elo15
TRANSCRIPT
-
8/10/2019 elo15
1/8
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 54, NO. 2, APRIL 2007 733
Zero-Steady-State-Error Input-Current Controllerfor Regenerative Multilevel Converters Based
on Single-Phase CellsPablo Lezana,Member, IEEE,Csar A. Silva,Member, IEEE,Jos Rodrguez,Senior Member, IEEE,
and Marcelo A. Prez,Member, IEEE
AbstractMulticell converters are one of the alternative topolo-gies for medium-voltage industrial drives. For an applicationrequiring regenerative capability, each power cell must be con-structed with a three- or single-phase pulsewidth-modulation(PWM) rectifier as front end. The choice of single-phase PWMrectifiers for the input of the cells results in a reduced number ofpower switches and a simpler input transformer than the three-phase equivalent. However, its control is not as straightforward.This paper proposes the use of higher order resonant controllersin the classical control structure of the single-phase PWM rectifier.This ensures zero steady-state tracking error of the reference cur-rent at fundamental frequency. A detailed description of the designcriteria for the position of the zeros and poles of the controller isgiven. Experimental results showing the good performance of thesingle-phase input cells and its proposed control are included.
Index TermsMultilevel converter, pulsewidth-modulation(PWM) rectifiers, resonant controller.
I. INTRODUCTION
THE use of medium-voltage variable-speed drives based on
voltage-source converters has become increasingly wide-spread in the last ten years. A wealth of multilevel topologies
has been developed to achieve the medium-voltage range using
available semiconductors [principally, the insulated-gate bipo-
lar transistor (IGBT)] [1]. These topologies also allow for lower
distortion of the output ac voltage of the converter. One of the
alternatives of multilevel topologies is known as a multicell
converter [2] and is based on the series connection of several
single-phase inverters per output phase.
The classical multicell converter [2], using diodes to obtain a
dc-link voltage of each output inverter, is not able to regenerate
power from the load. To achieve regeneration, the use of three-
and single-phase pulsewidth-modulation (PWM) rectifiers hasbeen proposed [3], [4]. These PWM rectifiers produce good-
Manuscript received January 21, 2006; revised December 18, 2006. Abstractpublished on the Internet January 14, 2007. This work was supported in part bythe Universidad Tcnica Federico Santa Mara, in part by the Chilean ResearchCouncil (Conicyt) under Grant Fondecyt 1050357, in part by the MillenniumNucleus on Industrial Electronics and Mechatronics P04048-F (MIDEPLAN),and in part by the postgraduate support program of the Fundacin Andes underGrant C-14055.
The authors are with the Departamento de Electrnica, Universidad TcnicaFederico Santa Mara, 239-0123 Valparaso, Chile (e-mail: [email protected]; [email protected]; [email protected]; [email protected]).
Digital Object Identifier 10.1109/TIE.2007.891994
quality input-current waveforms in addition to their regenera-
tive capability; this allows operation at high power factor (very
near unity).
The use of the three-phase PWM rectifier as the front end
of the cells has some operational advantages but requires more
semiconductors, sensors, and a more complex input transformer
than the single-phase alternative.Another important difference between the three- and single-
phase front-end alternatives is the way in which the current con-
trol is implemented. In three-phase PWM rectifiers, the current
control is normally performed in a synchronous rotating frame,
converting measured ac currents into dc values. This allows the
use of conventional proportionalintegral (PI) controllers for
the current control, achieving zero stationary error [5]. This
technique is not directly applicable in single-phase systems,
resulting in steady-state reference tracking error if PI current
controllers are used. This tracking error affects the current
amplitude and phase, deteriorating the power factor.
The use of resonant controllers in stationary frames have
been proposed for the control of ac currents with zero steady-state tracking error [6][8]. In [6], a proportional + pureresonant element is proposed for current control of three- and
single-phase PWM rectifiers. In [7], the derivation of a resonant
controller through the frequency transformation of a standard
PI controller is proposed for current control of inverters. Both
techniques result in infinite controller gain at the resonant fre-
quency, hence achieving zero steady-state current tracking error
at this frequency without coordinate rotations. Nevertheless,
in both cases, the proposed resonant controllers are somehow
derived from PI structures, resulting in restrictions on the zero
locations, and fail to take full advantage of the design flexibility
of resonant biproper controllers.This paper proposes new controller designs for the single-
phase voltage PWM rectifiers of a multicell inverter for the
classical cascade control structure. These controller designs
consist of a resonant biproper controller for the inner current
loop with unrestricted zero locations and an external voltage
loop closed with a modified PI. The voltage controller includes
the dc-link voltage filter to give a clean sinusoidal reference
for the inner current loop. This configuration ensures a good-
quality input-current waveform and, hence, high-power-factor
operation. A detailed discussion of the controller design criteria
and experimental results that shows their good performance is
presented.
0278-0046/$25.00 2007 IEEE
-
8/10/2019 elo15
2/8
734 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 54, NO. 2, APRIL 2007
Fig. 1. Multicell converter.
II. MULTICELLC ONVERTER
The multicell converter is based on the series connection of
the output of multiple cells. Each cell is composed of an inverterH-bridge fed by an isolated dc supply, as shown in Fig. 1.
With this configuration, the per-phase output voltage of the
converter is
vxN=
ky=1
vxy, x= a, b, c (1)
where vay is the output voltage of the yth cell connected to
phasea.
The classical multicell converter [2] uses a diode bridge
rectifier as the front end of each cell [Fig. 2(a)]. By using a
complex shifted input transformer, this configuration achievescancellation of the lower frequency input-current harmonics.
For an application that requires regeneration, PWM rectifiers
must be used to feed the dc-link of each cell. This additionally
improves the quality of the waveforms of the input current,
allowing operation at a high power factor (very near unity).
There are two main alternatives for the implementation of the
cell PWM rectifiers, namely, three- or single-phase rectifiers,
as proposed in [3] and [4], respectively. Both alternatives are
shown in Fig. 2(b) and (c).
The three-phase front end has some operational advantages:
First, it allows the implementation of the current control in a
synchronous(dq) frame, achieving zero steady-state currenttracking error with simple PI controllers [5]. Second, when op-erating with a sinusoidal input current, it draws constant power
from the mains, producing low voltage ripple in the dc link.
On the other hand, the single-phase front end has advantageous
constructive characteristics: It requires less power semicon-
ductors, less current sensors, and a simpler input transformer.
This makes it an attractive alternative for regenerative multicell
converters where the savings in part count are multiplied by
the number of cells of the converter. For these reasons, this is
the topology considered in this paper. As shown in Fig. 3, the
single-phase PWM voltage-source rectifier uses four controlled
switches in bridge connection in order to produce a controlled
dc-link voltage vDC in capacitor C, by means of controllingsinusoidal input current is in inductor Ls. This is achieved
because the input current can be freely handled by proper con-
trol of switches S1, . . . , S 4, for any condition ofvs, provided
that vDC > vs [9]. This allows any combination of active andreactive power at the input side, even regenerative operation.
The simple construction and the smaller part count of the
multicell converter built with single-phase PWM rectifiers
come at the cost of losing the previously mentioned operationaladvantages of the three-phase implementation. In other words,
the synchronous rotating frame cannot be directly used, and the
rectifiers draw pulsating power from the mains, resulting in a
dc-link voltage ripple at2fs. In the following section, a solutionto the aforementioned difficulties based on the use of resonant
controllers is presented.
III. PROPOSEDC ONTROLLERD ESIGN
A. Cascade Control Scheme
The typical cascade control scheme for the single-phase
active rectifier is shown in Fig. 4. A slow voltage control loop
is used to keep the dc-link voltage constant at a value vDCabove vs. The output of the voltage controller Cv is the valueof the dc current is required by the dc-link capacitor to keepits voltage at reference value v
DC. To obtain the reference
for is, is is multiplied by the desired waveform, which istypically a sinusoid of the same frequency and phase as vs. A
fast control loop is used for the input current (Ci), obtainingthe commanded value for vAFE. This commanded voltage is
converted into drive pulses forS1S4 by a PWM modulator.If the input current is successfully controlled to a sinusoidal
waveform that is in phase with the input voltage, the input
power drawn by the cell is
Pin(t) =issin(st) vssin(st)=is vs
2 [1 cos(2st)] . (2)
From (2), it is noted that the input power has a pulsating
component2fs. This results in a dc-link voltage ripple at thisfrequency. If this ripple is fed back into the control system, iswill also have a harmonic component at 2fs. This results inis having harmonics at fs and 3fs due to the multiplicationof is by sin(2fst). To avoid this harmonic distortion in theinput-current reference (and, hence, in the actual value of the
input current), a power filter in the dc link, a dc-link voltage
measurement filter, or a low cutoff frequency for the voltagecontrol loop must be used.
For high-power-factor operation, a resonant controller is used
asCi in the control scheme of Fig. 4. Additionally, a modified
PI controller for Cv, with additional filtering capability, is
proposed to avoid the detrimental influence of the2fs voltageharmonic in the current reference.
B. Resonant Current Controller
The tuning of this controller is made considering the circuit
shown in Fig. 5 as the plant. Then, the plant transfer function is
is(s) = 1Lss + Rs
(vs(s) vAFE(s)) . (3)
-
8/10/2019 elo15
3/8
LEZANAet al.: ZERO-STEADY-STATE-ERROR INPUT-CURRENT CONTROLLER FOR MULTILEVEL CONVERTERS 735
Fig. 2. Cells for multicell converter: (a) nonregenerative cell and regenerative cell with (b) three-phase PWM rectifier and (c) single-phase PWM rectifier.
Fig. 3. Single-phase PWM rectifier in bridge connection.
Fig. 4. Control scheme for a PWM rectifier.
Fig. 5. Input-current plant.
In this system, the mains voltage vsappear as a disturbance in
the control loop, while the actuation variable is the input voltage
of the cellvAFE.
As discussed in Section III-A, the reference for the current-
control loop is is sinusoidal with frequency fs. For perfect
reference tracking at this frequency, the controller must have
infinite gain atfs, meaning that the controller transfer function
must have two resonant poles at js, where s = 2fs.These poles are equivalent to the pole in s= 0on PI controllersfor tracking of a continuous reference. In addition, in order
to get a fast response, the controller must have a proportional
gain, i.e., the controller transfer function must be biproper.
Therefore, the generalized second-order resonant controller has
the following structure:
Ci(s) = Kps2 + as + b
s2 + 2s(4)
where a, b, and Kpare the controller parameters to be designed.One approach [6], [7] is to design a standard PI controller (5)
for the plant (3) and use a transformation to obtain the resonant
controller, i.e.,
PIi= Kp+
Ki
s . (5)
In [6], the transformation used is
1
s
s
s2 + 2s(6)
leading to
Ci(s) =Kps2 + 2s
1 + Ki
Kp
s2 + 2s
. (7)
This forces the open-loop zeros of the controller to be placed
on the imaginary axis ofs plane, as shown in Fig. 6(a), leadingto a poor phase margin of the closed-loop system.
Better results are obtained in [7] using the transformation
1
s
2s
s2 + 2s. (8)
The controller obtained with this transformation is
Ci(s) =Kps2 + 2 Ki
Kps + 2s
s2 + 2s. (9)
Although, the response of the closed loop using (9) is im-
proved, with respect to that obtained using (7), this techniquealso restricts the location of the open-loop zeros, as shown in
Fig. 6(b). This is a consequence of using the two degrees of
freedom of a PI (Kp and Ki) to adjust the three degrees of
freedom of the resonant structure of (4).
The unrestricted allocation of the zeros of the resonant con-
troller is proposed in this paper, making full use of the degrees
of freedom of (4) to obtain good closed-loop performance, i.e.,
high close-loop bandwidth and good phase margin. The design
of the controller is made directly in zplane in order to obtain an
expression that can be implemented directly in a digital signal
processor (DSP), so (4) is transformed in
Ci(z) = Kp z2
+ 2aiz+ biz2 2cos(sh)z+ 1
(10)
-
8/10/2019 elo15
4/8
736 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 54, NO. 2, APRIL 2007
Fig. 6. Location of open-loop controller zeros (a) according to transformation (6) and (b) according to transformation (8).
Fig. 7. Root locus of the current controller.
Fig. 8. Closed-loop Bode diagram.
where h is the sample period and s is the desired resonant
frequency. The values of the current-controller gain Kp and
the zero locations (determined by constants ai and bi) are
obtained through root-locus analysis, as shown in Fig. 7. In
addition, it can be noted that a pure delay has been included,
in order to model the sample processing time required by
the DSP.
As expected, due to the resonance, the closed-loop Bode
diagram presents perfect reference tracking at fs = 50 Hz,as shown in Fig. 8. The controller resonance also completely
eliminates the effect of the input disturbance produced by thefundamental mains voltage vs. This can be seen on the input-
Fig. 9. Closed-loop Bode diagram for a plant input disturbance.
Fig. 10. DC-link voltage plant.
disturbance Bode diagram of Fig. 9, which exhibits very high
attenuation at frequencyfs. For this reason, there is no need for
a feedforward term to cancel vsin the control loop.
C. Voltage Controller
Due to the fact that the dc-link voltage reference vDC
is con-
stant regardless of the current-control method, the PI controller
is the obvious choice for the voltage control loop. The tuning
of this controller can be done assuming fast response of the
inner current loop. In this way, plantGv can be considered as a
pure capacitorCin parallel with two current sources, as shown
in Fig. 10. The current value iDC is determined by the input
current of the cell and corresponds to the actuation variable. On
the other hand, the current source io is determined by the con-
trolled output current of the inverter H-bridge (output section of
the cell); therefore, it acts as an independent disturbance.
Thus, the transfer function of the plant is
vDC(s) = 1
Cs(iDC io)(s). (11)
In Section III-A, the limit on the bandwidth of the voltage
loop or the filtering of the dc-link measured voltage has been
established as a way to avoid the undesired effects of the dc-linkpulsating voltage, i.e., harmonic distortion and fundamental
-
8/10/2019 elo15
5/8
LEZANAet al.: ZERO-STEADY-STATE-ERROR INPUT-CURRENT CONTROLLER FOR MULTILEVEL CONVERTERS 737
Fig. 11. Root locus of the voltage controller.
Fig. 12. Closed-loop Bode diagram.
phase shift on the input current of the cell. In this section,
the use of a controller that includes the filter characteristic in
its structure is proposed. Although this technique is similar
to the conventional use of an independent filter in the voltage
measurement, the inclusion of the filter poles and zeros as
part of the controller structure increases the design flexibility,
allowing to obtain better performance of the control loop.
The final controller structure is
Cv(z) = Kvz avz 1
z2 2 cos(2sh)z+ 2
z2 + bvz+ cv(12)
where Kv and av are the gain and the zero location of thePI controller, respectively. 2s is the central frequency of theband-stop filter, bv and cv determine the location of the filter
poles, and 1 is a coefficient used to limit the Q-factor ofthe filter.
The design of the PI-controller + filter is illustrated in thez-domain root-locus diagram of Fig. 11. The zeros of the filter,
which are placed near the unit circle to reject the 2fsfrequency,are clearly identifiable. The complex poles are placed near the
filter zeros in order to obtain a narrow-enough filter response.
Finally, the PI zero and gain are chosen with no further con-
sideration than to obtain a sufficiently large bandwidth and
adequate damping factor.
As shown in Fig. 12, the closed-loop Bode diagram presentsperfect tracking at dc and a bandwidth of just below 100 Hz. In
Fig. 13. Antiwindup structure.
addition, Fig. 12 shows an important attenuation at2fs; this iscaused by the filter zeros of the controller at this frequency. As
a result, the actuation iswill be filtered, avoiding the undesired
harmonic distortion on the input-current reference is.
D. Antiwindup Scheme
As in any real plant, the actuation vAFEand isare limited and
can saturate, producing windup of the controllers. Solutions for
this problem are well known for PI controllers. Nevertheless,
for the more complex control structures presented in this paper,
the classical PI antiwindup techniques cannot be used.
An antiwindup technique for any minimum-phase biproper
controller, as control rules (12) and (10), is described in [10]
and will be used for their implementation. The block dia-
gram of Fig. 13 shows the implementation of this antiwindup
scheme, where C(z) is a minimum-phase biproper controllerandc = C(z)|is its dc gain.
If umin < u(t)< umax, the saturation is not active, so thetransfer function for the scheme is
U(z)
E(z) =
c
1 + c [C1(z) c1]
= c
1 + cC1(z) 1= C(z). (13)
Otherwise, when saturation occurs, the states of the con-
troller are always driven by its real output, achieving protection
against windup.
IV. SIMULATIONR ESULTS
To verify correct operation of the proposed control scheme
and to contrast its performance against that of more classical
control structures, a single cell has been simulated using the
software PSIM. The control scheme corresponds to that shown
in Fig. 4 and has been discussed in extenso in Section III-A.
The circuit parameters are those of the experimental prototypedescribed in the following section and are summarized in
Table I. The value of the cells single-phase input voltage used
for the simulation is 50 V peak. For comparison purposes, two
variations on this control structure were simulated: The first one
consists of standard PI controllers for dc-link voltage and input
current. The second alternative is the resonant structure pro-
posed in this paper. In this case, a controller with resonant poles
at the mains frequency is used in the inner current-control loop,
and a PI-controller + filter is used for the voltage loop. Thecurrent resonant controller is tuned with the same direct gain
Kpas the standard current PI and its zeros are located to achieve
the same closed-loop bandwidth of 300 Hz, as shown in Fig. 14.
The 0-dB gain and the 0 phase shift of the resonant controllerat the mains frequency is an improvement with respect to the
-
8/10/2019 elo15
6/8
738 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 54, NO. 2, APRIL 2007
TABLE IPARAMETERS OF THEPOWER CIRCUIT
Fig. 14. Closed-loop Bode diagram of the simulated current loop using bothalternative controllers, namely, standard PI and resonant controller.
amplification (0.59 dB) and lagging phase shift (5) introduced
by the standard PI. Additionally, for voltage control, thesame PI tuned for a closed-loop bandwidth of 80 Hz was
used for both alternative implementations, although a second-
order band-stop filter was included for the resonant structure
voltage PI.
The time response of both alternative controllers, under the
same dc-link voltage reference and load, is shown in Fig. 15.
For the control structure using only standard PI, the current
reference is not perfectly sinusoidal and contains some small
harmonic distortion, as shown in Fig. 15(a). Additionally, this
distorted reference is tracked with the phase lag and a small
amplification as expected from the closed-loop Bode plot
of Fig. 14. On the other hand, the use of the filter in thedc-link voltage controller avoids the distortion on the current
reference, as shown in Fig. 15(b). Furthermore, the resonant
current controller follows this reference without any tracking
error, obtaining the desired high-power-factor operation shown
in this figure.
The effect of the 2fs ripple on the dc-link voltage in bothschemes is better appreciated in the spectral analysis of the
steady-state response shown as the percentage of respective
fundamental reference current in Fig. 16. In the case of the
standard PI, the current reference has a clear third-harmonic
component, which is expected from the partial compensation
of this dc-link voltage variation. This reference is followed by
the current-control loop, causing a 3% third harmonic in theactual input current [Fig. 16(b)]. In the case of the resonant
Fig. 15. Simulated steady-state response of both control structures:(a) standard PI and (b) resonant controller.
Fig. 16. Spectral analysis of the simulated response of the (a) standardPI reference current, (b) standard PI actual current, (c) resonant controllerreference current, and (d) resonant controller actual current.
solution, the filter in the voltage prevents the voltage controllerto react to the 2fs dc-link voltage component, producing apurely sinusoidal current reference and the actual cell input
current, as shown in Fig. 16(c) and (d), respectively.
V. EXPERIMENTALR ESULTS
The proposed control scheme was implemented on a fixed-
point TMS320F2812 DSP and tested on a laboratory proto-
type. The schematic diagram of the power circuit is shown in
Fig. 17 and corresponds to a seven-level single-phase output
multicell converter. The hardware implementation of the de-
scribed converter is shown in Fig. 18. Each board shown in this
figure is built around a PM20CSJ060 Mitsubishi power module.We use 20-A/600-V rated three-phase IGBT bridges, out of
-
8/10/2019 elo15
7/8
LEZANAet al.: ZERO-STEADY-STATE-ERROR INPUT-CURRENT CONTROLLER FOR MULTILEVEL CONVERTERS 739
Fig. 17. Single-phase output prototype multicell converter.
Fig. 18. Hardware implementation of the seven-level single-phase multicellconverter.
which only two output phases are used to form the converterH-bridges. Each board also includes dc-link capacitors, gate
drive circuits, and current and voltage measurements. The
boards are connected back to back in pairs to build a single cell,
and the three cells are series connected to form the converter.
The transformers at the bottom of Fig. 18 are multiple output
transformers used for isolated power supplies for the gate drives
and measurement circuits on each board. This converter is
connected to the network through a Yy0 380/140-V 2.1-kVA
three-phase transformer. The single-phase secondary windings
are connected independently to each cell, and the input voltage
is adjusted by a variable autotransformer to obtain approxi-
mately 55 V peak at the cells input. The main parameters ofthe power circuit, including the equivalent impedance seen at
the connection point of cells Rs and Ls, are listed in Table I.
Finally, the PWM frequency for both the rectifier and the
inverter H-bridge of each cell was set at 4 kHz with a dead time
of 2 s.
The steady-state operation of the multicell converter is shown
in Fig. 19. The characteristic seven-level output voltage and the
resulting sinusoidal load current are shown in Fig. 19(b).
The steady-state input current of the cell is shown in Fig. 19(c).
The good phase relation between this current and the input
voltage is clear from this figure, while the current waveform is
highly sinusoidal, leading to a high-power-factor operation. Fi-
nally, the stationary response of the dc-link voltage [Fig. 19(a)]shows a significant spurious2fs component; nevertheless, this
Fig. 19. Steady-state operation of the multicell converter.
Fig. 20. Transient from loading to regeneration. (a) DC-link voltage. (b) Inputcurrent and voltage.
is expected due to the filtering characteristic of the voltage
controller that avoids reacting to this component. Furthermore,
due to this filtering characteristic, the voltage distortion has no
effect in the phase and harmonic content ofisu, achieving the
high-power-factor operation of Fig. 19(c).
The response to a large load impact, such that the rectifier
goes from consuming power from the mains to regenerating,
is presented in Fig. 20. During operation in rectification mode,
an almost sinusoidal current waveform in phase with the mains
voltage can be observed. When the load impact is applied, thedc-link voltage, as shown in Fig. 20(a), responds with a short
-
8/10/2019 elo15
8/8
740 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 54, NO. 2, APRIL 2007
transient, after which it continues regulating at its reference
value. This is achieved by an inversion of the input-current
reference, which is followed by the current loop without phase
error [Fig. 20(b)]. This result shows the inherent regenerative
characteristic of the converter, the fast response of the proposed
voltage control, and the high-power-factor operation obtained
with the resonant current controllers for both loading andregenerative operation.
VI. CONCLUSION
In this paper, a multicell converter built by the connection of
regenerative cells with single-phase PWM rectifiers has been
made to work with very high power factor. This improved
power factor is achieved by the use of higher order controllers,
i.e., a biproper resonant current controller and a modified PI for
the outer voltage loop. This means that the problems normally
associated with the use of single-phase PWM rectifiers have
been solved purely by careful control design and without any
hardware changes. The structure of the proposed controllers
have been theoretically justified.
The design criteria for the high number of controller
parameters have been given based on root-locus analysis
using computational aided tools. However, it would be possible
to determinate them through recursive methods as genetics
algorithms.
The proposed control strategy, including antiwindup, has
been programmed in a fixed-point DSP and tested experi-
mentally, demonstrating the feasibility of such controllers in
practical implementations.
REFERENCES
[1] J. Rodrguez, J. S. Lai, and F. Z. Peng, Multilevel inverters: A surveyof topologies, controls, and applications, IEEE Trans. Ind. Electron.,vol. 49, no. 49, pp. 724738, Aug. 2002.
[2] P. W. Hammond, A new approach to enhance power quality for mediumvoltage drives, IEEE Trans. Ind. Appl., vol. 33, no. 1, pp. 202208,Jan./Feb. 1997.
[3] J. Espinoza, M. Prez, J. Rodrguez, and P. Lezana, Regenerativemedium-voltage AC drive based on a multi-cell arrangement with min-imum energy storage requirements, IEEE Trans. Ind. Electron., vol. 52,no. 1, pp. 171180, Feb. 2005.
[4] J. Rodrguez, L. Morn, J. Pontt, J. L. Hernndez, L. Silva, C. Silva, andP. Lezana, High-voltage multilevel converter with regeneration capabil-ity,IEEE Trans. Ind. Electron., vol. 49, no. 4, pp. 839846, Aug. 2002.
[5] N. Zargari and G. Joz, Performance investigationof a current-controlledvoltage-regulated PWM rectifier in rotating and stationary frames, IEEE
Trans. Ind. Electron., vol. 42, no. 4, pp. 396401, Aug. 1995.[6] Y. Sato, T. Ishizuka, K. Nezu, and T. Kataoka, A new control strategy
for voltage-type PWM rectifiers to realize zero steady-state control errorin input current, IEEE Trans. Ind. Appl., vol. 34, no. 3, pp. 480486,May/Jun. 1998.
[7] D. N. Zmood and D. G. Holmes, Stationary frame current regulationof PWM inverters with zero steady-state error, IEEE Trans. Power
Electron., vol. 18, no. 3, pp. 814822, May 2003.[8] X. Yuan, W. Merk, and J. Allmeling, Stationary-frame generalized
integrators for current control of active power filters with zero steady-stateerror for current harmonics of concern under unbalanced and distortedoperating conditions, IEEE Trans. Ind. Appl., vol. 38, no. 2, pp. 523532, Mar./Apr. 2002.
[9] J. Rodrguez, P. Lezana, J. Espinoza, M. Prez, and J. Pontt, Inputcurrent harmonics in a regenerative multi-cell inverter with single phaseactive rectifiers, inProc. IEEE IECON, Seville, Espaa, Nov. 58, 2002,
pp. 932937.[10] G. Goodwing, S. Graebe, and M. Salgado, Control System Design.Englewood Cliffs, NJ: Prentice-Hall, 2000.
Pablo Lezana (S06M07) was born in Temuco,Chile, in 1977. He received the M.Sc. and Doc-tor degrees from the Universidad Tcnica FedericoSanta Mara (UTFSM), Valparaso, Chile, in 2005and 2006, respectively.
Since 2006, he has been an Assistant Researcherin the Departamento de Electrnica, UTFSM. Hisresearch interests include power converters and mod-
ern digital control devices (DSPs and FPGAs).
Csar A. Silva (S01M02) was born in Temuco,Chile, in 1972. He received the Civil Electronic En-gineer degree from the Universidad Tcnica FedericoSanta Mara, Valparaso, Chile, in 1998, and thePh.D. degree from the University of Nottingham,Nottingham, U.K., in 2003. He presented his doc-toral thesis on Sensorless Vector Control of Sur-face Mounted Permanent Magnet Machines Without
Restriction of Zero Frequency.Since 2003, he has been a Lecturer in the De-
partment of Electronic Engineering, UniversidadTcnica Federico Santa Mara, where he teaches courses on electric machines,power electronics, and ac machine dives. His research interests include sensor-less vector control of ac machines and control of static converters.
Dr. Silva was granted the Overseas Research Students Awards Scheme tojoin the Power Electronics Machines and Control Group at the University ofNottingham, as a Postgraduate Research Student, in 1999.
Jos Rodrguez (M81S83SM94) received the
Engineer degree from the Universidad TcnicaFederico Santa Mara, Valparaso, Chile, in 1977,and the Dr.-Ing. degree from the University ofErlangen, Nuremberg, Germany, in 1985, both inelectrical engineering.
Since 1977, he has been with the Departamentode Electrnica, Universidad Tcnica Federico SantaMara, where he is currently a Professor and thePresident. During his sabbatical leave in 1996, hewas responsible for the Mining Division, Siemens
Corporation, Providencia, Chile. He has extensive consulting experience inthe mining industry, especially in the application of large drives such ascycloconverter-fed synchronous motors for SAG mills, high-power conveyors,controlled drives for shovels, and power quality issues. He has authoredor coauthored more than 130 refereed journal and conference papers andcontributed to one chapter in the Power Electronics Handbook(Academic,2006). His research interests include power electronics and electrical drives.
In past years, his research interests have included multilevel inverters and newconverter topologies.
Marcelo A. Prez (M07) was born in Concepcin,Chile, in 1976. He received the Engineer degreein electronic engineering, the M.Sc. degree in elec-trical engineering, and the D.Sc. degree in electri-cal engineering from the University of Concepcin,Concepcin, Chile, in 2000, 2003, and 2006,respectively.
He is currently a Postdoctoral Researcher in the
Departamento de Electrnica, Universidad TcnicaFederico Santa Mara, Valparaso, Chile, conductingresearch in the area of power converters.