Electrical Wiring Diagrams by Compressor Series (3) Phase
PWS or Crossline StartHigh Voltage Low Voltage
** W1-U2, V1-W2, U1-V2 = ohm value depending on size and voltage ** Overloads – Thermik (NC contacts) 1-2 = .2 ohms or continuity / Kriwan (130 C PTC) = 160-180 ohms (75 degree F motor)
High Voltage Low Voltage
PWS or Crossline Start
** L1-L2, L1--L3, L2-L3 = ohm value depending on size and voltage (L1-L7, L2-L8, L3-L8) = Open ** L7-L8, L7-L9, L8-L9 = ohm value depending on size and voltage ** Overloads – Thermik (NC contacts) 1-2 = .2 ohms or continuity / Kriwan (130C PTC) = 160-180 ohms (75 degree F motor)
**** Refer to website: www.AmericanHermetics.net to cross reference compressor model # to compressor series
** W1-U2, V1-W2, U1-V2 = ohm value depending on size and voltage ** Overloads – Thermik (NC contacts) 1-2 = .2 ohms or continuity / Kriwan (130 C PTC) = 160-180 ohms (75 degree F motor)
Dorin Series: H11, H1, SCC_1, CDS11, CD200
Dorin Series: H2, H34, H33, H35, CDS35, CD4
Dorin Series: H41, H5, H6, H7, CDS41, CD300, CD400, CD500