’-0”
Figure Credits: MayotteGROUP Architects
8 cs. CMU = 0.50”W24x117 = 1.15”
Handle torsion and shear better with less complication◦ Torsion becomes moment in the adjacent pier◦No torsion provisions in masonry code◦ Historically no beams fail in torsion◦ Wide cavities with heavy veneer loads may change that…
◦ Shear generally very low compared to capacity
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 29
Handle torsion and shear better with less complication
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 30
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 31
Figure Credits: Bergmann
Figure Credit: GMB
Figure Credit: NCMA TEK 10-2C
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 32
Consider load balancing to reduce eccentric loading and keep bearing plate loose by keeping reaction in center 1/3 of bearing (kern) of the lintel plate which is coped to 5/8” less than wall thickness beyond M.O. See design example….
Or, run the lintel plate through the full length and use it to resist rotation? With no EJ at M.O. or lintel ends? How much differential movement is acceptable???
�116 "?�1
8 "?�1
4 "?
Figure Credit: GMB
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 33
Simple span with or without arching actionFixed-end / continuousDeep beamDoubly ReinforcedWide cavity options◦Outriggers◦Reinforced veneer
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 34
The basics:
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 35
The basics:
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 36
The basics:
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 37
The basics:Know your depth: 2.25” or 2.75” to bottom of bars?
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 38
The basics:Know your depthAnd detail it!
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 39
Figure Credits: Bergmann
½” CLR. MIN.
½”
CLR.
MIN
.
The basics:Know your depth (H – 3” max.?)Use the proper f’m (2300*** psi min.?)Grout more depth rather than stirrupsSelect and detail for end conditions◦ Simple span with CJ’s/EJ’s◦ Continuous with joints moved off the end
of lintel
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 40
Figure Credits: Masonry Structures Behavior and Design 4th Edition (Hamid)
Simple Span – the traditional approachFor Uniform Loads:◦𝑀𝑀 = 𝑊𝑊𝑙𝑙2
8
◦𝑉𝑉 = 𝑊𝑊𝑙𝑙2
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 41
Figure Credit: NCMA TEK 17-01D1
Simple Span – the traditional approach◦𝑀𝑀 = 𝑊𝑊𝑙𝑙2/8◦𝑉𝑉 = 𝑊𝑊𝑙𝑙/2
Arching Action?◦ CJ’s can inhibit arching◦No point loads within◦𝑀𝑀 = 𝑊𝑊𝑙𝑙/6◦𝑉𝑉 = 𝑊𝑊/2
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 42
Figure Credit: NCMA TEK 17-01D1
Simple Span – Hand CalculationsPure Flexure (ASD) Capacity:◦𝑀𝑀 = 𝑓𝑓′𝑚𝑚𝑘𝑘𝑘𝑘𝑘𝑘𝑑𝑑2
2(compression/masonry controls)
◦𝑀𝑀 = 𝐴𝐴𝑠𝑠𝑓𝑓𝑠𝑠𝑗𝑗𝑗𝑗 (tension/steel controls)◦ 𝑘𝑘 = 2𝑛𝑛𝜌𝜌 + (𝑛𝑛𝜌𝜌)2− 𝑛𝑛𝜌𝜌◦ 𝑗𝑗 = 1 − 𝑘𝑘
3
◦ 𝑓𝑓𝑣𝑣 = 𝑉𝑉𝐴𝐴𝑛𝑛𝑛𝑛
≤ 𝐹𝐹𝑣𝑣◦ Hand calcs or spreadsheets◦ (works for non-loadbearing walls)
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 43
Simple Span – Hand CalculationsTrial:◦M.O. = 9’-4”◦ habove = 6’-0” total◦ Tributary Width = 36’-4” / 2 = 18’-2”◦ Include bolted angle veneer weight / ignore torsion◦DLr = 364 plf / DLveneer = 240 plf / LLr = 364 plf / SnL = 421 plf◦Bearing length = 8” each side (Design Span = 10’-0”)◦DL + SnL = 604 + 421 = 1025 plf + wall wgt. + lintel weight
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 44
Simple Span – Hand Calc’sLintel Weight:◦ Try (3) courses:◦NCMA TEK 17-01: 174 plf/ft.
Wall Weight:◦NCMA TEK 14-13B◦ 47 psf = 188 plf at 4’
remaining above lintel
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 45
Simple Span – Hand CalculationsDL + SnL + lintel wgt. + wall wgt. = 604 + 421 + 174 + 188 plfTotal Load = 1,387 plf
𝑀𝑀 = 1,387∗102
8= 17,337.5 lb.-ft. = 208,050 lb.-in.
𝑉𝑉 = 1,387∗102
= 6,935 lbs.◦ Conservative to use full shear◦ Typically can use shear at d/2 from support (uniform loading)
At 𝑗𝑗 = 20.5" and 𝑙𝑙 = 7.625′: 𝑉𝑉 = 1,387𝑥𝑥7.6252
= 5,288 lbs.
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 46
Simple Span – Hand CalculationsDL + SnL + lintel wgt. + wall wgt. = 604 + 421 + 174 + 188 plfTotal Load = 1,387 plf
𝑀𝑀 = 208,050 lb.-in. ≤ 𝑓𝑓′𝑚𝑚𝑘𝑘𝑘𝑘𝑘𝑘𝑑𝑑2
2OR ≤ 𝐴𝐴𝑠𝑠𝑓𝑓𝑠𝑠𝑗𝑗𝑗𝑗
𝑛𝑛 = 29,000,000 𝑝𝑝𝑠𝑠𝑝𝑝900𝑥𝑥2,000 𝑝𝑝𝑠𝑠𝑝𝑝
= 16.11
𝜌𝜌 = �𝐴𝐴𝑠𝑠𝑘𝑘𝑑𝑑 = ⁄0.44
7.625𝑥𝑥20.5 = 0.00281𝑘𝑘 = 0.2592𝑗𝑗 = 0.9136
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 47
Simple Span – Hand Calculations
𝑀𝑀 = 208,050 lb.-in. ≤ 𝑓𝑓′𝑚𝑚𝑘𝑘𝑘𝑘𝑘𝑘𝑑𝑑2
2OR ≤ 𝐴𝐴𝑠𝑠𝑓𝑓𝑠𝑠𝑗𝑗𝑗𝑗
𝑀𝑀𝑐𝑐𝑐𝑐𝑐𝑐𝑝𝑝 = 𝑓𝑓′𝑚𝑚𝑘𝑘𝑘𝑘𝑘𝑘𝑑𝑑2
2= 2,000(0.2592)(0.9136)(7.625)(20.52)
2
𝑀𝑀𝑐𝑐𝑐𝑐𝑐𝑐𝑝𝑝 = 758,816 lb.−in. ≥ 208,050 → 𝑶𝑶𝑶𝑶𝑀𝑀𝑡𝑡𝑡𝑡𝑡𝑡𝑠𝑠 = 𝐴𝐴𝑠𝑠𝑓𝑓𝑠𝑠𝑗𝑗𝑗𝑗 = 0.44 32,000 0.9136) 20.5𝑀𝑀𝑡𝑡𝑡𝑡𝑡𝑡𝑠𝑠 = 263,702 lb.−in. ≥ 208,050 → 𝑶𝑶𝑶𝑶
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 48
Simple Span – Hand Calculations𝑉𝑉 = 5,288 𝑙𝑙𝑙𝑙𝑙𝑙.≤ (𝐹𝐹𝑣𝑣𝑐𝑐 + 𝐹𝐹𝑣𝑣𝑠𝑠)𝛾𝛾𝑔𝑔(𝐴𝐴𝑡𝑡𝑣𝑣)Avoid using stirrups, so only use masonry shear capacity𝛾𝛾𝑔𝑔 = 1.0 𝑓𝑓𝑓𝑓𝑓𝑓 𝑓𝑓𝑜𝑜𝑜𝑜𝑜𝑓𝑓 𝑜𝑜𝑜𝑡𝑡𝑛𝑛 𝑝𝑝𝑡𝑡𝑓𝑓𝑜𝑜𝑝𝑝𝑡𝑡𝑙𝑙𝑙𝑙𝑝𝑝 𝑔𝑔𝑓𝑓𝑓𝑓𝑔𝑔𝑜𝑜𝑜𝑜𝑗𝑗 𝑙𝑙𝑜𝑜𝑜𝑡𝑡𝑓𝑓 𝑤𝑤𝑡𝑡𝑙𝑙𝑙𝑙𝑙𝑙
𝐹𝐹𝑣𝑣𝑐𝑐 = 12
4.0 − 1.75 𝑀𝑀𝑉𝑉𝑑𝑑𝑛𝑛
𝑓𝑓𝑓𝑐𝑐 + 0.25 𝑃𝑃𝐴𝐴𝑛𝑛
Use M at 7.625’ / 2 from center… d/2 from face
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 49
Simple Span – Hand Calculations
𝐹𝐹𝑣𝑣𝑐𝑐 = 12
4.0 − 1.75 87,0895,288(23.625)
2,000 +
0.25 07.625(23.625)
𝐹𝐹𝑣𝑣𝑐𝑐 = 62.164 𝑝𝑝𝑙𝑙𝑝𝑝𝑉𝑉𝑎𝑎𝑙𝑙𝑙𝑙𝑐𝑐𝑎𝑎 = 𝐹𝐹𝑣𝑣𝑐𝑐𝐴𝐴𝑡𝑡𝑣𝑣 = 62.164 ∗ 7.625 ∗ 23.625 =11,198 𝑙𝑙𝑙𝑙𝑙𝑙.𝑉𝑉𝑎𝑎𝑙𝑙𝑙𝑙𝑐𝑐𝑎𝑎 = 11,198 𝑙𝑙𝑙𝑙𝑙𝑙.≥ 5,288 → 𝑶𝑶𝑶𝑶
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 50
Simple Span – design aids – NCMA TEK 17-01D1
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 51
Simple Span – SMDS
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 52
Simple Span – SMDS
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 53
Simple Span – SMDS
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 54
Fixed-end / continuous◦ Top steel required◦Reduced moment◦Reduced deflection◦Moment transferred
to jambs
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 55
Figure Credit: Masonry Institute of Michigan
Fixed-end / continuous – Hand/SMDS◦ Calculate fixed end (negative) moments and shears◦ Remember shear check at d/2 from face◦ Or conservatively use shear at face and assume 𝑀𝑀
𝑉𝑉𝑑𝑑𝑛𝑛= 1.0
◦ Remember that top bars must be developed (length, hooks, etc…)◦ Use TMS 402 development length equation
◦Design top steel / check shear capacity to avoid stirrups◦ Calculate mid-span (positive) moment◦Design bottom steel (shear won’t control here…)
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 56
Fixed-end / continuous – Hand/SMDS◦Use the same example as before, but with fixed ends
◦𝑀𝑀𝑡𝑡𝑡𝑡𝑑𝑑𝑠𝑠 = 𝑎𝑎𝑙𝑙2
12= 1025∗102
12= 8,541 𝑙𝑙𝑙𝑙.−𝑓𝑓𝑜𝑜. = 102,500 𝑙𝑙𝑙𝑙.−𝑝𝑝𝑛𝑛.
◦𝑉𝑉 = 1,025∗102
= 5,125 lbs. (at face, conservative)◦ Enter directly into SMDS◦Or, conduct hand or spreadsheet calculations…
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 57
Fixed-end / continuous –SMDS
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 58
Fixed-end / continuous –SMDS
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 59
Fixed-end / continuous –SMDS
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 60
Fixed-end / continuous – FEA (Ram Elements or RISA for design)
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 61
Ram Elements Lintel Results:𝑀𝑀 = 9,385 𝑙𝑙𝑙𝑙.−𝑓𝑓𝑜𝑜.𝑀𝑀 = 112,620 𝑙𝑙𝑙𝑙.−𝑝𝑝𝑛𝑛.Remember F-F:𝑀𝑀 = 102,500 𝑙𝑙𝑙𝑙.−𝑝𝑝𝑛𝑛.
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 62
Ram Elements FEA:
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 63
DL + SnL Deflection in Y DL + SnL M)min
Ram Elements Wall Results:
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 64
Deep beams (low span:depth)◦ 3:1 for continuous beams◦ 2:1 for simply supported beams◦Non-planar behavior◦Bottom reinforcement = tie◦Distributed steel required in
tension zone◦ Prescriptive vertical shear steel
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 65
Figure Credits: Masonry Structures Behavior and Design 4th Edition (Hamid)
Deep beam option (code specific requirements)
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 66
H/L > 2 @simple spanH/L > 3 @continuous
Doubly Reinforced◦ Like concrete beam design◦Utilize top bars in compression◦Will require stirrups to position top bars◦Not typical◦ Can help with minimizing depth
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 67
Doubly Reinforced◦Not common◦ Lintel capacity generally
controlled by flexural tension or shear
◦ Top bars must be confined (ties) – adds complication
◦Modest strength increase
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 68
Wide cavity options◦Outriggers◦Reinforced veneer
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 69
Figure Credits: Masonry Institute of Michigan
Reinforced veneer lintels - IRC
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 70
Reinforced veneer lintels – Hand Calculations◦ Same principals as before◦Different unit strengths, so different f’m◦Different reinforcement size◦ Two or three layers, so ‘d’ calculated to center of mass of group◦ Lateral load taken out by veneer ties◦Beam braced laterally by veneer ties
COPYRIGHT WALKOWICZ CONSULTING ENGINEERS 2019 71
Masonry lintels offer much improved detailingMasonry lintels lead to better structural performanceMasonry lintel design is not that challengingMasonry buildings perform better with masonry lintels