Page 1: SUBMITTAL AR24KSFPDWQXCV / AR24KSFPDWQNCV …...• The outdoor unit heat exchanger shall be aluminum, flat fin, micro channel Samsung HVAC maintains a policy of ongoing development,

Job Name LocationPurchaser EngineerSubmitted to Reference Approval ConstructionUnit Designation Schedule #

SUBMITTAL AR24KSFPDWQXCV / AR24KSFPDWQNCV Page 1 of 3

Samsung "Quantum", wall mounted evaporator, split system

QS-RAC-022017A www.SamsungHVAC.com

General Information• Outdoor unit shall provide 208/230V power to indoor unit via 14 AWG X 3 interconnect power cable• Electro-static, washable, main filter as standard

Construction• Indoor unit chassis shall be UL94 V0 with a galvanized steel mounting bracket• The outdoor unit shall be galvanized steel with a baked on powder coated finishfor durability

Heat Exchanger• The indoor unit heat exchanger shall be mechanically bonded fin to copper tube

Refrigerant System• The compressor shall be hermetically sealed, inverter controlled, BLDC Rotary• Refrigerant flow shall be controlled by electronic expansion valve at outdoor unit

Indoor Fan• The indoor fan shall be a single, antibacterial cross-flow type• Three fan speed settings and auto setting• Automatic (motorized) vertical swing louver (up/down)

• Control signal shall be DDC type signal• Interconnect control wiring shall be 16 AWG X 2 shielded wire between outdoorand indoor units

• The indoor unit shall ship with a wireless controller and batteries as standard• Optional wired control options available

Convenience• Auto restart• LED status indicator lights on front of the indoor unit to display unit operation and error status• "Fast Comfort" mode to quickly reach set temperature• Auto changeover• 24 hour, single event timer• Good'sleep mode• Quiet mode• Dry mode• Single event, ON/OFF timer• Single User Mode to reduce energy consumption during low demand operation • Air filter cleaning can be done easily without opening the indoor unit• Beep ON/OFF with included wireless controller

AR24KSFPDWQAR24KSFPDWQNCVAR24KSFPDWQXCV

Nominal Capacity* Cooling / Heating (Btu/h) 22,000 / 24,000Cooling (Btu/h) 6,100 - 27,300Heating (Btu/h) 4,400 - 28,000

17 / 10.53.079.0

9035289

Voltage ø / V / Hz 1 / 208-230 / 60176 - 254

Cooling (A) 2.4 / 9.8 / 13.0Heating (A) 1.9 / 10.5 / 11.5

Max. Breaker Amps 2519.0

Indoor Unit 41 15/16 X 11 3/4 X 9 1/16Outdoor Unit 34 5/8 X 31 9/32 X 12 3/16Indoor Unit 25.35Outdoor Unit 115.74

11/16" OD

Indoor Unit (dB) Quiet / High 28 / 45Outdoor Unit (dB) High 54

14 ≤ T ≤ 115Heating 5 ≤ T ≤ 75Cooling 61 ≤ T ≤ 90Heating T ≤ 80

High side (flare) 1/4"Low side (flare) 5/8"

98 / 1049

R410AElectronic Expansion Valve

Factory Charge oz. 51.225 feet

0.16 oz./ft. over 25 ft.

BLDC RotaryRLA A 13.5

BLDC motor with cross-flow fan (1)Air Volume CFM (High) 700Consumption Watts 25FLA Amps 0.12

BLDC motor with axial fan (1)Output Watts 39FLA Amps 0.17Air Volume CFM (max.) 1,950

DB61-06087AAspen Mini Orange ASP-MO-UNIV 110-250Blue Diamond BD-BLUE-230Standard AR-WRS 1

Premium (w/scheduling) AR-WRP 2

DB93-11412ADB93-11405A

MIM-B14

CKN-25025' - ILS250950' - ILS5009

Front WBMF-9/12/18Back WBMB-9/12/18/36

Certifications

Devices

Warranty

Condenser Fan

AHRI Reference Number

Wired controller sub-PCB harnessWired controller sub-PCB

External contract control interface module (requires sub-PCB and sub-PCB harness)

Optional Accessories

Wireless controller holder

Specifications

ModelSystem Model NumberIndoor Unit Model NumberOutdoor Unit Model Number

Power

Working Voltage Range (VAC)Operating Current (Min./Std./Max.)

Performance

Capacity Range

SEER / EER

HSPF

Min. Circuit Ampacity (A)

COP

Sound Pressure Level

Condensate Connection

Dimensions

W X H X D (inches)

Weight (lbs.)

Pipe ConnectionsIndoor & Outdoor

Maximum / Minimum Line Set Length (ft.)Maximum Vertical Separation (ft.)

Operating Temperatures ( F)

OutdoorCooling

Indoor

Refrigerant

TypeControl Method

Charged for Additional Refrigerant

CompressorType

Wired controller

Evaporator Fan

Type

Wall bracket (for outdoor unit)

Motor

Condensate pump

Safety

ETL & ETLcPCB fuses, indoor unit terminal block thermal fuse, current transformer, over-voltage protection, crankcase heating, temperature limit protection logic, compressor overload sensing

7 Years compressor, 5 years parts, 90 days limited labor (registration required)

Line sets - insulated and flared, interconnect cables includedWind Baffle / Guard

1 AR-WRS includes MWR-WH00 wired controller, sub-PCB (DB93-11412A), and sub-PCB harness (DB93-11405A)2 AR-WRP includes MWR-WE10 wired controller, sub-PCB (DB93-11412A), and sub-PCB harness (DB93-11405A)

* Nominal heating capacities are based on: Indoor temperature: 70 F DB, 60 F WB. Outdoor temperature: 47 F DB, 43°F WB* Nominal cooling capacities are based on: Indoor temperature: 80 F DB, 67 F WB. Outdoor temperature: 95 F DB, 75°F WB

• The outdoor unit heat exchanger shall be aluminum, flat fin, micro channel

Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice. Refer to www.AHRIdirectory.org for current reference numbers.

Page 2: SUBMITTAL AR24KSFPDWQXCV / AR24KSFPDWQNCV …...• The outdoor unit heat exchanger shall be aluminum, flat fin, micro channel Samsung HVAC maintains a policy of ongoing development,

Unit: inches

888-699-6067 www.SamsungHVAC.com

Indoor unit dimensional drawing

SUBMITTAL AR24KSFPDWQXCV / AR24KSFPDWQNCV Samsung "Quantum", wall mounted evaporator, split system

Page 2 of 3

20 3/4 20 3/4

22 7/16

2 7/16 1 15/16

7 19/32

11 3

/4

1 5/16 5 1/2 3 15/16 2 11/16

1 5/16

7 19/32

2 3/8

6 5/16

1 31/32

41 15/16

11 1

3/16

9 5/16

9 1/16

11 3

/42 3/8

2 5/81 31/32

Unit outline

INSTALLATION PLATERight rear pipe hole

TOP

LEFT RIGHTFRONT

BOTTOM

2 - Ø 2 9/16

Page 3: SUBMITTAL AR24KSFPDWQXCV / AR24KSFPDWQNCV …...• The outdoor unit heat exchanger shall be aluminum, flat fin, micro channel Samsung HVAC maintains a policy of ongoing development,

Minimum clearance from walls and ceiling

L1 L2

L1 L2

F1 F2

F1 F2

L1 L2 F1 F2

Indoor Unit

Outdoor Unit

CommunicationMain Power

Basic power and communication wiringbetween indoor and outdoor units

888-699-6067 www.SamsungHVAC.com

Outdoor unit dimensional drawing

SUBMITTAL AR24KSFPDWQXCV / AR24KSFPDWQNCV Samsung "Quantum", wall mounted evaporator, split system

Page 3 of 3

TOP(pictured without valve/wire cover on right side)

FRONT(pictured without valve/wire cover on right side)

RIGHT(pictured without valve/wire cover)

4 x ø 1 2

34 5/8

26

22 1/16 12 3/16