ece4762011 lect22
TRANSCRIPT
Lecture 22Power System Protection, Transient Stability
Professor Tom OverbyeDepartment of Electrical and
Computer Engineering
ECE 476
POWER SYSTEM ANALYSIS
2
Announcements
Be reading Chapters 9 and 10 After exam read Chapter 11 HW 9 is 8.4, 8.12, 9.1,9.2 (bus 2), 9.14; do by Nov 10 but does not need
to be turned in. Start working on Design Project. Firm due date has been extended to
Dec 1 in class Second exam is on Nov 15 in class. Same format as first exam, except
you can bring two note sheets (e.g., the one from the first exam and another) Exam/solution from 2008 will be posted on website shortly Exam covers through Chapter 10
3
In the News: Boulder municipalization
• Last week Boulder, CO narrowly voted to move forward with municipalization of their electric grid• Currently Boulder is in the Xcel Energy electric service territory
(Xcel is a large Investor Owned Utility)
• Xcel has recently decided not to continue funding the Boulder “SmartGridCity” initiative, which has cost $45 million, triple its original cost.
• Xcel does not wish to sell its electric grid in Boulder, saying it would be extremely expensive for Boulder to go on their own.
Source: NY Times 11/3/11; Thanks to Margaret for pointing out this story
4
Power System Protection
Main idea is to remove faults as quickly as possible while leaving as much of the system intact as possible
Fault sequence of events1. Fault occurs somewhere on the system, changing the
system currents and voltages
2. Current transformers (CTs) and potential transformers (PTs) sensors detect the change in currents/voltages
3. Relays use sensor input to determine whether a fault has occurred
4. If fault occurs relays open circuit breakers to isolate fault
5
Power System Protection
Protection systems must be designed with both primary protection and backup protection in case primary protection devices fail
In designing power system protection systems there are two main types of systems that need to be considered:
1. Radial: there is a single source of power, so power always flows in a single direction; this is the easiest from a protection point of view
2. Network: power can flow in either direction: protection is much more involved
6
Radial Power System Protection
Radial systems are primarily used in the lower voltage distribution systems. Protection actions usually result in loss of customer load, but the outages are usually quite local.
The figure showspotential protectionschemes for a radial system. Thebottom scheme ispreferred since itresults in less lost load
7
Radial Power System Protection
In radial power systems the amount of fault current is limited by the fault distance from the power source: faults further done the feeder have less fault current since the current is limited by feeder impedance
Radial power system protection systems usually use inverse-time overcurrent relays.
Coordination of relay current settings is needed toopen the correct breakers
8
Inverse Time Overcurrent Relays
Inverse time overcurrent relays respond instan-taneously to a current above their maximum setting
They respond slower to currents below this value but above the pickup current value
9
Inverse Time Relays, cont'd
The inverse time characteristic provides backup protection since relays further upstream (closer to power source) should eventually trip if relays closer to the fault fail
Challenge is to make sure the minimum pickup current is set low enough to pick up all likely faults, but high enough not to trip on load current
When outaged feeders are returned to service there can be a large in-rush current as all the motors try to simultaneously start; this in-rush current may re-trip the feeder
10
Inverse Time Overcurrent Relays
Relays havetraditionally beenelectromechanicaldevices, but aregradually beingreplaced by digital relays
Current and timesettings are ad-justed using dialson the relay
11
Protection of Network Systems
In a networked system there are a number of difference sources of power. Power flows are bidirectional
Networked system offer greater reliability, since the failure of a single device does not result in a loss of load
Networked systems are usually used with the transmission system, and are sometimes used with the distribution systems, particularly in urban areas
12
Network System Protection
Removing networked elements require the opening of circuit breakers at both ends of the device
There are several common protection schemes; multiple overlapping schemes are usually used
1. Directional relays with communication between the device terminals
2. Impedance (distance) relays.
3. Differential protection
13
Directional Relays
Directional relays are commonly used to protect high voltage transmission lines
Voltage and current measurements are used to determine direction of current flow (into or out of line)
Relays on both ends of line communicate and will only trip the line if excessive current is flowing into the line from both ends
– line carrier communication is popular in which a high frequency signal (30 kHz to 300 kHz) is used
– microwave communication is sometimes used
14
Impedance Relays
Impedance (distance) relays measure ratio of voltage to current to determine if a fault exists on a particular line
1 1
12 12
Assume Z is the line impedance and x is the
normalized fault location (x 0 at bus 1, x 1 at bus 2)
V VNormally is high; during fault
I IxZ
15
Impedance Relays Protection Zones
To avoid inadvertent tripping for faults on other transmission lines, impedance relays usually have several zones of protection:
– zone 1 may be 80% of line for a 3 fault; trip is instantaneous– zone 2 may cover 120% of line but with a delay to prevent
tripping for faults on adjacent lines– zone 3 went further; most removed due to 8/14/03 events
The key problem is that different fault types will present the relays with different apparent impedances; adequate protection for a 3 fault gives very limited protection for LL faults
16
Impedance Relay Trip Characteristics
Source: August 14th 2003 Blackout Final Report, p. 78
17
Differential Relays
Main idea behind differential protection is that during normal operation the net current into a device should sum to zero for each phase
– transformer turns ratios must, of course, be considered
Differential protection is used with geographically local devices
– buses– transformers– generators
1 2 3 0 for each phase
except during a fault
I I I
18
Other Types of Relays
In addition to providing fault protection, relays are used to protect the system against operational problems as well
Being automatic devices, relays can respond much quicker than a human operator and therefore have an advantage when time is of the essence
Other common types of relays include– under-frequency for load: e.g., 10% of system load must be shed if
system frequency falls to 59.3 Hz– over-frequency on generators– under-voltage on loads (less common)
19
Sequence of Events Recording
During major system disturbances numerous relays at a number of substations may operate
Event reconstruction requires time synchronization between substations to figure out the sequence of events
Most utilities now have sequence of events recording that provide time synchronization of at least 1 microsecond
20
Use of GPS for Fault Location
Since power system lines may span hundreds of miles, a key difficulty in power system restoration is determining the location of the fault
One newer technique is the use of the global positioning system (GPS).
GPS can provide time synchronization of about 1 microsecond
Since the traveling electromagnetic waves propagate at about the speed of light (300m per microsecond), the fault location can be found by comparing arrival times of the waves at each substation
21
Power System Transient Stability
In order to operate as an interconnected system all of the generators (and other synchronous machines) must remain in synchronism with one another– synchronism requires that (for two pole machines) the
rotors turn at exactly the same speed
Loss of synchronism results in a condition in which no net power can be transferred between the machines
A system is said to be transiently unstable if following a disturbance one or more of the generators lose synchronism
22
Generator Transient Stability Models
In order to study the transient response of a power system we need to develop models for the generator valid during the transient time frame of several seconds following a system disturbance
We need to develop both electrical and mechanical models for the generators
23
Example of Transient Behavior
24
Generator Electrical Model
The simplest generator model, known as the classical model, treats the generator as a voltage source behind the direct-axis transient reactance; the voltage magnitude is fixed, but its angle changes according to the mechanical dynamics
'( ) sinT ae
d
V EP
X
25
Generator Mechanical Model
Generator Mechanical Block Diagram
m
D
e
( )
mechanical input torque (N-m)
J moment of inertia of turbine & rotor
angular acceleration of turbine & rotor
T damping torque
T ( ) equivalent electrical torque
m m D e
m
T J T T
T
26
Generator Mechanical Model, cont’d
s
s s
s s
In general power = torque angular speed
Hence when a generator is spinning at speed
( )
( ( ))
( )
Initially we'll assume no damping (i.e., 0)
Then
m m D e
m m D e m
m m D e
D
m e
T J T T
T J T T P
P J T P
T
P P
s( )
is the mechanical power input, which is assumed
to be constant throughout the study time period
m
m
J
P
27
Generator Mechanical Model, cont’d
s
s s
s
s
( )
rotor angle
( )
inertia of machine at synchronous speed
Convert to per unit by dividing by MVA rating, ,
( ) 2
m e m
m s
mm m s
m m
m e m
B
m e s
B B B
P P J
t
ddt
P P J J
J
S
P P JS S S
2 s
28
Generator Mechanical Model, cont’d
s
2
2
( ) 22
( ) 1(since 2 )
2
Define H per unit inertia constant (sec)2
All values are now converted to per unit
( ) Define
Then ( )
m e s
B B B s
m e ss s
B B s
s
B
m es s
m e
P P JS S S
P P Jf
S S f
JS
H HP P M
f f
P P
M
29
Generator Swing Equation
This equation is known as the generator swing equation
( )
Adding damping we get
( )
This equation is analogous to a mass suspended by
a spring
m e
m e
P P M
P P M D
kx gM Mx Dx
30
Single Machine Infinite Bus (SMIB)
To understand the transient stability problem we’ll first consider the case of a single machine (generator) connected to a power system bus with a fixed voltage magnitude and angle (known as an infinite bus) through a transmission line with impedance jXL
31
SMIB, cont’d
'
'
( ) sin
sin
ae
d L
aM
d L
EP
X X
EM D P
X X
32
SMIB Equilibrium Points
'
Equilibrium points are determined by setting the
right-hand side to zero
sinaM
d L
EM D P
X X
'
'th
1
sin 0
Define X
sin
aM
d L
d L
M th
a
EP
X X
X X
P XE
33
Transient Stability Analysis
For transient stability analysis we need to consider three systems
1. Prefault - before the fault occurs the system is assumed to be at an equilibrium point
2. Faulted - the fault changes the system equations, moving the system away from its equilibrium point
3. Postfault - after fault is cleared the system hopefully returns to a new operating point
34
Transient Stability Solution Methods
There are two methods for solving the transient stability problem
1. Numerical integration this is by far the most common technique, particularly
for large systems; during the fault and after the fault the power system differential equations are solved using numerical methods
2. Direct or energy methods; for a two bus system this method is known as the equal area criteria mostly used to provide an intuitive insight into the
transient stability problem
35
SMIB Example
Assume a generator is supplying power to an infinite bus through two parallel transmission lines. Then a balanced three phase fault occurs at the terminal of one of the lines. The fault is cleared by the opening of this line’s circuit breakers.
36
SMIB Example, cont’d
Simplified prefault system
1
The prefault system has two
equilibrium points; the left one
is stable, the right one unstable
sin M th
a
P XE
37
SMIB Example, Faulted System
During the fault the system changes
The equivalent system during the fault is then
During this fault nopower can be transferredfrom the generator to the system
38
SMIB Example, Post Fault System
After the fault the system again changes
The equivalent system after the fault is then
39
SMIB Example, Dynamics
eDuring the disturbance the form of P ( ) changes,
altering the power system dynamics:
1sina th
Mth
E VP
M X