TWO(2) X 500MW
MONG DUONG 1 THERMAL POWER PLANT
avi anghorneSenior Mec Engineer07-Dec-12
-
8/12/2019 MD1-0-V-121-01-00001
2/2
Pyry CommentTwo(2) x 500MW Mong Duong 1 Thermal Power Plant Project
Dwg. / Doc. TitleG A Drawing BFP andBooster Pump Dwg. / Doc. No. MD1-0-V-121-01-00001
HDEC DT No. MD1-HDH-EVN-X-1219 Submitted Date Rev. A
PyryTR No. Received DateNew HDEC DT No. Re-Submitted Date
Status Submitted for Information Returned with Comment
Page 1/ 1
No. Pyrys Comments Contractors Reply / Action
1 Please provide KKS identifying number forequipment and instruments on the drawings.
2 Include a parts list for the major components(e.g. main pump, variable speed drive etc) withreference drawings.
3 Foundation drawings with loading data andanchor bolt information to be provided. Thesedrawings shall be identified as referencedrawings.
4 Confirm that there is personnel protection for allrotating components.
5 State what DBSE means
6 Identify the equipment on the edge of the
booster and main pump base plates at gridreference A2, A3, C5 and C6.