P122Site Acceptance Test Report
MiCOM P122
87B1-BBay Ref:Substation:
SUMMARYREVISION
PAGES01
1PURPOSE OF TESTS2X
2REFERENCE DOCUMENT2X
3SCOPE2X
4RELAY TERMINLOGY 3X
5TEST EQUIPMENT3X
6PRE-REQUISTES3X
7PROCEDURES4X
8RECORD TEST SHEET5X
8.1 RELAY INFORMATION
8.2 CT DATA:
8.3 PRODUCT CHECKS
8.4 MEASURMENT VALUE TEST:
8.5 87B HIGH IMPEDANCE DIFFERENTIAL PROTECTION
8.6 EXTERNAL STABILIZING RESITANCE MEASURMENT
8.7 EXTERNAL NON LINEAR RESITANCE MEASURMENT
8.8 CT SECONDARY RESISTANCE MEASURMENT :
8.9 BINARY INPUT TEST :
8.10 BINARY OUTPUT TEST:
8.11 FIXED LED INDICATIONS TEST:
8.12 LED INDICATIONS TEST:
8.13 FINAL CHECK
1 PURPOSE OF TESTSThe purpose of the tests is to check the full functionality of the protection relay.This procedure does not intend to check that all alarms and trips are correctly sent to the DCS or SCADA level. This part is already developed into dedicated DCS or SCADA Commissioning procedures.2 REFERENCE DOCUMENTSDOCUMENTDOCUMENT REFERENCEVERSION/ DATEREMARKS
Protection Line Diagram
Schematic Drawing
Service Manual
Operation Manual
Protection Relay Coordination Principles
Relay setting Calculation
LED Display Configuration
3 SCOPE
Substation Name :-
Diameter:
Bay :
Panel Number :
Relay Denomination in Scheme
Scheme to be Checked Relay Functionality Test.
4 TERMINOLOGYCode ( ANSI) Terminology
87BBusbar High Impedance Differential Protection
5 TEST EQUIPMENT USED
Sl NoDescriptionMakeEquipment
Sl No.Calibration dateCalibration due date
1.Secondary Injection Kit
2.Multimeter
3.LaptopNA
Setting software
Type : MICOM S1 Studio
Version : 2.14
6 PRE - REQUISITES
PRE-REQUISITESREMARKS
All Safety Condition Are Ok
All Competent Personnel Available For The Test
Ac & Dc Supply Availability And Security
PPE Safety Available.
All Other Relevant Safety Instructions Been Followed
Coordination With Other Parties ( GIS, Transformer, Etc..)
7 TEST PROCEDURESThe following procedures are written for demonstrating the main protection functions of the P821 relay using an Omicron test set or similar. The tests do not test the boundaries of all available function characteristics. They do test that the function is operating at a point on one chosen characteristic. This document is to be referred to when performing commissioning tests in association with the commissioning section of the service manual.
NOTE :
All the Test are performed in the Test Switch.
Omicron CMC156 Test Equipment or Any Equivalent To Be Used7.1 87RB High Impedance Differential Relay (87 Protection)- Inject Secondary Voltage across the metrosell (Phase R), and increase voltage until the relay operates.
- Record the operating Voltage and current at both the relay terminal and metrosell.-Repeat same procedure above for phase Y and B.7.2 Testing of Binary Inputs :
This test checks that all the opto-isolated inputs on the relay are functioning correctly. (3 opto-isolated inputs for the P122).
The opto-isolated inputs should be energized one at a time. Ensuring correct polarity, connect the auxiliary voltage to the appropriate terminals for the input being tested.
The line "INPUTS" in the "OP. PARAMETERS" menu gives the state of each input, a '1' indicating an energized input and a '0' indicating a de-energized input. When each input is energized one of the digits on the bottom line of the display will change to indicate the new state of the inputs.
7.3 Testing of Binary Outputs :
This test checks that all the output relays are functioning correctly. (6 output relays for the P122).The output relays should be energised one at a time. Connect a continuity tester across the terminals corresponding to output relay 1 .
In the following window in the "Relay Satus" sub-menu of the "OP PARAMETERS" menu:
Relay 8 7 6 5 4 3 2 1
Status 0 0 0 0 0 0 0 1
Repeat the test for each relay.Operation will be confirmed by the continuity tester operating for a normally open contact and ceasing to operate for a normally closed contact.
NOTE: It should be ensured that thermal ratings of anything connected to the output relays during the test procedure is not exceeded by the associated output relay being operated for too long. It is therefore advised that the time between application and removal of relay testing kept to the minimum.If the Outputs are assigned for function this will be tested along with Functional test of relays.
8 RECORD TEST SHEET8.1 RELAY INFORMATION
Type No.:P122Designation :
Model No :Nominal Current :
Serial Number Nominal Voltage` :
Firmware Version :Aux. Volts :
8.2 CT DATA:
CT rated primary current set as
CT rated secondary current set as
Ignd-CT rated primary current set as
Ignd-CT rated secondary current set as
8.3 PRODUCT CHECKS Relay damaged?
Rating information correct for installation?
Case earth installed?
External wiring checked against diagram?
Test block connections checked?
Measured auxiliary supplyV dc
LCD front panel display
Clock set to local time?
Time maintained when aux. supply removed?
8.4 MEASURMENT VALUE TEST:
Current Measurement
Phase injectedCurrent injected (Amps)Current read on relay display (A)
PH-NIRIYIBIN
L1-E1.000
L2-E1.000
L3-E1.000
L1-L2-L31.00
8.5 HIGH IMPEDANCE DIFF CURRENT 87B: PhaseMeasured Operating Voltage Measured Current at MetrosellMeasured Current at RelayCurrent Setting of RelayTime settingOperating Time at 2* Oper.V
R
Y
B
8.6 EXTERNAL STABILIZING RESITANCE MEASURMENT : PhaseDesignation In DrawingTheoretical ValueMeasured Value
RR111
YR121
BR131
8.7 EXTERNAL NON LINEAR (MERTCIL) RESITANCE MEASURMENT : PhaseDesignation In DrawingTheoretical ValueMeasured Value
RR1
YR2
BR3
8.8 CT SECONDARY RESISTANCE MEASURMENT : PhaseTheoretical ValueMeasured Value
R
Y
B
8.9 BINARY INPUT TEST :
Input No.Terminal No.ActiveFunction AssignedsheetResult
122-24HighNOT USED**
226-28HighNOT USED**
317-19HighNOT USED**
* SPARE: wired up to terminal blocks.
** NOT USED: Not wired.
8.10 BINARY OUTPUT TEST:
Output No.Terminal No.TypeFunction Assigned
(Aux relay operated)sheetResult
12-6NONOT USED**
2-4NC
28-12NONOT USED**
8-10NC
314-16NOTO BUS 1A GROUP-B262
418-20NONOT USED**
51-3NOSPARE*264
65-7NOSPARE*264
* SPARE: wired up to terminal blocks.
** NOT USED: Not wired.
8.11 FIXED LED INDICATIONS TEST:
LED No.LED LabelColorResult
1TripRed
2AlarmYellow
3WarningYellow
4healthyGreen
8.12 LED INDICATIONS TEST: ( LEFT SIDE LED)
LED No.LED LabelColorResult
1
2
3
4
8.13 FINAL CHECKSItem
Description Result
1All test equipment, leads, shorts and test block removed safely?
2Disturbed customer wiring re-checked?
3All commissioning tests disabled?
4Circuit breaker operations counter reset?
5Current counters reset?
6Event records reset?
7Fault records reset?
8Disturbance records reset?
9Alarms reset?
10LEDs reset?
11Secondary front cover replaced? (If applicable)
REMARKS
END OF REPORT
AREVA T&DGCCIA / SNCL
SignatureSignature
NameName
DateDate