earthing design software _rev01
TRANSCRIPT
Input Parameters taken for calculation:
Project Name = …………Customer = ………..Document No. = ………..PO No./ LOA No. = ………..
Weight of Person Kg = 50
= Symmetrical fault current, A = 40000
= Fault current division factor = 0.7
= Duration of shock for determining allowable body current, sec = 1
= 3000
= Surface layer thickness, m = 0.175r = 20
h = Depth of ground grid conductors, m = 30
= Number of Electrodes = 71
= Length of Individual Electrode, m = 3d = Diameter of Conductor/Equivalent diameter in case of Flat cond, m = 0.04L = Maximum length of grid conductor in x direction, m = 47
W = Maximum length of grid conductors in y direction, m = 103
= Number of Conductor along the length wise = 17
= Number of Conductor along the width wise = 35D = Average spacing between two conductors = 3
Input Parameters for Ampacity calculation:Type of conductor: mild Steel
20 °C
#REF! mm2
4.50E-03 1/°C
500 °C
45 °C
202.00022
13.8
TCAP= Thermal Capacity per Unit Volume= 3.8 J/cm³ · °C
1 sec
I= Current for sizing of Earthmat conductor = 40 kA
I f
Sf
ts
rs Surface layer resistivity, W-m =
hs Soil resistivity, W-m =
nR
Lr
NL
NW
Tr = Reference Temperature for Material Constants =
Amm2 = Minimum conductor cross section area required =
ar = Thermal Coefficient of Resistivity at Reference Temperature =
Tm= Fusing Temperature of Conductor =
Ta= Ambient Temperature =
K0= (1/ar ) – Tr =
rr =Resistivity of Conductor at Reference Temperature = mW-cm
tc= time duration for sizing the eartmat conductor =
Out Put of Earthing Design Calculation
Minimum Conductor Cross section area Required #REF!
Minimum Diameter of Conductor required 0
Value of Grid Resistance 0
Attainable Tolerable
Step Potential #REF! 0.00
Touch Potential #REF! 0
The Attainable touch as well as Step voltage should be less than tolerable limit.
Reference Drawings:
1. ………………………..
Reference Document :
1. IEEE-80 For Safety in AC Substation Grounding2. Design of Earthing Mat for High Voltage Sub-Station (CBIP - Manual)
CUSTOMER:
………..
Prepared & Checked: Approved: PROJECT:…………
REV DATE PO No/ LOA No : ………..
Title:
EARTHMAT DESIGN CALCULATION
abcd ALSTOM PROJECTS INDIA LTD. Rev
DOC No.
1 Following nomenclature are used in the calculation:
1 r =
2 =3 I f = Symmetrical fault current in substation [A]
4 A =
5 = Surface layer de-rating factor6 d = Diameter of grid conductor [m]7 D = Spacing between parallel conductors [m]
8 = Attainable Touch Voltage [V]
9 = Attainable Step Voltage [V]
10 = Tolerable step voltage for human with 50 kg body weight [V]
11 = Tolerable touch voltage for human with 50 kg body weight [V]
12 = Tolerable step voltage for human with 70 kg body weight [V]
13 = Tolerable touch voltage for human with 70 kg body weight [V]14 h = Depth of Buriel of Earthing conductors [m]
15 = Surface Gravel layer thickness [m]
16 = Maximum grid current that flows between ground grid and surrounding earth [A]
17 = Symmetrical grid current [A]18 K = Reflection factor between different resistivities
19 = Corrective weighting factor that emphasizes the effects of grid depth,
20 = Correction factor for grid geometry
21 = Corrective weighting factor that adjusts for the effects of inner conductors
22 = Spacing factor for mesh voltage
23 = Spacing factor for step voltage
24 = Total length of grid conductor [m]
25 =
26 = Periphery Length of the earthing equivalent area [m]
27 = Total length of ground rods [m]
28 = Length of Individual electrode
29 =
30 = Total effective length of grounding system conductor, including grid and ground rods [m]
31 =L= Maximum length of grid conductor in X direction [m]
32 =W= Maximum length of grid conductors in Y direction [m]
33 n =
34 = Number of Electrodes
35 =
36 = Duration of shock for determining allowable body current [sec]
Soil resistivity [W-m]
rs Surface layer (crushed rock) resistivity [W-m]
Total area enclosed by ground grid [m2]
Cs
Em
Es
Estep50
Etouch50
Estep70
Etouch70
hs
IG
Ig
Kh
Ki
Kii
Km
Ks
Lc
LM Effective length of Lc + LR for mesh voltage [m]
Lp
LR
Lr
LS Effective length of Lc + LR for step voltage [m]
LT
Lx
Ly
Geometric factor composed of factors na , nb , nc , and nd
NR
Rg Resistance of grounding system [W]
ts
2 Input Parameters taken for calculation:
= Symmetrical fault current in substation for conductor sizing, = 40000 A
= Fault current division factor = 0.7
= Duration of shock for determining allowable body current, = 1 sec
= 3000
= Surface layer thickness, = 0.175 mr = 20
h = Depth of ground grid conductors, = 30 m
= Number of Electrodes = 71
= Length of Individual electrode, = 3 md = Diameter of Conductor/Equivalent diameter in case of Flat conductor = 0.04 mL = Maximum length of grid conductor in x direction = 47 m
W = Maximum length of grid conductors in y direction = 103 m
= Number of Conductor along the length wise = 17
= Number of Conductor along the width wise = 35
Design Steps :
3 Ampacity calculation
Type of conductor: mild Steel
20 °C
#REF! mm2
4.50E-03 1/°C
500 °C
45 °C
202.0002
13.8
TCAP= Thermal Capacity per Unit Volume= 3.8 J/cm³ · °C
1 sec
I= Current for sizing of Earthmat conductor = 40 kA
As specified in IEEE std-80-2000
Equation no: (37)
=
I f
Sf
ts
rs Surface layer resistivity, W-m =
hs Soil resistivity, W-m =
nR
Lr
NL
NW
Tr= Reference Temperature for Material Constants =
Amm2= Minimum conductor cross section area required =
ar =Thermal Coefficient of Resistivity at Reference Temperature =
Tm= Fusing Temperature of Conductor =
Ta= Ambient Temperature =
K0= (1/ar ) – Tr =
rr =Resistivity of Conductor at Reference Temperature = mW-cm
tc= time duration for sizing the eartmat conductor =
Amm2
Minimum conductor diameter required dmin =
As per "Design of Steel earthing Grids in India" IEEE Transactions on power apparatus andsystems, volume PAS- 98 no.6, Nov/Dec-1979. PP 2126-2134, Corrosion allowance is recommended as per following Rules
15 mills = 0.381 mm
91.5 mills = 2.324 mm
180 mills = 4.572 mm
= + 2 x 4.572
= 9.14
Minimum conductor diameter with corrosion allowance
Minimum Cross section required with corrosion allowance = 1000.000 mm2
Cross section of selected conductor = 1256.637 mm2
Selected Conductor Cross section =
Calculation for Tolerable Touch and step Potential for Person of 50Kg
As specified in IEEE std 80-2000Equation no: (27)
=
Following equation can be used to compute the tolerable touch and step voltages respectively
As specified in IEEE std 80-2000Equation no: (29)
= V
As specified in IEEE std 80-2000Equation no: (32)
= V
_ In case of conductor to laid in soil having soil resistivity greater than 100 ohm-meter -
_ In case of conductor to laid in soil having soil resistivity from 25 to 100 ohm-meter -
_ In case of conductor to laid in soil having soil resistivity Lower than 25 ohm-meter -
dmin with corrosion = dmin + Corrosion Allowancedmin
The reduction factor (Derating Factor) Cs can be approximated by the equation
Cs
Estep50
Etouch50
Calculation for Tolerable Touch and step Potential for Person of 70Kg
=
Following equation can be used to compute the tolerable touch and step voltages respectively
As specified in IEEE std 80-2000Equation no: (30)
= VAs specified in IEEE std 80-2000Equation no: (33)
= V
The reduction factor (Derating Factor) Cs can be approximated by the equation
Cs
Estep70
Etouch70
4 Grid Configuration
Refer Annexure -I for Grid Configuration
Maximum Length in X- Direction L = 47
Maximum Length in Y- Direction W = 103
17
35
71
3
= 3590.333 m
Total Area of Earth Mat, A = 4841 m2
5 Determination of Grid ResistanceAs specified in IEEE std 80-2000
Equation no: ( 52)
= Ohm
6 Calculation of Attainable step and touch voltage
= 1 For grid with ground rods in perimeter
D = Average spacing between two conductors = 3
Geometric factor
As specified in IEEE std 80-2000
Equation no: (85)
Lc = Total Length of Grid Conductor
Lc = 3377.333
Lp = Periphery Length of earthing equivalent Area 2 x ( L + W )
Lp = 300
= Total length of all ground rods(electrodes) in m Nr x Lr
= 213
= 22.52
As specified in IEEE std 80-2000
Equation no: (86)
= 1.038238
Number of Conductor along the lengthwise NL =
Number of Conductor along the widthwise NW =
Number of Electrodes Nr =
length of Individual Electrode Lr =
LT
Rg
Kii
( L x Nw ) + ( W x NL )
LRLR
na
nb
= 1 for square and rectangular grid
= 1 for square and rectangular grid and L-shaped grid
n = Equation no: (84)
n = 23.3765
As specified in IEEE std 80-2000Equation no: (83)
5.567764
Now,As specified in IEEE std 80-2000Equation no: (80)
As specified in IEEE std 80-2000Equation no: (92)
Equation no: (81)
= #REF!
As specified in IEEE std 80-2000Equation no: (89)
= 4.103722
As specified in IEEE std 80-2000Equation no: (91)
= #REF!
=
= #REF! A
= #REF! V
As specified in IEEE std 80-2000
Equation no: (94)
nc
nd
na x nb x nc x nd
Kh
Km
Ki
Lm
Ig Sf x If
Ig
Em
=
= #REF!Ks
As specified in IEEE std 80-2000
Equation no: (93)
= #REF!
= #REF! V
7 Safety check
For the safe earthing design , Attainable step & Touch voltages should be less than Tolerable values respectively.
Attainable Tolerable
#REF! 0.000
#REF! 0.00
Ls
Es
Touch voltage in V
Step voltage in V