encore presentation sept 2007
TRANSCRIPT
Click For Animation
Product Summary – What is it?• Revolutionary, next generation product family from Dranetz-
BMI for the permanently (and semi-permanent) installed market
• Includes all components and functionality of Signature System.
• Encore Series Model 61000New!
• All new instrument design that builds upon the strengths of prior Dranetz-BMI products:
• Signature System• Strong PQ capabilities• Web browser based interface
• 4400/PX5• Power Quality compliance capabilities• Visualization – Bright, colorful, easy to use local user interface
• Measuring Pad• Physical measurements
Encore Series
AGDER ENERGI NETT AS – NorwayAllegheny PowerAlliant EnergyAmerican Electric PowerBKK NETT AS – NorwayBonneville ElectricCentral Electric CompanyCentral Networks – UKCentral Service Power of San AntonioCity of Danville, VACity of LakelandCity of Palo AltoCity of TucsonCITY UTILITIES OF SPRINGFIELDCMS EnergyCommonwealth EdisonCompanhia de Electriciadade, MacauConsolidated EdisonDayton Power & LightDuke EnergyELECTROBISTAND - NorwayElektro Primorska, SloveniaELES - Elektrogospodarstvo Slovenije EntergyEPRI-PEACHALOGALAND KRAFT AS - NorwayHawaii ElectricHELGELANDSKRAFT AS - NorwayHEP Transmission Company, CroatiaHEP Distribution Company, CroatiaHYDRO ALUMINIUM – NorwayISTAD NETT ASGuangdong EPRI, ChinaJiangSu EPRI, ChinaKansas City Board of Public UtilitiesKeyspanKnoxville Utility BoardKOREA INSTITUTE OF ENERGY RESLYSE NETT AS
Electric Utilities Government
Aberdeen Proving GroundArgonne National LaboratoriesArup LaboratoriesFederal Aviation AdministrationGovernment communications Headquarters, UKInternal Revenue ServiceInternational Broadcasting BureauLockheed MartinLondon Air Traffic Control, UKMI-5 - UKNASA AmesNational Institute of StandardsNational Renewable Energy Laboratory North Wales Police, UKOnizuka Air Force BaseRaytheonUS Air Force/Lockheed MartinUS ArmyUS NavyThe World BankMcCarran International Airport
Encore Series CustomersMaui ElectricMid American EnergyMorristown Power SystemNational Grid, UKNebraska Public Power
NORDMORE ENERGIVERK AS – NorwayNortheast Utilities
NOTODDEN ENERGY AS - NorwayNew York State Electric and GasOklahoma Gas & ElectricOmaha Public Power DeptPennsylvania Power And Light Electric Utilities CorpPolskie Sieci Elektroenergetyczne SA, PolandPublic Service of OklahomaReliant Energy
ROYOY-LUROY KRAFTVERKAS - NorwaySan Diego Gas & ElectricShanghai Municipal Electric Power Company, ChinaSFE NETT ASShanghai Metro Traffic Co, ChinaShanxi EPRI, China
SINTEF –Norway
SKAGRAK NETT AS – NorwaySouthern California EdisonSunnfjord Energi A/S/ Norway
STATNETT – NorwaySWECO GRONER AS – Norway
TAFJOR KRAFTNETT AS - NorwayTexas UtilitiesTennessee Valley Authority
TUSSA NETT AS - NorwayUnited IlluminatingUnity Electric Corporation
Original Equipment Manufacturers/Partners
BAE SystemsBeacon Power CorporationSocomec - FranceFuel Cell EnergySoft Switching Technologies
PillerToshibaS&C ElectricUTC Fuel Cells
PON CAT AB(Caterpillar) - Sweden
Alliance & Leicester Bank, UKAmerican ExpressAmSouth BankBank of America, UKBanco de PeruBanco PopularBear StearnsBloomberg, UKChicago Stock ExchangeCiticorpCredit Suisse, UKDeutsche Bank
ABC NetworkAK SteelAkzo NobelAmerican Physical SocietyAsltom BoeingCalvin CollegeCBS NetworksCHARLES SCHWAB & COMPANY INCCPIDade BehringDelta AirlinesDHL AirwaysDiscovery CommunicationsDupont Dyna ElectricElectrical Systems IntlEli LillyElgar SorensonEmerson, ChinaEpsilonFresh DirectGeorgia PacificGolden Era Prod.Hamilton SundstrandHearth & HomeIntelJohnson & JohnsonLOGAN ALUMINUMMead Westvaco
Finance/Banking
Computer/Information/Telco
Commercial & Industrial
Cingular/AT&T Wireless Next Level Comm.Cisco Systems Q Logic Pac BellComputer Sciences SIACControl Systems Intl Sun MicrosystemsDow Jones Sutro TowersExtreme Networks Telehouse lnt’lGC Micro Texas InstrumentsHarris Corp UnisysIBM VerizonMotorola
MEM SwitchgearMcCarren AirportMetropolitan CouncilMillennium ChemicalMinnesota Corn ProductsMurphy OilMystic Lake CasinoNiagara WaterNucor SteelOhio AerospacePfizer Pharmaceutical, UKPhillip MorrisPowell-ESCOReuters, UKRenault, Slovenia
SANDVIK COROMAT – Sweden
SafewaySharp ElectronicsShell OilSintefSkyguide, SwitzerlandStatoilTexaco, UKTexas PetrochemicalTLT BabcockUnited AirlinesWelsh Traffic, UK
Encore Series Customers
Education
University of North CarolinaUCLA Medical
Federal Reserve BankGoldman SachsHBC Bank UKJP Morgan/ChaseKPMGMorgan StanleyNASDAQNew York Stock ExchangeNomura SecuritiesNYCEThe World BankVisa
City of HopeKaiser Permanente HospitalMD Anderson Medical CenterPresbyterian Health Care
Hospital/Healthcare
San Jacinto Methodist HospitalSutter HealthcareTrillium HealthcareUniv. of Texas Medical Center
Design Goals• Modularity
• Ability to easily configure the instrument to cost-effectively meet customers applications
• Compliance• Meet (and exceed) all US (IEEE) and International (IEC, EN) Power Quality monitoring
standards
• Communications• Strong and diverse suite of communications
• Compatibility• Allow the customer to continue to use existing assets while taking advantage of the latest
technology
• Visualization• Provide an easy to use local user interface. Web browser based system interface
• Intelligence• Clear and simple event explanations. Apply years of Dranetz-BMI & Electrotek experience
by automatically performing advanced analysis and characterization of data. Answer Modules®
• Innovation• Continue Dranetz-BMI’s legacy of providing unique and innovative solutions to meet the
changing needs of our customers.• Continue to provide the features and benefits our customers expect while improving our
market position.
Encore Series
System Architecture
• Encore Series Software• PC compatible, Windows 2000/XP
• Web browser based user interface, supports from 1 to 50+ instruments• Power Quality, Demand, Energy and Process Analysis• Intelligent Answer Modules for automatic advanced analysis• Fully supports Signature System and other Dranetz-BMI products
• Enterprise Software• For large system management and/or advanced analysis• PQView or DranView
• Industrial grade computing platforms• For rugged and harsh environments where a PC is not appropriate• Runs Encore Series Software (see above)• Model 5502 – Compact Flash memory, Model 5504 – Hard Disk memory
• Demonstration site on the internet• Live Encore system monitoring the Dranetz-BMI facility in Edison, NJ USA• IP address: 72.4.197.9. Username: “guest”, Password: “password”
• One time only Java install. Follow the online instructions.
System Software
Modularity• Encore Series model 61000 has 4 slots within the instrument to
accept various types of measurement modules• 4 Channel voltage• 4 Channel current• 8 Channel digital input
• Each module can be it’s own instrument or combined with other modules to create Virtual Instruments – multiple instruments within one instrument
• Built to order • Customer “builds” the instrument:
1) Select your mainframe. Choose from Standard (61STD) or Switchgear with or without ¼ VGA touch display (61SGD, 61SG)
2) Select the modules needed for your application, up to a total of four.
Model 61000 New!
Build Your Own Instrument!
4 Channel Voltage Module
4 Channel Current Module
Digital Input Module
Click For Animation
Benefits of the 61000 Modularity
Encore Series
Before Encore Series
Four separate instruments
After Encore Series
One instrument
$ $ $
€ € €
Reduced Cost!
€ € €
$ $ $
61000 Compliance• Meets (and exceeds) all US (IEEE) and International (IEC, EN)
Power Quality monitoring standards• 61000-4-30 Class A compliant using technology from 4400/PX5
• Compliance certified by an independent laboratory. Certificate available on www.dranetz-bmi.com
• IEC61000-4-7 second revision, gapless, IEC61000-4-15
• EN50160
• NVE (Norway)
• CREG (Columbia)
• IEEE 1159, IEEE 519, IEEE1453, IEEE1459
Encore Series
61000 Communications• Standard built-in
• 10/100BaseT Ethernet - Adaptable to fiber, wireless and others • RS232, RS485
• External (optional)• Analog modem• GSM/GPRS modem
• Communication Protocols• XML (to Encore Series Software), Modbus TCP, RTU
• Cross-Triggering – Internal & external• Internal: Trigger on one channel causes others to record (within 1 instrument)• External: One instrument (or virtual instrument) can tell another to record data to
memory
• GPS• Internal GPS receiver (optional) and external antenna• Encore SW or 5504/5502 (optional)
Encore Series
Compatibility• New 61000• EPQ family, 5540 family, ADAM family Datanodes• 7100 PQNode• PQView• DranView• Other Dranetz-BMI & Electrotek products
Encore Series Software
61000 Visualization• Web Browser based remote system level interface via Encore Series
Software
• Local user interface
Encore Series
Switchgear mount with ¼ VGA touch display
19” Rack Mount with ¼ VGA touch display
Encore Home Page
Event Summary
Sample Timeline with Event List
PQ Event Details
Sample Energy Trend
Real Time Meters
Intelligence • Answer Modules (optional) are part of Encore Series Software and
perform advanced analysis and characterization of data.• Intelligent algorithms that interpret and/or compile data• Available Answer Modules
• Sag/Dip directivity: Did the sag original upstream or downstream• PF capacitor transient detection. Was the source of the transient a PF
cap switching. VAR verifier identifies unbalanced capacitor switching. • Optional VAR Verifier identifies unbalanced capacitor switching.
• UPS: Pass/Fail report that compares data from the input and the output of the UPS to determine if the Ups is mitigating input side problems.
• Energy Usage: Advanced energy analysis and aggregation.• Radial line fault: Estimate the distance to a fault• Oneline: Custom web based graphical user interface of your system.
Encore Series
Here’s the Data ...
Encore Series
along with the Information ...
Encore Series
… that leads to the Answer !
Encore Series
Encore Series Instrumentation
Available Instruments• Power Quality, Demand & Energy
• 61000 DataNodeNew!
• 61STD, 61SGNew!, 61SGDNew! mainframes
• 5530T/5520T, 5513T Enhanced Power Quality DataNode
• Demand & Energy• A230, A230s• 5546, 5547, 5548, 5549
• Physical measurements - Transducer and contact monitoring• 61000 digital input • Advantech ADAM DataNode’s
Encore Series
Encore Model 61000
• Instrument Mainframes – All have 4 slots• Aluminum Enclosure• Switchgear mount with or without display
• Standard communications• RS232, RS485• Ethernet
• 1GB internal Flash memory• Not removable
• Power Supply• On/Off Switch• Standard enclosure, 12Vdc input
• External AC adapter• Optional 125/220VDC
• Switchgear mount, internal 90-250VAC, 105-125VDC • Built in UPS
• Internal GPS receiver (optional), rear panel connector.
Model 61000 Family
12VDC Instrument Power Supply
Sample Rear Panel(actual instrument depends on your
configuration)
Voltage/Current Module Pod interface
Current module TR Connectors
Voltage Module Safety Connectors
Ethernet
RS232, RS485
Not Supported
GPS Antenna
Voltage Module Screw Terminals
Power Supply Output for Flex CT’s
Power Supply Output For
GSM
Power Switch
Encore Model 61000
Note: 61STD shown
• 4 Channel Voltage Module• Range: 0 – 600V, 1000Vpk, DC coupled (AC/DC)
• RMS: 512 Samples/cycle, +/- 0.1% Reading, +/-0.05%FS, over 7KHz bandwidth (1 second RMS readings)
• Standard low and medium frequency transients• Medium freq transient resolution is now 32.5us due to 512
samples/cycle• 4x EPQ DataNode (128s/c, 130us), 2x 4400 (256s/c, 65us)
• Connections available:• 61MVS: Screw Terminals• 61MVB: Safety Connectors• 61MZP: ‘D’ connector for
voltage or current pods
Encore Series
61MZP 61MVS61MVB
5536VPOD
• 4 Channel Current Module• Range: 0 – 1.5V, DC coupled (AC/DC)
• RMS: 512 Samples/Cycle, +/- 0.1% Reading, +/-0.05%FS, 3KHz bandwidth (1 second RMS readings)
• Standard low and medium frequency transients to 32us
• Connections available:• 61MAC: Dranetz-BMI ‘TR’ type connector• 61MAS5, 61MAS1: 5A or 1A
built in CT. Counts as 2
modules, double wide.• 61MZP: ‘D’ connector for
voltage or current pod
Encore Series
61MAC61MZP
5537APOD
61MAS5, 1
• 8 Channel Digital Input Module• 61MDIN: Range: 0 – 135VAC/DC • 1KHZ sampling, Edge or level triggered• Logic programmed by user (active high or active low)• Time stamped to the millisecond• Recorded and trended in parallel with voltage and current• Screw terminals• Use instead of InfoNode ADAM modules
• Faster sampling• DataNode is usually closer to the circuit being measured than the
InfoNode
• Applications• General digital input position monitoring such as breaker/switch
position.• Demand interval synchronization. Start and stop interval.• Pulse counting, KYZ metering
Encore Series61MDIN
• Communications• Built in, standard
• Ethernet• RS232, RS485
• Available• GSM, GPRS modem - 61GPRS, works
in all countries. User supplied SIM• Analog modem – 61MDM
Model 61000 Family
61MDM
61GPRS
• Mounting• Standard shelf mount• Available
• 19” Rack. Instrument mounts behind the rack panel. • With or without optional color/touch display.
• 61RMTS (no display), 61RMTD (with display)
• Wall/vertical surface using brackets. 61BRKTS• Weather resistant enclosure, 61WENCL
• Available for 61000 and 61000VCM• With or without phase power adapter to power from
phase (61000 only)
Model 61000 Family
61WENCL
61RMTD
Enhanced Power Quality (EPQ) Models 5530, 5520,
5513
• Instrument Mainframe• Models 5530, 5520, 5513, 5510 • Aluminum Enclosure
• 13” x 8” x 5”• Standard communications
• Ethernet• AUI – Adaptable to fiber, coax and others
• Power Supply• On/Off Switch• 90-250Vac, 50/60Hz• Optional 105-150Vdc• Built-in UPS
EPQ DataNode
EPQ Model 5530T, 5510T (no Pods)
Voltage Pod Current Pod
EPQ Model 5520
EPQ Model 5513(Connectors only shown)
EPQ DataNode
• Mounting • Standard shelf mount
• Optional• Weather resistant enclosures• 19” Rack mount• Wall mount brackets
EPQ DataNode
• Models 5530, 5520, 5513• 4 Voltage & 4 Current channels
• 5530, 5520:• 600VAC/DC, 5A or 1A (5530 only) CT Secondary
• 5513:• 600VAC/DC, 1.5V Clamp-on CT, Flex CT, DC CT
• Differential Inputs for direct Delta connections (A-B, B-C, C-A)• 128 samples/cycle • Standard low, medium and high speed peak detected transients to 1us• 1/2 Cycle RMS• IEC Harmonics, Interharmonics• Up to 16 pre/post cycle capture• Ethernet Communications to Encore SW• IEC 61000-4-30 Class B• CE, UL
EPQ DataNode
DataNode Series A230• 30+ Parameters
• RMS voltage and current, kVA, KVAR, kW, PF, frequency, kWh, demand, VTHD, ITHD.
• Harmonics
• Local Display• Bright 3 Line LED
• Panel Mount, Two Sizes:• A230: 144 x 144 x 46mm
• A230s: 96 x 96 x 46mm
• Screw Terminals for Voltage, Current and Power
DataNode Series A230• Communications
• RS232, Modbus RTU• Ethernet, Modbus TCP• None
• Instrument Power• 85 to 253V AC/DC, 45 to 400Hz
Rear panel view
DataNode Series 5540
• 32 Demand & Energy type Parameters• Local Display
• Bright 3 Line LED• Panel Mount• Screw Terminals Voltage• Feed through for Current• 2 wire RS485 Com’s
• Ethernet available using external adapters
DataNode Series 5540
Power Supply 120VAC or 230VAC
Enterprise SoftwareEnterprise Software
DataNode
EncoreSW
Encore
SW
Enterprise SW on PC
(Optional)
LAN, WAN, Internet, Ethernet,
Fiber, Wireless, Modem etc.
DataNode DataNode DataNode DataNode
Encore Series
LAN, WAN, Internet, Ethernet,Fiber, Wireless, Modem etc.
PQView
• Download Encore SW directly New Feature!
• Automatic or manual downloading
• View event or trended data• Advanced data and statistical analysis• Aggregation• Supports very large systems and databases• Data Manager supports many instruments
from Dranetz-BMI and other manufacturers
EncoreSW
7100 5540 EPQ
Web Browser
Key
Encore Series
Communications
Instrumentation
Visualization
DataBase
Dranetz-BMI Software
61000
Web Browser
PQDIF Files
DV 6.0
NodeLink
Key
Encore Series
Communications
Instrumentation
Visualization
DataBase
Dranetz-BMI Software
PQVIEW PQVIEWDB
Enterprise Software
New Feature!
PQView Encore SW DownloadsEncore
SW
7100 5540 EPQ 61000