ee es 2014 0836 rc_protocolo de pruebas norgener angamos
DESCRIPTION
protocolosTRANSCRIPT
-
AES Gener CHILE
PROTOCOLO DE PRUEBAS DE PSS CT Norgener y Angamos
Proyecto EE-2014-144
Informe Tcnico EE-ES-2014-0836
Revisin C
Power System Studies & Power Plant Field
Testing and Electrical Commissioning
ISO9001:2008 Certified
07/11/2014
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 1/16
Este documento EE-ES-2014-0836-RC fue preparado para AES Gener por Estudios Elctricos.
Para consultas tcnicas respecto del contenido del presente comunicarse con:
Ing. Alejandro Musto
Coordinador Dpto. Estudios
Ing. David Perrone
Departamento de Estudios
www.estudios-electricos.com
Este documento contiene 16 pginas y ha sido guardado por ltima vez el 07/11/2014 por
David Perrone, sus versiones y firmantes digitales se indican a continuacin:
Rev Fecha Comentario Realiz Revis Aprob
A 22/10/2014 Para revisin. DP AM FL
B 23/10/2014 Mayor detalle pruebas durante
interconexin SADI-SING. DP AM FL
C 07/11/2014 Mayor detalle, traduccin de pruebas a
ingls. DP AM FL
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 2/16
ndice
1 INTRODUCCIN ............................................................................................................................. 3
2 TAREAS / Tasks .............................................................................................................................. 4
2.1 CARTA GANTT ........................................................................................................................... 4
3 CT ANGAMOS ................................................................................................................................. 5
3.1 Curva de Carga (Load Profile) ..................................................................................................... 5
3.2 Measurement of local mode damping ........................................................................................... 6
3.3 Effects of variation in the mechanical power .................................................................................. 7
3.4 Maximum Gain .......................................................................................................................... 8
4 CT NORGENER ............................................................................................................................... 9
4.1 Curva de Carga (Load Profile) ..................................................................................................... 9
4.2 No-load test ............................................................................................................................ 10
4.3 Measurement of local mode damping ......................................................................................... 11
4.4 Effects of variation in the mechanical power ................................................................................ 12
4.5 Maximum Gain ........................................................................................................................ 13
5 Interconexin SADI-SING .............................................................................................................. 14
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 3/16
1 INTRODUCCIN
El presente documento establece el protocolo de pruebas a realizar en las centrales
NORGENER y ANGAMOS, con el objeto de re-ajustar y validar los parmetros de cada estabilizador
de sistemas de potencia (PSS), optimizando su capacidad de amortiguamiento a baja frecuencia;
especficamente en el rango de 0,25 a 0,35Hz.
Los nuevos parmetros a implementar derivan de un estudio de ajuste robusto de
estabilizadores, documentado en el informe tcnico EE-ES-2014-0888.
La eficacia de estos nuevos ajustes ser finalmente validada a travs de las pruebas de
interconexin SING-SADI, ya que dicha interconexin promover oscilaciones de potencia de modo
interrea del orden de 0,3Hz. Estas pruebas sern realizadas luego del reajuste de los
estabilizadores y contemplando distintos niveles de ganancias en los mismos.
Para el desarrollo de los reajustes y pruebas en terreno, se contempla una planificacin
conservadora de un da por cada unidad. Para esto, Estudios Elctricos pondr a disposicin en
planta al mismo especialista desarrolle los estudios previos de ajuste, para brindar soporte y
supervisar la implementacin de los ajustes.
This document establishes the protocol for the test to be performed in ANGAMOS and NORGENER
plants in order to re-adjust and validate the parameters of each power system stabilizer (PSS),
optimizing damping capacity at low frequency; specifically in the range of 0.25 to 0,35Hz.
The new parameters derived from a study of robust adjustment stabilizers; document ID EE-ES-
2014-0888.
The effectiveness of these new settings will eventually be validated through testing interconnection
SING-SADI, as this will promote interconnection of interarea power oscillation mode 0,3Hz order.
These tests will be made after the readjustment of the stabilizers and considering different levels
of gains in them.
For the development of the adjustments and field testing, a conservative planning a day
contemplated by each unit. An Estudios Elctricos engineer will be on site to support and supervise
the implementation of the adjustments.
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 4/16
2 TAREAS / Tasks
El proyecto de reajuste de estabilizadores contempla las siguientes tareas en campo:
The stabilizers readjustment project includes the following tasks:
CT ANGAMOS
o ANSALDO: Ensayos, registros y modificacin de ajustes de los estabilizadores
conforme a los ajustes resultantes de los estudios. Tests, records and modifying stabilizers settings according to the adjustments resulting from the studies.
o ESTUDIOS ELCTRICOS: Provisin de ajustes y supervisin de pruebas. Settings supply and test supervision.
o AES GENER: Soporte en sitio. Site support
CT NORGENER
o MITSUBISHI: Ensayos, registros y modificacin de ajustes del regulador de tensin
y los estabilizadores conforme a los ajustes resultantes de los estudios. Tests,
records and modifying stabilizers and voltage regulator settings according to the
adjustments resulting from the studies.
o ESTUDIOS ELCTRICOS: Provisin de ajustes y supervisin de pruebas. Settings
supply and test supervision.
o AES GENER: Soporte en sitio. Site support
2.1 CARTA GANTT
Fecha / Date LUNES
17/11/2014 MARTES
18/11/2014 MIRCOLES 19/11/2014
JUEVES 20/11/2014
VIERNES 21/11/2014
SBADO 22/11/2014
Da / ay 1 2 3 4 5 6
Lugar Place
Tareas Tasks
PSS ANGAMOS U1 y U2
AVR y PSS NORGENER U1 y U2
RESERVA SPARE
PRUEBAS TESTS SADI-SING
CT ANGAMOS
T.A. ANSALDO (EXECUTION)
Ajustes y registros. Test U1 y U2
- - - Registros Record
Estudios Elctricos (SUPERVISION)
Supervisin - - - Supervisin
CT NORGENER
T.A. MITSUBISHI (EXECUTION)
- - Ajustes y registros.
Test U1 y U2 -
Registros Record
Estudios Elctricos (SUPERVISION)
- - Supervisin - Supervisin
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 5/16
3 CT ANGAMOS
3.1 Curva de Carga (Load Profile)
Durante los das 1 y 2 se evaluarn las unidades ANGAMOS U1 y U2. Se prev la evaluacin
de una unidad por da conforme al siguiente diagrama de carga.
On days 1 and 2 ANGAMOS units U1 and U2 will be evaluated. Evaluation of one unit per day
according to the following load profile, is expected.
-100
-50
0
50
100
150
200
250
300
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
ANGAMOS - Diagrama de Carga (Load Profile)
P (MW) Q (MVAr)
Testing schedule
Hora P (MW) Q (MVAr) Tipo de Prueba Detalles
Time [h] Active Reactive Test Details
1 260 0 - Operacin prevista / Scheduled dispatch
2 260 0 - Operacin prevista / Scheduled dispatch
3 260 0 - Operacin prevista / Scheduled dispatch
4 260 0 - Operacin prevista / Scheduled dispatch
5 260 0 - Operacin prevista / Scheduled dispatch
6 260 0 - Operacin prevista / Scheduled dispatch
7 195 0 Preparacin / Preparation Reduccin / Reduction
8 130 0 Carga / Load Calibracin PSS / PSS setting
9 130 -80 Carga / Load Pruebas PSS - SUB / PSS Test - Underexcitation
10 130 100 Carga / Load Pruebas PSS - SOB / PSS Test - Overexcitation
11 130 0 Carga / Load Pruebas PSS - MAX G / PSS Test - Max Gain
12 260 0 Carga / Load Pruebas PSS - RAMP PM/ PSS Test - Mechanical Power Ramp
13 260 -80 Carga / Load Pruebas PSS - SUB / PSS Test - Underexcitation
14 260 100 Carga / Load Pruebas PSS - SOB / PSS Test - Overexcitation
15 195 0 Carga / Load Pruebas PSS - RAMP PM/ PSS Test - Mechanical Power Ramp
16 260 0 Carga / Load Finalizacin/End
17 260 0 - Operacin prevista / Scheduled dispatch
18 260 0 - Operacin prevista / Scheduled dispatch
19 260 0 - Operacin prevista / Scheduled dispatch
20 260 0 - Operacin prevista / Scheduled dispatch
21 260 0 - Operacin prevista / Scheduled dispatch
22 260 0 - Operacin prevista / Scheduled dispatch
23 260 0 - Operacin prevista / Scheduled dispatch
24 260 0 - Operacin prevista / Scheduled dispatch
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 6/16
3.2 Measurement of local mode damping
Temporal Response of the Control Loop tests are used to verify the PSS when the generator
is on load.
Preliminary conditions: The unit must be connected to the system, loaded, without oscillations
from the network and dispatched in the operating conditions listed below. The AVR must be in
voltage control mode.
Tests development: Step changes shall be applied in the AVR voltage reference for the
following conditions of operation:
Test Voltage
[%]
Active
Power
[%]
Reactive
Power Step [%]
Length
[sec] PSS
1* ~100 ML or IL 0 2 120 ON
2 ~100 ML or IL 0 2 120 OFF
3 ~100 ML or IL (+) -2 120 ON
4 ~100 ML or IL (+) -2 120 OFF
5 ~100 ML or IL (-) 2 120 ON
6 ~100 ML or IL (-) 2 120 OFF *Test 1 will be performed for several PSS Gain levels, from cero to the value define in the studies. Other PSS settings could
be change according to the actual response of the unit.
Notes:
FL: active power near to full load (maximum achievable at test's day)
IL: intermediate value between FL and ML
ML: minimum load (minimum stable working point) The generator terminal voltage shall be as close as possible to 100% of its nominal value. Reactive Power: (+) indicates overexcited operating conditions near the limit of
overexcitation. Reactive Power: (-) indicates underexcited operating conditions near the limit of
underexcitation. Step 2%: the value may be adjusted depending on system conditions.
Electrical signals to be recorded:
1. Applied pulse 2. Terminal voltage 3. Field (excitation) voltage 4. Field (excitation) current 5. Active Power 6. Reactive Power 7. Frequency 8. PSS output 9. Additional signals of the control system
The list of tests is a reference, the EE team leader will decide on site whether is necessary to add
or omit any.
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 7/16
3.3 Effects of variation in the mechanical power
The objective of this test is to verify that the settings of the filters and the design of PSS
allows to minimize the effect on the output of PSS of rapid variations in mechanical power.
Preliminary conditions: the unit must be connected to the system, without oscillations from
the network. The AVR must be in voltage control mode.
Tests development: When the unit is operating at 75% of its nominal active power, the
active power of the unit shall be increased up to 100% of its capacity according in the following
conditions:
Test Voltage
[%]
Active
Power
[%]
Reactive
Power
Loading
[%] PSS
1 ~100 75 0 25 ON
2 ~100 75 0 25 OFF
The loading process must be performed at the highest ramp rate that can be selected by the
operator. The list of tests is a reference, the EE team leader will decide on site whether is necessary
to add or omit any test.
Electrical signals to be recorded:
1. Terminal voltage 2. Field (excitation) voltage 3. Field (excitation) current 4. Active Power 5. Reactive Power 6. Frequency 7. PSS output 8. Additional signals of the control system
The list of tests is a reference, the EE team leader will decide on site whether is necessary to add
or omit any.
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 8/16
3.4 Maximum Gain
The objective of this test is to determine the maximum gain of the PSS and verify that it
keeps a proper stability margin.
Preliminary conditions: The unit must be connected to the grid, without oscillations from
the network. The AVR must be in voltage control mode.
Tests development: The gain of the PSS shall be gradually increased until high frequency
poorly damped oscillations are observed on terminal voltage and/or field current. This value gain
must be recorded as limit
Test Voltage
[%]
Active
Power[%]
Reactive
Power PSS
2 ~100 FL or IL
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 9/16
4 CT NORGENER
4.1 Curva de Carga (Load Profile)
Durante los das 3 y 4 se evaluarn las unidades NORGENER U1 y U2. Se prev la evaluacin
de una unidad por da conforme al siguiente diagrama de carga.
On days 3 and 4 NORGENER units U1 and U2 will be evaluated. Evaluation of one unit per
day according to the following load profile, is expected.
-40
-20
0
20
40
60
80
100
120
140
160
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
NORGENER - Diagrama de Carga (Load Profile)
P (MW) Q (MVAr)
Hora P (MW) Q (MVAr) Tipo de Prueba Detalles
Time [h] Active Reactive Test Details
1 135 0 - Operacin prevista / Scheduled dispatch
2 135 0 - Operacin prevista / Scheduled dispatch
3 135 0 - Operacin prevista / Scheduled dispatch
4 135 0 - Operacin prevista / Scheduled dispatch
5 135 0 - Operacin prevista / Scheduled dispatch
6 135 0 - Operacin prevista / Scheduled dispatch
7 67,5 0 Preparacin / Preparation Reduccin / Reduction
8 0 0 Vaco (FSNL*) Ajuste AVR / AVR Setting
9 0 0 Vaco (FSNL*) Ajuste AVR / AVR Setting
10 67,5 0 Carga / Load Calibracin PSS / PSS setting
11 67,5 -20 Carga / Load Pruebas PSS - SUB / PSS Test - Underexcitation
12 67,5 50 Carga / Load Pruebas PSS - SOB / PSS Test - Overexcitation
13 67,5 0 Carga / Load Pruebas PSS - MAX G / PSS Test - Max Gain
14 135 0 Carga / Load Pruebas PSS - RAMP PM/ PSS Test - Mechanical Power Ramp
15 135 -20 Carga / Load Pruebas PSS - SUB / PSS Test - Underexcitation
16 135 50 Carga / Load Pruebas PSS - SOB / PSS Test - Overexcitation
17 101,5 0 Carga / Load Pruebas PSS - RAMP PM/ PSS Test - Mechanical Power Ramp
18 135 0 Carga / Load Finalizacin/End
19 135 0 - Operacin prevista / Scheduled dispatch
20 135 0 - Operacin prevista / Scheduled dispatch
21 135 0 - Operacin prevista / Scheduled dispatch
22 135 0 - Operacin prevista / Scheduled dispatch
23 135 0 - Operacin prevista / Scheduled dispatch
24 135 0 - Operacin prevista / Scheduled dispatch
*FULL SPEED NO LOAD
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 10/16
4.2 No-load test
Temporal Response of the Excitation Control Loop tests are made to verify the performance
of the voltage regulation when the generator working at full speed no load (FSNL).
Preliminary conditions: The unit shall be spinning at nominal speed. The terminal voltage of
the unit shall be at its nominal value and the unit shall be disconnected from the grid. The AVR
must be in voltage control mode.
Tests development: Step changes shall be applied to the AVR reference voltage in the following
operation conditions:
Test Voltage
[%]
Step
[%]
Length
[sec]
1* 100 5 20
2 90 5 20
*Test 1 will be performed for several AVR Gain levels, from the current value to at least half of it.
Then it would be set to the value define in the studies.
The list of tests is a reference, the EE team leader will decide on site whether is necessary to add
or omit any test.
Electrical signals to be recorded:
1. The applied pulse.
2. The terminal voltage. 3. The field (excitation) voltage. 4. The field (excitation) current. 5. Additional signals of the control system
The list of tests is a reference, the EE team leader will decide on site whether is necessary to add
or omit any.
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 11/16
4.3 Measurement of local mode damping
Temporal Response of the Control Loop tests are used to verify the PSS when the generator
is on load.
Preliminary conditions: The unit must be connected to the system, loaded, without oscillations
from the network and dispatched in the operating conditions listed below. The AVR must be in
voltage control mode.
Tests development: Step changes shall be applied in the AVR voltage reference for the
following conditions of operation:
Test Voltage
[%]
Active
Power
[%]
Reactive
Power Step [%]
Length
[sec] PSS
1* ~100 ML or IL 0 2 120 ON
2 ~100 ML or IL 0 2 120 OFF
3 ~100 ML or IL (+) -2 120 ON
4 ~100 ML or IL (+) -2 120 OFF
5 ~100 ML or IL (-) 2 120 ON
6 ~100 ML or IL (-) 2 120 OFF *Test 1 will be performed for several PSS Gain levels, from cero to the value define in the studies. Other PSS settings could
be change according to the actual response of the unit.
Notes:
FL: active power near to full load (maximum achievable at test's day)
IL: intermediate value between FL and ML
ML: minimum load (minimum stable working point) The generator terminal voltage shall be as close as possible to 100% of its nominal value. Reactive Power: (+) indicates overexcited operating conditions near the limit of
overexcitation. Reactive Power: (-) indicates underexcited operating conditions near the limit of
underexcitation. Step 2%: the value may be adjusted depending on system conditions.
Electrical signals to be recorded:
1. Applied pulse 2. Terminal voltage 3. Field (excitation) voltage 4. Field (excitation) current 5. Active Power 6. Reactive Power 7. Frequency 8. PSS output 9. Additional signals of the control system
The list of tests is a reference, the EE team leader will decide on site whether is necessary to add
or omit any.
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 12/16
4.4 Effects of variation in the mechanical power
The objective of this test is to verify that the settings of the filters and the design of PSS
allows to minimize the effect on the output of PSS of rapid variations in mechanical power.
Preliminary conditions: the unit must be connected to the system, without oscillations from
the network. The AVR must be in voltage control mode.
Tests development: When the unit is operating at 75% of its nominal active power, the
active power of the unit shall be increased up to 100% of its capacity according in the following
conditions:
Test Voltage
[%]
Active
Power
[%]
Reactive
Power
Loading
[%] PSS
1 ~100 75 0 25 ON
2 ~100 75 0 25 OFF
The loading process must be performed at the highest ramp rate that can be selected by the
operator. The list of tests is a reference, the EE team leader will decide on site whether is necessary
to add or omit any test.
Electrical signals to be recorded:
1. Terminal voltage 2. Field (excitation) voltage 3. Field (excitation) current 4. Active Power 5. Reactive Power 6. Frequency 7. PSS output 8. Additional signals of the control system
The list of tests is a reference, the EE team leader will decide on site whether is necessary to add
or omit any.
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 13/16
4.5 Maximum Gain
The objective of this test is to determine the maximum gain of the PSS and verify that it
keeps a proper stability margin.
Preliminary conditions: The unit must be connected to the grid, without oscillations from
the network. The AVR must be in voltage control mode.
Tests development: The gain of the PSS shall be gradually increased until high frequency
poorly damped oscillations are observed on terminal voltage and/or field current. This value gain
must be recorded as limit
Test Voltage
[%]
Active
Power[%]
Reactive
Power PSS
2 ~100 FL or IL
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 14/16
5 Interconexin SADI-SING
El da 6 se prevn las pruebas de vinculacin SADI-SING. En funcin de los requerimientos
de CAMMESA y CDEC se realizarn pruebas contemplando distintos niveles de transferencia por la
vinculacin SADI-SING y ajustes de ganancias en los estabilizadores de las 4 (cuatro) unidades en
estudio.
Para contemplar un comportamiento seguro de la red se propone que las pruebas de variacin
de ganancia de los estabilizadores se realicen conforme se describe en la siguiente curva de
transferencia y nivel de ganancia de los estabilizadores.
On day 6th SADI-SING interconnection is expected. According to the transmission system
operators different power transfer levels and PSS gains are to be tested. The following power
transfer and PSS Gain settings curve is proposed.
0
20
40
60
80
100
120
140
160
INTERCONECTION TESTS
P [MW]SING->SADI
PSS Gain [% Setting]
Security limit,cero gain if possible
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 15/16
Durante las pruebas de interconexin SADI-SING se debern registrar en cada unidad en
estudio, las seales:
1. Tensin en bornes generador
2. La tensin de campo del generador o campo de la excitatriz
3. La corriente de campo del generador o campo de la excitatriz
4. Potencia Activa
5. Potencia Reactiva
6. Frecuencia
7. Seal de salida del PSS
8. Otras variables definidas en campo
During the tests the following variables should be recorded in each unit:
1. Terminal voltage
2. Field (excitation) voltage
3. Field (excitation) current
4. Active Power
5. Reactive Power
6. Frequency
7. PSS output
8. Additional signals of the control system
P [MW]
SING->SADI
PSS Gain
[% Setting]Comentarios / comments
0 100 Enlace Abierto / Tie Open
0 100 Enlace Cerrado / Tie Closed
0 100 Enlace Cerrado / Tie Closed
50 100 Aumento transferencia / Increase transfer
50 100 Registros / Record
100 100 Aumento transferencia / Increase transfer
100 50 Reduccin Ganancia PSS / PSS Gain Reduction
100 0 Reduccin Ganancia PSS / PSS Gain Reduction
100 100 Reestablecimiento de ganancia / Restore Gain
150 100 Aumento transferencia / Increase transfer
150 100 Registros / Record
100 100 Reduccin transferencia / Decrease transfer
50 100 Reduccin transferencia / Decrease transfer
0 100 Fin / End
0 100 Enlace Abierto / Tie Open
-
Tel +54 341 4516 422 www.estudios-electricos.com
Ir al ndice
P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por
escrito de ESTUDIOS ELECTRICOS S.A. 16/16
Esta pgina ha sido intencionalmente dejada en blanco
1 INTRODUCCIN2 TAREAS / Tasks2.1 CARTA GANTT
3 CT ANGAMOS3.1 Curva de Carga (Load Profile)3.2 Measurement of local mode damping3.3 Effects of variation in the mechanical power3.4 Maximum Gain
4 CT NORGENER4.1 Curva de Carga (Load Profile)4.2 No-load test4.3 Measurement of local mode damping4.4 Effects of variation in the mechanical power4.5 Maximum Gain
5 Interconexin SADI-SING
David Perrone2014-11-07T17:41:47-0300RosarioFirma informe
Alejandro Musto2014-11-07T17:41:48-0300RosarioFirma informe
Fernando Libonati2014-11-07T17:41:49-0300RosarioFirma informe