e-mon meter mounting & wiring instructions amr jack 8-pin rj-45, used to connect kwh meter to...

50
Part # E-Mon Meters EMONMETER- INS 2/16/2012 For the latest technical documentation, visit www.novar.com/manuals 1 E-Mon Meter Mounting & Wiring Instructions Table of Contents Introduction ......................................................................................1 Specifications ...................................................................................2 Start-up Checklist...........................................................................10 Precautions .....................................................................................11 Mounting ........................................................................................12 Typical Installation ........................................................................13 Non-typical Installations ................................................................28 Checking Installation .....................................................................34 Pulse ...............................................................................................44 Troubleshooting .............................................................................44 Regulatory Compliance .................................................................50 Introduction The E-Mon meter family consists of the Class 200, Class 5000 meters, Interval Data Recorder (IDR), and Multiple Meter Unit (MMU). The meter family designed as a revenue grade system (unlike basic commercial meters that meter for the presence of power.) These instructions will cover the necessary step procedures, notes, and cautions for installing these systems as well as integrating them with Logic One and Opus. Figure 1. MMU, Current Sensors, and Class 2000 or 5000 meter

Upload: others

Post on 31-Jul-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 1

E-Mon Meter Mounting & Wiring Instructions

Table of Contents Introduction ......................................................................................1

Specifications ...................................................................................2

Start-up Checklist...........................................................................10

Precautions .....................................................................................11

Mounting ........................................................................................12

Typical Installation ........................................................................13

Non-typical Installations ................................................................28

Checking Installation .....................................................................34

Pulse ...............................................................................................44

Troubleshooting .............................................................................44

Regulatory Compliance .................................................................50

Introduction The E-Mon meter family consists of the Class 200, Class 5000 meters,

Interval Data Recorder (IDR), and Multiple Meter Unit (MMU). The

meter family designed as a revenue grade system (unlike basic

commercial meters that meter for the presence of power.) These

instructions will cover the necessary step procedures, notes, and cautions

for installing these systems as well as integrating them with Logic One

and Opus.

Figure 1. MMU, Current Sensors, and Class 2000 or 5000 meter

Page 2: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 2

CAUTION!

Caution should be taken when installing current sensors as they

are not the same as a current transformer. All instructions

should be read carefully prior to beginning any work.

Specifications Class 2000

Features:

Page 3: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 3

Phase Loss:

Not included

Physical Dimensions

Height: 6 3/4"

Width: 5 3/16”

Depth: 3 1/4“

Identification Pictures (How to identify out of the box)

Look to the current sensor rating to determine the correct current sensor

Single display demand meters manufactured from 2001 to present.

� Contains 2 RJ-45 output jacks

� Testing method: Instantaneous kW test

� See typical label below

Figure 2. Typical Class 2000 meter label

Page 4: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 4

Class 5000

Features:

Page 5: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 5

Phase Loss Included

Physical Dimensions

Height: 6 3/4"

Width: 5 3/16”

Depth: 3 1/4“

Identification Pictures (How to identify out of the box)

Look to the current sensor rating to determine the correct current sensor

Single display demand meters manufactured from 2001 to present.

� Contains 2 RJ-45 output jacks

� Testing method: Instantaneous kW test

� See typical label below

Figure 3. Typical Class 5000 meter label

Page 6: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 6

Interval Data Recorder

Features:

Page 7: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 7

Physical Dimensions

Height: 9 1/2"

Width: 6 3/4”

Depth: 3 3/4“

Identification Pictures (How to identify out of the box)

� See typical label below

Figure 4. Typical Interval Data Recorder label

MMU (Multiple Meter Unit)

Features:

Physical Dimensions

See the figures below

Page 8: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 8

Identification Pictures

Figure 5. Multiple Meter Unit

Figure 6. MMU Dimensions by model

Page 9: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 9

Current Sensors

Features:

Physical Dimensions

Interior dimensions may include:

1” x 1 3/8”

1 1/2” x 2 3/4”

3 1/4” x 4 1/2”

6” x 8”

Identification Pictures

Figure 7. Current Sensors

Page 10: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 10

Start-up Checklist See the checklist below.

Page 11: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 11

Precautions The E-Mon D-Mon® Class 2000 meter is wired as a single-, dual- or

three-element unit that is used to monitor electric power to individual

loads after the utility meter. Installation must be performed by

qualified personnel and ONLY according to these instructions and

all applicable electrical codes. E-Mon and its representatives assume no

responsibility for damage or injury resulting from the improper

installation of this meter.

Check the rating and configuration on the meter label to ensure it is

suitable for the intended service. Meters listed for use on 120/208 volt

services cannot be used on 277/480 volt services, and vice versa.

Verify that the meter rating (amperage) is suitable for the intended load.

Compare the color of the arrows on the current sensor assembly to the

chart below to find the amperage of the current sensors.

Sensor Arrow Color Code Sensor Rating

Brown 100 Amp

Red 200 Amp

Yellow 400 Amp

Black 800 Amp

Blue 1600 Amp

Blue 3200 Amp

Mount the meter in the desired location using the mounting flanges

located on the top and bottom of the meter enclosure. This E-Mon D-

Mon meter model must be installed indoors, in an area that is free from moisture and extreme temperatures. (An optional outdoor

enclosure is available; contact E-Mon for details.)

Assemble and install the current sensors around the conductors that are

to be monitored.

NOTE:

The modular jacks located on the meter board are to be used

only in conjunction with E-Mon peripherals. The jacks contain

neutral-accessible circuits.

Take the following precautions during installation:

CAUTION!

Observe national and local electrical codes.

Page 12: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 12

CAUTION!

This device contains a NiMH battery that must be disposed of

properly. Replacing it with the wrong type of battery can cause

an explosion. Only qualified personnel should service this

equipment.

� Reduce the risk of electrical shock or fire. Do not interconnect the

outputs of different Class 2 circuits.

� Do not rely on the xcm.10S as a final safety device.

� Make sure that the 24-VAC power wiring is connected to a

dedicated transformer. No other devices (including the outputs)

should be powered by the transformer connected to the xcm.10S.

� Do not ground the transformer for this module on the secondary

side.

� Make sure that the xcm.10S power cannot be switched off

accidentally. The xcm.10S requires continuous power for proper

operation.

Mounting Mounting is comparable for all devices.

NOTE:

Be sure to read all precautions and warnings prior to

performing any electrical work.

Class 2000 and 5000

Screws should be securely fastened to all flanges of each device to

ensure the device is safely attached to the wall or surface.

MMU

Use the following diagram to attach the different MMU models.

Page 13: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 13

Figure 8. MMU Dimensions

Typical Installation

Meter Terminal Block Connections

Current Sensor Connections

STEP 1: Connect the black and white leads from the current sensor

assembly to the meter terminal block. The current sensor leads can be

extended up to 2000 feet using #14-22 AWG wire and do not have to be

twisted (consult your local electrical codes for proper sizing). When

extending the sensor leads, be sure to note what color lead on the

extension is connected to the black lead from the sensor, and what color

lead on the extension is connected to the white lead from the sensor.

There is no hazardous voltage across the current sensor wires and there

will be no damage if the sensor wires are shorted together. When

connecting current sensor leads to the meter terminal block be sure that

the white wire is connected to the "W" terminal, and the black wire is

connected to the "B" terminal for that phase.

NOTE:

Refer to the Wiring Diagrams, for further information on

current sensor connections.

Page 14: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 14

Voltage Connections

STEP 1: Verify that the voltage supplied to the meter is from the same

source as the loads being monitored by the current sensors. Connect the

line voltage input wires to the meter terminal block. (See the various

installation diagrams.)

NOTE:

LINE VOLTAGE INPUTS MUST CORRESPOND TO THE

SAME CONDUCTOR BEING MONITORED BY THE

CURRENT SENSOR INPUTS. THE CONFIGURATION

SHOWN MUST BE FOLLOWED OR INACCURATE

READINGS WILL RESULT.

These wires are normally #14 AWG, but consult your local electrical

codes for proper sizing. Voltage input conductors require protection; it is

recommended that in-line fuses with a one-amp rating be installed to

protect all phases. Do not connect the voltage wires to the unit while they

are live. Push Lexan shield down over meter terminal block. Apply

voltage to meter only after installation is complete.

IMPORTANT:

The line voltage and current sensor inputs must correspond. If

the phasing between the voltage and the current sensors does

not correspond, inaccurate readings will result.

NOTE:

Refer to Chapter 4, Wiring Diagrams, for further details.

NOTE:

The line voltage input may be taken from wherever it is most

convenient (lugs, another breaker, another subpanel, etc.) as

long as it is the same power source as the items being

monitored. Line voltage cannot be pulled from a subpanel

powered from a different transformer than the item(s) being

monitored.

Page 15: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 15

NOTE:

Push the insulating cover down over the terminal block inside

the meter. Apply voltage to meter only after installation is

complete.

Current Sensor

This section provides you with various installation diagrams depending on your monitoring needs. The diagrams below are standard installation diagrams using one (1) set of current sensors.

Figure 9. Three-phase, three-wire connection (delta system) (In four-wire delta system, NEUTRAL is not used)

Line voltage connection: #14 AWG

Sensor Connection:

B = Black

W = White

* One-amp inline fuse recommended

Page 16: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 16

Figure 10. Three-phase, four-wire connection (wye system)

Line voltage connection: #14 AWG

Sensor Connection:

B = Black

W = White

* One-amp inline fuse recommended

Conductors A-B

Figure 11. Single-phase, three-wire connection (monitoring conductors A-B, A-C or B-C)

Line Voltage Connections: #14 AWG

Sensor Connections:

B=Black lead

W=White lead

* One-amp inline fuses recommended

Page 17: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 17

IMPORTANT:

Line voltage MUST be present at the A- & B-phase voltage

terminals. (You cannot bring power into A- & C-phase

terminals only, or into B- & C-phase terminals only.)

Shorting link MUST be installed on C-phase current sensor terminals.

Figure 12. Conductors B-C

Figure 13. Conductors A-C

For other applications (120V, 1-phase, 2-wire, high-voltage, etc.) contact

E-Mon, toll-free, at (800) 334-3666.

Page 18: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 18

Page 19: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 19

Page 20: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 20

Class 2000 Board Details

Figure 14. Main circuit board located inside meter enclosure

Figure 15. Circuit board located inside door of meter enclosure

Page 21: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 21

� AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon

EnergyTM/IDR

� Peripheral Jack 6-pin RJ-11 jack used to interface meter

withperipherals such as the P2 Pulser or the D/A converter

� Check Sensor LED When lit, indicates that the current sensor is

backwards or on the incorrect phase

� Meter Pulse LED Blinks to show meter load. Blink rate

increaseswith load.

� Power On LED When lit, indicates power to meter is on

� Real-Time Load Press Up once and wait 6 seconds to display

� Push Button present load in kW; press again to return to (Up in

demand option) standard kWh display (update is not

instantaneous). Also used when adjusting time and date for meter

display for demand option.

� RESET Button Press RESET to reset display to zero

� CPU Reset Press CPU to test display. Shows "88888888"

� Push Button then amp rating of meter; to be used by field

service personnel only. � CPU Active LED One blink per second indicates normal

operation.

� Mode Push Button Used to select adjustment mode when setting

up the (Demand only) meter (clock adjust, date adjust, input

select).

� Down Push Button Used when adjusting time and date for meter

display. (Demand only)

� DIP Switch Meter setup. Used ONLY by E-Mon factory

personnel.

Interval Data Recorder

The IDR (Interval Data Recorder) is an energy data collection device.

Installation must be performed by qualified personnel only and must be

in accordance with local and national electrical codes. Novar and E-Mon

are not responsible for damage or injury from improper installation.

The IDR is contained within a NEMA 12 enclosure and is designed for

INDOOR USE ONLY, where ambient temperatures are between +32 and

+120 degrees Fahrenheit. The IDR must be located in an area that is

central to the meters connected to it.

IMPORTANT:

The E-Mon D-Mon® meter that is connected to meter jack #1

on the IDR must be within 100 feet from the IDR, as it supplies

low-voltage power to operate the IDR.

All other meters can be located up to 500 feet from the IDR.

Page 22: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 22

NOTE:

The IDR with modular jacks is designed to operate with E-Mon

D-Mon meters only. Terminal input models can support the

monitoring of third-party metering equipment; contact E-Mon

for further information.

The IDR must be installed in a location according to these guidelines to

ensure continued safe, trouble-free operation.

• Do not install near sensitive radio communications

equipment or receiving antenna systems.

• Do not install near high-energy electrical fields such as

those produced by welding equipment or by high-power

electrical motors.

• Always install in an area that is dry, away from any

potential liquid or chemical splash hazards. Never install

electrical equipment in an area where flammable chemicals

or vapors are present..

• The IDR enclosure's door must be kept closed once

installed. Exposing the internal circuits to dust, dirt, fumes

or high humidity can damage the IDR.

NOTE:

All internal circuits are isolated from the AC line.

NOTE:

IDRs with modular jacks can be powered from either the first

E-Mon D-Mon meter or by an external power supply (requires

120VAC). IDRs with removable screw-type connectors require

an external power supply (provided).

IDRs are supplied with an ID letter for each group of 8 inputs to make

them compatible with the E-Mon EnergyTM software. Available choices

are: A-B, C-D, E-F, G-H, I-J, K-L, M-N, O-P, Q-R, S-T, U-V, W-X and

Y-Z. No other combinations are available. When mixing 8-point and 16-

point IDRs together, it may be necessary to jump up a letter in the

system. As an example, if you have 8-point IDRs labeled “A”, “B” and

“C”, the 16-point IDR to choose would be the E-F unit.

The IDR is available in three configurations.

Modular Jacks (IDR-8 and IDR-16): Supplied with all modular jacks

Page 23: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 23

for use only with the E-Mon D-Mon® meters.

Figure 16. Modular Jacks

Plug-In Screw-Type Connectors (IDR-8 and IDR-16): Supplied with

all plug-in screw-type connectors for use with third-party meters

(electric, gas, water, etc.) that are provided with a dry contact output

pulse.

Figure 17. Screw-Type Connectors

Modular Jacks & Screw-Type Connectors (IDR-16 ONLY): Supplied

with 8 modular jacks and 8 screw-type connectors. Used with a mixture

of E-Mon D-Mon and third-party meters.

Page 24: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 24

Figure 18. Modular Jacks

Bias Resistor for xcms

NOTE!

The xcm.20R is equipped with mechanisms to compensate for

the bias resistor therefore one is not needed. Xcm.10, xcm.20,

and xcm.10S may also be equipped with a jumper that can be

installed in the field. If you install the jumper, then you do not

need to install the bias resistor.

Installing RS-485 local bias resistor pack to NSUB-IDR(x)

Page 25: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 25

Figure 19. Bias Resistor

Page 26: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 26

Figure 20. Bias Resistor 2

Stand-alone (no EMS)

Class 2000 with IDR Modem or Ethernet

Class 2000 with MMU Modem or Ethernet

Class 5000 with Modem or Ethernet

Integrated (EMS installed)

Class 2000 with Logic One

When a Logic One executive is connected to a utility-provided pulse

meter, the Demand Meter Input may count 60 Hz electrical noise because

of electrical leakage in the utility-provided device. To eliminate this

noise, a 22mf/16-volt Tantalum capacitor has been wired to the EC.

Page 27: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 27

The capacitor is connected to the terminals as shown in Figure 5. The

positive (+) lead of the capacitor is wired to Terminal 63 under Demand

Pulse Input and the other lead is wired to Terminal 61 under Outdoor

Temperature Sensor Input.

Figure 21. Wiring Logic One

Connect the Demand Meter contacts to Terminals 63 and 64.

NOTE:

If the capacitor is removed to make the connections, caution

must be used when it is reconnected. Tantalum capacitors are

polarity-sensitive and can be damaged if improperly installed.

Class 2000 (pulse input ) Opus

Class 2000 w IDR (RS485 to Opus)

Class 2000 w MMU (RS485 to Opus) EZ7

Class 5000 (RS485 to Opus) EZ7

*Other supported protocols include LON, Modbus, BACnet

Page 28: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 28

Non-typical Installations

Subtractive The following is an example of Subtractive Metering using an extra set

of current sensors.

Figure 22. Subtractive

Page 29: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 29

Figure 22. Subtractive connections

For each phase you will have two sets of current sensor wires. Join the

two white wires together in a splice (wire nuts, terminal block, etc.) and

bring one extension wire back to the white sensor input screw on the

terminal block in the meter. Do the same for the black wires and repeat

for each phase.

The extra set of current sensors is installed in a backwards direction. This

will subtract the usage of the breaker from the total usage seen by the

meter.

As with all situations where you are using more than one set of sensors

into one meter, all sets of sensors must be of the same amperage rating.

Phase correspondence must be maintained.

Multiple Loads Parallel Current Sensor Wiring Diagrams

Page 30: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 30

Figure 24. Monitoring two three-phase loads

When reading the E-Mon D-Mon® meter, be sure to multiply the meter

reading by the number of sets of sensors in parallel.

Figure 25. Monitoring two two-phase loads

Page 31: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 31

IMPORTANT:

Line voltage MUST be present at the A- & B-phase voltage

Monitoring two two-phase loads: terminals. (You cannot

bring power into A- & C-phase terminals only, or into B- & C-

phase terminals only.)

Shorting link MUST be installed on C-phase current sensor terminals.

Parallel Current Sensor Rules

The E-Mon D-Mon® Class 2000 meter provides extreme flexibility by

allowing additional sets of current sensors to be used in parallel so

multiple locations can be monitored by one meter. This feature allows a

totalized display from two or more loads.

You may use parallel sensors to monitor specific breakers from one

panel, specific breakers from more than one panel, two or more complete

panels, etc.

You may also monitor three-phase loads and single-phase loads for a

totalized reading, provided they are from the same power source.

When paralleling current sensors, the following rules must be followed

for accurate readings.

RULE 1: Current sensors must be installed in complete sets of three.

This is necessary even when paralleling poly-phase with single-phase

loads.

RULE 2: All sensors used in parallel must be of the same amperage

rating (e.g., all 100 amp or all 400 amp). The rating will be determined

by the current rating (amperage) of the meter. A 200-amp meter, for

example, must use extra sets of 200-amp current sensors.

RULE 3: All locations being monitored must have the same power

source. A 480-volt meter, for example cannot monitor a 208- volt load,

nor can a meter monitor two 480-volt loads if they are from a different

originating power source or from different transformers.

RULE 4: The meter reading shown on the display must be multiplied by

the number of sets of current sensors installed.

Example: A meter using 2 sets of current sensors, with a display reading

of 20....2 x 20 = 40....the actual usage is 40.

Page 32: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 32

NOTE:

Sets of current sensors consist of three sensors, one per phase.

The multiplier only applies when extra sets of sensors are

installed on one meter.

If you are only using one set of three sensors, this multiplier DOES NOT

apply.

Breakout Within Panel

Figure 26. Breakout within panel

Page 33: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 33

1. In this instance, there are 2 breakers that need to be separated out

from the panel. They could be for a single tenant or common

area loads, etc.

2. You will notice, the two A phase load wires both run through the

A phase sensor, both B phase load wires through the B phase

sensor and the same for the C phase.

3. Make sure the load wires are going the same direction through

the sensor.

4. When ordering, size the meters amperage for the combined

amperage of the phase with the largest load.

High Voltage Installation (Above 600V)

Page 34: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 34

Figure 27. High voltage

0

Checking Installation

o When testing a meter for proper installation, it is first necessary

to determine if the meter is receiving the proper line voltage

Page 35: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 35

needed to be operational.

o 120 volt , 2-wire meter: deliver 120 volts to A phase voltage

terminal

o 277 volt, 2-wire meter: deliver 277 volts to A phase terminal

o 208/240 volt 3-wire meter: deliver 208 or 240 volts to A and B

phase voltage terminals

o 208 volt 3-phase meter: deliver 208 volts to A , B and C phase

voltage terminals

o 240 volt 3-phase delta meter:240 volts between phases- neutral is

not connected

o 480 volt 3-phase meter: deliver 480 volts to A, B and C phase

voltage terminals

o After the installer has verified proper voltage, he or she must

determine if the meter is functional.

o The step that is common to all the versions of Class 1000, 2000

and 4000 meters, is to disconnect all the current sensors wires

from the meter.

o Before removing the sensor wires, be sure they are labeled

properly so they can be put back into the correct connection

point when the testing is finished.

o The next step in the test varies somewhat for the different

versions of meter. On the next page you will find this next step

outlined for each meter type.

Class 2000 demand series

Once the sensor wires are disconnected, locate the 2-prong test jumper

above the terminal block and short across the two prongs with a

screwdriver or wire. As long as you are shorting the test jumper, the

check sensor light on the power supply circuit board and the ‘check

sensor’ light on the display will remain on. This indicates the meter is

functional.

QAT Checklist

Instantaneous kW test Class 2000 kWh and demand meters

Tools needed for this test: Screwdriver, multi-meter, calculator,

paper and pencil

1. On the meter display circuit board on the inside of the board,

door, there is a row of small pushbuttons, below the large IC

display chip. The second button from the left is the CPU Reset

button. Pressing this button will show the amperage rating of the

meter on the display. Verify that the amperage rating of the

meter matches the amperage rating of the sensors connected to

the meter. Pressing this button will not reset the kWh or kW

readings.

2. Check for the installation error indicators: if either the ‘Check

Sensor’ light inside the meter or the ‘Check Sensor’ icon on the

display is visible, it is likely the meter is installed incorrectly.

Page 36: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 36

Follow the procedure below to verify.

3. On the circuit board on the inside of the meter door, below the

display, there is a row of small buttons. The third button from the

left toggles on the instantaneous kW on the display. Press this

button. The instantaneous kW will show up on the screen, and

the reading will stabilize after a few seconds. Record the kW

reading.

4. Measure each phases current sensor voltage at the input screws,

(range is 0~2 volts), record the three voltages and then add them

together. This number is the Current sensor voltage total, and

will be used in subsequent steps in this test.

5. Perform the calculations shown below. They will result in the

Calculated instantaneous kW. Compare this figure to the

Measured instantaneous kW. If the two figures are within 2 kW,

the meter is installed correctly.

6. If the measured kW is approximately 1/3 low, check for an open

current sensor wire. If it is roughly 2/3 low check for a phasing

error.

QAT kWh Meter Verification

1. Meter type: kWh meter Utility pulse meter Other

(explain)

2. Has the meter been installed? Yes No If no, explain

here and in Deficiencies

3. Have the CTs been installed? Yes No If no, explain

here and in Deficiencies

4. Watts transducer make: - none - Model: - none - Pulse

duration: - Unknown - ms

(Open the Veris meter enclosure to find its model number.)

5. Power for Veris Meter must be the same source and voltage as

the CTs. Confirmed: Yes No

NOTES:

Please describe "Other" or "Unknown" from above parameters.

A. Verify the meter calibration by taking actual readings at the

Main Distribution Panel or service entrance. This test should be

performed during the day or at any time the building is under a

high power condition to yield the most accurate results.

B. Use your amp probe to take amp readings from Phases A, B, and

C at the service entrance conductors in the Main Distribution

Panel and record them in the table below.

Page 37: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 37

C. Use your voltmeter to take volt readings from phases A to B, B

to C, and C to A at the service entrance conductors in the Main

Distribution Panel to determine the correct power value for the

Novar system and record the readings below. The total amps

and volts will be used to calculate the average for each reading

below.

D. Fill in the values (amps and volts at each phase for each reading)

to calculate the Calculated kW below.

E. Fill in the Novar kW reading so the Calculated kW and Novar’s

Power Value can be calculated and the average kW will be used

for a new Power Value, if necessary.

NOTE!

This should be done as soon as possible after the amperage and

voltage readings have been taken to ensure that the building

kW does not change significantly during the test.

CT Ratio from decal < must match > CT Value from Meter Novar

Multiplier Enter Novar Multiplier

Wire Configuration Choose Wire Configuration

Verify Meter is set to the proper wire Configuration: Yes No

PHASE A PHASE B PHASE C TOTAL AVERAGE CALCULATED

KW NOVAR

KW VARIANCE

Amps 000.0

0

000.0

0

000.0

0

000.0

0

000.0

0 0.00

Volts (A-B, B-C,

C-A)

000.0

0

000.0

0

000.0

0

000.0

0

000.0

0

Power Factors

from Meter 0.000 0.000 0.000 0.000

Conductors per

Phase 0 0 0

Conductors in CT 0 0 0

Difference 0 0 0

3-Phase Factor 1.732

Watts to KW 1000 0.00

Enter all data above. Use the “Tab” key to advance to the next field. See Note below !______

Page 38: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 38

NOTE!

If the “Variance” is greater than ± 0.05, contact

[email protected] or call 800.348.1235 for

instructions. If the value for any of the Power Factors for Phase

A, B, or C is less than 0.90 contact [email protected]

Software

NOTE!

The system programming must be downloaded to the xcm.10S

panel before the installation can be checked. Refer to the

xcm10 & 20 Software Installation & Start-Up Guide.

NOTE!

System Programming must be based on the xcm.10S station

template. To obtain the latest version, go to: www.novar.com

and register or log-in, then click on Software Updates.

Adding Novar IP Meter

Step Procedure

1 Obtain the following information & provide to E-MON:

• Serial # of device:

• Sets of Current Sensors installed:

• IP Address:

• Meter Model:

• Store Name:

• Store City & State:

• Emon_Meter_ID (novar):

2 Connect to remote network

3 Open Digi Connect Web Interface (http://meteripaddress)

4 Username: root password: dbps

5 Click Configuration Serial Ports � Port 1

6 Select, connect when data is present on the serial line

7 Verify Match string = ATDT0.0.0.0

8 Verify IP Address = 72.237.119.121 (EICT Servers)

9 Verify TCP Port = 7400

10 Click Apply and reboot (if changes were made)

Page 39: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 39

11 Click AMR tab, click Plus sign, Set Schedule to desired frequency,

then click checkmark to SAVE

• Create a 15 Minute schedule

• Create a Daily schedule for anytime after midnight

12 Click Server, click Plus sign to add a new server, enter a name, enter

phone no. as 0.0.0.0, Checkmark to SAVE

13 Add Location to EmonEnergy:

• Setup Location, enter a name, select connection type IP, enter

the IP Address of remote meter, enter port 3000. If connection

Page 40: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 40

type is missing, go to Connection tab and add new connection

type; select TCP/IP and name it IP.

14 Connect to Location and add to database

• Verify ID is 1A

• Verify Meter Volt & Amps (Verify Hardware)

• Check Power Factor (Power Graph)

• Disable DST, Set Time Zone and send to recorder (Access

Database)

• Set Hardware Time (Read Hardware)

• View & Clear flags (Read Hardware)

15 Set AMR Call-in Schedule

• Select 15 minute Name

• Select Server

• Set AMR Schedule

• Verify AMR Schedule

• Disconnect

16 Add object to EICT Server (E-MON)

17 After E-MON confirms meter communication, Connect to location,

Click Access, Select Location tab, set AMR Schedule

• Select Daily schedule

• Set AMR Schedule

• Verify AMR Schedule

• Disconnect

Adding AcquiSuite Meter

Step Table

Step Procedure

1 Obtain the following information from the device or Novar:

• Serial # of device:

• Meter Multiplier:

• Dial-up #:

• Modbus ID(s):

• Store Name:

• Store City & State:

• Emon_Meter_ID(s):

Ex. BassPro Shops = BAS-xx-yyyyyy

2 If you have access to the device, dial device using dial-up connection

Obvius Devices, username is admin and password may be fiduser,

fidppp, or admin

Page 41: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 41

3 After successfully connecting to the remote device you will see the

connection icon on your taskbar:

4 Open Internet Explorer, go to http://192.168.238.1

5 Click link to login

6 Click Setup/Upload

Page 42: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 42

Dial Up use options *1,2,4,5

IP Address use options *1,2,3,5

7 Configure as shown below

1

2

3

4

5

Page 43: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 43

8 Click apply, then click Upload Data Now, then immediately

disconnect your connection

9 Immediately disconnect your connection after clicking upload data

now by right-clicking the connection icon and click disconnect

10 Check EI server for device under non-commissioning folder and

create objects (see commissioning procedures)

11 Verify Channel Data on EI Server after scheduled call-in time passes

12 Set the date range to today and click OK

Page 44: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 44

13 If Data appears in the value column for the time specified, the meter

is ok to schedule for daily downloads

14 After verifying data is received, dial device and set upload schedule

(not to exceed past 8am eastern), click apply, then click upload

data now, then disconnect immediately.

Pulse The output of the Class 2000 meter is not configurable.

The Class 5000 does not have a pulse output.

Troubleshooting

Class 2000 Demand Meter

Q. How do I figure out if my meter is a kWh or a kWh/demand meter?

A. Your meter has the demand option if its model number ends in “D”.

Q. When providing line voltage to the E-Mon D-Mon® meter, can I tap

off the same breaker I am monitoring?

A. Yes, the voltage can be pulled off the same breaker being monitored.

The meter draws .025 amps, so the load from the meter will have

minimal affect on your readings. (Refer to proper fusing instructions.)

Q. Can the meter line voltage wires be run in the same conduit as the

current sensor leads?

A. Yes, there will be no effect on the meter if the sensor leads and the

meter line voltage wires are run in the same conduit.

Page 45: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 45

Q. What size wire do I use for the line voltage leads?

A. These wires are normally #14 AWG, but be sure to check your local

electrical codes for proper sizing.

Q. What size wire do I use to extend the current sensor leads?

A. These wires are normally 14-22 AWG wire, but consult your local

electrical codes for proper sizing. The sensor wires do not have to be

twisted, and can be extended up to 2000 feet.

Q. The load I need to monitor has parallel feeds. How do I install the

sensors for this application?

A. There are two ways to monitor parallel feeds. The first (and easiest)

way is to clamp the sensors around all feed wires for that phase; if the

core supplied with your meter is not large enough, contact your local

distributor and ask them to order a larger core size for your meter. The

second way is to clamp the sensor around one of the feed wires. When

you read the meter, the final reading must be multiplied by the number of

feed wires for each phase. For example, if you were using 6 conductors

in parallel per phase, you would clamp current sensors around one of the

conductors of each phase, take the reading from the display and multiply

it by six (6) for the parallel conductors. This result would be your total

kWh for the loads being monitored.

Q. I have two subpanels that I would like to monitor with one meter.

These subpanels are fed by different transformers in the building. Can I

parallel sensors and monitor both panels with one meter?

A. No. These panels cannot be monitored by one meter because they are

from different power sources. When you parallel current sensors, all

loads being monitored must be from the same voltage source.

Q. I have 5 breakers in one subpanel I would like to monitor with one

meter. Can this be done without having to parallel current sensors?

A. Yes. Simply run all the breaker wires through one set of current

sensors. Make sure all A-phase circuits are through the A-phase sensor,

and the same for phases B and C. The meter should be sized by the

highest amount of current being monitored by one sensor.

Q. I've gone through the troubleshooting guide and I still can't get my

meter to work. What should I do?

A. Contact Novar's technical department at ########## before

removing the meter. E-Mon's technical department will help you do

detailed troubleshooting of the meter installation in the field and assist

you in getting the meter up and running without you having to remove

and return the meter.

Q. How accurate are the E-Mon D-Mon meters?

A. E-Mon D-Mon meters are certified to ANSI C12.1 metering

standards. (+/-1% from 1-100% of the rated load.)

Page 46: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 46

Q. What are the plugs inside the meter used for?

A. The plugs inside the meter are used to interface E-Mon D-Mon meters

with several available options, including pulse output, D/A output, high-

resolution displays and Automatic Meter Reading systems.

Q. How do I find the cost for kWh to bill my tenants?

A. Your local utility electric bill should list the cost per kWh; if it does

not, give your utility company a call and ask them the cost per kWh.

Q. I have an existing meter that I would like to interface with my energy

management system.

Can I field install the pulse output option into the E-Mon D-Mon meter?

Yes. Simply contact your local distributor and order the Pulser option.

Current Sensors Following is a list of diagnostic messages that may appear on the meter

display.

DIAGNOSTIC MESSAGES SHOULD NOT BE ON

CONTINUOUSLY WHEN THE METER IS INSTALLED PROPERLY

AND IS IN WORKING ORDER.

Line Voltage Diagnostics

The diagnostics program detects line voltage faults by displaying one of

two messages: *PHASE [2] or *PHASE [3]

*PHASE [2]

Indicates that the 3-phase line voltage is not hooked up in the proper

phase sequence. This message should never be seen on the display

continuously. The meter will not display correct electrical data in this

condition. The phase sequence problem must be remedied in order for

the meter to work properly.

*PHASE [3] Indicates that line voltage is missing on Phase B and/or Phase C. This

message will appear whenever the power on either Phase B or Phase C is

off. Screen 5 (Voltage per Phase) will also indicate a loss of line voltage.

Current Sensor Diagnostics

The load current must be at least 1% of the meter's rated load in order to

operate.

Current sensor diagnostics can detect:

1. Reversed current sensors

2. Incorrect phase correspondence

3. Unusually low power factor (0.642 or lower)

Two different sensor diagnostic messages are used: *SENSOR or *PH-

ANGLE

Page 47: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 47

*SENSOR (ABC)

Used to detect reverse phasing of a current sensor. This message should

never be seen in normal operation of a properly installed meter.

*PH-ANGLE (ABC) Used to detect the swapping of current sensor phases. This message

could (in some rare cases) indicate an extremely low power factor

condition. This message may appear intermittently due to changes in line

conditions. It should never be on continuously.

NOTE:

If you have connected the current sensor to all three terminals

and the error message is still appearing, reverse the black and

white wires and repeat the previous steps until the correct

connection is found.

If the *SENSOR error message disappears you have found the correct

sensor connection; however, the current sensor was not installed properly

around the conductor, or the sensor wires were extended and not spliced

together correctly. Correct the sensor installation, reconnect the black

wire to the black terminal and the white wire to the white terminal on the

plug and reinstall the plug into the correct phase terminal for that current

sensor. The error message should disappear and the current sensor is now

installed properly.

If the *SENSOR message does not disappear at any time while trying all

3 inputs both ways, check the AC voltage output from the current sensor

between the black and white wires using an AC voltmeter. It will read

approximately zero volts indicating that the load current is very small (or

zero) or the current sensors are not secured properly (tight connection

between core halves or lead splices not secure).

Once the first current sensor is connected properly and the error message

disappears, repeat the previous procedure for the remaining two current

sensors. When all error messages have disappeared and all sensors are

installed correctly, the meter is operational.

The table below shows possible sensor connection errors that can be

detected and the error message displayed for each. In these conditions,

the current sensor wire pairs are tied to the correct inputs, but the

direction of at least one sensor is reversed as indicated. These are the

most common errors.

NOTE:

Underline denotes incorrect installation.

Page 48: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 48

The table below shows connection errors in which two or three current

sensors are connected to the wrong inputs.

Page 49: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 49

Model & Part Numbers

E-Mon meters can be ordered according to the following:

� Voltage Input 2-wire, 3-wire and 4-wire.

� Configuration: This covers all secondary voltage supplies:

single-phase, split secondary and three-phase, both grounded and

ungrounded.

� Voltage Input:: Up to 600VAC rms

� Current Input: Up to 3200 amps rms AC

� Power Factor: 0.5 leading or lagging

� Frequency: 50 Hz to 60 Hz

� Accuracy: Certified to ANSI C12.16

� Voltage Operating Range: +/- 25% of rated voltage

� Temperature Range: -20 degrees C to +50 degrees C

� Voltage Overload: +25% continuously; +100% for 20 cycles

� Current Overload: Can be overloaded 100% without damaging

meter

� Display: Fully electronic, 8-digit display. Manual reset to zero.

� Standard Ranges: 120/240 volts; 100, 200, 400, 800, 1600 or

3200 amps 115/208 volts; 100, 200, 400, 800, 1600 or 3200 amps

277/480 volts; 100, 200, 400, 800, 1600 or 3200 amps

� High-Voltage Metering: Contact E-Mon's technical department

for 2300 V, 4160 V and higher voltage applications, (800) 334-

3666.

Page 50: E-Mon Meter Mounting & Wiring Instructions AMR Jack 8-pin RJ-45, used to connect kWh meter to E-Mon Energy TM /IDR Peripheral Jack 6-pin RJ-11 jack used to interface meter withperipherals

Part # E-Mon Meters

EMONMETER- INS 2/16/2012

For the latest technical documentation, visit www.novar.com/manuals 50

Regulatory Compliance

Thess devices are UL/CUL listed. Please contact the manufacturer for

specific details.

Opus™ is a registered trademark of Honeywell International Savvy®, Spectrum®, Envoi®, Lingo®, Logic One®, iScope® are registered trademarks of Novar

Ethernet® is a registered trademark of Xerox Corporation E-Mon D-Mon is a registered trademark of Honeywell International

The material in this document is for information purposes only. The content and the product it describes

are subject to change without notice. Novar makes no representations or warranties with respect to this document. In no event shall Novar be liable for technical or editorial omissions or mistakes in this document, nor shall it be liable for any damages, direct or incidental, arising out of or related to the use of this document. No part of this document

may be reproduced in any form or by any means without prior written permission from Novar.

Copyright © 2009 by Honeywell International, Inc.. All Rights Reserved.

Novar 6060 Rockside Woods Blvd.,

Cleveland, OH 44131 Phone: 1.800.348.1235

www.novar.com