Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999 1 of 27 EARTHING OF ELECTRICAL SYSTEM Introduction Definition of Earthing and Grounding: Grounding implies connection of power system neutral to ground (earth). e.g. neutral grounding / system grounding. In grounding current carrying parts are connected to ground. Earthing implies the connection of non current carrying parts to ground e.g metallic enclosures. Another term for earthing is equipment grounding. Earthing is done for human and equipment safety. Human Element Electric 'shock' is possible only when the human body bridges two objects of unequal potential. Current flows when potential difference exists between hand and feet (touch potential), or between feet (step potential). TRANSFORMER GENERATOR NG NG EARTHING

Upload: nkbhagalpur

Post on 12-Apr-2015

198 views

Category:

Documents


44 download

TRANSCRIPT

Page 1: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

1 of 27

EARTHING OF ELECTRICAL SYSTEM

Introduction Definition of Earthing and Grounding:

• Grounding implies connection of power system neutral to ground (earth). e.g.

neutral grounding / system grounding. In grounding current carrying parts are

connected to ground.

• Earthing implies the connection of non current carrying parts to ground e.g

metallic enclosures. Another term for earthing is equipment grounding.

Earthing is done for human and equipment safety.

Human Element

• Electric 'shock' is possible only when the human body bridges two objects of

unequal potential. Current flows when potential difference exists between

hand and feet (touch potential), or between feet (step potential).

TRANSFORMER

GENERATOR

NG NG

EARTHING

Page 2: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

2 of 27

• Maximum tolerable current for a human body is approximately 160 mA for

one second duration (i.e. if current through body exceeds about 160 mA, for

more than a second, almost certain death, due to ventricular fibrillation or

heart attack).

• Allowable body current ΙB (Ampere) as per IEEE Standard 80 is as given

below:

ΙB = 0.116 / √TS, for a body weight of 50 Kg

ΙB = 0.157 / √TS, for a body weight of 70 Kg

where TS is the duration of current exposure (fault clearance time).

• For various exposure times, the withstand currents of human body are as

follows:

TS ΙB (50 Kg) ΙB (70 Kg)

0.2 sec

259 mA 351 mA

0.5 sec 164 mA 222 mA

1 sec 116 mA 157 mA

Thus human body can withstand higher current for shorter time duration. The

advantage high-speed protection is evident from human safety point of view.

• Average value of human body resistance RB is approximately 8000 Ω to 9000

Ω (under dry conditions). For standards purposes, RB is taken as 1000Ω as

per IEEE Std 80. Use of lower RB value results in conservative values for

allowable touch and step potentials.

Page 3: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

3 of 27

Soil Resistivity

Resistivity ( ρ) of element:

• R = ρ L / A ⇒ ρ = R A / L ⇒ Ω M2 / M = Ω M ; where ρ - Resistivity of

element, R – Resistance of element, L – Length, A – Area,

• Earth is a not a good conductor. In fact it is one of the worst equipment-

grounding conductors. The comparison of resistivity is given below:

Material Resistivity

Earth 100 ΩM

GI 10-7 ΩM

Copper 1.7 x 10-8 ΩM

• Soil resistivity ( ρ in Ω M ) is value of resistance in Ω of 1M cube. Soil

resistivity for different types of soil is given below:

Type of Earth Wet Soil Moist Soil Dry Soil Bed Rock

Resistivity (Ω - M ) 10 100 1,000 10,000

Effect of moisture on soil resistivity:

• Soil resistivity ρ rapidly increases for moisture content of less than 10 % of

soil weight. There is marginal decrease in soil resistivity for moisture content

exceeding 25% of soil weight.

Page 4: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

4 of 27

Effect of salt on soil resistivity:

• Minute amount of salt causes sharp decrease in soil resistivity provided there

is moisture content of say 10%. Salt when added to dry soil gives hardly any

improvement in the resistivity value.

• Substances used for improving soil resistivity are sodium chloride (common

salt), copper sulphate, calcium chloride and magnesium sulphate. To account

for corrosion, electrode size is increased from calculated value.

Corrosion intensity:

• Soil classification based on corrosion intensity is given below:

Page 5: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

5 of 27

ρ of virgin soil Ω M <25 25 to 50 50 to 100 ρ > 100

Corrosion Intensity Severe Moderate Mild Very Mild

• Alternative substances used for earthing are coke or wood charcoal and

Bentonite. Coke is less corrosive compared to salt. Bentonite is a natural clay

and non-corrosive and needs watering periodically.

• Performance over time for earth resistivity is shown below:

After treatment there is initial decrease in ρ. However there is gradual

increase in soil resistivity ρ with time as the salt is washed away by continual

water seepage. Hence, re-treatment is typically required to be carried out

once in 3 years.

Effect of Temperature on Soil Resistivity:

• Soil resistivity decreases with increase in temperature. In summer ρ is less

and in winter it is more. However, effect of temperature on ρ is not serious

until freezing point is approached. Near 0°C, ρ abruptly rises to a very high

Page 6: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

6 of 27

value. It is preferable to place electrodes well below ground level. Surface

temperature may be freezing but below 1M, soil temperature will be higher.

Soil resistivity measurement:

• Soil resistivity measurement setup is as shown below. AC supply source is

preferred for the set up as compared to the DC supply source.

• Resistivity measured for spacing ‘A’ represents apparent soil resistivity to

depth of 'A'. Measurements are made with different spacings. Rapidly

increasing value of ρ with spacing 'A' indicates underlying stratum is rock and

it is difficult to install earth electrodes to great depths.

Page 7: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

7 of 27

Resistance to earth

• Resistance between metal of electrode in question and general mass of earth

is known as earth resistance. It is resistance between specific electrode and

imaginary electrode of zero resistance placed at infinity. 90% of resistance is

contributed by earth within 5 meters distance.

Resistance vs Distance:

• Resistance to earth of hemi-spherical electrode is shown below:

dX

A

X

Page 8: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

8 of 27

R = ρ L / A; RX = ∫ ρ dX / 2 Π X2 Resistance area of tube or rod electrode:

• Resistance area is the region of earth that immediately surrounds the

electrode and contributes to practical value of resistance.

• Current flows away from electrode in all directions and through a series of

shells of earth of continuously increasing cross section. At sufficient distance

from earth electrode, shells approach hemi-spherical shape. Hence results

given earlier for hemi-spherical electrode are also nearly valid here.

Resistance of electrode to earth here also is predominantly influenced by

earth with in the vicinity of electrode. This justifies artificial treatment of soil in

the immediate neighborhood of soil to achieve low resistance between

electrode and earth.

Resistance of Driven Rod or Pipe Electrode: L : depth of Driven Rod in met

Φ : diameter of Driven Rod in met

R = (ρ / 2 Π L ) [ LN (8L /Φ x 2.7183 )] R ≅ (ρ / 2 Π L ) [ LN (4L / Φ )]

L

Page 9: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

9 of 27

Length / diameter of rod vs Resistance is given below:

The diameter of the rod has minor influence on the resistance. Length of the rod has

major impact. For lengths more than 3M, resistance is almost the same even if

diameter is increased by four times.

Resistance of Horizontal Wire (Strip) Electrode: If excavation is difficult beyond a meter due to underlying rock, strip electrode is the

alternative. The earth electrode is as shown below:

RESISTANCE OF ROD ELECTRODE

0

50

100

150

200

250

300

0 1 2 3 4 5 6 7 8 9 10LENGTH OF ROD, MET

RES

ISTA

NC

E, O

HM

S

2.5 CM

10 CM

DIAMETER : 2.5, 5, 7.5, 10 CM

RHO - 100 OHM-MET

ROD LENGTH: 6M

R10 = 15.3 ΩR2.5 = 16.4 Ω φ ⇑ 300%

R⇓ 7%

RESISTANCE OF ROD ELECTRODE

0

50

100

150

200

250

300

0 1 2 3 4 5 6 7 8 9 10LENGTH OF ROD, MET

RES

ISTA

NC

E, O

HM

S

2.5 CM

10 CM

DIAMETER : 2.5, 5, 7.5, 10 CM

RHO - 100 OHM-MET

ROD LENGTH: 6M

R10 = 15.3 ΩR2.5 = 16.4 Ω φ ⇑ 300%

R⇓ 7%

Page 10: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

10 of 27

Exact Formula (RYDER) R = (ρ / 2 Π L) [LN(8L/T) + LN(L/h) – 2 + (2h/L) – (h2 / L2)]

Where, h is depth in Met, L is length in Met.

T : width in Met (for strip)

: 2 x diameter in Met (for wire)

Approximate Formula:

R = (ρ / 2 Π L) [LN( 2L2 / hT )] IS 3043 • Length / diameter of wire Vs Resistance variation is shown below,

• The diameter of the rod (width in case of strip electrode) has minor influence

on the resistance. Length of the rod has major impact on resistance value.

For length more than 50M, resistance is almost the same even if diameter

is increased by four times.

• Resistance of electrode to earth is only influenced by maximum dimension of

electrode, i.e. depth in case of rod electrode and length in case of wire

electrode. It is not much influenced by minor dimensions like diameter or

width. It is not dependent on material of electrode. It is the function of physical

dimensions of the electrode and not its physical properties.

Page 11: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

11 of 27

• The cross section of strip with width 'W' is approximately equivalent to round

conductor with diameter of 'W / 2'. W

W/2

Plate electrode:

• In early days only plate electrode were used. It was assumed that to get low

resistance, surface area of electrode be increased. The fallacy of increased

electrode surface area persisted for a long time. But as can be seen from

following figures, plate electrode is very inefficient. It is rarely used in modern

times.

Page 12: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

12 of 27

Two electrodes in parallel

• To obtain low effective earth grid resistance, earth rods are connected in

parallel. For achieving minimum resistance, resistance area of each electrode

must be clear of one another. Theoretically, the effective resistance shall be

half of one electrode. If electrodes are well separated, this can be achieved.

The figure below shows the relation between percentage effective resistance

and separation between electrodes in meters.

• If rod length is 'L' meters, spacing between electrodes shall be greater than

2L meters, as shown below.

Ι Ι L 2L Three electrodes in parallel Theoretically, the effective resistance shall be 33% of one electrode. If electrodes

are well separated, this can be achieved. The figure below shows the relation

between effective resistance and separation between electrodes in meters.

Page 13: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

13 of 27

• If rod length is 'L' meters, spacing between electrodes shall be greater than

2L meters.

Ι 2 L 1 3 1 2 3 > 2L

Grounding Grid Resistance

• Previous discussions centered around resistance to earth from individual

electrodes. Present discussion is on resistance to earth from entire grounding

grid.

Sverak formula

C1 = 1 / L ; C2 = 1/√(20A); C3 = 1 + h √(20A)

RG = ρ [ C1 + C2 1 + (1 / C3) ]

Where,

RG = Grid resistance to earth in Ω

h = Depth of grid in m

ρ = Average earth resistivity in Ω Μ

A = Area of grounding grid M2

L = Total length of buried conductor, including rod electrodes in meters

Page 14: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

14 of 27

• Example of rectangular grounding grid is shown below:

Area of Grounding grid = A = 80 x 50 = 4000 M2

Horizontal electrodes length = LH = (9 x 50 ) + (6x 80) = 930 M

Vertical rods length = LV = 18x 6 = 108 M

L = LH + LV = 930 + 108 = 1038 M

H = depth of grid = 0.5 M

ρ = soil resistivity = 100 Ω - M

Applying Sverak Formula, RG = 0.79 Ω

Caution in using formula for individual electrodes is illustrated below: • For Vertical rod electrodes:

Soil resistivity ρ = 100 Ω M ; L = 6 M; Φ = 0.05 M ( ≅2")

Formula for individual vertical rod:

R = (ρ / 2 Π L ) [ LN (8L /Φ x 2.7183 )] = 15.5625 Ω

For 18 rods in parallel, RV = 15.5625 / 18 = 0.8646 Ω

• For Horizontal Electrodes:

Soil resistivity = ρ = 100 Ω M; L = LH = (9 x 50 + 6 x 80) = 930 M

T = 0.1M ; h = 0.5 M

Applying Ryder's formula for horizontal electrodes

R = (ρ / 2 Π L) [LN(8L/T) + LN(L/h) – 2 + (2h/L) – (h2 / L2)]

= 0.2866 Ω

Page 15: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

15 of 27

• Thus effective Grid Resistance = R'G

= RV in parallel with RH

R'G = ( RV RH ) / ( RV + RH ) = 0.2152 Ω

But as per Sverak formula for entire grid, equivalent resistance = RG = 0.79 Ω .

• Thus RG is very much greater than R'G. This is due to the fact that resistance

areas of electrodes are not independent and partially overlap.

• Sverak formula for grounding grid resistance does not involve conductor size

or material at all. It involves only linear dimension (length of horizontal or

vertical electrodes) that makes it very special.

Measurement Of Earth Electrode Resistance by “Fall Of Potential” method.

It is also called “Two-current and one potential electrode” method.

In the above figure,

• C_E_T implies current electrode under test. It can be a single electrode or

earthing grid whose resistance to earth is to be measured. Test current ('Ι')

enters C_E_T.

• C_E_R implies reference electrode placed at sufficient distance ('L') from test

electrode. Test current ('Ι') leaves C_E_R.

• V_E implies Voltage electrode.

Page 16: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

16 of 27

Voltage ('V') between C_E_T & V_E measured

Electrode (grid) resistance is given by R = V / Ι Ω Take three measurements with,

L_P = L / 2

L_P = L / 2 + D

L_P = L / 2 – D

L = 100 to 500 M, D = 5 to 10 M

If three readings agree within tolerable accuracy, electrode (grid) resistance is the

mean of the three readings. If the three readings are not sufficiently close, increase

spacing 'L’ between test electrode and reference electrode and repeat the test.

Overlapping resistance areas Non-overlapping resistance areas

X-Y Distance

Res

ista

nce

Reading Variation

X Y1 Y Y11 Z

Effective ResistanceAreas (No Overlap)

X Y1 Y Y11 Z

Reading Variation

X-Y Distance

Effective ResistanceAreas (Overlapping)

Res

ista

nce

X Y1 Y Y11 Z

Reading Variation

X-Y Distance

Effective ResistanceAreas (Overlapping)

Res

ista

nce

Page 17: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

17 of 27

Electrode Sizing

• Materials generally used for earth electrodes are Galvanized Iron, Copper

and Aluminum. Current ratings for above materials are given below in A /

mm2 (as per IS 3043):

Material GI Copper Aluminum 0.5 sec Rating 113 290 178 1 sec Rating 80 205 126 3 sec Rating 46 118 73

For EHV switchyards, electrodes are designed for 0.5 sec duty. Primary

protection clears fault within 0.1 sec. Back up protection operating time is

about 0.5 sec. For electrodes other than those in EHV switchyards, design

duty is for 1 sec. Rating of 3 sec is rarely used.

Example The fault current magnitude is 40 kA. The duration of fault is 0.5 sec. The electrode

material is GI.

Minimum cross section:

113 A - 1 mm2

40 KA - 40,000 / 113 = 353 mm2

Taking corrosion allowance as 10%,

Desired cross section = 353 x 1.1 = 388 mm2

Chosen size: 50 x 8 mm

General Formula for Electrode rating in Amps / mm2 is K / √T Where,

K implies constant defined for 1 sec duty (e.g. 80 for GΙ )

T implies time considered for grid design (e.g. 0.5, 0.7, 1, 3 Sec )

Considering mechanical strength and ruggedness requirements, minimum electrode

size shall be greater than 50 mm2 for GΙ and 25 mm2 for Copper.

Resistance of electrode to earth (REL) is independent of electrode material (GΙ, CU,

AL). It is hardly influenced by cross section (e.g. REL not much different if cross

Page 18: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

18 of 27

section is 400mm2 or 600 mm2 ). In fact, Sverak’s formula for ground grid resistance

does not even involve diameter or cross section!.

Earthing in LV & MV Systems

Following three cases have been considered for illustrating the concepts of earthing

in LV and MV systems.

Case –1: Source grounded – Equipment ungrounded For easy conceptualization, single-phase network is shown below.

In the above figure,

AB indicates source of supply.

C indicates equipment.

Point B is earthed through earth electrode 'E'

RC indicates equipment load resistance (e.g. 2302 / 1000 = 53)

RΙ indicates equipment insulation resistance (MΩ)

RH indicates resistance of a person (e.g. 2000 ohms)

Under normal conditions, RΙ is very high. Even if a person touches the body, very

little current flows through him. Under the condition of insulation failure of equipment,

RΙ reduces to 0. Current through body is given by,

ΙH = V / (RH + RE1) = 240 / (2000+1) ≅ 120 mA

Page 19: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

19 of 27

This current is small and not sufficient to blow the fuse, but it can be dangerous to a

person (IEEE Std- 116 mA for 1 sec).

Case –2: Source grounded – Equipment grounded

In the above figure B & C are earthed trough earth electrodes E1 & E2.

In the event of insulation failure of equipment RΙ reduces to 0.

Equivalent resistance REQ = RE2 RH = 1Ω 2000Ω ≅ 1Ω

Fault current, ΙF = V / (REQ + RE1) = 240 / (1+1) = 120 A

Current through body, ΙH = 1/(1+2000) x 120 ≅ 60 mA ΙF is significant but not very high. Fuse may or may not blow. But current ΙH, through

body, though low, is not insignificant.

Case –3: Source grounded – Equipment grounded – With Bonding

Page 20: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

20 of 27

Bonding conductor, which is the physical connection between equipment casing and

source, is also called ‘earth continuity conductor’.

Bonding conductor resistance is indicated as RB, which is very small.

Even assuming RB = 0.01 Ω,

Fault current, ΙF = 240 / 0.01 = 24 kA

ΙF is high enough to cause instantaneous fuse blowing. Thus the human safety is

inherently achieved. Hence, it is not reliable to depend solely on earth for return of

fault current. Physical earth continuity conductor (bonding) that runs from equipment

to source is the most reliable conductor for return of earth fault current.

Low Voltage System (415V) Generally Low Voltage System is solidly grounded as per IE rules. Best earth

electrode resistance is approximately 1Ω. on 415 V system. If only earth is used for

return of fault current,

ΙMAX ≤ (415/√3) / 1 ≤ 240 A

If fault current is limited to 240A, neither over current relay nor fuse will ever operate.

Hence, earth shall not be treated as sole equipment grounding conductor for return

of fault current. We can make many supplementary connections to earth from

equipment. But metallic connection (bonding conductor) must exist between

equipment and source neutral. Majority of fault currents shall be carried by

grounding grid conductor and very little by earth.

Page 21: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

21 of 27

EARTHING IN LV SYSTEM CORRECT METHOD

EARTHING IN LV SYSTEM WRONG METHOD

Page 22: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

22 of 27

Unsafe earthing is shown below where no earth continuity conductor is provided.

Safe Earthing is shown below where earth continuity conductor is provided.

MV (Resistance Grounded System) is shown below:

Even here, earth conductor must run all over the plant and must carry return current

back to NGR.

MV (Ungrounded System) is shown below:

Page 23: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

23 of 27

Even for ungrounded system earth continuity conductor is recommended to be

provided.

`Clean’ Earth:

Correct method of electronic equipment earthing is shown below:

Page 24: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

24 of 27

Wrong method of electronic equipment earthing is indicated below:

Monitoring currents through neutral and ground is recommended:

High neutral current indicates unbalance load. High current through ground

conductor indicates earth fault.

Page 25: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

25 of 27

Two cardinal principles of electronic earthing are as follows:

• Neutral conductor and ground conductor are connected only at the service

entrance. From this point on, neutral and ground conductors should not be

bonded together. i.e. neutral and ground conductors should never touch each

other after leaving service entrance panel board.

• Unbalanced load currents shall return only through the neutral back to the

service entrance. Ground shall carry only fault current and not unbalanced

load currents.

UPS Configurations and its earthing Configuration - I

In this configuration neutral and ground is bonded only at the service entrance.

Bypass input neutral and UPS module neutral is solidly bonded and therefore UPS

module is not considered as a separate source. Neutral and ground should not be

bonded at any other point either at UPS or distribution board. Ground shall be used

only for body earthing.

Configuration – II In this configuration bypass transformer is used to feed bypass input of UPS. The

bypass transformer and UPS module is considered as a separately derived source

Page 26: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

26 of 27

since there is no electrical connection between the UPS and input service supply.

Therefore in this particular configuration it is imperative to bond the neutral and

ground at the UPS module. After this point, neutral and ground should not be

bonded further in the distribution circuit.

Configuration - III

Similar to Configuration –I, in this configuration also, UPS is not considered as

separately derived source. However distribution board is provided with an

Page 27: Earthing Rajamani

Reliance Energy Center, Santacruz, Mumbai – 400 055, Tel – (022) 3009 9999

27 of 27

isolation transformer and is considered a separately derived source. Therefore in

this configuration distribution board neutral shall be bonded to ground.

Neutral to ground voltage

It is very important to check the integrity of the neutral to ground bonding for

critical loads. Many electronic systems need ground wire as the signal reference

for the electronic signal. System can malfunction if there is potential difference

between neutral and ground.

It is necessary to measure the voltage between neutral and ground points. Ideally

this voltage should be “zero”, which is practically not achievable. Maximum

acceptable value is typically 2 volt.

The presence of voltage between neutral and ground is because of the

impedance in the length of the cable. During normal operation, the ground wire

will have no current flow while there will be return current flow in the neutral wire.

It is often recommended to use higher cross section for neutral wire (twice the

cross section of phase conductor) for reducing the neutral cable impedance.

Eg.: If a five core 16 sq. mm cable is used, three core is used for phases and two

core is used for neutral.

In practice neutral potential should never be zero in anywhere in the distribution

except near the legitimate neutral to ground bond at the source point. If it is found

zero all along the neutral circuit, it implies that there is a illegal bond between

neutral and ground. Neutral to ground potential of few hundred millivolts is a sign of

healthy distribution and earthing system.

References

• IEEE std – 80 : Guide for safety in AC substation grounding

• IS – 3043 : Code of practice for earthing

• IEEE -1100: Guide for Powering and Grounding Electronic Equipment

• Earthing principles and practices: R W RYDER

• Electrical earthing and accident prevention: Edited by M G SAY