dynamic analysis of renewable energy systems and their ... · pdf filedynamic analysis of...
TRANSCRIPT
Dynamic analysis of renewable energy systems and their impact on
smart grid
Suhas Shirbavikar S. Ashok
M. M Babu Narayanan
Abstract – This paper presents the modeling and performance analysis of integrated renewable system connected with the
smart power distribution grid. The renewable energy sources considered in the analysis are wind and biomass generation.
The smart grid has been simulated using PSCAD/EMTDC software considering various dynamic conditions of renewable
energy sources. Results show that when Renewable energy sources are connected to the Distribution system, the power
flow gets altered and this would necessitate a change in the protection system settings. Also, sudden connection or
disconnection of renewable energy sources due to faults etc. may result in unacceptable transients in voltages in the
distribution system which needs to be mitigated. The study reported here makes an important contribution to the concept of smart grid in Indian power distribution system.
Keywords: Electromagnetic transients, Wind, Biomass, Smart grid
I. Introduction
Distributed power generation system is emerging as a complementary infrastructure to the traditional
central power plants. This infrastructure is constructed on
the basis of decentralized generation of electricity close to
consumption sites using Distributed Generation (DG)
sources [1].The increase in DG penetration and the
presence of multiple DG units in electrical proximity to
one another have brought about the concept of the Smart
grid.
A smart grid is a digital upgrade of power
system that is capable of assessing its health in real-time,
predicting its behavior, adaptation to new environment,
handling distributed resources, stochastic demand and optimal response to the smart appliances. A smart grid
also includes diverse and distributed energy sources like
wind, biomass, solar PV etc; to improve overall system
reliability and availability for the benefit of customers
and the environment. Integration of two or more DGs
improves reliability of smart grid but poses a variety of
issues like dynamic response and advanced protection to
take into account the bi directional flow of power.[1]
Transients during start-up might affect the
operation of these plants and other dispersed generation
sources connected at the distribution level. In case of distributed generation which comprises a significant part
of the generation system, their sudden disconnection
might lead to a large unbalance of power and in worst
cases to system collapse. This becomes more pronounced
in cases where the renewable energy sources are
connected to weak AC systems.
The study reported in this paper addresses some
of the above issues and attempts at parametric analysis.
Besides, the study is also aimed at investigating the
optimal location and sizing of renewable energy sources
in the context of typical distribution system in India.
Accurate model of biomass-wind generation suitable for
electromagnetic transient simulation has been developed
and the results are presented in this paper. As an introduction, the paper also gives a status of various
renewable energy sources in India.
II. Biomass energy in India
Biomass is a primary source of energy. Biomass
is very versatile in terms of variety of forms and number of options available for its utilization. Biomass is a
renewable energy source derived from various humane
and natural waste products [2]. Biomass is considered as
renewable source of energy because the organic matter is
generated every day. Present contribution of biomass
energy is between 4% and 18% of total primary energy
consumption of various developed and developing
countries respectively. By 2015 A.D. the situation is
likely to change with increase in the biomass energy
consumption to 25%-40% [2].The estimated potential of
Biomass based renewable energy options in India are as
follows: Biomass energy - 16,000 MW
Biogas Co-generation - 3,500 MW
Total - 19,500 MW
Electrical energy can be obtained from biomass
using one of several processes such as direct combustion,
gasification, pyrolysis, anaerobic digestion etc. One of the
popular methods is direct combustion. In this method
biomass is used to heat up water and generate steam and
the steam is used to rotate a turbine that is connected to a
synchronous generator. Electricity from biomass reduces
our dependence on fossil fuels. Being renewable source of energy there is no threat of running out of resources.
Electricity produced by biomass reduces the threat of
global climate change. Clearing biomass from forest areas
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 62
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
help to prevent forest fires. Biomass by-product methane
gas eliminates odor and reduces air pollution[2]. Use of
biomass waste for electricity generation eliminates the
need to place it in landfills.
Biomass based power generation has been considered to be an important component of the
Distributed generation being planned in India during the
coming decade. Besides, increased penetration of
renewable energy sources would go a long way in
reducing carbon emission from the conventional coal
based thermal power generating stations in India.
III. Wind energy conversion system
The wind-turbine based DG unit is one of the
fastest growing sources of power generation in the world
mainly due to (i) strong worldwide available wind
resources, (ii) environment friendly power generation
source especially suitable for remote areas, and (iii) rapid
technological development [4]. The continuous trend of
increase in the rate of DG connection and penetration
depth of wind-turbine based DG units can provoke
several technical concerns and adverse impact on the operation of distribution systems [4].
Control and protection, stability issues and
power quality of the supply are the main concerns.
However, the presence of an electronically-interfaced DG
unit in a Smart grid environment an ensure stability of the
grid and maintain power quality of the system.
IV. Renewable integration in
smart grid
Smart Grid technology is recognized as a key component of the solution to challenges such as
increasing electric demand, an ageing utility
infrastructure and workforce, and the environmental
impact of greenhouse gases produced during electric
power generation. Integrated Smart Grid solutions
combine advanced sensing technology, two-way high-
speed communications using the utilities assets, 24/7
monitoring and enterprise analysis software and related
services to provide location-specific, real-time
actionable data as well as home energy management
solutions to provide enhanced services for the end-users. As a result, these solutions increase the efficiency
and reliability of the electric grid while reducing the
environmental impact of electric usage benefiting
utilities, their customers, and the environment [6].
Renewable energy sources such as wind or solar
are variable and thus the operating schedules of such
plants are largely dictated by the changing “fuel” supply. This is especially pertinent in the case of wind,
photovoltaic solar and run-of-the-river hydro, none of
which have inherent storage in their power plant design.
These systems cannot be controlled in the same manner
as a conventional generation facility. With low levels of
wind or solar energy penetration the overall effect on
grid operations is limited, yet as the penetration levels
increase so too do the effects. It has been recognized
that as the penetration levels increase, more advanced
control of the power system will be required to maintain
system reliability [6]. These controls include more efficient use of transmission, use of demand response
and intelligent energy storage, all of which can be
enabled through the application of a smart grid. In fact,
the ability to better integrate renewable energy is one of
the driving factors in some smart grid installations.
V. Study system
KIADB industrial feeder
The problems associated with integration of
renewable energy sources in a smart grid have been
studied by considering an actual 11 kV power distribution
feeder in Karnataka. The KIADB Industrial Feeder (Appendix1) in Tumkur District of BESCOM is fed from
Antharasanahalli 220/66/11kV Substation. This is an
industrial feeder which contains most of the HT
consumers. The radial network consists of 8km length of
11 kV feeder. Although there are more than 19 nos. of
Distribution Transformer Centres (DTC) of various
ratings, transformers of lower ratings have been lumped
with their equivalent ratings being considered for the
study without changing the characteristics of the loads.
Ratings of transformers are 250kVA, 500kVA and 1000
kVA respectively. The utility substation is represented as
a 11kV source with its equivalent power frequency short circuit capacity of 750 MVA.
The 11 kV feeder includes two DG units. DG1 is
a 1.875-MVA conventional Biomass synchronous
generator equipped with excitation and governor control
systems. DG2 represents a fixed-speed induction
generator type wind-turbine set with rated capacity of
1.25-MVA.
VI. System model
The well known PSCAD/EMTDC software
package is used for the simulation of the Smart-grid
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 63
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
system of Fig. 6. The component models used for the
simulation are as follows:
The main grid is represented by an equivalent model of
an 11-kV three-phase voltage source with the short-
circuit capacity of 750 MVA and appropriate X/R ratio.
The loads are modelled as constant impedances. DG1 is
modelled as a single-mass synchronous machine. The
machine electrical system is represented in the d-q-0
frame with one rotor winding on each axis. The excitation and governor systems of the machine are also
included in the model. During start-up procedure, the
synchronous generator is treated as a source where the
rotor speed is constant. After 0.3 s the machine model is
activated and at 0.4 s the rotor speed is released to be
adjusted by the governor. The synchronous machine
parameters are given in table given below. DG2 is
modelled as a squirrel cage induction generator with a
wind source, turbine and a governor.
A. Biomass generator model
The electrical part of DG1 is represented by a
synchronous generator connected to the utility grid. The biomass system consists of synchronous generator,
exciter, steam turbine and governor. The rated power is
1.875 MVA, rated voltage 11 kV (L-L rms) and
generated power is 1.5 MW.
B. Wind generator Model
The electrical part of DG2 is represented by a
squirrel cage induction generator connected to the utility
grid. The mechanical systems of the DG2 are also
modelled. The variable nature of the wind speed and its
reflection on the input mechanical torque of the induction
generator are also modelled by a wind-speed control
panel. The rated power is 1.25 MVA, rated voltage is 11
kV and generated power is 1.4 MW.
VII. Study cases
A. Optimum location of REs
In the first study we will find the optimal locations of
both the renewable. The objective function is to achieve
minimum total losses in the network. There is a
constraint for the optimal location.
(i) Voltage should be within permissible limits (10.5 kV
to 11.5 kV).
Annual energy loss calculation is given in table 1.
TABLE 1
ANNUAL ENERGY LOSS CALCULATION
Table 1 show that when we integrate renewable energy
sources into the system, the losses reduces the losses in the system and the optimum location of biomass
generator is Bus 5 and wind generator is Bus 8.
B. Steady state analysis Base case consists of 11 kV radial distribution network
without the integration of any renewable energy sources. Power flow study was conducted. The PSCAD/EMTDC
representation of the 11 kV study system of fig 1 is
shown in fig 4.The bus 5 and bus 8 voltages, active and
reactive powers are given in table 2.
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 64
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
TABLE 2
COMPARISON OF VOLTAGE, POWER AND REACTIVE POWER IN RENEWABLE INTEGRATION
Table 2 shows that when we integrate renewable into the
system, the voltage profile on remote buses will improve. Simultaneously reliability of the system increased.
Comparison graphs of voltages, active powers and
reactive powers during integration of renewables are
shown {fig 1(a), 1(b) and 1(c)} below.
Fig 1(a) Voltages at all buses
Fig 1(b) Active powers at all buses
Fig 1(c) Reactive powers at all buses
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 65
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
C. Dynamic Analysis
In this case, power flow studies were initially
carried out by including the two renewable energy
sources. Subsequently, the impact of disconnection of
renewable sources is simulated by disconnecting each of
the two sources, one at a time and observing the change
in the load flow as also the voltage profile of the buses to
which these sources are originally connected in the
distribution system. At t=1 sec, wind system is
disconnected and remains in the same condition.
Dynamic analysis of renewable integration with the
smart grid is studied. Comparison graphs of voltages, active powers and reactive powers during integration of
renewables are shown in Table 3 and same is represented
as fig. 2(a)(b) and(c) in graphical representation.
TABLE 3
COMPARISON OF VOLTAGE, POWER AND REACTIVE POWER IN RENEWABLE DISCONNECTION
Fig 2(a) Voltages at all buses
Fig 2(b) Active power at all buses
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 66
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
Fig 2(c) Reactive power at all buses
We observe that when renewable are disconnected from
the network, voltage profile of all buses reduces and
reliability of the system weakens. Simultaneously load
on the grid increases in view of disconnected renewable.
D. Fault analysis
Case 1: In this case a 3phase symmetrical fault is
applied on the bus 5. The fault occurs at t= 1 sec and
remains for 5 cycles in the system. The bus voltage and
fault current without renewable are shown in fig below:-
Fig 3(a) Fault Voltage at Bus 5 without REs
Fig 3(b) Fault current at Bus 5 without REs
Case 2: In this case a 3phase symmetrical fault is
applied on the bus 5. The fault occurs at t= 1 sec and
remains for 5 cycles in the system. The bus voltage and
fault current with biomass renewable integration are
shown in fig below:-
Fig 3(c) Fault Voltage at Bus 5 with biomass integration
Fig 3(d) Fault current at Bus 5 with biomass integration
Case 3: In this case a 3phase symmetrical fault is
applied on the bus 5. The fault occurs at t= 1 sec and
remains for 5 cycles in the system. The bus voltage and
fault current with wind renewable are shown in fig
below:-
Fig 3(e) Fault Voltage at Bus 5 with wind integration
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 67
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
Fig 3(f) Fault current at Bus 5 with wind integration
We observe from all the above mentioned 3 cases that
when fault is cleared at t=1 sec, in that case time of
recovery voltage with biomass renewable integration is
very less but with wind integration time of recovery
voltage is very high. Table 4 shows the comparison of
TRVs with biomass and wind integration.
TABLE 4
COMPARISON OF TIME OF RECOVERY
VOLTAGES
Faulted
bus
number
Without
REs
integration
(TRV) in
sec
With only
biomass
integration(TRV)
in sec
With only
wind(TRV)
in sec
Bus 5 0.001 sec 0.001 sec 2.5 sec
It is seen from table 4 that time of recovery voltage is
more in case of wind induction generator.
E.Unbalance voltage
In this case voltage unbalance occurs in the system and
Fig 4.1(a) shows the unbalance in voltage without
renewable integration and fig 4.1(b) shows the unbalance
with integration of renewables.
Time in sec
Time ... 0.225 0.250 0.275 0.300 0.325 0.350 0.375 0.400 0.425 ...
...
...
-8.0
-6.0
-4.0
-2.0
0.0
2.0
4.0
6.0
8.0
Vo
lta
ge
(kV
)
Es
Fig 4.1(a) Voltage unbalances at bus 1 without REs
Time in sec
1.750 1.775 1.800 1.825 1.850 1.875 1.900 1.925 ...
...
...
-8.0
-6.0
-4.0
-2.0
0.0
2.0
4.0
6.0
8.0
Vo
lta
ge
(kV
)
Es
Fig 4.1(b) Voltage unbalances at bus 1with REs
It is observed that at t= 1sec, renewables are integrated
into the system and percentage unbalance reduced
significantly. Table 5 shows the comparison of
percentage unbalance without renewable and with
renewables.
TABLE 5
COMPARISON OF PERCENTAGE UNBALANCE
WITH AND WITHOUT RENEWABLES
Bus No Voltage unbalance
without REs(in %)
Voltage unbalance
with REs (in %)
Near feeder 6.4 1.3
At biomass
bus
6.5 1.24
At wind bus 6.71 1.0
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 68
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
F. Islanding phenomenon
An island is “That part of a power system
consisting of one or more power sources and load that is,
for some period of time, separated from the rest of the
system.” An effect of large power unbalance in a newly
formed island can be serious; such an island may not
survive very long. On the other hand an island with
perfect production balance can very well survive for a
long time, even if there are no voltage or frequency
controllers. Islanding condition occurs when breaker is
intentionally opened to create an island. A controller has
been designed in order to shed the loads to bring the
frequency at steady state condition i.e.50 Hz. A priority
index for shedding of loads has been shown in table 6.
TABLE 6
PRIORITY INDEX FOR LOAD SHEDDING
Fig 5 shows the algorithm for load shedding.
Main : Graphs
5.60 5.80 6.00 6.20 6.40 6.60 6.80 7.00 ...
...
...
49.900
49.920
49.940
49.960
49.980
50.000
y
Frequency
Fig 5.1(a) Frequency before controller operation
Fig 5.1 (a) shows the condition when grid is
disconnected and renewables are not sufficient to supply
the entire load of the network.
Main : Graphs
5.900 5.950 6.000 6.050 6.100 6.150 6.200 6.250 ...
...
...
49.940
49.950
49.960
49.970
49.980
49.990
50.000
50.010
50.020
50.030
y
Frequency
Fig 5.1(b) Frequency after controller operation
Fig 5.1 (b) shows the condition with controller operation
and shedding of the load as per priority index(Table 6) in
order to bring the frequency back to 50 Hz.
VII Results & Discussion
This paper investigates dynamics of a 11-kV
multiple DG smart-grid system and performance of the
adopted power management strategies in two analysis,(a)
steady state analysis,(b) dynamic analysis. In steady state
analysis when we connect renewable energy sources at
bus 5 and bus 8.In dynamic analysis the radial network
consists of biomass and wind generators. During
disconnection of renewable voltage profile is reduced.
When 3phase symmetrical fault is applied on bus 5, it is
observed that time of recovery voltage is very high in
case of wind integration. During unbalance percentage
unbalance reduced with renewable integration. In
Islanding phenomenon algorithm is developed for load
shedding of non-sensitive loads.
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 69
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
Fig 5 Algorithm for load shedding
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 70
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
A sudden fluctuation in power and voltage is observed
which may cause severe disturbance in the systems,
which needs to be mitigated. The future work is to
mitigate these transients with different techniques.
VIII. Conclusion
The smart grid has been simulated using
PSCAD/EMTDC software considering various dynamic
conditions of renewable energy sources. Results show
that when Renewable energy sources are connected to
the Distribution system, the voltage profile gets
improved and this improves reliability of the system.
Also, sudden connection or disconnection of renewable energy sources due to faults etc. may result in
unacceptable transients in voltages in the distribution
system which needs to be mitigated.
IX. Acknowledgement
This work is carried out at Central Power Research
Institute, Bangalore. The authors wish to thank CPRI and
NITC for permitting to publish this work. The assistance
rendered by Ms. Reshma, Project Engineer in simulation is gratefully acknowledged.
XII. References [1] Robert H. Lasseter, “Microgrids and Distributed
Generation” Transaction on journal of Energy
Engineering, American Society of Civil Engineers, Sept.
2007
[2] Dr. Mrinalini Das ,Nripen Das,” Biomass : A
sustainable source of energy”IEEE-transaction ,Volume
1 ,issue 3,pp 978-982,2009. [3] Amit Kumar Jindal, Aniruddha M. Gole and
Dharshana Muthumuni,”Modeling and performance
analysis of an integrated wind/diesel power system for
off-grid Locations Fifteenth National Power Systems
Conference (NPSC) Transaction pp 574-579,
December,2008.
[4]Badrul Chowdhury,Srinivas Chellapilla”Double-fed
induction generator control for variable speed
wind power generation” Science@Direct on Electric
Power Research,Vol.76,PP.786-800,2006.
[5] F. Mei, B. C. Pal: Modeling and small-signal analysis of a grid connected doublyfed induction
generator, presented at Proceeding of IEEE PES General
Meeting 2005, San Francisco, USA, 2005.
[6] X. P. Zhang,” A Framework for Operation and
Control of Smart Grids with Distributed
Generation”,IEEE transaction Vol 29,issue 2,pp 1-
5,2008.
Authors’ information
1 Suhas shirbavikar, department of Electrical Engg., NIT
Calicut ([email protected])
2 S.Ashok, department of Electrical Engg. NIT Calicut
3 M. M Babu Narayanan, central power research
institute, Bangalore.
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 71
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
#1
#2
#1
#2
#1
#2
#1
#2
#1
#2
P = 1.528Q = 1.332V = 10.53
V
A
P = 0.8802Q = 0.9511V = 10.37
V
A
BUS 6 BUS 7
0.099[ohm] 0.27[ohm]
1.16[ohm] 1.008[ohm]
0.54 [mH]0.19 [mH]
2.33 [mH] 2.35[mH]
0.305[ohm]
0.61 [mH]
#1
#2
P = 0.5635Q = 0.7653V = 10.26
V
A
BUS 8
1.12[ohm]
2.34[mH]
BUS 1
#1
#2
0.2[ohm]
0.4 [mH]
0.26[ohm]
0.52[mH]
P = 0.9407Q = 1.785V = 10.92
V
A
EF IF
VTIT 3
IfEfEf0
Vref
Exciter_(AC1A)
Vref0
S2M
STe
3
AV
Tm
Tm0
Ef0
Tmw
Ef If
1.875 MVA1.5 MW6.3kV0.1 kA
S / Hinhold
out
P = 1.571Q = 1.359V = 10.79
V
A
TIME
BETA
ES Vw
TmVw
Beta
W P
Wind TurbineMOD 5 Type
GR
TIME
Wind TurbineGovernor
Beta
PgMOD 2 Type
PwindA
B
Ctrl
Ctrl = 1
CNT
0.72
VwES
Wind SourceMean
1.0
A
B
Ctrl
Ctrl = 1
CNT
*N
D
N/D
3.0Pole pairs
1.01308
*-1
I M
W
S
Twind gen
*-1
2 Pi *50.0
P = 0.03516Q = -0.4148
V = 10.26
V
A
P = 0.9496Q = 1.79
V = 10.97
V
A
P = 1.467Q = 0.07325V = 10.79
V
A
W
W
1.0
w
Wref
Cv
Steam Gov 2
Iv
Steam_Tur_2
w Tm1
Tm2WrefIv
CvTmstdy
Ef
POUT QOUT
P =
0.1
64
3Q
= 0
.08
17
1V
= 0
.41
24
V A
P =
0.3
29
3Q
= 0
.16
22
V =
0.4
10
4
V A
P =
0.1
63
5Q
= 0
.08
08
4V
= 0
.41
V A
P =
0.1
58
8Q
= 0
.07
99
4V
= 0
.40
89
V A
P =
0.6
31
6Q
= 0
.30
76
V =
0.3
99
V A
P =
0.3
07
Q =
0.1
49
4V
= 0
.39
31
V A
P =
0.5
98
7Q
= 0
.29
19
V =
0.3
88
7
V A
Main : Controls
30
0
Es
9.52381
200
0
GR
25.3968
RLC
P+jQ
P+jQ P+jQ
P+jQ
P+jQ
P+jQ
P+jQ
BUS 5P = 0.2618Q = 1.382V = 10.79
V
A
P = 0.4298Q = 1.481V = 10.82
V
A
BUS 4BUS 3P = 0.7609Q = 1.677V = 10.83
V
A
BUS 2P = 0.9338Q = 1.781V = 10.88
V
A
Fig 6.PSCAD/EMTDC model of biomass and wind integrated system
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 72
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.
Appendix
Study system is taken as KIADB feeder in Tumkur
district in Karnataka. Rabbit conductor is used for
transmission line .The total length of distribution
network is 8 kms.17 distribution transformers are taken
into consideration for the study. Ratings of transformers
are 250kVA, 500kVA and 1000 kVA respectively.
Loading on the transformer is 90% as per the survey
conducted. The utility substation is represented as a
11kV source with its equivalent power frequency short
circuit capacity of 750 MVA.
Study system
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 73
Department of Electrical Engineering, Univ. College of Engg., Osmania University, Hyderabad, A.P, INDIA.