ee es 2014 0836 rc_protocolo de pruebas norgener angamos

17
AES Gener CHILE PROTOCOLO DE PRUEBAS DE PSS CT Norgener y Angamos Proyecto EE-2014-144 Informe Técnico EE-ES-2014-0836 Revisión C Power System Studies & Power Plant Field Testing and Electrical Commissioning ISO9001:2008 Certified 07/11/2014

Upload: rigoberto-urrutia

Post on 30-Sep-2015

9 views

Category:

Documents


4 download

DESCRIPTION

protocolos

TRANSCRIPT

  • AES Gener CHILE

    PROTOCOLO DE PRUEBAS DE PSS CT Norgener y Angamos

    Proyecto EE-2014-144

    Informe Tcnico EE-ES-2014-0836

    Revisin C

    Power System Studies & Power Plant Field

    Testing and Electrical Commissioning

    ISO9001:2008 Certified

    07/11/2014

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 1/16

    Este documento EE-ES-2014-0836-RC fue preparado para AES Gener por Estudios Elctricos.

    Para consultas tcnicas respecto del contenido del presente comunicarse con:

    Ing. Alejandro Musto

    Coordinador Dpto. Estudios

    [email protected]

    Ing. David Perrone

    Departamento de Estudios

    [email protected]

    www.estudios-electricos.com

    Este documento contiene 16 pginas y ha sido guardado por ltima vez el 07/11/2014 por

    David Perrone, sus versiones y firmantes digitales se indican a continuacin:

    Rev Fecha Comentario Realiz Revis Aprob

    A 22/10/2014 Para revisin. DP AM FL

    B 23/10/2014 Mayor detalle pruebas durante

    interconexin SADI-SING. DP AM FL

    C 07/11/2014 Mayor detalle, traduccin de pruebas a

    ingls. DP AM FL

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 2/16

    ndice

    1 INTRODUCCIN ............................................................................................................................. 3

    2 TAREAS / Tasks .............................................................................................................................. 4

    2.1 CARTA GANTT ........................................................................................................................... 4

    3 CT ANGAMOS ................................................................................................................................. 5

    3.1 Curva de Carga (Load Profile) ..................................................................................................... 5

    3.2 Measurement of local mode damping ........................................................................................... 6

    3.3 Effects of variation in the mechanical power .................................................................................. 7

    3.4 Maximum Gain .......................................................................................................................... 8

    4 CT NORGENER ............................................................................................................................... 9

    4.1 Curva de Carga (Load Profile) ..................................................................................................... 9

    4.2 No-load test ............................................................................................................................ 10

    4.3 Measurement of local mode damping ......................................................................................... 11

    4.4 Effects of variation in the mechanical power ................................................................................ 12

    4.5 Maximum Gain ........................................................................................................................ 13

    5 Interconexin SADI-SING .............................................................................................................. 14

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 3/16

    1 INTRODUCCIN

    El presente documento establece el protocolo de pruebas a realizar en las centrales

    NORGENER y ANGAMOS, con el objeto de re-ajustar y validar los parmetros de cada estabilizador

    de sistemas de potencia (PSS), optimizando su capacidad de amortiguamiento a baja frecuencia;

    especficamente en el rango de 0,25 a 0,35Hz.

    Los nuevos parmetros a implementar derivan de un estudio de ajuste robusto de

    estabilizadores, documentado en el informe tcnico EE-ES-2014-0888.

    La eficacia de estos nuevos ajustes ser finalmente validada a travs de las pruebas de

    interconexin SING-SADI, ya que dicha interconexin promover oscilaciones de potencia de modo

    interrea del orden de 0,3Hz. Estas pruebas sern realizadas luego del reajuste de los

    estabilizadores y contemplando distintos niveles de ganancias en los mismos.

    Para el desarrollo de los reajustes y pruebas en terreno, se contempla una planificacin

    conservadora de un da por cada unidad. Para esto, Estudios Elctricos pondr a disposicin en

    planta al mismo especialista desarrolle los estudios previos de ajuste, para brindar soporte y

    supervisar la implementacin de los ajustes.

    This document establishes the protocol for the test to be performed in ANGAMOS and NORGENER

    plants in order to re-adjust and validate the parameters of each power system stabilizer (PSS),

    optimizing damping capacity at low frequency; specifically in the range of 0.25 to 0,35Hz.

    The new parameters derived from a study of robust adjustment stabilizers; document ID EE-ES-

    2014-0888.

    The effectiveness of these new settings will eventually be validated through testing interconnection

    SING-SADI, as this will promote interconnection of interarea power oscillation mode 0,3Hz order.

    These tests will be made after the readjustment of the stabilizers and considering different levels

    of gains in them.

    For the development of the adjustments and field testing, a conservative planning a day

    contemplated by each unit. An Estudios Elctricos engineer will be on site to support and supervise

    the implementation of the adjustments.

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 4/16

    2 TAREAS / Tasks

    El proyecto de reajuste de estabilizadores contempla las siguientes tareas en campo:

    The stabilizers readjustment project includes the following tasks:

    CT ANGAMOS

    o ANSALDO: Ensayos, registros y modificacin de ajustes de los estabilizadores

    conforme a los ajustes resultantes de los estudios. Tests, records and modifying stabilizers settings according to the adjustments resulting from the studies.

    o ESTUDIOS ELCTRICOS: Provisin de ajustes y supervisin de pruebas. Settings supply and test supervision.

    o AES GENER: Soporte en sitio. Site support

    CT NORGENER

    o MITSUBISHI: Ensayos, registros y modificacin de ajustes del regulador de tensin

    y los estabilizadores conforme a los ajustes resultantes de los estudios. Tests,

    records and modifying stabilizers and voltage regulator settings according to the

    adjustments resulting from the studies.

    o ESTUDIOS ELCTRICOS: Provisin de ajustes y supervisin de pruebas. Settings

    supply and test supervision.

    o AES GENER: Soporte en sitio. Site support

    2.1 CARTA GANTT

    Fecha / Date LUNES

    17/11/2014 MARTES

    18/11/2014 MIRCOLES 19/11/2014

    JUEVES 20/11/2014

    VIERNES 21/11/2014

    SBADO 22/11/2014

    Da / ay 1 2 3 4 5 6

    Lugar Place

    Tareas Tasks

    PSS ANGAMOS U1 y U2

    AVR y PSS NORGENER U1 y U2

    RESERVA SPARE

    PRUEBAS TESTS SADI-SING

    CT ANGAMOS

    T.A. ANSALDO (EXECUTION)

    Ajustes y registros. Test U1 y U2

    - - - Registros Record

    Estudios Elctricos (SUPERVISION)

    Supervisin - - - Supervisin

    CT NORGENER

    T.A. MITSUBISHI (EXECUTION)

    - - Ajustes y registros.

    Test U1 y U2 -

    Registros Record

    Estudios Elctricos (SUPERVISION)

    - - Supervisin - Supervisin

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 5/16

    3 CT ANGAMOS

    3.1 Curva de Carga (Load Profile)

    Durante los das 1 y 2 se evaluarn las unidades ANGAMOS U1 y U2. Se prev la evaluacin

    de una unidad por da conforme al siguiente diagrama de carga.

    On days 1 and 2 ANGAMOS units U1 and U2 will be evaluated. Evaluation of one unit per day

    according to the following load profile, is expected.

    -100

    -50

    0

    50

    100

    150

    200

    250

    300

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

    ANGAMOS - Diagrama de Carga (Load Profile)

    P (MW) Q (MVAr)

    Testing schedule

    Hora P (MW) Q (MVAr) Tipo de Prueba Detalles

    Time [h] Active Reactive Test Details

    1 260 0 - Operacin prevista / Scheduled dispatch

    2 260 0 - Operacin prevista / Scheduled dispatch

    3 260 0 - Operacin prevista / Scheduled dispatch

    4 260 0 - Operacin prevista / Scheduled dispatch

    5 260 0 - Operacin prevista / Scheduled dispatch

    6 260 0 - Operacin prevista / Scheduled dispatch

    7 195 0 Preparacin / Preparation Reduccin / Reduction

    8 130 0 Carga / Load Calibracin PSS / PSS setting

    9 130 -80 Carga / Load Pruebas PSS - SUB / PSS Test - Underexcitation

    10 130 100 Carga / Load Pruebas PSS - SOB / PSS Test - Overexcitation

    11 130 0 Carga / Load Pruebas PSS - MAX G / PSS Test - Max Gain

    12 260 0 Carga / Load Pruebas PSS - RAMP PM/ PSS Test - Mechanical Power Ramp

    13 260 -80 Carga / Load Pruebas PSS - SUB / PSS Test - Underexcitation

    14 260 100 Carga / Load Pruebas PSS - SOB / PSS Test - Overexcitation

    15 195 0 Carga / Load Pruebas PSS - RAMP PM/ PSS Test - Mechanical Power Ramp

    16 260 0 Carga / Load Finalizacin/End

    17 260 0 - Operacin prevista / Scheduled dispatch

    18 260 0 - Operacin prevista / Scheduled dispatch

    19 260 0 - Operacin prevista / Scheduled dispatch

    20 260 0 - Operacin prevista / Scheduled dispatch

    21 260 0 - Operacin prevista / Scheduled dispatch

    22 260 0 - Operacin prevista / Scheduled dispatch

    23 260 0 - Operacin prevista / Scheduled dispatch

    24 260 0 - Operacin prevista / Scheduled dispatch

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 6/16

    3.2 Measurement of local mode damping

    Temporal Response of the Control Loop tests are used to verify the PSS when the generator

    is on load.

    Preliminary conditions: The unit must be connected to the system, loaded, without oscillations

    from the network and dispatched in the operating conditions listed below. The AVR must be in

    voltage control mode.

    Tests development: Step changes shall be applied in the AVR voltage reference for the

    following conditions of operation:

    Test Voltage

    [%]

    Active

    Power

    [%]

    Reactive

    Power Step [%]

    Length

    [sec] PSS

    1* ~100 ML or IL 0 2 120 ON

    2 ~100 ML or IL 0 2 120 OFF

    3 ~100 ML or IL (+) -2 120 ON

    4 ~100 ML or IL (+) -2 120 OFF

    5 ~100 ML or IL (-) 2 120 ON

    6 ~100 ML or IL (-) 2 120 OFF *Test 1 will be performed for several PSS Gain levels, from cero to the value define in the studies. Other PSS settings could

    be change according to the actual response of the unit.

    Notes:

    FL: active power near to full load (maximum achievable at test's day)

    IL: intermediate value between FL and ML

    ML: minimum load (minimum stable working point) The generator terminal voltage shall be as close as possible to 100% of its nominal value. Reactive Power: (+) indicates overexcited operating conditions near the limit of

    overexcitation. Reactive Power: (-) indicates underexcited operating conditions near the limit of

    underexcitation. Step 2%: the value may be adjusted depending on system conditions.

    Electrical signals to be recorded:

    1. Applied pulse 2. Terminal voltage 3. Field (excitation) voltage 4. Field (excitation) current 5. Active Power 6. Reactive Power 7. Frequency 8. PSS output 9. Additional signals of the control system

    The list of tests is a reference, the EE team leader will decide on site whether is necessary to add

    or omit any.

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 7/16

    3.3 Effects of variation in the mechanical power

    The objective of this test is to verify that the settings of the filters and the design of PSS

    allows to minimize the effect on the output of PSS of rapid variations in mechanical power.

    Preliminary conditions: the unit must be connected to the system, without oscillations from

    the network. The AVR must be in voltage control mode.

    Tests development: When the unit is operating at 75% of its nominal active power, the

    active power of the unit shall be increased up to 100% of its capacity according in the following

    conditions:

    Test Voltage

    [%]

    Active

    Power

    [%]

    Reactive

    Power

    Loading

    [%] PSS

    1 ~100 75 0 25 ON

    2 ~100 75 0 25 OFF

    The loading process must be performed at the highest ramp rate that can be selected by the

    operator. The list of tests is a reference, the EE team leader will decide on site whether is necessary

    to add or omit any test.

    Electrical signals to be recorded:

    1. Terminal voltage 2. Field (excitation) voltage 3. Field (excitation) current 4. Active Power 5. Reactive Power 6. Frequency 7. PSS output 8. Additional signals of the control system

    The list of tests is a reference, the EE team leader will decide on site whether is necessary to add

    or omit any.

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 8/16

    3.4 Maximum Gain

    The objective of this test is to determine the maximum gain of the PSS and verify that it

    keeps a proper stability margin.

    Preliminary conditions: The unit must be connected to the grid, without oscillations from

    the network. The AVR must be in voltage control mode.

    Tests development: The gain of the PSS shall be gradually increased until high frequency

    poorly damped oscillations are observed on terminal voltage and/or field current. This value gain

    must be recorded as limit

    Test Voltage

    [%]

    Active

    Power[%]

    Reactive

    Power PSS

    2 ~100 FL or IL

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 9/16

    4 CT NORGENER

    4.1 Curva de Carga (Load Profile)

    Durante los das 3 y 4 se evaluarn las unidades NORGENER U1 y U2. Se prev la evaluacin

    de una unidad por da conforme al siguiente diagrama de carga.

    On days 3 and 4 NORGENER units U1 and U2 will be evaluated. Evaluation of one unit per

    day according to the following load profile, is expected.

    -40

    -20

    0

    20

    40

    60

    80

    100

    120

    140

    160

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

    NORGENER - Diagrama de Carga (Load Profile)

    P (MW) Q (MVAr)

    Hora P (MW) Q (MVAr) Tipo de Prueba Detalles

    Time [h] Active Reactive Test Details

    1 135 0 - Operacin prevista / Scheduled dispatch

    2 135 0 - Operacin prevista / Scheduled dispatch

    3 135 0 - Operacin prevista / Scheduled dispatch

    4 135 0 - Operacin prevista / Scheduled dispatch

    5 135 0 - Operacin prevista / Scheduled dispatch

    6 135 0 - Operacin prevista / Scheduled dispatch

    7 67,5 0 Preparacin / Preparation Reduccin / Reduction

    8 0 0 Vaco (FSNL*) Ajuste AVR / AVR Setting

    9 0 0 Vaco (FSNL*) Ajuste AVR / AVR Setting

    10 67,5 0 Carga / Load Calibracin PSS / PSS setting

    11 67,5 -20 Carga / Load Pruebas PSS - SUB / PSS Test - Underexcitation

    12 67,5 50 Carga / Load Pruebas PSS - SOB / PSS Test - Overexcitation

    13 67,5 0 Carga / Load Pruebas PSS - MAX G / PSS Test - Max Gain

    14 135 0 Carga / Load Pruebas PSS - RAMP PM/ PSS Test - Mechanical Power Ramp

    15 135 -20 Carga / Load Pruebas PSS - SUB / PSS Test - Underexcitation

    16 135 50 Carga / Load Pruebas PSS - SOB / PSS Test - Overexcitation

    17 101,5 0 Carga / Load Pruebas PSS - RAMP PM/ PSS Test - Mechanical Power Ramp

    18 135 0 Carga / Load Finalizacin/End

    19 135 0 - Operacin prevista / Scheduled dispatch

    20 135 0 - Operacin prevista / Scheduled dispatch

    21 135 0 - Operacin prevista / Scheduled dispatch

    22 135 0 - Operacin prevista / Scheduled dispatch

    23 135 0 - Operacin prevista / Scheduled dispatch

    24 135 0 - Operacin prevista / Scheduled dispatch

    *FULL SPEED NO LOAD

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 10/16

    4.2 No-load test

    Temporal Response of the Excitation Control Loop tests are made to verify the performance

    of the voltage regulation when the generator working at full speed no load (FSNL).

    Preliminary conditions: The unit shall be spinning at nominal speed. The terminal voltage of

    the unit shall be at its nominal value and the unit shall be disconnected from the grid. The AVR

    must be in voltage control mode.

    Tests development: Step changes shall be applied to the AVR reference voltage in the following

    operation conditions:

    Test Voltage

    [%]

    Step

    [%]

    Length

    [sec]

    1* 100 5 20

    2 90 5 20

    *Test 1 will be performed for several AVR Gain levels, from the current value to at least half of it.

    Then it would be set to the value define in the studies.

    The list of tests is a reference, the EE team leader will decide on site whether is necessary to add

    or omit any test.

    Electrical signals to be recorded:

    1. The applied pulse.

    2. The terminal voltage. 3. The field (excitation) voltage. 4. The field (excitation) current. 5. Additional signals of the control system

    The list of tests is a reference, the EE team leader will decide on site whether is necessary to add

    or omit any.

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 11/16

    4.3 Measurement of local mode damping

    Temporal Response of the Control Loop tests are used to verify the PSS when the generator

    is on load.

    Preliminary conditions: The unit must be connected to the system, loaded, without oscillations

    from the network and dispatched in the operating conditions listed below. The AVR must be in

    voltage control mode.

    Tests development: Step changes shall be applied in the AVR voltage reference for the

    following conditions of operation:

    Test Voltage

    [%]

    Active

    Power

    [%]

    Reactive

    Power Step [%]

    Length

    [sec] PSS

    1* ~100 ML or IL 0 2 120 ON

    2 ~100 ML or IL 0 2 120 OFF

    3 ~100 ML or IL (+) -2 120 ON

    4 ~100 ML or IL (+) -2 120 OFF

    5 ~100 ML or IL (-) 2 120 ON

    6 ~100 ML or IL (-) 2 120 OFF *Test 1 will be performed for several PSS Gain levels, from cero to the value define in the studies. Other PSS settings could

    be change according to the actual response of the unit.

    Notes:

    FL: active power near to full load (maximum achievable at test's day)

    IL: intermediate value between FL and ML

    ML: minimum load (minimum stable working point) The generator terminal voltage shall be as close as possible to 100% of its nominal value. Reactive Power: (+) indicates overexcited operating conditions near the limit of

    overexcitation. Reactive Power: (-) indicates underexcited operating conditions near the limit of

    underexcitation. Step 2%: the value may be adjusted depending on system conditions.

    Electrical signals to be recorded:

    1. Applied pulse 2. Terminal voltage 3. Field (excitation) voltage 4. Field (excitation) current 5. Active Power 6. Reactive Power 7. Frequency 8. PSS output 9. Additional signals of the control system

    The list of tests is a reference, the EE team leader will decide on site whether is necessary to add

    or omit any.

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 12/16

    4.4 Effects of variation in the mechanical power

    The objective of this test is to verify that the settings of the filters and the design of PSS

    allows to minimize the effect on the output of PSS of rapid variations in mechanical power.

    Preliminary conditions: the unit must be connected to the system, without oscillations from

    the network. The AVR must be in voltage control mode.

    Tests development: When the unit is operating at 75% of its nominal active power, the

    active power of the unit shall be increased up to 100% of its capacity according in the following

    conditions:

    Test Voltage

    [%]

    Active

    Power

    [%]

    Reactive

    Power

    Loading

    [%] PSS

    1 ~100 75 0 25 ON

    2 ~100 75 0 25 OFF

    The loading process must be performed at the highest ramp rate that can be selected by the

    operator. The list of tests is a reference, the EE team leader will decide on site whether is necessary

    to add or omit any test.

    Electrical signals to be recorded:

    1. Terminal voltage 2. Field (excitation) voltage 3. Field (excitation) current 4. Active Power 5. Reactive Power 6. Frequency 7. PSS output 8. Additional signals of the control system

    The list of tests is a reference, the EE team leader will decide on site whether is necessary to add

    or omit any.

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 13/16

    4.5 Maximum Gain

    The objective of this test is to determine the maximum gain of the PSS and verify that it

    keeps a proper stability margin.

    Preliminary conditions: The unit must be connected to the grid, without oscillations from

    the network. The AVR must be in voltage control mode.

    Tests development: The gain of the PSS shall be gradually increased until high frequency

    poorly damped oscillations are observed on terminal voltage and/or field current. This value gain

    must be recorded as limit

    Test Voltage

    [%]

    Active

    Power[%]

    Reactive

    Power PSS

    2 ~100 FL or IL

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 14/16

    5 Interconexin SADI-SING

    El da 6 se prevn las pruebas de vinculacin SADI-SING. En funcin de los requerimientos

    de CAMMESA y CDEC se realizarn pruebas contemplando distintos niveles de transferencia por la

    vinculacin SADI-SING y ajustes de ganancias en los estabilizadores de las 4 (cuatro) unidades en

    estudio.

    Para contemplar un comportamiento seguro de la red se propone que las pruebas de variacin

    de ganancia de los estabilizadores se realicen conforme se describe en la siguiente curva de

    transferencia y nivel de ganancia de los estabilizadores.

    On day 6th SADI-SING interconnection is expected. According to the transmission system

    operators different power transfer levels and PSS gains are to be tested. The following power

    transfer and PSS Gain settings curve is proposed.

    0

    20

    40

    60

    80

    100

    120

    140

    160

    INTERCONECTION TESTS

    P [MW]SING->SADI

    PSS Gain [% Setting]

    Security limit,cero gain if possible

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 15/16

    Durante las pruebas de interconexin SADI-SING se debern registrar en cada unidad en

    estudio, las seales:

    1. Tensin en bornes generador

    2. La tensin de campo del generador o campo de la excitatriz

    3. La corriente de campo del generador o campo de la excitatriz

    4. Potencia Activa

    5. Potencia Reactiva

    6. Frecuencia

    7. Seal de salida del PSS

    8. Otras variables definidas en campo

    During the tests the following variables should be recorded in each unit:

    1. Terminal voltage

    2. Field (excitation) voltage

    3. Field (excitation) current

    4. Active Power

    5. Reactive Power

    6. Frequency

    7. PSS output

    8. Additional signals of the control system

    P [MW]

    SING->SADI

    PSS Gain

    [% Setting]Comentarios / comments

    0 100 Enlace Abierto / Tie Open

    0 100 Enlace Cerrado / Tie Closed

    0 100 Enlace Cerrado / Tie Closed

    50 100 Aumento transferencia / Increase transfer

    50 100 Registros / Record

    100 100 Aumento transferencia / Increase transfer

    100 50 Reduccin Ganancia PSS / PSS Gain Reduction

    100 0 Reduccin Ganancia PSS / PSS Gain Reduction

    100 100 Reestablecimiento de ganancia / Restore Gain

    150 100 Aumento transferencia / Increase transfer

    150 100 Registros / Record

    100 100 Reduccin transferencia / Decrease transfer

    50 100 Reduccin transferencia / Decrease transfer

    0 100 Fin / End

    0 100 Enlace Abierto / Tie Open

  • Tel +54 341 4516 422 www.estudios-electricos.com

    Ir al ndice

    P:EE-2014-144/I:EE-ES-2014-0836/R:C No se autorizan copias del presente documento sin autorizacin previa por

    escrito de ESTUDIOS ELECTRICOS S.A. 16/16

    Esta pgina ha sido intencionalmente dejada en blanco

    1 INTRODUCCIN2 TAREAS / Tasks2.1 CARTA GANTT

    3 CT ANGAMOS3.1 Curva de Carga (Load Profile)3.2 Measurement of local mode damping3.3 Effects of variation in the mechanical power3.4 Maximum Gain

    4 CT NORGENER4.1 Curva de Carga (Load Profile)4.2 No-load test4.3 Measurement of local mode damping4.4 Effects of variation in the mechanical power4.5 Maximum Gain

    5 Interconexin SADI-SING

    David Perrone2014-11-07T17:41:47-0300RosarioFirma informe

    Alejandro Musto2014-11-07T17:41:48-0300RosarioFirma informe

    Fernando Libonati2014-11-07T17:41:49-0300RosarioFirma informe