Download - Manual Power Monitor Nsc
Publication 1403-5.1
Smart Communications Card(Cat. No. 1403-NSC)
Important User Information
Solid-state equipment has operational characteristicsdiffering from those of electromechanical equipment.Safety Guidelines for the Application, Installation, andMaintenance of Solid-state Controllers (PublicationSGI-1.1) describes some important differences betweensolid-state equipment and hard-wired electromechanicaldevices. Because of this difference, and also because ofthe wide variety of uses for solid-state equipment, allpersons responsible for applying this equipment mustsatisfy themselves that each intended application of thisequipment is acceptable.
In no event will the Allen-Bradley Company, Inc. beresponsible for indirect or consequential damagesresulting from the use or application of this equipment.
The examples and diagrams in this manual are includedsolely for illustrative purposes. Because of the manyvariables and requirements associated with any particularinstallation, the Allen-Bradley Company, Inc. cannotassume responsibility or liability for actual use based onthe examples and diagrams.
No patent liability is assumed by the Allen-BradleyCompany, Inc. with respect to use of information,circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole orin part, without written permission of Allen-BradleyCompany, Inc., is prohibited.
Throughout this manual we use notes to make you awareof safety considerations:
!ATTENTION: Identifies informationabout practices or circumstances that canlead to personal injury or death, propertydamage or economic loss.
Attention statements help you to:
• identify a hazard
• avoid the hazard
• recognize the consequences
Important: Identifies information that is critical forsuccessful application and understandingof the product.
Terms and Conventions
In this instruction sheet, the following terms andconventions are used:
Abbreviation Term
BTR Block Transfer Read
BTW Block Transfer Write
MSG Message
Table of Contents
Product Description 2. . . . . . . . . . . . . . . . . . . . . Installation 3. . . . . . . . . . . . . . . . . . . . . . . . . . . General Operation 8. . . . . . . . . . . . . . . . . . . . . . Catalog Number Explanation App. A. . . . . . . . . . . . . . Smart Communication Card Data Tables App. B. . . . . . Smart Communication Protocol Tutorial App. C. . . . . . . Sample Ladder Listing App. D. . . . . . . . . . . . . . . . . . . Technical Specifications App. E. . . . . . . . . . . . . . . . . .
PLC is a registered trademark of Allen-Bradley Company, Inc.Data Highway Plus and SLC are trademarks of Allen-Bradley Company, Inc.
Instruction Sheet
Smart Communications Card 2
Publication 1403-5.1
Product Description
Chapter Objectives
After completing this chapter, you should be able toidentify the product features and system applications.
Introduction
The Cat. No. 1403-NSC Smart Communications Card isa microprocessor-controlled dual-port communicationplug-in accessory to the Powermonitor II Master Module.This accessory provides the Powermonitor II with twoactive communication ports which can be used at thesame time. Required configuration parameters (R I/Orack address, baud rates, etc.) are provided byconfiguring the Master Module. One port is dedicated tothe Allen-Bradley PLC R I/O network and the otherport is software configurable for either EIA StandardsRS-232C or RS-485. (There are no hardware options toconfigure when the card is installed.)
Performance Features
The Smart Communication Card performance featuresinclude:
• PLC via R I/O
• SLC 500 via R I/O with (1747-SN) Series B or laterscanner module
• SLC 500 via DF-1 master slave protocol
• R I/O Baud rates: 57.6K baud-230K baud
• Serial Baud rates: 1,200–19,200 baud
• Simultaneous R I/O and serial communication
• 124 units per subnet, 255 per network via RS-485
• 500 V isolation on communications ports
• Fully software configurable, no hardware jumpersrequired
Figure 1. Cat. No 1403-NSC Communications Module
Serial Transmit (TXD) LED
Serial Receive (RXD) LED
Finger hold
Captive fastening screwConnectorR I/O Active LED
3Smart Communications Card
Publication 1403-5.1
Installation
!ATTENTION: Please followappropriate ESD procedures beforeremoval and/or installation of the SmartCommunications Card. Failure to followthese procedures can result in physicaldamage to both the SmartCommunications Card and the MasterModule.
1. To remove the blank plate on the Master Module,unscrew the two corner retaining screws as shown inFigure 2. Save these two screws for reassembly.
Figure 2.
2. If you plan to remove the communications card at alater date, retain the blank plate. Otherwise, disposeof properly.
3. Remove the communications card from the staticprotection shipping bag.
4. Grasp the card with the components side up and thethree LEDs on the left. Place the right index finger inthe top notch and the thumb in the bottom notch.
5. With the Master Module labels right side up, placethe card into opening on the left side. The card toMaster Module connector should align properly whenthe top right and bottom left guide pins of the MasterModule mate with holes in the card. With your leftthumb, press just above the card to Master Moduleconnector to attach the connector. Tighten the fourcorner screws.
Figure 3.
6. Place the closure plate over the opening and secure itwith the two screws from the original blank plate.
Figure 4.
Note: Refer to Appendix E, Specifications for screwtorque requirements and wire sizes.
Smart Communications Card 4
Publication 1403-5.1
Wiring
!ATTENTION: Special high levelisolation is required between units whenthe possibility of high ground potentialdifferences exist. This may occur whenseparate grounds are used or whencommunicating to a unit connected to apower ground mat. Failure to do so canlead to personal injury or death, propertydamage, or economic loss.
Table A. Wiring Connections
Connector
CommunicationFormat
Terminal #(Countingfrom the
bottom up)
TerminalLabel
Intended Use, Pin Connection,or Wire Color
RecommendedCable Type
Maximum CableLength/Baud Rate
12 Do not connect
11 Do not connect
10 SHLD Cable shield grounding point2 ire shieldedRS-485 9 – Minus signal data 2-wire shielded(Belden 9841)
4000 ft/19.2kBRS 4858 + Plus signal data
(Belden 9841) 4000 ft/19.2kB
7 RXDPC Transmit, DB25, pin 2, (DB9, pin 3)
RS-2326 TXD PC Receive, DB25, pin3 (DB9, pin 2) 3-wire Shielded 50 ft/19 2kBRS-2325 SG
PC signal return, DB25, pin 7 (DB9, pin 5)
3-wire Shielded(Belden 9608) 50 ft/19.2kB
4 SHLD Cable Shield
3 1 Blue Wire insulation 1770-CDT i i l 10,000 ft /57.6kBaud
R-I/O 2 SHLD Cable shield ground point
1770 CDTwinaxial
(Blue Hose)
10,000 ft /57.6kBaud5,000 ft/115.2kBaud2 500 ft/230 4kB d
R I/O
1 2 Clear wire insulation(Blue Hose)
(Belden 9463)
5,000 ft/115.2kBaud2,500 ft/230.4kBaud
Notes:
1. The communications topology for both R I/O andRS-485 is designed to operate in a daisy-chaintopology. Use of the star or bridging method willcause signal distortion unless impedances arematched for each spur. Bridging is not recommendedwithout matching networks.
2. To prevent end reflections, each end of the daisy-chain should be terminated in the characteristicimpedance for the cable, the baud rate, and frequencyused.
CommunicationFormat
Baud RateTerminating
Resistor
RS-485 1200–19.2k 150 Ω 1/4 W
R I/O57.6–115.2k 150 Ω 1/4 W
R I/O230.4k 84 Ω 1/4 W
3. Each end section of cable should have the shieldconnected to the terminal labeled SHLD. This SHLDground provides a high frequency ground, whilelimiting DC or power line frequencies from flowingdown the cable shield.
4. The RS-485 receivers in the communications cardprovide a 1/4 load impedance instead of the normalfull load impedance. This therefore allows the use offour times the number of receivers (32 4 or 128total) on one network.
5Smart Communications Card
Publication 1403-5.1
Figure 5. R I/O Wiring
BLUE
SHIELD
CLEAR
PLC PROCESSOR
INTERNAL TERMINATING
150Ω RESISTOR
84Ω OR 150Ω RESISTOR
Powermonitor II
DEVICE #1
Powermonitor II
DEVICE #2
Powermonitor II
DEVICE #3
0.047uF
150KΩ
0.047uF
150KΩ
0.047uF
150KΩ
Note: All ground wires should be kept as short aspossible between the R/C and the cover plate.
Smart Communications Card 6
Publication 1403-5.1
Figure 6. RS-485 Wiring
150Ω RESISTOR
Powermonitor II
DEVICE #1
Powermonitor II
DEVICE #2
Powermonitor II
DEVICE #3
EXTERNAL
RS–232C TO RS–485
CONVERTER
IBM PC
PLC PROCESSOR
RS–232C
150Ω RESISTOR
0.047uF
150KΩ
0.047uF
150KΩ
0.047uF
150KΩ
Note: All ground wires should be kept as short aspossible between the R/C and the cover plate.
7Smart Communications Card
Publication 1403-5.1
Figure 7. RS-232C Wiring
IBM PC
PLC PROCESSOR
1
3
2
7
CASE
GROUND
2
3
5
25 PIN
D–SHELL
9 PIN
D–SHELL
Powermonitor II
Note: For CE compliance, the communication cable shield mustbe connected directly to the chassis ground terminallocated on the communication card cover plate. Theexposed shield wire should be as short as possible.
Field Service Considerations
If the Smart Communications Card requires service,please contact your nearest Allen-Bradley Sales Office.To minimize your inconvenience, the initial installationshould be performed in a manner which makesremoval easy.
Smart Communications Card 8
Publication 1403-5.1
General Operation
Communications Card Set-Up
All communications card options such ascommunications format, baud rate, address, etc., are setby configuring the Master Module. Refer toPowermonitor II Instruction Sheet, Publication 1403-5.0,Chapter 4.
Indicators
Figure 1. on page 2 shows the location of the LEDIndicators on the communications card.
Table B. LED Indicators
LEDLocation
LEDColor
Port Assignment LED State and Communications Condition
Top Red RS-232 or RS-485 ReceiveOFF = IdleON/OFF Pulsing = Receiving Data
Middle Red RS-232 or RS-485 TransmitOFF = IdleON/OFF Pulsing = Transmitting Data
Bottom Green R I/OON = Communications EstablishedON/OFF Blinking = Communications Established With Some ErrorsOFF = Communications Not Established
Configuration Items
Communication
Table C. Communication Configuration Items
Parameter Description Range DefaultUser
Setting
R I/O Rack AddressSpecifies the logical rack of the Smart CommunicationCard.
0 to 63 1
R I/O Group Number Determines the group number of the logical rack.
0 = First Quarter2 = Second Quarter4 = Third Quarter6 = Fourth Quarter
0 = FirstQuarter
R I/O Last RackDefines whether or not the configured rack is the lastrack.
0 = No1 = Yes
0 = No
R I/O Baud Rate Specifies the baud rate of the RIO network.0 to 56K1 to 115K2 to 230K
0 to 56K
Serial DelayDefines the delay in ms between the request andresponse serial packets.
0 to 15 0
Serial Mode Specifies the serial communications mode.0 = RS-4851 = RS-232
1 = RS-232
RS-232/RS-485 BaudRate
Determines the baud rate for the serial communications.
0 to 12001 to 24002 to 48003 to 96004 to 19200
3 to 9600
Serial Device IdentifierDefines the specific serial address. A value of 255 isused as a broadcast address.
0 to 254 Device ID#
Appendix A
Publication 1403-5.1
Catalog Number Explanation
Communications Cards
1403 - NSC
Bulletin Number Type of Device
Power Quality andAutomation Products
1403 = Plug-in Communications Card for Bulletin 1403-MM Devices(RS-232C / RS-485 / Allen-Bradley R I/O Protocols)
NSC =
A–2 Catalog Number Explanation
Publication 1403-5.1
Appendix B
Publication 1403-5.1
Smart Communication Card Data Tables
Table B.1 Data Table List
Table Name Number of Parameters
ID/Numberof Words Type of Table Page
Device Configuration Data Table 32 44 Block Transfer Read/Write
B–2
Smart Communication Card Data Table 21 30 Block Transfer Read/Write
B–4
Command Data Table 12 22 Block Transfer Write B–5
Bit Fields for Command Data Table (Command Word 1)
— — — B–6
Bit Fields for Command Data Table(Command Word 2)
— — — B–6
Voltage/Current Data 23 53 Block Transfer Read B–6
Real Time Power Data 25 62 Block Transfer Read B–7
Cumulative Power Data 7 45 Block Transfer Read B–9
Demand Data 18 42 Block Transfer Read B–10
Event Log 12 23 Block Transfer Read B–11
Voltage/Current/Miscellaneous Snapshot LogData Table
28 54 Block Transfer Read B–12
Power Snapshot Log Data Table 30 59 Block Transfer Read B–13
Min_Max Log 8 24 Block Transfer Read B–15
Log Selection Command Table 4 9 Block Transfer Write B–16
Available Min/Max Log Parameters 84 — — B–17
Even Harmonic Distortion Table 29 60 Block Transfer Read B–18
Odd Harmonic Distortion Table 29 61 Block Transfer Read B–19
Even Harmonic Magnitude Data Table 29 58 Block Transfer Read B–21
Odd Harmonic Magnitude Data Table 29 57 Block Transfer Read B–22
Even Harmonic Phase Angle Data Table 29 56 Block Transfer Read B–24
Odd Harmonic Phase Angle Data Table 29 55 Block Transfer Read B–25
Oscillogram Capture Data 54 63 Block Transfer Read B–27
Diagnostic Data Table (Self-test Results) 35 39 Block Transfer Read B–29
Setpoint Setup Data Table 9 20 Block Transfer Read/ B–30Setpoint Setup Data Table 9 20 Block Transfer Read/Write
B–30
Setpoint Type — — — B–31
Setpoint Action — — — B–31
Relay/Setpoint Status Table 29 38 Block Transfer Read B–32
Status Inputs Bitfield Definitions 16 bits — — B–33
Alarm Word Bitfield Definitions 16 bits — — B–33
Setpoint Status Bitfield Definitions 16 bits — — B–33
B–2 Smart Communication Card Data Tables
Publication 1403-5.1
Table B.2 Device Configuration Data Table – Write and Read
ÁÁÁÁÁÁÁÁÁÁ
ParameterNo.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter Name ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module Range ÁÁÁÁÁÁÁÁ
DefaultSettingÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁ
Range
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Voltage Mode
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Demo1 = Single2 = Open Delta3 = 3-Wire Delta4 = 4-Wire Wye5 = Direct Delta
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 5
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Present Unit PasswordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 is always returned on a Read 0 to 9999 is required for a Write
ÁÁÁÁÁÁÁÁÁÁÁÁ
0ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 to +9999
ÁÁÁÁÁÁÁÁÁÁ
1.3 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
New Password ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 does not change the password 0 to 9999 is new password value
ÁÁÁÁÁÁÁÁ
0 ÁÁÁÁÁÁÁÁÁÁ
3 ÁÁÁÁÁÁÁÁÁÁÁÁ
–1 to +9999
ÁÁÁÁÁÁÁÁÁÁ
1.4 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Voltage Scale ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ120 0
ÁÁÁÁÁÁÁÁÁÁ
4 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
PT Primary ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.0 to 10,000,000.0 ÁÁÁÁÁÁÁÁ
120.0ÁÁÁÁÁÁÁÁÁÁ
5 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
1.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Voltage Scale ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
PT Secondary ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 999 ÁÁÁÁÁÁÁÁ
120ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 999
ÁÁÁÁÁÁÁÁÁÁ
1.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Current Scale (For I1, I2, I3) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
1 or 5➀ÁÁÁÁÁÁÁÁÁÁ
7 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁCT Primary ÁÁÁÁÁÁÁÁÁ1.0 to 10,000,000.0 ÁÁÁÁ1 or 5➀
ÁÁÁÁÁ8 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁ1.7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁCurrent Scale (For I1, I2, I3)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁCT Secondary
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ1 to 999
ÁÁÁÁÁÁÁÁ1 or 5➀
ÁÁÁÁÁÁÁÁÁÁ9
ÁÁÁÁÁÁÁÁÁÁÁÁ1 to 999ÁÁÁÁÁ
ÁÁÁÁÁ1.8
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Analog Input ScaleÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ1 0
ÁÁÁÁÁÁÁÁÁÁ
10ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
PT Primary ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.0 to 10,000,000.0 ÁÁÁÁÁÁÁÁ
1.0ÁÁÁÁÁÁÁÁÁÁ
11 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
1.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Analog Input Scale ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
PT Secondary ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 999 ÁÁÁÁÁÁÁÁ
1 ÁÁÁÁÁÁÁÁÁÁ
12 ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 999
ÁÁÁÁÁÁÁÁÁÁ
1.10 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Neutral Current Scale (For I4) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
1 or 5➀ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
CT Primary ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.0 to 10,000,000.0 ÁÁÁÁÁÁÁÁ
1 or 5➀
ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁ1.11
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁNeutral Current Scale (For I4)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁCT Secondary
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ1 to 999
ÁÁÁÁÁÁÁÁ1 or 5➀
ÁÁÁÁÁÁÁÁÁÁ15
ÁÁÁÁÁÁÁÁÁÁÁÁ1 to 999ÁÁÁÁÁ
ÁÁÁÁÁ1.12
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Demand Period LengthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–99 to +99ÁÁÁÁÁÁÁÁ
1ÁÁÁÁÁÁÁÁÁÁ
16ÁÁÁÁÁÁÁÁÁÁÁÁ
–99 to +99ÁÁÁÁÁÁÁÁÁÁ
1.13ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of Demand PeriodsÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 15ÁÁÁÁÁÁÁÁ
1ÁÁÁÁÁÁÁÁÁÁ
17ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 15ÁÁÁÁÁÁÁÁÁÁ
1.14 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
0 ÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ1.15 ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁSnapshot Interval – Hours ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32,767
ÁÁÁÁÁÁÁÁÁÁ
1.16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Snapshot Interval – Minutes ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
0 ÁÁÁÁÁÁÁÁÁÁ
20 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32,767
ÁÁÁÁÁÁÁÁÁÁ
1.17 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Snapshot Interval – Seconds ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
0 ÁÁÁÁÁÁÁÁÁÁ
21 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32,767
ÁÁÁÁÁÁÁÁÁÁ
1.18 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Snapshot Buffer Type ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Fill and Stop1 = Circular
ÁÁÁÁÁÁÁÁ
1 ÁÁÁÁÁÁÁÁÁÁ
22 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
0 ÁÁÁÁÁÁÁÁÁÁ
23 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
0 ÁÁÁÁÁÁÁÁÁÁ
24 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
0 ÁÁÁÁÁÁÁÁÁÁ
25 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
0 ÁÁÁÁÁÁÁÁÁÁ
26 ÁÁÁÁÁÁÁÁÁÁÁÁ
B–3Smart Communication Card Data Tables
Publication 1403-5.1
ÁÁÁÁÁÁÁÁÁÁ
ParameterNo.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter Name ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module Range ÁÁÁÁÁÁ
DefaultSettingÁÁÁÁÁÁÁÁÁÁÁÁ
Word No. ÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
0ÁÁÁÁÁÁÁÁÁÁÁÁ
27ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
1.19
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Output Pulse Relay No.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = None1 = Relay 12 = Relay 2
ÁÁÁÁÁÁÁÁÁ
0
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
28
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.20
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Output Pulse Parameter
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = kWh Forward1 = kWh Reverse2 = kVarh Forward3 = kVarh Reverse
ÁÁÁÁÁÁÁÁÁÁÁÁ
0
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
29
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 3
ÁÁÁÁÁÁÁÁÁÁ
1.21 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Output Pulse Increment ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 32766 ÁÁÁÁÁÁ
1 ÁÁÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁ
1 to 32766ÁÁÁÁÁÁÁÁÁÁ
1.22 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Output Pulse Width (ms) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
40 to 2000 ÁÁÁÁÁÁ
100ÁÁÁÁÁÁÁÁÁÁÁÁ
31 ÁÁÁÁÁÁÁÁÁÁ
40 to 2000
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.23
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Ch A 12 Cycle Oscillogram
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = Phase 1 Voltage2 = Phase 1 Current3 = Phase 2 Voltage4 = Phase 2 Current5 = Phase 3 Voltage6 = Phase 3 Current7 = Phase 4 Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
32
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.24
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Ch B 12 Cycle Oscillogram
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = Phase 1 Voltage2 = Phase 1 Current3 = Phase 2 Voltage4 = Phase 2 Current5 = Phase 3 Voltage6 = Phase 3 Current7 = Phase 4 Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
33
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 7
ÁÁÁÁÁÁÁÁÁÁ
1.25 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillography Type ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Hold1 = Overwrite
ÁÁÁÁÁÁ
1 ÁÁÁÁÁÁÁÁÁÁÁÁ
34 ÁÁÁÁÁÁÁÁÁÁ
0 to 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.26ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of Pretrigger Cycles forthe 12 Cycle Oscillogram
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 = No Pretrig 0 to +8 = Cycles
ÁÁÁÁÁÁÁÁÁ
0ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
35ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 to +8
ÁÁÁÁÁÁÁÁÁÁ
1.27 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEEE 519 Max. Short CircuitCurrent
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ0ÁÁÁÁÁÁÁÁÁÁÁÁ
36 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0.0 to 10,000,000.0 ÁÁÁÁÁÁ
0 ÁÁÁÁÁÁÁÁÁÁÁÁ
37 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.28ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEEE 519 Max. Demand/LoadCurrent
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
0
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
38ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0.0 to 10,000,000.0
ÁÁÁÁÁÁ
0 ÁÁÁÁÁÁÁÁÁÁÁÁ39
ÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.29ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Save Status Changes to EventLog
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = No1 = Yes
ÁÁÁÁÁÁÁÁÁ
0ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
40ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
ÁÁÁÁÁÁÁÁÁÁ
1.30ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Vaux Voltage ModeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = AC1 = DC
ÁÁÁÁÁÁ
0ÁÁÁÁÁÁÁÁÁÁÁÁ
41ÁÁÁÁÁÁÁÁÁÁ
0 to 1ÁÁÁÁÁÁÁÁÁÁ1.31
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁEnable THD
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 or 1
ÁÁÁÁÁÁ1ÁÁÁÁÁÁÁÁÁÁÁÁ42
ÁÁÁÁÁÁÁÁÁÁ0 to 1ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
1.32ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Enable Min_Max LogÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = No1 = Yes
ÁÁÁÁÁÁÁÁÁ
1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
43ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
ÁÁÁÁÁÁÁÁÁÁ
1.33 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data Format ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁ
0 ÁÁÁÁÁÁÁÁÁÁÁÁ
44 ÁÁÁÁÁÁÁÁÁÁ
0 to 1
➀ This value will be 1 for 1 Amp Master Module (Cat. No. 1403-MM01X) or 5 for a 5 Amp Master Module (Cat. No. 1403-MM05X).
B–4 Smart Communication Card Data Tables
Publication 1403-5.1
Table B.3 Smart Communication Card Data Table – Write and Read
Note: The device will not respond to a broadcast of this table.
ÁÁÁÁÁÁÁÁÁÁ
ParameterNo.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter Name ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module Range ÁÁÁÁÁÁÁÁÁÁ
PLC Word No.ÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
2.1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
R I/O Rack AddressÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 63ÁÁÁÁÁÁÁÁÁÁ
1ÁÁÁÁÁÁÁÁÁÁ
0 to 63ÁÁÁÁÁÁÁÁÁÁ
2.2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
R I/O Group NumberÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 6ÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁÁÁÁÁ
0 to 6ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2.3ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
R I/O Last RackÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = No – Default1 = Yes
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2.4ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
R I/O Baud RateÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = 56K – Default1 = 115K2 = 230K
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 2
ÁÁÁÁÁÁÁÁÁÁ
2.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Serial Response Delay ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 15 ÁÁÁÁÁÁÁÁÁÁ
5 ÁÁÁÁÁÁÁÁÁÁ
0 to 15
ÁÁÁÁÁÁÁÁÁÁ
2.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Serial Type Specifier RS-232 or RS-485 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = RS-4851 = RS-232 – Default
ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁÁÁÁÁ
0 to 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2.7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
SCC RS-232/RS-485 Baud Rate
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = 12001 = 24002 = 48003 = 9600 – Default4 = 19200
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 4
ÁÁÁÁÁÁÁÁÁÁ2.8
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁSerial Device Identifier
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 255
ÁÁÁÁÁÁÁÁÁÁ8
ÁÁÁÁÁÁÁÁÁÁ0 to 255ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
2.9ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
R I/O Port Data FormatÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
9ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
ÁÁÁÁÁÁÁÁÁÁ
2.10ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Serial Port Data FormatÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁ
10ÁÁÁÁÁÁÁÁÁÁ
0 to 1ÁÁÁÁÁÁÁÁÁÁ2.11
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ11
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ2.12
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ReservedÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
12ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ2.13
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ReservedÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
13ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ2.14 ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁReserved ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ2.15 ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁReserved ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
15 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ2.16 ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁReserved ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ2.17 ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁReserved ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
17 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ2.18 ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁReserved ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ2.19
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ19
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ2.20ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ20
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
2.21ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Present Unit PasswordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 is always returned for a Read0 to 9999 is required for a Write
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
21ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 to +9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
22 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
23 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
24 ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ25
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ26
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ReservedÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
27ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
28 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
29 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁ
B–5Smart Communication Card Data Tables
Publication 1403-5.1
Table B.4 Command Data Table Write
ÁÁÁÁÁParameter No.ÁÁÁÁÁÁÁÁÁÁÁParameter Name ÁÁÁÁÁÁÁÁÁÁÁMaster Module Range ÁÁÁÁÁWord No. ÁÁÁÁÁRangeÁÁÁÁÁÁÁÁÁÁ3.1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁCommand Word 1 (Bit Fields)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 2047
ÁÁÁÁÁÁÁÁÁÁ1
ÁÁÁÁÁÁÁÁÁÁ0 to 2047ÁÁÁÁÁ
ÁÁÁÁÁ3.2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Command Word 2 (Bit Fields)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 511ÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁÁÁÁÁ
0 to 511ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3.3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Analysis➀
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = L1 Voltage2 = L1 Current3 = L2 Voltage4 = L2 Current5 = L3 Voltage6 = L3 Current7 = L4 Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3.4
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Channel Request➀(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = L1 Voltage2 = L1 Current3 = L2 Voltage4 = L2 Current5 = L3 Voltage6 = L3 Current7 = L4 Current8 = Ch–A 12 Cycle9 = Ch–B 12 Cycle
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 9
ÁÁÁÁÁ3.5 ÁÁÁÁÁÁÁÁÁÁÁW Hour Data for Set Command➀ ÁÁÁÁÁÁÁÁÁÁÁ–9999x108 to +9999x108 ÁÁÁÁÁ5 ÁÁÁÁÁ–9999 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ6
ÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ3.6
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁVAR Hour Data for Set Command➀
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ–9999x108 to +9999x108
ÁÁÁÁÁÁÁÁÁÁ7
ÁÁÁÁÁÁÁÁÁÁ–9999 to 9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
8ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
3.7 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁ
9ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
10 ÁÁÁÁÁÁÁÁÁÁ
10ÁÁÁÁÁÁÁÁÁÁ
3.8ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Time for Set Command➀ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
YearÁÁÁÁÁÁÁÁÁÁ
11ÁÁÁÁÁÁÁÁÁÁ
0–99 16 Bit IntegerÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, Day
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
12
ÁÁÁÁÁÁÁÁÁ
1–128 Bit
ÁÁÁÁÁÁÁÁÁ
1–318 Bit
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, MinutesÁÁÁÁÁÁÁÁÁÁ
13ÁÁÁÁÁÁ
0–238 BitÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, Hundredths
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
14
ÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁ
0–998 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3.9ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Force Specifics Relay 1➀
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = Energize2 = De-energize4 = Remove Force
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
15ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1, 2, 4
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3.10
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Force Specifics Relay 2➀
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = Energize2 = De-energize4 = Remove Force
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
16
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1, 2, 4
ÁÁÁÁÁÁÁÁÁÁ
3.11ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint Number➀ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 20ÁÁÁÁÁÁÁÁÁÁ
17ÁÁÁÁÁÁÁÁÁÁ
1 to 20ÁÁÁÁÁÁÁÁÁÁ
3.12 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Present Unit Password ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999 ÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
20 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
21 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
3.13ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data FormatÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
22ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
➀ See Table B.5 in Publication 1403-5.1 for specific command bits toenable these features.
B–6 Smart Communication Card Data Tables
Publication 1403-5.1
Table B.5 Bit Fields for Command Data Table – (Command Word 1)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
CommandÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Bit Locationand Value
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Clear Snapshot Log ÁÁÁÁÁÁÁÁÁÁÁÁ
b0 = 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Clear Min_Max Log ÁÁÁÁÁÁÁÁÁÁÁÁ
b1 = 1
ÁÁÁÁÁÁÁÁÁÁÁRestore Factory Default Configuration ÁÁÁÁÁÁb2 = 1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Clear Hold of Oscillogram (Reserved1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
b3 = 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Initiate Oscillogram (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁ
b4 = 1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Force Self Test ÁÁÁÁÁÁÁÁÁÁÁÁ
b5 = 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Clear Status Input Counter 1 ÁÁÁÁÁÁÁÁÁÁÁÁ
b6 = 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Clear Status Input Counter 2 ÁÁÁÁÁÁÁÁÁÁÁÁ
b7 = 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Clear Status Input Counter 3 ÁÁÁÁÁÁÁÁÁÁÁÁ
b8 = 1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁClear Status Input Counter 4
ÁÁÁÁÁÁÁÁÁÁÁÁb9 = 1ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁClear Battery Usage TimerÁÁÁÁÁÁÁÁÁÁÁÁb10 = 1
Table B.6 Bit fields for Command Data Table – (Command Word 2)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
CommandÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Bit Locationand Value
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Set Analysis Channel Request ÁÁÁÁÁÁÁÁÁÁÁÁ
b0 = 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Set Oscillogram Channel Request(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁ
b1 = 1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Set W HoursÁÁÁÁÁÁÁÁÁÁÁÁ
b2 = 1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Set VAR HoursÁÁÁÁÁÁÁÁÁÁÁÁ
b3 = 1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved ÁÁÁÁÁÁÁÁÁÁÁÁ
b4 = not usedÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Set Time ÁÁÁÁÁÁÁÁÁÁÁÁ
b5 = 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Relay 1 ÁÁÁÁÁÁÁÁÁÁÁÁ
b6 = 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Relay 2 ÁÁÁÁÁÁÁÁÁÁÁÁ
b7 = 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Select Setpoint Number ÁÁÁÁÁÁÁÁÁÁÁÁ
b8 = 1
Table B.7 Voltage/Current Data – Read
ÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter Name ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module Range ÁÁÁÁÁÁÁÁÁÁ
Word No. ÁÁÁÁÁÁÁÁÁÁ
Range
ÁÁÁÁÁÁÁÁÁÁ
4.1 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Time Stamp ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Year ÁÁÁÁÁÁÁÁÁÁ
1 ÁÁÁÁÁÁÁÁÁÁ
0–9916 Bit IntegerÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, DateÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁÁÁÁ
1–128 Bit
ÁÁÁÁÁÁÁÁÁ
1–318 Bit
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, Minute ÁÁÁÁÁÁÁÁÁÁ
3 ÁÁÁÁÁÁ
0–238 BitÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, HundredthsÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4ÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁ
0–998 Bit
ÁÁÁÁÁÁÁÁÁÁ
4.2 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1 Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 amps ÁÁÁÁÁÁÁÁÁÁ
5 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.3 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2 Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 amps ÁÁÁÁÁÁÁÁÁÁ
7 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ8
ÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ4.4
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁL3 Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 amps
ÁÁÁÁÁÁÁÁÁÁ9
ÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
10ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.5ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L4 (Neutral) CurrentÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ampsÁÁÁÁÁÁÁÁÁÁ
11ÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
12 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3-Phase Average Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 amps ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.7 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Positive Sequence Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 amps ÁÁÁÁÁÁÁÁÁÁ
15 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
16 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁ4.8
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁNegative Sequence Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 amps
ÁÁÁÁÁÁÁÁÁÁ17
ÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ18
ÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.9ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Percent Current UnbalanceÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0.0 to 100.0ÁÁÁÁÁÁÁÁÁÁ
19ÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
20ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.10 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1 to L2 Voltage ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 volts ÁÁÁÁÁÁÁÁÁÁ
21 ÁÁÁÁÁÁÁÁÁÁ
0 to9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
22 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.11 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2 to L3 Voltage ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 volts ÁÁÁÁÁÁÁÁÁÁ
23 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
24 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.12 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3 to L1 Voltage ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 volts ÁÁÁÁÁÁÁÁÁÁ
25 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ26
ÁÁÁÁÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁ
ÁÁÁÁÁ4.13ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁAUX Voltage
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 volts
ÁÁÁÁÁÁÁÁÁÁ27
ÁÁÁÁÁÁÁÁÁÁ0 to 9999
B–7Smart Communication Card Data Tables
Publication 1403-5.1
ÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module RangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter NameÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ28
ÁÁÁÁÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁ
ÁÁÁÁÁ4.14ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ3–Phase Average Voltage (L–L)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 volts
ÁÁÁÁÁÁÁÁÁÁ29
ÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
30ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.15ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Positive Sequence VoltageÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 voltsÁÁÁÁÁÁÁÁÁÁ
31ÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
32 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Negative Sequence Voltage ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 volts ÁÁÁÁÁÁÁÁÁÁ
33 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
34 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.17 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Percent Voltage Unbalance ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0.0 to 100.0 ÁÁÁÁÁÁÁÁÁÁ
35 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
36 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁ4.18
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁL1–N Voltage
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 volts
ÁÁÁÁÁÁÁÁÁÁ37
ÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ38
ÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.19ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2–N VoltageÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 voltsÁÁÁÁÁÁÁÁÁÁ
39ÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
40ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.20 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3–N Voltage ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 volts ÁÁÁÁÁÁÁÁÁÁ
41 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
42 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4.21 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3–Phase Average Voltage (L–N) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 volts ÁÁÁÁÁÁÁÁÁÁ
43 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
44 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
4 22 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Average Frequency ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
20 0 to 132 0 ÁÁÁÁÁÁÁÁÁÁ
45 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
4.22 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Average Frequency ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
20.0 to 132.0 ÁÁÁÁÁÁÁÁÁÁ46
ÁÁÁÁÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁ
ÁÁÁÁÁ4.23ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁLast Cycle Frequency
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ20.0 to 132.0
ÁÁÁÁÁÁÁÁÁÁ47
ÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
48ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4.24
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Phase Rotation
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = No Rotation1 = ABC2 = ACB
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
49
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 2
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
50ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
51ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
52 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
4.25ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data FormatÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
53ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
Table B.8 Real Time Power Data – ReadÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter Name ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module Range ÁÁÁÁÁÁÁÁÁÁ
Word No. ÁÁÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
5.1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Time StampÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
YearÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0–9916 Bit IntegerÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, Date
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2
ÁÁÁÁÁÁÁÁÁ
1–128 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
1–318 Bit
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, MinuteÁÁÁÁÁÁÁÁÁÁ
3ÁÁÁÁÁÁ
0–238 BitÁÁÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, Hundredths
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4
ÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
0–998 Bit
ÁÁÁÁÁÁÁÁÁÁ
5.2 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1 Real Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 W ÁÁÁÁÁÁÁÁÁÁ
5 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁ5.3 ÁÁÁÁÁÁÁÁÁÁÁL2 Real Power ÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 W ÁÁÁÁÁ7 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ8
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.4ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3 Real PowerÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 WÁÁÁÁÁÁÁÁÁÁ
9ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
10 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Total Real Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 W ÁÁÁÁÁÁÁÁÁÁ
11 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
12 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1 Reactive Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VAR ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ14
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
B–8 Smart Communication Card Data Tables
Publication 1403-5.1
ÁÁÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module RangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter NameÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁ5.7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁL2 Reactive Power
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 VAR
ÁÁÁÁÁÁÁÁÁÁ15
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
16ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.8 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3 Reactive Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VAR ÁÁÁÁÁÁÁÁÁÁ
17 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Total Reactive Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VAR ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
20 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁ5.10 ÁÁÁÁÁÁÁÁÁÁÁL1 Apparent Power ÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 VA ÁÁÁÁÁ21 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ22
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.11ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2 Apparent PowerÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VAÁÁÁÁÁÁÁÁÁÁ
23ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
24 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.12 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3 Apparent Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VA ÁÁÁÁÁÁÁÁÁÁ
25 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
26 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.13 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Total Apparent Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VA ÁÁÁÁÁÁÁÁÁÁ
27 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ28
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.14ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1 True PFÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–100.0 to +100.0ÁÁÁÁÁÁÁÁÁÁ
29ÁÁÁÁÁÁÁÁÁÁÁÁ
–9999 to +9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.15 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2 True PF ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–100.0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
31 ÁÁÁÁÁÁÁÁÁÁÁÁ
–9999 to +9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
32 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3 True PF ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–100.0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
33 ÁÁÁÁÁÁÁÁÁÁÁÁ
–9999 to +9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ34 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁ5.17
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁTotal True PF
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ–100.0 to +100.0
ÁÁÁÁÁÁÁÁÁÁ35
ÁÁÁÁÁÁÁÁÁÁÁÁ–9999 to +9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
36ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.18 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1 Displacement PF➀ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–100.0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
37 ÁÁÁÁÁÁÁÁÁÁÁÁ
–9999 to +9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
38 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.19 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2 Displacement PF➀ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–100.0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
39 ÁÁÁÁÁÁÁÁÁÁÁÁ
–9999 to +9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ40 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁ5.20
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁL3 Displacement PF➀
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ–100.0 to +100.0
ÁÁÁÁÁÁÁÁÁÁ41
ÁÁÁÁÁÁÁÁÁÁÁÁ–9999 to +9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
42ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.21 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Total Displacement PF➀ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–100.0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
43 ÁÁÁÁÁÁÁÁÁÁÁÁ
–9999 to +9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
44 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.22 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1 Distortion PF➀ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
45 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
46 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁ5.23
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁL2 Distortion PF➀
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to +100.0
ÁÁÁÁÁÁÁÁÁÁ47
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
48ÁÁÁÁÁÁÁÁÁÁÁÁ
0±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.24 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3 Distortion PF➀ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
49 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
50 ÁÁÁÁÁÁÁÁÁÁÁÁ
0±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
5.25 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Total Distortion PF➀ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
51 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
52 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ53 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ54
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
55ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
56 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
57 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
58 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
59 ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ60
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
61ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
5.26ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data FormatÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
62ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
➀ This value has the same update rate as harmonic analysis.
B–9Smart Communication Card Data Tables
Publication 1403-5.1
Table B.9 Cumulative Power Data – Read
ÁÁÁÁÁÁParameter No. ÁÁÁÁÁÁÁÁParameter Name ÁÁÁÁÁÁÁMaster Module Range ÁÁÁÁÁWord No.ÁÁÁÁÁÁRange ÁÁÁÁÁÁModulusÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁYear
ÁÁÁÁÁÁÁÁÁÁ1
ÁÁÁÁÁÁÁÁÁÁÁÁ0–99 16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁS
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, DateÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁÁÁÁÁÁÁ
1–128 Bit
ÁÁÁÁÁÁÁÁÁ
1–318 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
N/A
ÁÁÁÁÁÁÁÁÁÁÁÁ
6.1 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Time Stamp ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, Minute ÁÁÁÁÁÁÁÁÁÁ
3 ÁÁÁÁÁÁÁÁ
0–238 BitÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁÁÁÁÁÁÁÁ
N/AÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, HundredthsÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4ÁÁÁÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁ
0–998 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
N/A
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
5 ÁÁÁÁÁÁÁÁÁÁÁÁ
+0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
1012
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁÁÁÁÁÁÁ
+0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
109
ÁÁÁÁÁÁ6.2 ÁÁÁÁÁÁÁÁkW Hours Forward ÁÁÁÁÁÁÁ0 to 1.0x1012 ÁÁÁÁÁ7 ÁÁÁÁÁÁ+0 to 999 ÁÁÁÁÁÁ106ÁÁÁÁÁÁÁÁÁÁÁÁ
6.2 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
kW Hours Forward ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1.0x10 ÁÁÁÁÁÁÁÁÁÁ8
ÁÁÁÁÁÁÁÁÁÁÁÁ+0 to 999
ÁÁÁÁÁÁÁÁÁÁÁÁ103
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
9ÁÁÁÁÁÁÁÁÁÁÁÁ
+0 to 999ÁÁÁÁÁÁÁÁÁÁÁÁ
100
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
10 ÁÁÁÁÁÁÁÁÁÁÁÁ
–0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
1012
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
11 ÁÁÁÁÁÁÁÁÁÁÁÁ
–0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
109
ÁÁÁÁÁÁÁÁÁÁÁÁ
6.3 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
kW Hours Reverse ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1.0x1012 to 0 ÁÁÁÁÁÁÁÁÁÁ
12 ÁÁÁÁÁÁÁÁÁÁÁÁ
–0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
106
ÁÁÁÁÁÁÁÁÁÁÁÁ
6.3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
kW Hours Reverse
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.0x10 to 0
ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁ
–0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
103
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁ
–0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
100
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ15 ÁÁÁÁÁÁ±0 to 999 ÁÁÁÁÁÁ1012ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ16
ÁÁÁÁÁÁÁÁÁÁÁÁ±0 to 999
ÁÁÁÁÁÁÁÁÁÁÁÁ109
ÁÁÁÁÁÁÁÁÁÁÁÁ
6.4ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
kW Hours NetÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1.0x1012 to 1.0x1012ÁÁÁÁÁÁÁÁÁÁ
17ÁÁÁÁÁÁÁÁÁÁÁÁ
±0 to 999ÁÁÁÁÁÁÁÁÁÁÁÁ
106
ÁÁÁÁÁÁÁÁÁÁÁÁ
6.4ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
kW Hours NetÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.0x10 to 1.0x10ÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁÁÁ
±0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
103
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁ
±0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
100
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
20 ÁÁÁÁÁÁÁÁÁÁÁÁ
+0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
1012
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
21 ÁÁÁÁÁÁÁÁÁÁÁÁ
+0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
109
ÁÁÁÁÁÁÁÁÁÁÁÁ
6.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
kVAR Hours Forward ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1.0x1012 ÁÁÁÁÁÁÁÁÁÁ
22 ÁÁÁÁÁÁÁÁÁÁÁÁ
+0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
106
ÁÁÁÁÁÁ6.5
ÁÁÁÁÁÁÁÁkVAR Hours Forward
ÁÁÁÁÁÁÁ0 to 1.0x10
ÁÁÁÁÁ23 ÁÁÁÁÁÁ+0 to 999 ÁÁÁÁÁÁ103ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ24
ÁÁÁÁÁÁÁÁÁÁÁÁ+0 to 999
ÁÁÁÁÁÁÁÁÁÁÁÁ100
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
25ÁÁÁÁÁÁÁÁÁÁÁÁ
–0 to 999ÁÁÁÁÁÁÁÁÁÁÁÁ
1012
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
26 ÁÁÁÁÁÁÁÁÁÁÁÁ
–0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
109
ÁÁÁÁÁÁÁÁÁÁÁÁ
6.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
kVAR Hours Reverse ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1.0x1012 to 0 ÁÁÁÁÁÁÁÁÁÁ
27 ÁÁÁÁÁÁÁÁÁÁÁÁ
–0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
106
ÁÁÁÁÁÁÁÁÁÁÁÁ
6.6ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
kVAR Hours ReverseÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.0x10 to 0ÁÁÁÁÁÁÁÁÁÁ
28 ÁÁÁÁÁÁÁÁÁÁÁÁ
–0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
103
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
29 ÁÁÁÁÁÁÁÁÁÁÁÁ
–0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
100
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁÁÁ
±0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
1012
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ31 ÁÁÁÁÁÁ±0 to 999 ÁÁÁÁÁÁ109ÁÁÁÁÁÁÁÁÁÁÁÁ6.7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁkVAR Hours Net
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ–1.0x1012 to 1.0x1012
ÁÁÁÁÁÁÁÁÁÁ32
ÁÁÁÁÁÁÁÁÁÁÁÁ±0 to 999
ÁÁÁÁÁÁÁÁÁÁÁÁ106
ÁÁÁÁÁÁÁÁÁÁÁÁ
6.7 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
kVAR Hours Net ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.0x10 to 1.0x10 ÁÁÁÁÁÁÁÁÁÁ
33ÁÁÁÁÁÁÁÁÁÁÁÁ
±0 to 999ÁÁÁÁÁÁÁÁÁÁÁÁ
103
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
34 ÁÁÁÁÁÁÁÁÁÁÁÁ
±0 to 999 ÁÁÁÁÁÁÁÁÁÁÁÁ
100
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
35 ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
36 ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
37 ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word ÁÁÁÁÁÁÁÁÁÁÁÁ38 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ39
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
40ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
41 ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
42 ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
43 ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
44 ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ45
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
B–10 Smart Communication Card Data Tables
Publication 1403-5.1
Table B.10 Demand Data – Read
ÁÁÁÁÁParameter No.ÁÁÁÁÁÁÁÁÁÁÁÁParameter Name ÁÁÁÁÁÁÁÁÁMaster Module Range ÁÁÁÁÁWord No. ÁÁÁÁÁÁRangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
7.1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Time Stamp
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Year
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0–9916 Bit Integer
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, DateÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁ
1–128 BitÁÁÁÁÁÁÁÁ
1–318 BitÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, Minute
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3
ÁÁÁÁÁÁÁÁÁ
0–238 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, HundredthsÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4ÁÁÁÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁÁÁÁÁÁÁÁ
0–998 BitÁÁÁÁÁ
ÁÁÁÁÁ7.2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁDemand Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 amps
ÁÁÁÁÁÁÁÁÁÁ5
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ6
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.3ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Demand PowerÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 WÁÁÁÁÁÁÁÁÁÁ
7ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
8ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.4 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Demand Reactive Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VAR ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
10 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Demand Apparent Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VA ÁÁÁÁÁÁÁÁÁÁ
11 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
12 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Projected No. 1 Demand Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 amps ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ14
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁ
ÁÁÁÁÁ7.7ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁProjected No. 1 Demand Power
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 W
ÁÁÁÁÁÁÁÁÁÁ15
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
16ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.8ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Projected No. 1 Demand Reactive PowerÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VARÁÁÁÁÁÁÁÁÁÁ
17ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Projected No. 1 Demand Apparent Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VA ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
20 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.10 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Projected No. 2 Demand Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 amps ÁÁÁÁÁÁÁÁÁÁ
21 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
22 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁ7.11
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁProjected No. 2 Demand Power
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 W
ÁÁÁÁÁÁÁÁÁÁ23
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ24
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.12ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Projected No. 2 Demand Reactive PowerÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VARÁÁÁÁÁÁÁÁÁÁ
25ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
26ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.13 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Projected No. 2 Demand Apparent Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VA ÁÁÁÁÁÁÁÁÁÁ
27 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
28 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.14 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Projected No. 3 Demand Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 amps ÁÁÁÁÁÁÁÁÁÁ
29 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.15 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Projected No. 3 Demand Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 W ÁÁÁÁÁÁÁÁÁÁ
31 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ32 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁ7.16
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁProjected No. 3 Demand Reactive Power
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 VAR
ÁÁÁÁÁÁÁÁÁÁ33
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
34ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.17ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Projected No. 3 Demand Apparent PowerÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VAÁÁÁÁÁÁÁÁÁÁ
35ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
36 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
7.18 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Elapsed Time ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
37 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
38 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
39 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
40 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ41 ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
7.19
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data Format
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
42
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
B–11Smart Communication Card Data Tables
Publication 1403-5.1
Table B.11 Event Log – Read
ÁÁÁÁÁÁParameter No. ÁÁÁÁÁÁÁÁÁÁÁParameter Name ÁÁÁÁÁÁÁÁÁMaster Module Range ÁÁÁÁÁWord No. ÁÁÁÁÁÁRangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
8.1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Event Time Log Stamp
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Year
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0–9916 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, DateÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁ
1–128 BitÁÁÁÁÁÁÁÁ
1–318 BitÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, Minute
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3
ÁÁÁÁÁÁÁÁÁ
0–238 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, HundredthsÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4ÁÁÁÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁÁÁÁÁÁÁÁ
0–998 BitÁÁÁÁÁÁ
ÁÁÁÁÁÁ8.2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁEvent Type Value
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 14
ÁÁÁÁÁÁÁÁÁÁ5
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 14ÁÁÁÁÁÁ
ÁÁÁÁÁÁ8.3ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁEvent Code Value
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 10
ÁÁÁÁÁÁÁÁÁÁ6
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 10ÁÁÁÁÁÁ
ÁÁÁÁÁÁ8.4
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint TypeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 54ÁÁÁÁÁÁÁÁÁÁ
7ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 54ÁÁÁÁÁÁÁÁÁÁÁÁ
8.5ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint Evaluation ConditionÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 5ÁÁÁÁÁÁÁÁÁÁ
8ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 5ÁÁÁÁÁÁÁÁÁÁÁÁ
8.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint Level ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±9999x1021 ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁÁÁ
±0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
10 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
8.7 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint Action/Release Delay ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999 ÁÁÁÁÁÁÁÁÁÁ
11 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
8.8 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint Action ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 20 ÁÁÁÁÁÁÁÁÁÁ
12 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 20
ÁÁÁÁÁÁÁÁÁÁÁÁ
8.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of Event Logs Requested ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 100 ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 100ÁÁÁÁÁÁÁÁÁÁÁÁ8.10
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁNumber of Event Log Received (Counter)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ1 to 100
ÁÁÁÁÁÁÁÁÁÁ14
ÁÁÁÁÁÁÁÁÁÁÁÁ1 to 100ÁÁÁÁÁÁ
ÁÁÁÁÁÁ8.11ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁNumber of Event Log Being Returned
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ1 to 100
ÁÁÁÁÁÁÁÁÁÁ15
ÁÁÁÁÁÁÁÁÁÁÁÁ1 to 100ÁÁÁÁÁÁ
ÁÁÁÁÁÁ8.12
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Internal IdentifierÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–32767 to +32767ÁÁÁÁÁÁÁÁÁÁ
16ÁÁÁÁÁÁÁÁÁÁÁÁ
–32767 to +32767ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
17ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
20 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
21 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
22 ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
8.13
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data Format
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
23
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
B–12 Smart Communication Card Data Tables
Publication 1403-5.1
Table B.12 Voltage/Current/Miscellaneous Snapshot Log Data Table Read
ÁÁÁÁÁÁParameter No. ÁÁÁÁÁÁÁÁÁÁParameter Name ÁÁÁÁÁÁÁÁÁÁMaster Module Parameter Range ÁÁÁÁÁWord No. ÁÁÁÁÁÁRangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
9.1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Event Time Log Stamp
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Year
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0–9916 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, DateÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁ
1–128 BitÁÁÁÁÁÁÁÁ
1–318 BitÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, Minute
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3
ÁÁÁÁÁÁÁÁÁ
0–238 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, HundredthsÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4ÁÁÁÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁÁÁÁÁÁÁÁ
0–998 BitÁÁÁÁÁÁ
ÁÁÁÁÁÁ9.2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ5
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ9.3ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁL1 Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 amps
ÁÁÁÁÁÁÁÁÁÁ6
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
7ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.4ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2 CurrentÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ampsÁÁÁÁÁÁÁÁÁÁ
8ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3 Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 amps ÁÁÁÁÁÁÁÁÁÁ
10 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
11 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L4 (Neutral) Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 amps ÁÁÁÁÁÁÁÁÁÁ
12 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ9.7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ3-Phase Average Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 amps
ÁÁÁÁÁÁÁÁÁÁ14
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ15
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.8ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Positive Sequence CurrentÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ampsÁÁÁÁÁÁÁÁÁÁ
16ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
17ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Negative Sequence Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 amps ÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.10 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Percent Current Unbalance ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0.0 to 100.0 ÁÁÁÁÁÁÁÁÁÁ
20 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
21 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.11 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1–L2 Voltage ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 volts ÁÁÁÁÁÁÁÁÁÁ
22 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ23
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁ
ÁÁÁÁÁÁ9.12ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁL2–L3 Voltage
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 volts
ÁÁÁÁÁÁÁÁÁÁ24
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
25ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.13ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3–L1 VoltageÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 voltsÁÁÁÁÁÁÁÁÁÁ
26ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
27 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.14 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
AUX Voltage ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 volts ÁÁÁÁÁÁÁÁÁÁ
28 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
29 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.15 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3-Phase Average Voltage (L–L) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 volts ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
31 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁ9.16 ÁÁÁÁÁÁÁÁÁÁPositive Sequence Voltage ÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 volts ÁÁÁÁÁ32 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ33
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.17ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Negative Sequence VoltageÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 voltsÁÁÁÁÁÁÁÁÁÁ
34ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
35ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.18 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Percent Voltage Unbalance ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0.0 to 100.0 ÁÁÁÁÁÁÁÁÁÁ
36 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
37 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.19 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1–N Voltage ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 volts ÁÁÁÁÁÁÁÁÁÁ
38 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
39 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.20 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2–N Voltage ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 volts ÁÁÁÁÁÁÁÁÁÁ
40 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ41 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ9.21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁL3–N Voltage
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 volts
ÁÁÁÁÁÁÁÁÁÁ42
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ43
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
B–13Smart Communication Card Data Tables
Publication 1403-5.1
ÁÁÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module Parameter RangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter NameÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁÁÁ9.22
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ3–Phase Average Voltage (L–N)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 volts
ÁÁÁÁÁÁÁÁÁÁ44
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ45
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ReservedÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
46ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ReservedÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
47ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ9.23 ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁLast Cycle Frequency ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ20.0 to 132.0 ÁÁÁÁÁ
ÁÁÁÁÁ48 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
49 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
9.24ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Phase RotationÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = No Rotation1 = ABC2 = ACB
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
50ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 2
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.25 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of Snapshot Logs RequestedÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 50 ÁÁÁÁÁÁÁÁÁÁ
51 ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 50ÁÁÁÁÁÁÁÁÁÁÁÁ
9.26ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of snapshot Log Received(Counter)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 50ÁÁÁÁÁÁÁÁÁÁ
52ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 50ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
9.27
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of Snapshot Log BeingReturned
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 50
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
53
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 50
ÁÁÁÁÁÁÁÁÁÁÁÁ
9.28 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Internal Identifier ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–32767 to +32767 ÁÁÁÁÁÁÁÁÁÁ
54 ÁÁÁÁÁÁÁÁÁÁÁÁ
–32767 to +32767
Table B.13 Power Snapshot Log Data TableÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter Name
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master ModuleParameter Range
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Word No.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Range
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
10.1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Event Time Log StampÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
YearÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0–9916 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, Date ÁÁÁÁÁÁÁÁÁÁ
2 ÁÁÁÁÁÁ
1–128 BitÁÁÁÁÁÁÁÁ
1–318 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, MinuteÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3ÁÁÁÁÁÁÁÁÁ
0–238 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, Hundredths ÁÁÁÁÁÁÁÁÁÁ
4 ÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.2 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ10.3 ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁL1 Real Power ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ0 to 9999x1021 W ÁÁÁÁÁ
ÁÁÁÁÁ6 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
7 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.4 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2 Real Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 W ÁÁÁÁÁÁÁÁÁÁ
8 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3 Real Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 W ÁÁÁÁÁÁÁÁÁÁ
10 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ11
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ10.6
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁTotal Real Power
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 W
ÁÁÁÁÁÁÁÁÁÁ12
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
13ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.7 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1 Reactive Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VAR ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
15 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.8 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2 Reactive Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VAR ÁÁÁÁÁÁÁÁÁÁ
16 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
17 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3 Reactive Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VAR ÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ10.10
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁTotal Reactive Power
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 VAR
ÁÁÁÁÁÁÁÁÁÁ20
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ21
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.11ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1 Apparent PowerÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VAÁÁÁÁÁÁÁÁÁÁ
22ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
23 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.12 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2 Apparent Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VA ÁÁÁÁÁÁÁÁÁÁ
24 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
25 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.13 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3 Apparent Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VA ÁÁÁÁÁÁÁÁÁÁ
26 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
B–14 Smart Communication Card Data Tables
Publication 1403-5.1
ÁÁÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master ModuleParameter Range
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter NameÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
27ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.14 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Total Apparent Power ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 VA ÁÁÁÁÁÁÁÁÁÁ
28 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
29 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.15 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1 True PF ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–100.0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁÁÁ
–9999 to +9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
31 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2 True PF ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–100.0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
32 ÁÁÁÁÁÁÁÁÁÁÁÁ
–9999 to +9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
33 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ10.17
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁL3 True PF
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ–100.0 to +100.0
ÁÁÁÁÁÁÁÁÁÁ34
ÁÁÁÁÁÁÁÁÁÁÁÁ–9999 to +9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ35
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.18ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Total True PFÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–100.0 to +100.0ÁÁÁÁÁÁÁÁÁÁ
36ÁÁÁÁÁÁÁÁÁÁÁÁ
–9999 to +9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
37 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.19 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1 Displacement PF ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–100.0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
38 ÁÁÁÁÁÁÁÁÁÁÁÁ
–9999 to +9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
39 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.20 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2 Displacement PF ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–100.0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
40 ÁÁÁÁÁÁÁÁÁÁÁÁ
–9999 to +9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
41 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.21 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3 Displacement PF ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–100.0 to +100.0 ÁÁÁÁÁÁÁÁÁÁ
42 ÁÁÁÁÁÁÁÁÁÁÁÁ
–9999 to +9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ43
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁ
ÁÁÁÁÁÁ10.22ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁTotal Displacement PF
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ–100.0 to +100.0
ÁÁÁÁÁÁÁÁÁÁ44
ÁÁÁÁÁÁÁÁÁÁÁÁ–9999 to +9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
45ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.23ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L1 Distortion PFÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 100.0ÁÁÁÁÁÁÁÁÁÁ
46ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
47 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.24 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L2 Distortion PF ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 100.0 ÁÁÁÁÁÁÁÁÁÁ
48 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
49 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.25 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L3 Distortion PF ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 100.0 ÁÁÁÁÁÁÁÁÁÁ
50 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
51 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ10.26
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁTotal Distortion PF
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 100.0
ÁÁÁÁÁÁÁÁÁÁ52
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ53
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
10.27ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of Snapshot Logs RequestedÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 50ÁÁÁÁÁÁÁÁÁÁ
54ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 50ÁÁÁÁÁÁÁÁÁÁÁÁ
10.28ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of snapshot Log Received (Counter)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 50ÁÁÁÁÁÁÁÁÁÁ
55ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 50ÁÁÁÁÁÁÁÁÁÁÁÁ
10.29 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of Snapshot Log Being Returned ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 50 ÁÁÁÁÁÁÁÁÁÁ
56 ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 50ÁÁÁÁÁÁÁÁÁÁÁÁ
10.30 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Internal Identifier ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–32767 to +32767 ÁÁÁÁÁÁÁÁÁÁ
57 ÁÁÁÁÁÁÁÁÁÁÁÁ
–32767 to +32767
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
58 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ10.31 ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁData Format ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁ
59 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
B–15Smart Communication Card Data Tables
Publication 1403-5.1
Table B.14 Min_Max Log – Read
ÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No. ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter Name ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master ModuleParameter Range
ÁÁÁÁÁÁÁÁÁÁ
Word No. ÁÁÁÁÁÁÁÁÁÁÁÁ
Range
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
11.1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Time Stamp of last Min/Max Log ResetÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
YearÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0–9916 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, Date ÁÁÁÁÁÁÁÁÁÁ
2 ÁÁÁÁÁÁ
1–128 BitÁÁÁÁÁÁÁÁ
1–318 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, MinuteÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3ÁÁÁÁÁÁÁÁÁ
0–238 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, Hundredths ÁÁÁÁÁÁÁÁÁÁ
4 ÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁÁÁÁ
0–998 BitÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
11.2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Time Stamp of MIN for ParameterÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
YearÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
5ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0–9916 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, Date ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁ
1–128 BitÁÁÁÁÁÁÁÁ
1–318 BitÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, MinuteÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
7ÁÁÁÁÁÁÁÁÁ
0–238 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, Hundredths ÁÁÁÁÁÁÁÁÁÁ
8 ÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁÁÁÁ
0–998 BitÁÁÁÁÁÁ
ÁÁÁÁÁÁ11.3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
MIN Value for ParameterÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x10ÁÁÁÁÁÁÁÁÁÁ
9ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999
±0 t 21ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
10ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 999910±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
11.4ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Time Stamp of MAX for ParameterÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
YearÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
11ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0–9916 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, Date ÁÁÁÁÁÁÁÁÁÁ
12 ÁÁÁÁÁÁ
1–128 BitÁÁÁÁÁÁÁÁ
1–318 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, MinuteÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
13ÁÁÁÁÁÁÁÁÁ
0–238 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, Hundredths ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁÁÁÁ
0–998 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
11.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
MAX Value for Parameter ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
15 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
16 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
11.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of Min_Max Logs Requested ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 84 ÁÁÁÁÁÁÁÁÁÁ
17 ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 84
ÁÁÁÁÁÁÁÁÁÁÁÁ
11.7 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of Min_Max Log Received (Counter)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 84 ÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 84
ÁÁÁÁÁÁÁÁÁÁÁÁ
11.8 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of Min_Max Log Being Returned ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 84 ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 84
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
20 ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ22
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
23ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
11.9ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data FormatÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
24ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
B–16 Smart Communication Card Data Tables
Publication 1403-5.1
Table B.15 Log Selection Command Table Write
ÁÁÁÁÁÁParam. No. ÁÁÁÁÁÁÁÁÁÁParameter Name ÁÁÁÁÁÁÁÁÁÁMaster Module Range ÁÁÁÁÁWord No. ÁÁÁÁÁÁRangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
12.1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Selected Log
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
23 = Event Log24 = Min/Max Log54 = Snapshot V/I Log59 = Snapshot Power Log
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
23, 24, 54, 59
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
12.2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Requested Number of Data Sets
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 100 for Event Log1 to 84 for Min/Max Log1 to 50 for Snapshot V/I Log1 to 50 for Snapshot Power Log
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 1001 to 841 to 501 to 50
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
12.3ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Chronology of Returned DataÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Reverse1 = ForwardNote: Not used for Min/Max Log
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
12.4ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
First Min/Max Parameter to beReturned
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 84ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 84ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ5
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ6
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
7ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
8ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁÁÁ
B–17Smart Communication Card Data Tables
Publication 1403-5.1
Table B.16 Available Min/Max Log Parameters (Identifiers for parameter 12.4)Parameter Number Parameter Description
1 Phase 1 Current
2 Phase 2 Current
3 Phase 3 Current
4 Phase 4 Current
5 Average Current
6 Positive Sequence Current
7 Negative Sequence Current
8 Current Unbalance
9 Phase 1 L–L Voltage
10 Phase 2 L–L Voltage
11 Phase 3 L–L Voltage
12 Auxiliary Voltage
13 Average L–L Voltage
14 Positive Sequence Voltage
15 Negative Sequence Voltage
16 Voltage Unbalance
17 Phase 1 L–N Voltage
18 Phase 2 L–N Voltage
19 Phase 3 L–N Voltage
20 Average L–N Voltage
21 Frequency
22 Phase 1 Real Power
23 Phase 2 Real Power
24 Phase 3 Real Power
25 Total Real Power
26 Phase 1 Reactive Power
27 Phase 2 Reactive Power
28 Phase 3 Reactive Power
29 Total Reactive Power
30 Phase 1 Apparent Power
31 Phase 2 Apparent Power
32 Phase 3 Apparent Power
33 Total Apparent Power
34 Phase 1 True Power Factor
35 Phase 2 True Power Factor
36 Phase 3 True Power Factor
37 Total True Power Factor
38 Phase 1 Displacement Power Factor
39 Phase 2 Displacement Power Factor
40 Phase 3 Displacement Power Factor
41 Total Displacement Power Factor
42 Phase 1 Distortion Power Factor
Parameter Number Parameter Description
43 Phase 2 Distortion Power Factor
44 Phase 3 Distortion Power Factor
45 Total Distortion Power Factor
46 Current Demand
47 Real Power Demand
48 Reactive Power Demand
49 Apparent Power Demand
50 Phase 1 Voltage IEEE THD
51 Phase 1 Voltage IEC THD
52 Phase 1 Voltage TIF①
53 Phase 1 Voltage Crest Factor①
54 Phase 1 Voltage K-factor①
55 Phase 1 Current IEEE THD
56 Phase 1 Current IEC THD
57 Phase 1 Current TIF①
58 Phase 1 Current Crest Factor①
59 Phase 1 Current K-factor①
60 Phase 2 Voltage IEEE THD
61 Phase 2 Voltage IEC THD
62 Phase 2 Voltage TIF①
63 Phase 2 Voltage Crest Factor①
64 Phase 2 Voltage K-factor①
65 Phase 2 Current IEEE THD
66 Phase 2 Current IEC THD
67 Phase 2 Current TIF①
68 Phase 2 Current Crest Factor①
69 Phase 2 Current K-factor①
70 Phase 3 Voltage IEEE THD
71 Phase 3 Voltage IEC THD
72 Phase 3 Voltage TIF①
73 Phase 3 Voltage Crest Factor①
74 Phase 3 Voltage K-factor①
75 Phase 3 Current IEEE THD
76 Phase 3 Current IEC THD
77 Phase 3 Current TIF①
78 Phase 3 Current Crest Factor①
79 Phase 3 Current K-factor①
80 Phase 4 Current IEEE THD
81 Phase 4 Current IEC THD
82 Phase 4 Current TIF①
83 Phase 4 Current Crest Factor①
84 Phase 4 Current K-factor①
➀ Not available on 1403-LM.
B–18 Smart Communication Card Data Tables
Publication 1403-5.1
Harmonic Distortion T ables – Read
Harmonic Distortion Data Tables for Channel 2 through Channel 7 are identical to the Even and Odd HarmonicDistortion Tables for Channel 1. There are a total of 14 tables for this information.
(V1, V2, V3, I1, I2, I3, I4) The table sizes indicate this is Harmonic Distortion Data. The Channel Number designateswhich one.
Table B.17 Even Harmonic Distortion Table – Channel 1
ÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No. ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter Name ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module Range ÁÁÁÁÁÁÁÁÁÁ
Word No. ÁÁÁÁÁÁÁÁÁÁÁÁ
Range
ÁÁÁÁÁÁ13.1 ÁÁÁÁÁÁÁÁÁÁIEEE Total Harmonic Distortion ÁÁÁÁÁÁÁÁÁÁ0 to 1000% ÁÁÁÁÁ1 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ2
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ13.2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁIEC Total Harmonic Distortion
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 1000%
ÁÁÁÁÁÁÁÁÁÁ3
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
4ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
13.3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Meets IEEE 519(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 = Unknown 0 = Fail 1 = Pass
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
5
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 to +1
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.4ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
TIFÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021ÁÁÁÁÁÁÁÁÁÁ
6ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
7ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Crest Factor ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
8 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
K-Factor ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
10 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
11 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
13.7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Channel Number
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = L1 Voltage2 = L1 Current3 = L2 Voltage4 = L2 Current5 = L3 Voltage6 = L3 Current7 = L4 Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
12
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 7
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.8ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – FundamentalÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000%ÁÁÁÁÁÁÁÁÁÁ
13ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Second ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
15 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
16 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.10 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Fourth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
17 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁ13.11 ÁÁÁÁÁÁÁÁÁÁHarmonic Distortion – Sixth ÁÁÁÁÁÁÁÁÁÁ0 to 1000% ÁÁÁÁÁ19 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ20
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ13.12
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Distortion – Eighth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 1000 %
ÁÁÁÁÁÁÁÁÁÁ21
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
22ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.13 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Tenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
23 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
24 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.14 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Twelfth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
25 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
26 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.15 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Fourteenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
27 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ28 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ13.16
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Distortion – Sixteenth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 1000%
ÁÁÁÁÁÁÁÁÁÁ29
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ30
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.17ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – EighteenthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000%ÁÁÁÁÁÁÁÁÁÁ
31ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
32 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.18 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Twentieth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
33 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
34 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
B–19Smart Communication Card Data Tables
Publication 1403-5.1
ÁÁÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module RangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter NameÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁÁÁ13.19
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Distortion – Twenty-second
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 1000%
ÁÁÁÁÁÁÁÁÁÁ35
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ36
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.20ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Twenty-fourthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000%ÁÁÁÁÁÁÁÁÁÁ
37ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
38ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.21 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Twenty-sixth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
39 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
40 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.22 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Twenty-eighth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
41 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
42 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.23 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Thirtieth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
43 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ44
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁ
ÁÁÁÁÁÁ13.24ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Distortion – Thirty-second
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 1000%
ÁÁÁÁÁÁÁÁÁÁ45
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
46ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.25ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Thirty-fourthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000%ÁÁÁÁÁÁÁÁÁÁ
47ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
48 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.26 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Thirty-sixth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
49 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
50 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.27 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Thirty-eighth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
51 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
52 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁ13.28 ÁÁÁÁÁÁÁÁÁÁHarmonic Distortion – Fortieth ÁÁÁÁÁÁÁÁÁÁ0 to 1000% ÁÁÁÁÁ53 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ54
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
13.29ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
FFT Chronological Reference NumberÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁ
55ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
56ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
57 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
58 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
59 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ13.30 ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁData Format ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁ
60 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
Table B.18 Odd Harmonic Distortion Table – Channel 1ÁÁÁÁÁÁÁÁÁÁÁÁParameter No.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁParameter Name
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁMaster Module Range
ÁÁÁÁÁÁÁÁÁÁWord No.
ÁÁÁÁÁÁÁÁÁÁÁÁRangeÁÁÁÁÁÁ
ÁÁÁÁÁÁ14.1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEEE Total Harmonic DistortionÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000%ÁÁÁÁÁÁÁÁÁÁ
1ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
2 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.2 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEC Total Harmonic Distortion ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
3 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
4 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
14.3ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Meets IEEE 519(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 = Unknown 0 = Fail 1 = Pass
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
5ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 to +1
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.4 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
TIF Value ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ7 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ14.5
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁCrest Factor
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021
ÁÁÁÁÁÁÁÁÁÁ8
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
9ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
K-Factor ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
10 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
11 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
14.7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Channel Number
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = L1 Voltage2 = L1 Current3 = L2 Voltage4 = L2 Current5 = L3 Voltage6 = L3 Current7 = L4 Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
12
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 7
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.8ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – FundamentalÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000%ÁÁÁÁÁÁÁÁÁÁ
13ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
B–20 Smart Communication Card Data Tables
Publication 1403-5.1
ÁÁÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module RangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter NameÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ14
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.9ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – ThirdÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000%ÁÁÁÁÁÁÁÁÁÁ
15ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
16 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.10 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Fifth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
17 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.11 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Seventh ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ20 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ14.12
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Distortion – Ninth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 1000%
ÁÁÁÁÁÁÁÁÁÁ21
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
22ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.13 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Eleventh ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
23 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
24 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.14 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Thirteenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
25 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
26 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ14.15
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Distortion – Fifteenth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 1000%
ÁÁÁÁÁÁÁÁÁÁ27
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
28ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Seventeenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
29 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.17 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Nineteenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
31 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
32 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁ14.18 ÁÁÁÁÁÁÁÁÁÁHarmonic Distortion – Twenty-first ÁÁÁÁÁÁÁÁÁÁ0 to 1000% ÁÁÁÁÁ33 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ34
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.19ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Twenty-thirdÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000%ÁÁÁÁÁÁÁÁÁÁ
35ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
36 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.20 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Twenty-fifth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
37 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
38 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁ14.21 ÁÁÁÁÁÁÁÁÁÁHarmonic Distortion – Twenty-seventhÁÁÁÁÁÁÁÁÁÁ0 to 1000% ÁÁÁÁÁ39 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ40
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.22ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Twenty-ninthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000%ÁÁÁÁÁÁÁÁÁÁ
41ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
42 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.23 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Thirty-first ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
43 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
44 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.24 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Thirty-third ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
45 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ46
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.25ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Thirty-fifthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000%ÁÁÁÁÁÁÁÁÁÁ
47ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
48 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.26 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Thirty-seventh ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
49 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
50 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.27 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Distortion – Thirty-ninth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
51 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ52 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ14.28
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Distortion – Forty-first
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 1000%
ÁÁÁÁÁÁÁÁÁÁ53
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
54ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.29 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
FFT Chronological Reference NumberÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767 ÁÁÁÁÁÁÁÁÁÁ
55 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
56 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
57 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
58 ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ59
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
60ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
14.30ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data FormatÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
61ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
B–21Smart Communication Card Data Tables
Publication 1403-5.1
Harmonic Magnitude Data Tables for Channel 2 through Channel 7 are identical to the Even and Odd HarmonicMagnitude Tables for Channel 1. There are a total of 14 tables for this information. (V1, V2, V3, I1, I2, I3, I4)
Table B.19 Even Harmonic Magnitude Data Table Channel 1ÁÁÁÁÁÁÁÁÁÁÁÁParameter No.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁParameter Name
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁMaster Module Range
ÁÁÁÁÁÁÁÁÁÁWord No.
ÁÁÁÁÁÁÁÁÁÁÁÁRangeÁÁÁÁÁÁ
ÁÁÁÁÁÁ15.1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEEE Total Harmonic DistortionÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000%ÁÁÁÁÁÁÁÁÁÁ
1ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
2 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.2 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEC Total Harmonic Distortion ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
3 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
4 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
15.3ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Meets IEEE 519(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 = Unknown 0 = Fail 1 = Pass
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
5ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 to +1
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.4 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
TIF Value ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
7 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Crest Factor ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
8 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁ15.6 ÁÁÁÁÁÁÁÁÁÁK-Factor ÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 ÁÁÁÁÁ10 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ11
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
15.7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Channel Number
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = L1 Voltage2 = L1 Current3 = L2 Voltage4 = L2 Current5 = L3 Voltage6 = L3 Current7 = L4 Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
12
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 7
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.8 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Fundamental ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Second ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
15 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ16 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ15.10
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Magnitude – Fourth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021
ÁÁÁÁÁÁÁÁÁÁ17
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ18
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.11ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – SixthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
19ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
20 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.12 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Eighth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
21 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
22 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.13 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Tenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
23 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
24 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.14 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Twelfth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
25 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ26
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ15.15
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Magnitude – Fourteenth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021
ÁÁÁÁÁÁÁÁÁÁ27
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
28ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Sixteenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
29 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.17 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Eighteenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
31 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
32 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.18 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Twentieth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
33 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
34 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ15.19
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Magnitude – Twenty-second
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021
ÁÁÁÁÁÁÁÁÁÁ35
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ36
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
B–22 Smart Communication Card Data Tables
Publication 1403-5.1
ÁÁÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module RangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter NameÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁÁÁ15.20
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Magnitude – Twenty-fourth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021
ÁÁÁÁÁÁÁÁÁÁ37
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ38
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.21ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Twenty-sixthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021ÁÁÁÁÁÁÁÁÁÁ
39ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
40ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.22 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Twenty-eighth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
41 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
42 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.23 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Thirtieth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
43 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
44 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.24 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Thirty-second ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
45 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ46
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁ
ÁÁÁÁÁÁ15.25ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Magnitude – Thirty-fourth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021
ÁÁÁÁÁÁÁÁÁÁ47
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
48ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.26ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Thirty-sixthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
49ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
50 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.27 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Thirty-eighth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
51 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
52 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.28 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Fortieth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
53 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
54 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁ15.29 ÁÁÁÁÁÁÁÁÁÁFFT Update Reference Number ÁÁÁÁÁÁÁÁÁÁ0 to 32767 ÁÁÁÁÁ55 ÁÁÁÁÁÁ0 to 32767ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ56
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
57ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
15.30ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data FormatÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
58ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 t o 1
Table B.20 Odd Harmonic Magnitude Data TableÁÁÁÁÁÁÁÁÁÁÁÁParameter No.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁParameter Name
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁMaster Module Range
ÁÁÁÁÁÁÁÁÁÁWord No.
ÁÁÁÁÁÁÁÁÁÁÁÁRangeÁÁÁÁÁÁ
ÁÁÁÁÁÁ16.1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEEE Total Harmonic DistortionÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000%ÁÁÁÁÁÁÁÁÁÁ
1ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
2 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.2 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEC Total Harmonic Distortion ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1000% ÁÁÁÁÁÁÁÁÁÁ
3 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
4 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
16.3ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Meets IEEE 519(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 = Unknown 0 = Fail 1 = Pass
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
5ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–1 to +1
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.4 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
TIF Value ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
7 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Crest Factor ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
8 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ16.6
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁK-Factor
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021
ÁÁÁÁÁÁÁÁÁÁ10
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ11
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
16.7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Channel Number
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = L1 Voltage2 = L1 Current3 = L2 Voltage4 = L2 Current5 = L3 Voltage6 = L3 Current7 = L4 Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
12
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 7
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.8 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Fundamental ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Third ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
15 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ16 ÁÁÁÁÁÁ10±0 to 21
B–23Smart Communication Card Data Tables
Publication 1403-5.1
ÁÁÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module RangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter NameÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁÁÁ16.10
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Magnitude – Fifth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021
ÁÁÁÁÁÁÁÁÁÁ17
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ18
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.11ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – SeventhÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021ÁÁÁÁÁÁÁÁÁÁ
19ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
20ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.12 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Ninth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
21 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
22 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.13 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Eleventh ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
23 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
24 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.14 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Thirteenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
25 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ26
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁ
ÁÁÁÁÁÁ16.15ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Magnitude – Fifteenth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021
ÁÁÁÁÁÁÁÁÁÁ27
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
28ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.16ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – SeventeenthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
29ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.17 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Nineteenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
31 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
32 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.18 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Twenty-first ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
33 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
34 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁ16.19 ÁÁÁÁÁÁÁÁÁÁHarmonic Magnitude – Twenty-third ÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 ÁÁÁÁÁ35 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ36
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.20ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Twenty-fifthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021ÁÁÁÁÁÁÁÁÁÁ
37ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
38ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.21 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Twenty-seventhÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
39 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
40 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.22 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Twenty-ninth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
41 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
42 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.23 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Thirty-first ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
43 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ44 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ16.24
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Magnitude – Thirty-third
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021
ÁÁÁÁÁÁÁÁÁÁ45
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ46
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.25ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Thirty-fifthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
47ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
48 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.26 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Thirty-seventhÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
49 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
50 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.27 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Magnitude – Thirty-ninth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
51 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
52 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁ16.28 ÁÁÁÁÁÁÁÁÁÁHarmonic Magnitude – Forty-first ÁÁÁÁÁÁÁÁÁÁ0 to 9999x1021 ÁÁÁÁÁ53 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ54
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ16.29
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁFFT Chronological Reference Number
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 32767
ÁÁÁÁÁÁÁÁÁÁ55
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 32767ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
56ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
16.30ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data FormatÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
57ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
B–24 Smart Communication Card Data Tables
Publication 1403-5.1
Harmonic Phase Angle Data Tables for Channel 2 through Channel 7 are identical to the Even and Odd Harmonic PhaseAngle Data Tables for Channel 1. There are a total of 14 tables for this information. (V1, V2, V3, I1, I2, I3, I4)
Table B.21 Even Harmonic Phase Angle Data Table Channel 1
ÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No. ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter Name ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module Range ÁÁÁÁÁÁÁÁÁÁ
Word No. ÁÁÁÁÁÁÁÁÁÁÁÁ
Range
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ1 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ2
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ3
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
4ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
5 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 –1ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
7 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
8 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
10 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ11
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
17.7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Channel Number(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = L1 Voltage2 = L1 Current3 = L2 Voltage4 = L2 Current5 = L3 Voltage6 = L3 Current7 = L4 Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
12
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 7
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.8 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – FundamentalÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Second ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
15 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
16 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ17.10
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Phase Angle – Fourth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 360 degrees
ÁÁÁÁÁÁÁÁÁÁ17
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ18
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.11ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – SixthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degreesÁÁÁÁÁÁÁÁÁÁ
19ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
20ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.12 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Eighth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
21 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
22 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.13 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Tenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
23 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
24 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.14 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Twelfth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
25 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ26 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ17.15
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Phase Angle – Fourteenth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 360 degrees
ÁÁÁÁÁÁÁÁÁÁ27
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
28ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.16ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – SixteenthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degreesÁÁÁÁÁÁÁÁÁÁ
29ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.17 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Eighteenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
31 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
32 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.18 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Twentieth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
33 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
34 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁ17.19 ÁÁÁÁÁÁÁÁÁÁHarmonic Phase Angle – Twenty-secondÁÁÁÁÁÁÁÁÁÁ0 to 360 degrees ÁÁÁÁÁ35 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ36
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ17.20
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Phase Angle – Twenty-fourth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 360 degrees
ÁÁÁÁÁÁÁÁÁÁ37
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
38ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
B–25Smart Communication Card Data Tables
Publication 1403-5.1
ÁÁÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module RangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter NameÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁÁÁ17.21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Phase Angle – Twenty-sixth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 360 degrees
ÁÁÁÁÁÁÁÁÁÁ39
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ40
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.22ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Twenty-eighthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degreesÁÁÁÁÁÁÁÁÁÁ
41ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
42ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.23 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Thirtieth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
43 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
44 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.24 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Thirty-secondÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
45 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
46 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.25 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Thirty-fourthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
47 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ48
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁ
ÁÁÁÁÁÁ17.26ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Phase Angle – Thirty-sixth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 360 degrees
ÁÁÁÁÁÁÁÁÁÁ49
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
50ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.27ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Thirty-eighthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degreesÁÁÁÁÁÁÁÁÁÁ
51ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
52 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.28 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Fortieth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
53 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
54 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.29 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
FFT Chronological Reference NumberÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767 ÁÁÁÁÁÁÁÁÁÁ
55 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767
ÁÁÁÁÁÁÁÁÁÁÁÁ
17.30 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data Format ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁ
56 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
Table B.22 Odd Harmonic Phase Angle Data Table
ÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No. ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter Name ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module Range ÁÁÁÁÁÁÁÁÁÁ
Word No. ÁÁÁÁÁÁÁÁÁÁÁÁ
Range
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
1 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ2 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ3
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ4
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
5ÁÁÁÁÁÁÁÁÁÁÁÁ
0 –1ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
7 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
8 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
10 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
11 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
18.7ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Channel Number(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = L1 Voltage2 = L1 Current3 = L2 Voltage4 = L2 Current5 = L3 Voltage6 = L3 Current7 = L4 Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
12ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 7
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.8 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Fundamental ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Third ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
15 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
16 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.10 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Fifth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
17 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ18
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁ
ÁÁÁÁÁÁ18.11ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Phase Angle – Seventh
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 360 degrees
ÁÁÁÁÁÁÁÁÁÁ19
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
20ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.12ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – NinthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degreesÁÁÁÁÁÁÁÁÁÁ
21ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
B–26 Smart Communication Card Data Tables
Publication 1403-5.1
ÁÁÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module RangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter NameÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ22
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁ
ÁÁÁÁÁÁ18.13ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Phase Angle – Eleventh
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 360 degrees
ÁÁÁÁÁÁÁÁÁÁ23
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
24ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.14ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – ThirteenthÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degreesÁÁÁÁÁÁÁÁÁÁ
25ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
26 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.15 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Fifteenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
27 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
28 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Seventeenth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
29 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ18.17
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Phase Angle – Nineteenth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 360 degrees
ÁÁÁÁÁÁÁÁÁÁ31
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ32
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.18ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Twenty-firstÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degreesÁÁÁÁÁÁÁÁÁÁ
33ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
34ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.19 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Twenty-third ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
35 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
36 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.20 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Twenty-fifth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
37 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
38 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.21 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Twenty-seventh ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
39 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ40 ÁÁÁÁÁÁ10±0 to 21ÁÁÁÁÁÁÁÁÁÁÁÁ18.22
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Phase Angle – Twenty-ninth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 360 degrees
ÁÁÁÁÁÁÁÁÁÁ41
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
42ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.23ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Thirty-firstÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degreesÁÁÁÁÁÁÁÁÁÁ
43ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
44 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.24 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Thirty-third ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
45 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
46 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.25 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Thirty-fifth ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
47 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
48 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁ18.26 ÁÁÁÁÁÁÁÁÁÁÁHarmonic Phase Angle – Thirty-seventh ÁÁÁÁÁÁÁÁÁ0 to 360 degrees ÁÁÁÁÁ49 ÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ50
ÁÁÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ18.27
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁHarmonic Phase Angle – Thirty-ninth
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 360 degrees
ÁÁÁÁÁÁÁÁÁÁ51
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
52ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.28 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Harmonic Phase Angle – Forty-first ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 360 degrees ÁÁÁÁÁÁÁÁÁÁ
53 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
54 ÁÁÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ
18.29 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
FFT Chronological Reference Number ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767 ÁÁÁÁÁÁÁÁÁÁ
55 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767
B–27Smart Communication Card Data Tables
Publication 1403-5.1
Table B.23 Oscillogram Capture Data – Read (54 Reads of 48 data points for 2-channel 12-cycle oscillogram or 9 Reads of 48 data pointsfor 7-channel 2-cycle oscillogram)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter NameÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master ModuleRange
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Range
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.1 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Time Stamp of Oscillogram ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Year ÁÁÁÁÁÁÁÁÁÁ
1 ÁÁÁÁÁÁÁÁÁÁÁÁ
0–9916 Bit IntegerÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, DateÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁÁÁÁ
1–128 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
1–318 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, Minute ÁÁÁÁÁÁÁÁÁÁ
3 ÁÁÁÁÁÁ
0–238 BitÁÁÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, HundredthsÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4ÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
0–998 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
19.2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Channel Number(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = L1 Voltage2 = L1 Current3 = L2 Voltage4 = L2 Current5 = L3 Voltage6 = L3 Current7 = L4 Current8 = Ch A 12-Cycle9 = Ch B 12-Cycle
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
5
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 9
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.3 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Channel Data Count (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
for 2-cycle 432for 12-cycle 2592
ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁÁÁÁÁÁÁ
432 or 2592
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
19.4ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Chronological Reference Number(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to +32767ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
7ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Block Number (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 54 ÁÁÁÁÁÁÁÁÁÁ
8 ÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 54ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
19.6
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Actual Channel Numer(Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 = L1 Voltage2 = L1 Current3 = L2 Voltage4 = L2 Current5 = L3 Voltage6 = L3 Current7 = L4 Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
9
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 to 7
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.7 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 1 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
10 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.8 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 2 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
11 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 3 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
12 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.10 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 4 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.11 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 5 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁ19.12 ÁÁÁÁÁÁÁÁÁÁÁÁÁOscillogram Data Point 6 (Reserved 1403-LM) ÁÁÁÁÁÁÁ±5000 ÁÁÁÁÁ15 ÁÁÁÁÁÁ±5000ÁÁÁÁÁÁÁÁÁÁÁÁ19.13
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁOscillogram Data Point 7 (Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ±5000
ÁÁÁÁÁÁÁÁÁÁ16
ÁÁÁÁÁÁÁÁÁÁÁÁ±5000ÁÁÁÁÁÁ
ÁÁÁÁÁÁ19.14ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁOscillogram Data Point 8 (Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ±5000
ÁÁÁÁÁÁÁÁÁÁ17
ÁÁÁÁÁÁÁÁÁÁÁÁ±5000ÁÁÁÁÁÁ
ÁÁÁÁÁÁ19.15
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 9 (Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁ
18ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 10 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.17 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 11 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
20 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.18 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 12 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
21 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.19 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 13 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
22 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.20 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 14 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
23 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁ19.21 ÁÁÁÁÁÁÁÁÁÁÁÁÁOscillogram Data Point 15 (Reserved 1403-LM) ÁÁÁÁÁÁÁ±5000 ÁÁÁÁÁ24 ÁÁÁÁÁÁ±5000ÁÁÁÁÁÁÁÁÁÁÁÁ19.22
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁOscillogram Data Point 16 (Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ±5000
ÁÁÁÁÁÁÁÁÁÁ25
ÁÁÁÁÁÁÁÁÁÁÁÁ±5000ÁÁÁÁÁÁ
ÁÁÁÁÁÁ19.23ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁOscillogram Data Point 17 (Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ±5000
ÁÁÁÁÁÁÁÁÁÁ26
ÁÁÁÁÁÁÁÁÁÁÁÁ±5000ÁÁÁÁÁÁ
ÁÁÁÁÁÁ19.24
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 18 (Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁ
27ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.25 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 19 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
28 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.26 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 20 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
29 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.27 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 21 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
B–28 Smart Communication Card Data Tables
Publication 1403-5.1
ÁÁÁÁÁÁÁÁÁÁÁÁ
RangeÁÁÁÁÁÁÁÁÁÁ
Word No.ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master ModuleRange
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter NameÁÁÁÁÁÁÁÁÁÁÁÁ
Parameter No.ÁÁÁÁÁÁÁÁÁÁÁÁ
19.28ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 22 (Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁ
31ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.29 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 23 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
32 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.30 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 24 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
33 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.31 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 25 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
34 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.32 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 26 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
35 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.33 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 27 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
36 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.34 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 28 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
37 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ19.35
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁOscillogram Data Point 29 (Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ±5000
ÁÁÁÁÁÁÁÁÁÁ38
ÁÁÁÁÁÁÁÁÁÁÁÁ±5000ÁÁÁÁÁÁ
ÁÁÁÁÁÁ19.36ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁOscillogram Data Point 30 (Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ±5000
ÁÁÁÁÁÁÁÁÁÁ39
ÁÁÁÁÁÁÁÁÁÁÁÁ±5000ÁÁÁÁÁÁ
ÁÁÁÁÁÁ19.37
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 31 (Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁ
40ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.38 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 32 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁ
41 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.39 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 33 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
42 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.40 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 34 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
43 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.41 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 35 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
44 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.42 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 36 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
45 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.43 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 37 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
46 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ19.44
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁOscillogram Data Point 38 (Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ±5000
ÁÁÁÁÁÁÁÁÁÁ47
ÁÁÁÁÁÁÁÁÁÁÁÁ±5000ÁÁÁÁÁÁ
ÁÁÁÁÁÁ19.45ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁOscillogram Data Point 39 (Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ±5000
ÁÁÁÁÁÁÁÁÁÁ48
ÁÁÁÁÁÁÁÁÁÁÁÁ±5000ÁÁÁÁÁÁ
ÁÁÁÁÁÁ19.46
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 40 (Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁ
49ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.47ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 41 (Reserved 1403-LM)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁ
50ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.48 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 42 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
51 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ
19.49 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 43 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
52 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.50 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 44 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
53 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.51 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 45 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
54 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000
ÁÁÁÁÁÁÁÁÁÁÁÁ
19.52 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Oscillogram Data Point 46 (Reserved 1403-LM) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±5000 ÁÁÁÁÁÁÁÁÁÁ
55 ÁÁÁÁÁÁÁÁÁÁÁÁ
±5000ÁÁÁÁÁÁÁÁÁÁÁÁ19.53
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁOscillogram Data Point 47 (Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ±5000
ÁÁÁÁÁÁÁÁÁÁ56
ÁÁÁÁÁÁÁÁÁÁÁÁ±5000ÁÁÁÁÁÁ
ÁÁÁÁÁÁ19.54ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁOscillogram Data Point 48 (Reserved 1403-LM)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ±5000
ÁÁÁÁÁÁÁÁÁÁ57
ÁÁÁÁÁÁÁÁÁÁÁÁ±5000ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
58ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
59ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
60 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
61 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
62 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
63 ÁÁÁÁÁÁÁÁÁÁÁÁ
For PT Secondary Values 138 Max Voltage = 138.0For PT Secondary Values 138 Max Voltage = 399.0
For MM01A or MM01B Max Current = 1.42For MM05A or MM05B Max Current = 7.10
Max Counts = 4095
Max Voltage or Max Current 2
Max Counts
PT or CT Primary
PT or CT SecondaryOscillogram Data Point Voltage or Current
B–29Smart Communication Card Data Tables
Publication 1403-5.1
Table B.24 Diagnostic Data Table (Self-test Results) Read
ÁÁÁÁÁÁParameter No. ÁÁÁÁÁÁÁÁÁÁParameter Name ÁÁÁÁÁÁÁÁÁÁMaster Module Range ÁÁÁÁÁWord No. ÁÁÁÁÁÁRangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
20.1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Time Stamp of Diagnostic Data
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Year
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0–9916 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, Date ÁÁÁÁÁÁÁÁÁÁ
2 ÁÁÁÁÁÁ
1–128 BitÁÁÁÁÁÁÁÁ
1–318 BitÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, MinuteÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3ÁÁÁÁÁÁÁÁÁ
0–238 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, Hundredths ÁÁÁÁÁÁÁÁÁÁ
4 ÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁÁÁÁ
0–998 BitÁÁÁÁÁÁ
ÁÁÁÁÁÁ20.2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Bulletin NumberÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1403ÁÁÁÁÁÁÁÁÁÁ
5ÁÁÁÁÁÁÁÁÁÁÁÁ
1403ÁÁÁÁÁÁÁÁÁÁÁÁ
20.3 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module FRN ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767 ÁÁÁÁÁÁÁÁÁÁ
6 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁÁÁ
20.4 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Options Bit Field ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
7 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
20.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Summary Status ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
8 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
20.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module ROM Status ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ20.7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁMaster Module RAM Status
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ10
ÁÁÁÁÁÁÁÁÁÁÁÁ16 Bit IntegerÁÁÁÁÁÁ
ÁÁÁÁÁÁ20.8
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
NV RAM StatusÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
11ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
20.9ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Power Supply CheckÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
12ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
20.10 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data Acquisition ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
20.11 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Master Module Watchdog Timer ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
20.12 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Real Time Clock Status ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
15 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁ20.13 ÁÁÁÁÁÁÁÁÁÁReserved ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ20.14
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ17
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ20.15
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Battery UsageÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁ
18ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁÁÁ
20.16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Smart Communication Card Status ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
20.17 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
20 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ20.18 ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁSmart Communication Card Type ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ0 = none1 = 1403-NSC
ÁÁÁÁÁÁÁÁÁÁ
21 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁÁÁ
20.19ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Smart Communication Card FRNÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁ
22ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁÁÁ
20.20 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of Display Modules ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 3 ÁÁÁÁÁÁÁÁÁÁ
23 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 3ÁÁÁÁÁÁÁÁÁÁÁÁ
20.21 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Display Module Status ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
24 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
20.22 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Display Module Self Test Results Word 1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
25 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
20.23 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Display Module Self Test Results Word 2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
26 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ20.24
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁDisplay Module No. 1 FRN
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 32767
ÁÁÁÁÁÁÁÁÁÁ27
ÁÁÁÁÁÁÁÁÁÁÁÁ0 to 32767ÁÁÁÁÁÁ
ÁÁÁÁÁÁ20.25
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Display Module No. 2 FRNÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁ
28ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁÁÁ
20.26 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Display Module No. 3 FRN ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767 ÁÁÁÁÁÁÁÁÁÁ
29 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁÁÁ
20.27 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Auxiliary Frequency ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999x1021 ÁÁÁÁÁÁÁÁÁÁ
30 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
31 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32
ÁÁÁÁÁÁÁÁÁÁÁÁ
20.28 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Fiber Loop Back Test Results ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Fail1 = Pass
ÁÁÁÁÁÁÁÁÁÁ
32 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1ÁÁÁÁÁÁÁÁÁÁÁÁ
20.29 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
EEPROM Status ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
33 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
20.30 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Device ID ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 255 ÁÁÁÁÁÁÁÁÁÁ
34 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 255ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
20.31
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
General Purpose Status Bits
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
bit 0 = oscillogram capturedbit 1 = snapshot buffer fullbit 2 = oscillogram triggered by asetpoint
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
35
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 7
ÁÁÁÁÁÁÁÁÁÁÁÁ
20.32 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Block Write Error Status Word (BlockSize ID) ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
0 = OKOther value = Error ÁÁÁÁÁ
ÁÁÁÁÁ36 ÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 64
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
20.33ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Block Write Error Status Word(Parameter Number)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = OKOther value = Error
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
37ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 32767ÁÁÁÁÁÁÁÁÁÁÁÁ20.34
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ38
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ20.35
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
39ÁÁÁÁÁÁÁÁÁÁÁÁ
B–30 Smart Communication Card Data Tables
Publication 1403-5.1
Table B.25 Setpoint Setup Data Table – Write/Read
ÁÁÁÁÁÁParameter No. ÁÁÁÁÁÁÁÁÁÁParameter Name ÁÁÁÁÁÁÁÁÁÁÁMaster Module Range ÁÁÁÁÁWord No. ÁÁÁÁÁRangeÁÁÁÁÁÁÁÁÁÁÁÁ21.1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁSetpoint Number
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ1 to 20
ÁÁÁÁÁÁÁÁÁÁ1
ÁÁÁÁÁÁÁÁÁÁ1 to 20ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
21.2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint TypeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 54 (see Table B.26 in Publication1403-5.1)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 54
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
21.3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint Evaluation Condition
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Over Forward = 0Over Reverse = 1Under Forward = 2Under Reverse = 3Equal = 4Not Equal = 5
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 5
ÁÁÁÁÁÁÁÁÁÁÁÁ
21.4 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint High Limit ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0.0 to 1,000,000.0 ÁÁÁÁÁÁÁÁÁÁ
4 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
5 ÁÁÁÁÁÁÁÁÁÁ
10±0 to 21
ÁÁÁÁÁÁ21.5 ÁÁÁÁÁÁÁÁÁÁSetpoint Low Limit ÁÁÁÁÁÁÁÁÁÁÁ0.0 to 1,000,000.0 ÁÁÁÁÁ6 ÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ7
ÁÁÁÁÁÁÁÁÁÁ10±0 to 21
ÁÁÁÁÁÁÁÁÁÁÁÁ21.6
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁSetpoint Action Delay
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ0 to 9999
ÁÁÁÁÁÁÁÁÁÁ8
ÁÁÁÁÁÁÁÁÁÁ0 to 9999ÁÁÁÁÁÁ
ÁÁÁÁÁÁ21.7
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint Release DelayÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁ
9ÁÁÁÁÁÁÁÁÁÁ
0 to 9999ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
21.8ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint Action TypeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 20 (see Table B.26 in Publication1403-5.1)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
10ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 20
ÁÁÁÁÁÁÁÁÁÁÁÁ
21.9 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Present Unit Password ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 9999Default = 0
ÁÁÁÁÁÁÁÁÁÁ
11 ÁÁÁÁÁÁÁÁÁÁ
0 to 9999
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved WordÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
12ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
13 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
15 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
17 ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ18
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ19
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
21.10ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data FormatÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = Integer/Exponent1 = Floating Point
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
20ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 1
B–31Smart Communication Card Data Tables
Publication 1403-5.1
Table B.26 Setpoint TypeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁSetpoint Type Name
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁValueÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁNot Used (Inactive)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Voltage ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Voltage Unbalance ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Current Unbalance ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Vaux Voltage ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
5
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Neutral (I4) Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
6ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁkW
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ7ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁkVARÁÁÁÁÁÁÁÁÁÁÁÁÁÁ8ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁkVA
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
9ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Total True Power FactorÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
10ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Total Displacement Power Factor ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
11ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Total Distortion Power Factor ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
12
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
kW Demand ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
13
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
kVAR Demand ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
14
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
kVA Demand ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
15ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁCurrent Demand
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ16ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁType 1 Predictive Demand AÁÁÁÁÁÁÁÁÁÁÁÁÁÁ17ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁType 1 Predictive Demand W
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
18ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Type 1 Predictive Demand VARÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
19ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Type 1 Predictive Demand VA ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
20ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Type 2 Predictive Demand A ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
21
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Type 2 Predictive Demand W ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
22
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Type 2 Predictive Demand VAR ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
23
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Type 2 Predictive Demand VA ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
24
ÁÁÁÁÁÁÁÁÁÁType 3 Predictive Demand A ÁÁÁÁÁÁÁ25ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁType 3 Predictive Demand W
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ26ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁType 3 Predictive Demand VAR
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
27ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Type 3 Predictive Demand VAÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
28ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Frequency ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
29ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Phase Rotation ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
30ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
K-Factor: Voltage① ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
31
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
K-Factor: Current① ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
32
① Not Available For 1403-LM
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁSetpoint Type Name
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁValueÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁK-Factor: Neutral Current①
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
33ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Crest Factor: Voltage①ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
34ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Crest Factor: Current① ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
35ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Crest Factor: Neutral Current① ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
36
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
TIF: Voltage① ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
37
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
TIF: Current① ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
38
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
TIF: Neutral Current① ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
39ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁIEEE THD: Voltage
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ40ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁIEEE THD: CurrentÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ41ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁIEEE THD: Neutral Current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
42ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEC THD: VoltageÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
43ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEC THD: Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
44ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEC THD: Neutral Current ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
45
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEEE519: Voltage① ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
46
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEEE519: Current① ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
47
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IEEE519: Neutral Current① ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
48ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁStatus Input No. 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ49ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁStatus Input No. 2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ50ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁStatus Input No. 3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
51ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Status Input No. 4ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
52ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Any Status Input ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
53ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Battery Usage Timer ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
54
Table B.27 Setpoint ActionÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁSetpoint Action
ÁÁÁÁÁÁÁÁÁÁValueÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁNo ActionÁÁÁÁÁÁÁÁÁÁ0ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁActivate Relay No. 1 and Output Flag No. 1
ÁÁÁÁÁÁÁÁÁÁ
1ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Activate Relay No. 2 and Output Flag No. 2 ÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Activate Output Flag No. 3 ÁÁÁÁÁÁÁÁÁÁ
3ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Activate Output Flag No. 4 ÁÁÁÁÁÁÁÁÁÁ
4
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Activate Output Flag No. 5 ÁÁÁÁÁÁÁÁÁÁ
5
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Activate Output Flag No. 6 ÁÁÁÁÁÁÁÁÁÁ
6
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Activate Output Flag No. 7 ÁÁÁÁÁÁÁÁÁÁ
7ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁActivate Output Flag No. 8
ÁÁÁÁÁÁÁÁÁÁ8ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁActivate Output Flag No. 9ÁÁÁÁÁÁÁÁÁÁ9ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁActivate Output Flag No. 10
ÁÁÁÁÁÁÁÁÁÁ
10ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Activate Output Flag No. 11ÁÁÁÁÁÁÁÁÁÁ
11ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Activate Output Flag No. 12 ÁÁÁÁÁÁÁÁÁÁ
12ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Activate Output Flag No. 13 ÁÁÁÁÁÁÁÁÁÁ
13
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Activate Output Flag No. 14 ÁÁÁÁÁÁÁÁÁÁ
14
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Activate Output Flag No. 15 ÁÁÁÁÁÁÁÁÁÁ
15
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Activate Output Flag No. 16 ÁÁÁÁÁÁÁÁÁÁ
16ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁInitiate Waveform Capture①
ÁÁÁÁÁÁÁÁÁÁ17ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁPerform SnapshotÁÁÁÁÁÁÁÁÁÁ18ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁClear kW-HR Power Counter
ÁÁÁÁÁÁÁÁÁÁ
19ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Clear kVAR-HR Power CounterÁÁÁÁÁÁÁÁÁÁ
20
B–32 Smart Communication Card Data Tables
Publication 1403-5.1
Table B.28 Relay/Setpoint Status Table Read
ÁÁÁÁÁÁParameter No. ÁÁÁÁÁÁÁÁÁÁParameter Name ÁÁÁÁÁÁÁÁÁÁMaster Module Range ÁÁÁÁÁWord No. ÁÁÁÁÁÁRangeÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
22.1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Time Stamp
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Year
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0–9916 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Month, DateÁÁÁÁÁÁÁÁÁÁ
2ÁÁÁÁÁÁ
1–128 BitÁÁÁÁÁÁÁÁ
1–318 BitÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Hour, Minute
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3
ÁÁÁÁÁÁÁÁÁ
0–238 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁ
0–598 Bit
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Seconds, HundredthsÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4ÁÁÁÁÁÁÁÁÁ
0–598 BitÁÁÁÁÁÁÁÁÁÁÁÁ
0–998 BitÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
22.2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Relay No. 1 Status (Bit Fields)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = De-energized1 = Energized2 = Forced De-energized3 = Forced Energized
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
5
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
22.3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Relay No. 2 Status (Bit Fields)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 = De-energized1 = Energized2 = Forced De-energized3 = Forced Energized
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
6
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 3
ÁÁÁÁÁÁÁÁÁÁÁÁ
22.4 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Alarm Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
7 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
22.5 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Status Inputs (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
8 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
22.6 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Counter Status Input No. 1 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–32767 to 32767 ÁÁÁÁÁÁÁÁÁÁ
9 ÁÁÁÁÁÁÁÁÁÁÁÁ
–32767 to 32767
ÁÁÁÁÁÁ22.7 ÁÁÁÁÁÁÁÁÁÁCounter Status Input No. 2 ÁÁÁÁÁÁÁÁÁÁ–32767 to 32767 ÁÁÁÁÁ10 ÁÁÁÁÁÁ–32767 to 32767ÁÁÁÁÁÁÁÁÁÁÁÁ22.8
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁCounter Status Input No. 3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ–32767 to 32767
ÁÁÁÁÁÁÁÁÁÁ11
ÁÁÁÁÁÁÁÁÁÁÁÁ–32767 to 32767ÁÁÁÁÁÁ
ÁÁÁÁÁÁ22.9ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁCounter Status Input No. 4
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ–32767 to 32767
ÁÁÁÁÁÁÁÁÁÁ12
ÁÁÁÁÁÁÁÁÁÁÁÁ–32767 to 32767ÁÁÁÁÁÁ
ÁÁÁÁÁÁ22.10
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 1 Status (Bit Fields)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
13ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
22.11 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 2 Status (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
14 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
22.12 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 3 Status (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
15 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
22.13 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 4 Status (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
16 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
22,14 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 5 Status (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
17 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
22.15 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 6 Status (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
18 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
22.16 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 7 Status (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
19 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ22.17
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁSetpoint No. 8 Status (Bit Fields)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ20
ÁÁÁÁÁÁÁÁÁÁÁÁ16 Bit IntegerÁÁÁÁÁÁ
ÁÁÁÁÁÁ22.18ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁSetpoint No. 9 Status (Bit Fields)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ21
ÁÁÁÁÁÁÁÁÁÁÁÁ16 Bit IntegerÁÁÁÁÁÁ
ÁÁÁÁÁÁ22.19
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 10 Status (Bit Fields)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
22ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
22.20 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 11 Status (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
23 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
22.21 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 12 Status (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
24 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
22.22 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 13 Status (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
25 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
22.23 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 14 Status (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
26 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
22.24 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 15 Status (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
27 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit Integer
ÁÁÁÁÁÁÁÁÁÁÁÁ
22.25 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 16 Status (Bit Fields) ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
28 ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ22.26
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁSetpoint No. 17 Status (Bit Fields)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ29
ÁÁÁÁÁÁÁÁÁÁÁÁ16 Bit IntegerÁÁÁÁÁÁ
ÁÁÁÁÁÁ22.27ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁSetpoint No. 18 Status (Bit Fields)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ30
ÁÁÁÁÁÁÁÁÁÁÁÁ16 Bit IntegerÁÁÁÁÁÁ
ÁÁÁÁÁÁ22.28
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 19 Status (Bit Fields)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
31ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
22.29ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Setpoint No. 20 Status (Bit Fields)ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
32ÁÁÁÁÁÁÁÁÁÁÁÁ
16 Bit IntegerÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
33 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
34 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
35 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
36 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved Word ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
37 ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁReserved Word
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ38
ÁÁÁÁÁÁÁÁÁÁÁÁ
B–33Smart Communication Card Data Tables
Publication 1403-5.1
Table B.29 Status Inputs Bitfield Definitions
Bit Location and Value Description
b0 = 1 Status Input 1 Active
b1 = 1 Status Input 2 Active
b2 = 1 Status Input 3 Active
b3 = 1 Status Input 4 Active
b4 to b15 Reserved
Table B.30 Alarm word Bitfield Definitions
Bit Location and Value Description
b0 = 1 Alarm Input 1 Active
b1 = 1 Alarm Input 2 Active
b2 = 1 Alarm Input 3 Active
b3 = 1 Alarm Input 4 Active
b4 = 1 Alarm Input 5 Active
b5 = 1 Alarm Input 6 Active
b6 = 1 Alarm Input 7 Active
b7 = 1 Alarm Input 8 Active
b8 = 1 Alarm Input 9 Active
b9 = 1 Alarm Input 10 Active
b10 = 1 Alarm Input 11 Active
b11 = 1 Alarm Input 12 Active
b12 = 1 Alarm Input 13 Active
b13 = 1 Alarm Input 14 Active
b14 = 1 Alarm Input 15 Active
b15 = 1 Alarm Input 16 Active
Table B.31 Setpoint Status Bitfield Definitions
Bit Location and Value Description
b0 to b7 Setpoint Assert Counter
b8 = not used Reserved
b9 = 1 Waiting for Release
b10 = 1 Limit Met for Release
b11 = 1 Setpoint Asserted
b12 = 1 Waiting for Assert
b13 = 1 Limit Met for Assert
b14 = 1 Setpoint Released
b15 = 1 Setpoint Active
B–34 Smart Communication Card Data Tables
Publication 1403-5.1
Appendix C
Publication 1403-5.1
Serial Communication Protocol Tutorial
The Smart Communication Card supports the DF1 linklayer protocol
For additional information regarding the DF1 link layerprotocol, refer to the Data Highway/Data HighwayPlus /DH-485 Communication Protocol and CommandSet, Allen-Bradley Publication 1770-6.5.16 (November1991).
Table C.1 contains definitions of single byte codes.
Table C.1 Special Byte Codes
Symbol Value
SOH 0x01
STX 0x02
ETX 0x03
EOT 0x04
ENQ 0x05
ACK 0x06
DLE 0x10
NAK 0x15
DST Address of destination Powermonitor II
SRCAddress of master (device that is sending thisrequest)
BCC8 bit block check character. (For Powermonitor IIused only in poll command where it is equal to the2’s compliment of the STN value)
CRC16 bit CRC calculated as described in the CRC16section below.
STNData symbol. Station number of the slave node onyour half-duplex link.
Table C.2 contains definitions of multiple byte codes.
Table C.2 Special Symbol Meanings
Symbol Type Meaning
DLE SOHControlsymbol
Sender symbol that indicates thestart of a master message.
DLE STXControlsymbol
Sender symbol that separates themulti-drop header from the data.
DLE ETXBCC/CRC
Controlsymbol
Sender symbol that terminates amessage.
DLE ACKControlsymbol
Response symbol which signalsthat a message has beensuccessfully received.
DLE NAKControlsymbol
Global link reset command onlyissued by the master. Causes theslaves to cancel all messages thatare ready to transmit to themaster. Typically, the slavereturns the message and an errorcode to the originator.
DLE ENQSender symbol, issued only by themaster, that starts a pollcommand.
DLE EOTControlsymbol
Response symbol used by slavesas a response to a poll when theyhave no messages to send. (Onlysent by Powermonitor II if a pollcommand is sent that was notpreceded by a read requestcommand.)
APP DATA Data symbol
Single characters having hexvalues 00-0F and 11-FF (i.e.,00-FF not including 0x10).Includes data from applicationlayer including user programs andcommon application routines.
DLE DLE Data symbolRepresents the data value or STNvalue of 0x10.
C–2 Serial Communication Protocol Tutorial
Publication 1403-5.1
Generic Packet Construction
Polling Packet
[ DLE / ENQ / STN / BCC ]
Slave Message Link Packet
[ DLE / STX / APP_DATA / DLE / ETX / CRC ]
APP_DATA = [ DST / SRC / CMD / STS / TNS / TNS /Response_Data ]
Read
Response_Data = [ 1st_dataword_lo / 1st_dataword_hi /... / last_dataword_lo / last_dataword_hi ]
Write
Response_Data = [ Ext Status (if error) ]
Master Message Link Packet
[ DLE / SOH / STN / DLE / STX / APP_DATA / DLE /ETX / CRC]
APP_DATA = [ DST / SRC / CMD / STS / TNS / TNS /Command_Block ]
Read
Command_Block = [ FNC_byte / Byte_size /File_number / File_type / Element_number /Sub-element_number ]
FNC_byte = 0xA2
byte_size = size/ID of data table being requested in bytes (words X 2)
file_number = 0x00
file_type = 0x89
element_number = 0x00
sub-element_number = 0x00
Write
Command_Block = [ FNC_byte / Byte_size /File_number / File_type / Element_number /Sub-element_number / 1st_dataword_lo /1st_dataword_hi / ... / last_dataword_lo /last_dataword_hi ]
FNC_byte = 0xAA
byte_size = size/ID of data table being requested in bytes (words X 2)
file_number = 0x00
file_type = 0x89
element_number = 0x00
sub-element_number = 0x00
C–3Serial Communication Protocol Tutorial
Publication 1403-5.1
Table C.3 Write Sequence
Transmitted from SerialNetwork Master
Description/Direction
Transmitted fromSmart
CommunicationCard
[ DLE / SOH / STN / DLE /STX / DST / SRC / 0x0F /0x00 / 0x00 / 0x00 / 0xAA/ data_size / 0x00 / 0x89 /0x00 / 0x00 /1st_dataword_lo /1st_dataword_hi /.../last_dataword_lo /last_dataword_hi / DLE /ETX / CRC ]
Write Data
DF1 Ack
[ DLE / ACK ]
[ DLE / ENQ / STN / BCC ]
(Note: should wait forapplication ack, time-out,and repeat poll until datais received)
Poll
ApplicationAck [ DLE / STX / DST /
SRC / 0x4F / STS /TNS / TNS /Ext_STS(if error) / DLE / ETX/ CRC ]
[ DLE / ACK ]
DF1 Ack
Table C.4 Read Sequence
Transmitted from SerialNetwork Master
Description/Direction
Transmitted fromSmart
CommunicationCard
[ DLE / SOH / STN / DLE /STX / DST / SRC / 0x0F /0x00 / 0x00 / 0x00 / 0xA2 /data_size / 0x00 / 0x89 /0x00 / 0x00 / DLE / ETX /CRC ]
ReadRequest
DF1 Ack
[ DLE / ACK ]
[ DLE / ENQ / STN / BCC ]
(Note: should wait fordata, time-out, and repeatpoll until data is received)
Poll
Data[ DLE / STX / DST /SRC / 0x4F / STS /TNS / TNS /1st_dataword_lo /1st_dataword_hi /.../last_dataword_lo /last_dataword_hi /DLE / ETX / CRC ]
[ DLE / ACK ]
DF1 Ack
C–4 Serial Communication Protocol Tutorial
Publication 1403-5.1
CRC16 (Cyclic Redundancy Check)
The 16-bit cyclic redundancy check (CRC16) is a methodto check the integrity of a message packet. CRC16provides a higher level of data security than block checkcharacter.
Calculate the CRC value for master messages using thevalue of the STN, STX, data bytes, and the ETX (do notadd in the associated DLE for STX and ETX). Calculatethe CRC value for slave messages the same way, exceptDO NOT include the STX byte in the CRC calculation.
Important: To transmit the STN or data value of 10hex, you must use the data symbol DLEDLE. However, only one of these DLEdata bytes is included in the CRC value.
At the start of a message packet, the transmitter clears a16-bit register for the CRC value. As the first byte istransmitted, it is Exclusive-Or’ed (least significant bit tothe right) with the right eight bits of the CRC register.The result is placed back into the right eight bits of theCRC register.
The CRC register is then shifted right eight times byinserting 0x on the left. Each time a 1 is shifted out onthe right, the CRC register is Exclusive-OR’ed with thefollowing 16-bit binary constant:
CONSTANT = 1010 0000 0000 0001
The result is placed back into the CRC register. Afterthis shifting is completed, you are ready to transmit thenext byte.
As each additional byte is transmitted, it is included inthe value in the CRC register the same way. After theETX value is included in the value in the register and istransmitted, the value in the CRC register is transmitted(right bit first) as the CRC field.
The receiver also calculates the CRC value and comparesit to the received CRC value to verify the accuracy of thedata received.
The following structured English procedure shows thesteps involved in determining the CRC16 value.
data_byte = STN, STX, all application layer data, ETXCLEAR CRC_REGISTERFor each data_byte
Get data_byteXOR (data_byte, right 8 bits of CRC_REGISTER)PLACE RESULT in right 8 bits of CRC_REGISTERDO 8 times
Shift bit right, shift in 0 at leftIF bit shifted = 1
XOR (CONSTANT, CRC_REGISTER) PLACE RESULT in CRC_REGISTER
END IFEND DO
END FORTRANSMIT CRC_REGISTER as 2 byte CRC field
Examples
Example Destination Address = 123 (0x78)
Example Source Address = 0 (0x00)
Write
Device Configuration Data Table (Table 1 of DataTables)
Size = 44 words (88 bytes = 0x58)
C–5Serial Communication Protocol Tutorial
Publication 1403-5.1
With table containing the following data:
Word # Data Word # Data
1 4 23 0
2 0 24 0
3 0 25 0
4 120 26 0
5 0 27 0
6 120 28 0
7 1000 29 1
8 0 30 1
9 5 31 100
10 10 32 5
11 0 33 6
12 1 34 1
13 125 35 3
14 0 36 0
15 5 37 0
16 1 38 0
17 1 39 0
18 0 40 0
19 1 41 1
20 0 42 2
21 0 43 0
22 1 44 0
Table C.5 Sample Write Sequence
Transmitted fromMaster
Description/Direction
Transmitted fromSmart
Communication Card
[ 10 / 01 / 7B / 10 / 02 /7B / 00 / 0F / 00 / 00 /00 / AA / 58 / 00 / 89 /00 / 00 / 04 / 00 / 00 /00 / 00 / 00 / 78 / 00 /00 / 00 / 78 / 00 / E8 /03 / 00 / 00 / 05 / 00 /0A / 00 / 00 / 00 / 01 /00 / 7D / 00 / 00 / 00 /05 / 00 / 01 / 00 / 01 /00 / 00 / 00 / 01 / 00 /00 / 00 / 00 / 00 / 01 /00 / 00 / 00 / 00 / 00 /00 / 00 / 00 / 00 / 00 /00 / 00 / 00 / 01 / 00 /01 / 00 / 64 / 00 / 05 /00 / 06 / 00 / 01 / 00 /03 / 00 / 00 / 00 / 00 /00 / 00 / 00 / 00 / 00 /00 / 00 / 01 / 00 / 02 /00 / 00 / 00 / 00 / 00 /10 / 03 / 7E / AD ]
Write Data
DF1 Ack
[ 10 / 06 ]
[ 10 / 05 / 7B / 85 ]
Poll
ApplicationAck
[ 10 / 02 / 00 / 7B / 4F /00 / 00 / 00 / 10 / 03 /1F / 84 ]
[ 10 / 06 ]
DF1 Ack
C–6 Serial Communication Protocol Tutorial
Publication 1403-5.1
Read
Diagnostic Data Table (Appendix ???, Table 20)
Size = 39 words (78 bytes = 0x4E)
With table containing the following data:
Word # Data Word # Data
1 96 23 1
2 1043 24 0
3 2309 25 0
4 1890 26 0
5 1403 27 5
6 11 28 0
7 9 29 0
8 0 30 0
9 0 31 0
10 0 32 0
11 0 33 0
12 0 34 123
13 0 35 0
14 0 36 0
15 0 37 0
16 1 38 0
17 261 39 0
18 17472
19 0
20 0
21 1
22 15
Table C.6 Sample Read Sequence
Transmitted fromMaster
Description/Direction
Transmitted fromSmart
Communication Card
[ 10 / 01 / 7B / 10 / 02 /7B / 00 / 0F / 00 / 00 /00 / A2 / 4E / 00 / 89 /00 / 00 / 10 / 03 / 4B /37 ]
ReadRequest
DF1 Ack
[ 10 / 06 ]
[ 10 / 05 / 7B / 85 ]
Poll
ApplicationAck
[ 10 / 02 / 00 / 7B / 4F /00 / 00 / 00 / 60 / 00 /13 / 04 / 05 / 09 / 62 /07 / 7B / 05 / 0B / 00 /09 / 00 / 00 / 00 / 00 /00 / 00 / 00 / 00 / 00 /00 / 00 / 00 / 00 / 00 /00 / 00 / 00 / 01 / 00 /00 / F5 / 00 / 40 / 44 /00 / 00 / 00 / 00 / 01 /00 / 0F / 01 / 00 / 00 /00 / 00 / 00 / 00 / 00 /05 / 00 / 00 / 00 / 00 /00 / 00 / 00 / 00 / 00 /00 / 00 / 00 / 00 / 7B /00 / 00 / 00 / 00 / 00 /00 / 00 / 00 / 00 / 00 /00 / 10 / 03 / 61 / C0 ]
[ 10 / 06 ]
DF1 Ack
Appendix D
Publication 1403-5.1
Sample Ladder Listing
Ladder Program Description
Appendix D contains sample ladder programs thatinterface to the Powermonitor II for PLC-5 R I/O,SLC-500 R I/O and SLC-500 RS-232. Because of thesimilarities of these three programs, only the PLC-5R I/O example operation is discussed in detail, and thedifferences in operation for the SLC-500 R I/O andSLC-500 RS-232 are noted. Rung-by-rung descriptionsare given for all three.
PLC-5 R I/O Operation
There are three modes of operation:
• Configuration
• Setpoint
• Run
Each mode uses a single Sequencer Output Instruction inorder to process the required block transfers. There areonly two block transfers required. These two blocktransfers are repeated until each mode is completedsuccessfully. For Run mode, the number of blocktransfers processed by the sequencer is variable. Becausethere is only one sequencer to be used for three modes,the sequencer’s input file must be updated at thebeginning of each new mode. The numberscorresponding to the block transfers required for eachmode are contained in three separate files. The contentof each file is moved to the sequencer’s input file at thebeginning of its corresponding mode.
Configuration Mode
During initialization of Configuration mode, thesequencer input file is loaded with the two numbers.These numbers correspond to the configuration tableBTW and the diagnostic table BTR. The sequencerlength is set to 2. After completion of the configurationdata BTW, a diagnostic table BTR is performed to verifythat the BTW was successful. If the configuration tableBTW is successful, the Configuration mode bit isunlatched and the setpoint mode bit is latched. If theBTW is not successful, the configuration table BTW anddiagnostic table BTR sequence continues until theproblem is corrected. This most likely requires a changein the configuration table data.
Setpoint Mode
During initialization of Setpoint mode, the sequencerinput file is loaded with the two numbers. Thesenumbers correspond to the setpoint data table BTW andthe diagnostic data table BTR. The sequencer length isset to 2. Also, the number of setpoints is written to acounter which is used to determine the address of the userpopulated setpoint data tables. After the completion ofthe setpoint BTW, a diagnostic table BTR is performed toverify the BTW was successful. If it was not successful,further setpoints will not be written until the setpoint datatable that caused the error is corrected. If all thesetpoints are written correctly, the Setpoint mode bit isunlatched, and the Run mode bit is latched.
Run Mode
During initialization of Run mode, the sequencer inputfile is loaded with the numbers corresponding to theblock transfers to be performed. Once Run mode hasbegun, the ladder program will remain in this mode.
Note: The speed with which the processor performsthe block transfers may be altered byrearranging or changing the size of the blocktransfer sequence. However, the availability ofnew data values is controlled by thePowermonitor II table update rate.
SLC-500 R I/O Operation
The SLC-500 R I/O requires more attention. BTW andBTR instructions subroutines have been developed forimplementation of the SLC-500 R I/O sample ladder.The BTR and BTW subroutines are patterned after theblock transfer examples shown in the R I/O Scanner UserManual ( Cat. No. 1747-SN, Publication 1747-6.6 –February 1995), pp. 5-23 to 5-28. Refer to this manualfor a more detailed description of how these blocktransfer routines work.
In addition to the two files that contain the BTR andBTW subroutines, there is a third subroutine file. Thisfile executes a small amount of initialization ladderbefore each block transfer subroutine.
D–2 Sample Ladder Listing
Publication 1403-5.1
The SLC-500 R I/O version requires that all read andwrite tables be 64 words in length. This is a necessaryrequirement stemming from the use of the block transfersubroutines.
A four word length control file needs to be initialized foreach individual block transfer subroutine. Theinitialization values for each word are discussed in theData Files Used section.
SLC-500 RS-232 Operation
Use of an SLC-500 MSG instruction in place of the BTWand BTR instructions is the only difference between thePLC-5 R I/O and the SLC-500 RS-232 versions of thePowermonitor II sample ladder.
PLC-5 R I/O Data Files Used
Data FileAddress
Data FileSize
Description
B3 20 b3/0 Configuration mode enable
b3/2 Run mode enable
b3/1 Setpoint mode enable
b3/300 One-shot bit
b3/301 One-shot bit
b3/302 One-shot bit
b3/303 One-shot bit
b3/304 One-shot bit
N9 1 N9:0 Sequencer output
N10 variable N10:0 Sequencer input
Data FileAddress
Data FileSize
Description
N11 3 N11:0 Sequencer input data forconfiguration mode
N12 3 N12:0 Sequencer input data forsetpoint mode
N13 variable N13:0 Sequencer input data forrun mode
N20 2 N20:0 Number of setpoints
N20:1 Temporary storage forsetpoint address
N22 21 Setpoint #1 location
N23•••
21 Setpoint #2 location•••
N39 21 Setpoint #20 location
R6:0 Sequencer control
BTR Data Table Locations
(control / data)
N40 / N70 54 Voltage/current data
N41 / N71 63 Real-time power
N42 / N72 46 Cumulative power
N43 / N73 45 Device configuration
N44 / N74 31 Communication configuration
N45 / N75 43 Demand
N46 / N76 61 Even harmonic distortion
N47 / N77 62 Odd harmonic distortion
N48 / N78 59 Even harmonic magnitude
N49 / N79 58 Odd harmonic magnitude
N50 / N80 57 Even harmonic phase
N51 / N81 56 Odd harmonic phase
N52 / N82 40 Diagnostic
N53 / N83 39 Relay/setpoint
BTW Data Table Locations
(control / data)
N54 / N84 23 Command
N55 / N85 45 Device configuration
N56 / N86 21 Setpoint
Sequencer input file N10 contains a list of the blocktransfers required to complete the active mode. Thecontents of N10 are copied from N11 for Configurationmode, N12 for Setpoint mode and N13 for Run modeduring each mode’s initialization.
D–3Sample Ladder Listing
Publication 1403-5.1
The reset word for the sequencer is N10:1. The firstword in the rotation of the sequencer N10:1. The valuein N10:0 must be the same as that in N10:1. This meansN11:0 must equal N11:1, N12:0 must equal N12:1 andN13:0 must equal N13:1. The size of file N10 is equal tothe size of the largest sequencer input file. Forconfiguration and setpoint modes, this size will always be2. In Run mode the size depends on the number of blocktransfers to be performed. The sequencer length may beexpanded or reduced for run mode. It is imperative thatthe corresponding file that serves as the source of thesequencer’s input file, N13, must be modifiedaccordingly.
Important: Failure to modify the length of file N13 fora modification of the run mode sequencersize will result in improper operation of therun mode block transfer ladder, andpossible FAULT of the processor due toinvalid indirect offsets.
File Data Values
Prior to running the sample ladder, each of the threesequencer initialization files need to be loaded with thenumbers that correspond to each mode’s block transfersequence. The following is a list of each mode’sinitialization file and the required/possible numbers to bestored in each. The first value of a block transfersequence must be duplicated in both position 0 and 1 ofan initialization file.
N11 – Configuration Mode
Required numbers are 55, 55, and 52.
N12 – Setpoint Mode
Required numbers are 56, 56, and 52.
N13 – Run Mode
Possible numbers are 40, 41, 42, 43, 44, 45, 46, 47, 48,49, 50, 51, 52, 53, 54, 55, 56
SLC-500 R I/O Data Files Used
There are three differences between the SLC-500 R I/Oand PLC-5 implementations of the sample ladder.
1. All BTR and BTW control files are four words inlength and need to be initialized. For control file x,this initialization is:
x:0 = block transfer control bits (M0 “control flags”)See R I/O Scanner User Manual, Publication1747-6.6. (Bit 0 = BTW; Bit 7 = BTR)
x:1 = block transfer size
x:2 = SLC-5 logical address (logical rack, group andslot) See R I/O Scanner User Manual.
x:3 = data file location
For example, the control file for a configuration tableBTW, file 55 should be initialized to:
55:0 = 0 (BTW)
55:1 = 44 (Configuration table block transfer size)
55:2 = 100 (Logical rack 1, group 0, slot 0)
55:3 = 85 (Configuration table data file)
2. All data storage files for BTR and BTW subroutineexecution are 64 words in length.
3. The SLC-500 R I/O block transfer subroutine N15,requires a file that is eight words in length. In thisexample N15 is used. No initialization is required.
SLC-500 RS-232 Data Files Used
Same as PLC-5 R I/O.
Sample Ladder Listing
These example ladder programs show a way to configurethe block transfers for the Powermonitor II.
!ATTENTION: Proper operation of theladder program is the responsibility of theuser. No warranty is expressed or impliedby using these ladder configurations.
These ladders are subject to change.
D–4 Sample Ladder Listing
Publication 1403-5.1
PLC-5 R I/ORung 2:0 Enable configuration mode and clear one shot bits.| First-Pass Config || Bit Mode || S:1 B3 |+––––] [––––––––––––––––––––––––––––––––––––––––––––––––+–––––––––––––(L)––––+–+| 15 | 0 | || | Setpoint | || | Mode | || | B3 | || +–––––––––––––(U)––––+ || | 1 | || | Run | || | Mode | || | B3 | || +–––––––––––––(U)––––+ || | 2 | || | Clear | || | One Shots | || |+CLR–––––––––––––––+| || ++CLEAR ++ || ||Destination B3:18|| || || 1000000000000000|| || |+––––––––––––––––––+| || |+CLR–––––––––––––––+| || ++CLEAR ++ || |Destination B3:19| || | 0000000000000000| || +––––––––––––––––––+ |Rung 2:1 Initialize for appropriate mode.| First–Pass Initialize || Bit Sequencer || Input File || S:1 +COP–––––––––––––––+ |+––––] [–––––––––––––––––––––––––––––––––––––––––––+–––––+COPY FILE ++–+| 15 | |Source #N11:0|| || | |Destination #N10:0|| || | |Length 3|| || | +––––––––––––––––––+| || | Initialize | || | Sequencer | || | Length | || |+MOV––––––––––––––––––––+| || ++MOVE ++ || ||Source 2|| || || || || ||Destination R6:0.LEN|| || || 7|| || |+–––––––––––––––––––––––+| || | Initialize | || | Sequencer | || | Position | || |+CLR––––––––––––––––––––+| || ++CLEAR ++ || ||Destination R6:0.POS|| || || 5|| || |+–––––––––––––––––––––––+| || | Initialize | || | Sequencer | || | Address | || | +MOV–––––––––––––––+| || +–––––+MOVE ++ || |Source N10:0| || | 40| || |Destination N9:0| || | 40| || +––––––––––––––––––+ |
Rung 2:0
Latch configuration mode andunlatch setpoint and run modes.Clear one-shot bits.
Rung 2:1
Initialize the sequencer forconfiguration mode. Thisincludes loading the sequencerinput file with the configurationblock transfer numbers, settingthe sequencer length, clearingthe sequencer position andmoving the reset word into thesequencer’s output file.
D–5Sample Ladder Listing
Publication 1403-5.1
Rung 2:2 Begin setpoint mode once configuration is complete.| Config |Config |Status Status – Status – Config || Mode |BTW |BTR Bad Table Bad Param. Mode || |Done |Done Check Check || B3 N55:0 N52:0 +CMP–––––––––––––+ +CMP–––––––––––––+ B3 |+––] [–––––] [–––––] [–––+COMPARE +–+COMPARE ++–––––––(U)––––+–+| 0 13 13 |Expression | |Expression || 0 | || |N82:36 = 0 | |N82:37 = 0 || Setpoint | || +––––––––––––––––+ +––––––––––––––––+| Mode | || | B3 | || +–––––––(L)––––+ || 1 | Rung 2:3 Initialize for appropriate mode.| Setpoint |One Shot 1 Initialize || Mode | Sequencer || Input File || B3 B3 +COP–––––––––––––––+ |+––––] [–––––––[ONS]–––––––––––––––––––––––––––––––+–––––+COPY FILE ++–+| 1 300 | |Source #N12:0|| || | |Destination #N10:0|| || | |Length 3|| || | +––––––––––––––––––+| || | Initialize | || | Sequencer | || | Length | || |+MOV––––––––––––––––––––+| || ++MOVE ++ || ||Source 2|| || || || || ||Destination R6:0.LEN|| || || 7|| || |+–––––––––––––––––––––––+| || | Initialize | || | Sequencer | || | Position | || |+CLR––––––––––––––––––––+| || ++CLEAR ++ || ||Destination R6:0.POS|| || || 5|| || |+–––––––––––––––––––––––+| || | Initialize | || | Sequencer | || | Address | || | +MOV–––––––––––––––+| || +–––––+MOVE ++ || |Source N10:0| || | 40| || |Destination N9:0| || | 40| || +––––––––––––––––––+ |Rung 2:4 Load number of setpoints into setpoint counter.| Setpoint |One Shot 2 Number of || Mode | Setpoints || B3 B3 +MOV––––––––––––––––––––+ |+––––] [–––––––[ONS]–––––––––––––––––––––––––––––––++MOVE ++–+| 1 301 ||Source N20:0|| || || 3|| || ||Destination C5:0.PRE|| || || 3|| || |+–––––––––––––––––––––––+| || | C5:0| || +––––––––––––––––––––(RES)+ || |
Rung 2:2
If the configuration BTW anddiagnostic BTR are done, checkthat the diagnostic tableparameters indicate a successfulBTW (word 36 and 37 equal 0).If so, unlatch the configurationmode bit and latch the setpointmode bit.
Rung 2:3
Initialize the sequencer forsetpoint mode. Samefunctionality as Rung 2:0.
Rung 2:4
Move the number of setpointsinto the setpoint addresscounter. Reset the setpointcounter.
D–6 Sample Ladder Listing
Publication 1403-5.1
Rung 2:5 Initialize for appropriate mode.| Run |One Shot 3 Initialize || Mode | Sequencer || Input File || B3 B3 +COP–––––––––––––––+ |+––––] [–––––––[ONS]–––––––––––––––––––––––––––––––+–––––+COPY FILE ++–+| 2 302 | |Source #N13:0|| || | |Destination #N10:0|| || | |Length 8|| || | +––––––––––––––––––+| || | Initialize | || | Sequencer | || | Length | || |+MOV––––––––––––––––––––+| || ++MOVE ++ || ||Source 7|| || || || || ||Destination R6:0.LEN|| || || 7|| || |+–––––––––––––––––––––––+| || | Initialize | || | Sequencer | || | Position | || |+CLR––––––––––––––––––––+| || ++CLEAR ++ || ||Destination R6:0.POS|| || || 5|| || |+–––––––––––––––––––––––+| || | Initialize | || | Sequencer | || | Address | || | +MOV–––––––––––––––+| || +–––––+MOVE ++ || |Source N10:0| || | 40| || |Destination N9:0| || | 40| || +––––––––––––––––––+ |Rung 2:6 Main block transfer sequencer.| BT || Done || Bit || N[N9:0]:0 R6:0 +SQO–––––––––––––––+ |+–+–––] [––––+–]/[–––––––––––––––––––––––––––––––––––+SEQUENCER OUTPUT +–(EN)–+| | 13 | EN |File #N10:0| || |BT | |Mask FFFF+–(DN) || |Error | |Destination N9:0| || |Bit | |Control R6:0| || |N[N9:0]:0 | |Length 7| || +–––] [––––+ |Position 5| || 12 +––––––––––––––––––+ |Rung 2:7| Voltage/ || Current || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 40 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N40:0+–(ER) || |Data file N70:1| || |Length 53| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:8| Real–Time || Power || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 41 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N41:0+–(ER) || |Data file N71:1| || |Length 62| || |Continuous N| || +–––––––––––––––––––––––+ |
Rung 2:5
Initialize the sequencer for runmode. Same functionality asRungs 2:0 and 2:1.
Rung 2:6
This is the main block transfersequencer. The sequenceroutput word, N9:0, is updatedwhenever the previous blocktransfer is done or fails.
Rung 2:7
Voltage/current BTR.
Rung 2:8
Real time power BTR.
D–7Sample Ladder Listing
Publication 1403-5.1
Rung 2:9| Cumulative || Power || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 42 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N42:0+–(ER) || |Data file N72:1| || |Length 45| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:10| Device || Config || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 43 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N43:0+–(ER) || |Data file N73:1| || |Length 44| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:11| Comm. || Config || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 44 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N44:0+–(ER) || |Data file N74:1| || |Length 30| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:12| Demand || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 45 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N45:0+–(ER) || |Data file N75:1| || |Length 42| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:13| Even || Harmonic || Distortion || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 46 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N46:0+–(ER) || |Data file N76:1| || |Length 60| || |Continuous N| || +–––––––––––––––––––––––+ |
Rung 2:9
Cumulative power BTR.
Rung 2:10
Device configuration BTR.
Rung 2:11
Communication configurationBTR.
Rung 2:12
Demand BTR.
Rung 2:13
Even harmonic distortion BTR.
D–8 Sample Ladder Listing
Publication 1403-5.1
Rung 2:14| Odd || Harmonic || Distortion || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 47 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N47:0+–(ER) || |Data file N77:1| || |Length 61| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:15| Even || Harmonic || Magnitude || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 48 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N48:0+–(ER) || |Data file N78:1| || |Length 58| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:16| Odd || Harmonic || Magnitude || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 49 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N49:0+–(ER) || |Data file N79:1| || |Length 57| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:17| Even || Harmonic || Phase || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 50 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N50:0+–(ER) || |Data file N80:1| || |Length 56| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:18| Odd || Harmonic || Phase || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 51 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N51:0+–(ER) || |Data file N81:1| || |Length 55| || |Continuous N| || +–––––––––––––––––––––––+ |
Rung 2:14
Odd harmonic distortion BTR.
Rung 2:15
Even harmonic magnitudeBTR.
Rung 2:16
Odd harmonic magnitude BTR.
Rung 2:17
Even harmonic phase BTR.
Rung 2:18
Odd harmonic phase BTR.
D–9Sample Ladder Listing
Publication 1403-5.1
Rung 2:19| Diagnostic || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 52 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N52:0+–(ER) || |Data file N82:1| || |Length 39| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:20| Relay/ || Setpoint || BTR || +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 53 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N53:0+–(ER) || |Data file N83:1| || |Length 38| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:21| Command || BTW || +CMP–––––––––––––––+ +BTW––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER WRITE +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 54 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N54:0+–(ER) || |Data file N84:1| || |Length 22| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:22| Config || BTW || +CMP–––––––––––––––+ +BTW––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER WRITE +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 55 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N55:0+–(ER) || |Data file N85:1| || |Length 44| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:23 Begin run mode once all setpoint block transfers are complete.| One Shot 4 Status – Setpoint Setpoint || Bad Table Counter Mode || Check Done Bit || +CMP–––––––––––––––+ B3 +CMP–––––––––––––––+ C5:0 B3 |+–+COMPARE +–––[ONS]––––+COMPARE +––––] [–––––+–––(U)––––+–+| |Expression | 303 |Expression | DN | 1 | || |N9:0 = 56 | |N82:36 = 0 | |Run | || +––––––––––––––––––+ +––––––––––––––––––+ |Mode | || | B3 | || +–––(L)––––+ || 2 |
Rung 2:19
Diagnostic BTR.
Rung 2:20
Relay/setpoint BTR.
Rung 2:21
Command BTW.
Rung 2:22
Configuration BTW.
Rung 2:23
If the setpoint counter done bitis set, the last setpoint BTW hasoccurred and was followed by adiagnostic BTR. If thediagnostic table indicates asuccessful setpoint BTW,setpoint mode is done. Thesetpoint mode bit is unlatched,and the run mode bit is latched.
D–10 Sample Ladder Listing
Publication 1403-5.1
Rung 2:24 Load next setpoint into setpoint write data location.| One Shot 5 Status – Setpoint Setpoint || Bad Table Counter Number || Check Done Bit || +CMP–––––––––+ B3 +CMP–––––––––––+ C5:0 +CTU––––––––––––+ |+–+COMPARE +–––[ONS]–––+++COMPARE ++–––]/[–––+COUNT UP +–(CU)+–+| |Expression | 304 |||Expression || DN |Counter C5:0| | || |N9:0 = 56 | |||N82:36 = 0 || |Preset 3+–(DN)| || +––––––––––––+ ||+––––––––––––––+| |Accum 3| | || || Prepare | +–––––––––––––––+ | || || Initial | | || || Setpoint | | || || Write | | || ||+CMP–––––––––––+| | || |++COMPARE ++ | || | |Expression | | || | |C5:0.ACC = 0 | | || | +––––––––––––––+ | || | Setpoint | || | Data | || | Address | || |+ADD–––––––––––––––+ | || ++ADD +–––––––––––––––––––––––––––––+ || ||Source A 21| | || || | | || ||Source B C5:0.ACC| | || || 3| | || ||Destination N20:1| | || || 24| | || |+––––––––––––––––––+ | || | | || | | || | | || | | || | | || | | || | | || | | || | | || | | || | | || | | || | | || | | | | | | | | | Move | || | Current | || | Setpoint | || | Data into | || | BTW Table | || |+COP–––––––––––––––+ | || ++COPY FILE +–––––––––––––––––––––––––––––+ || |Source #N[N20:1]:1| || |Destination #N86:1| || |Length 20| || +––––––––––––––––––+ | Rung 2:25| Setpoint || BTW || +CMP–––––––––––––––+ +BTW––––––––––––––––––––+ |+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER WRITE +–(EN)–+| |Expression | |Rack 01| || |N9:0 = 56 | |Group 0+–(DN) || +––––––––––––––––––+ |Module 0| || |Control block N56:0+–(ER) || |Data file N86:1| || |Length 20| || |Continuous N| || +–––––––––––––––––––––––+ |Rung 2:26| |+––––––––––––––––––––––––––––––––[END OF FILE]–––––––––––––––––––––––––––––––––+| |
Rung 2:24
This rung is activated oncewhen the sequencer output filechanges to setpoint BTW. Itspurpose is to determine theaddress of the next setpoint dataand to copy the data residing atthis address into the setpointBTW data location. This isaccomplished by first adding anaddress offset to a base addressto determine the location of thenext setpoint data. The dataresiding at the resulting addressis then transferred to thesetpoint BTW data location. Acounter is used to determine theaddress offset. Prior to the firstsetpoint BTW, the counter isautomatically incremented. Forsubsequent setpoint BTWs, thecounter is incremented whenthe diagnostic table BTR for theprevious setpoint BTW issuccessful. For example, the3rd setpoint will reside at baseaddress 24. In this case, acounter value of 3 will be addedto the base address 21. Thedata residing at location 24 willthen be transferred into thesetpoint BTW data locationN86:1.
Rung 2:25
Setpoint BTW.
Rung 2:26
End of file.
D–11Sample Ladder Listing
Publication 1403-5.1
Rung 2:0 Enable configuration mode and clear one shot bits.| First Config || Pass Mode || S:1 B3 ||––––] [––––––––––––––––––––––––––––––––––––––––––––––+––––(L)–––––––––––––––+–|| 15 | 0 | || | Setpoint | || | Mode | || | B3 | || +––––(U)–––––––––––––––+ || | 1 | || | Run | || | Mode | || | B3 | || +––––(U)–––––––––––––––+ || | 2 | || | Clear | || | One Shots | || | +CLR–––––––––––––––+ | || +–+CLEAR +–+ || | |Dest B3:18| | || | | 0100000000000000| | || | +––––––––––––––––––+ | || | +CLR–––––––––––––––+ | || +–+CLEAR +–+ || |Dest B3:19| || | 0000000000000000| || +––––––––––––––––––+ |Rung 2:1 Initialize for appropriate mode.| First Initialize || Pass Sequencer || Input File || S:1 +COP–––––––––––––––+ ||––––] [––––––––––––––––––––––––––––––––––––––––––––––+–+COPY FILE +–+–|| 15 | |Source #N11:0| | || | |Dest #N10:0| | || | |Length 3| | || | +––––––––––––––––––+ | | | | | || | Initialize | || | Sequencer | || | Length | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || | |Source 2| | || | | | | || | |Dest R6:0.LEN| | || | | 1| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Position | || | +CLR–––––––––––––––+ | || +–+CLEAR +–+ || | |Dest R6:0.POS| | || | | 1| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Address | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || | |Source N10:0| | || | | 40| | || | |Dest N9:0| | || | | 40| | || | +––––––––––––––––––+ | || | BT Done | || | Bit | || | N[N9:0]:0 | || +––––(U)–––––––––––––––+ || | 13 | || | Prepare | || | For BT | || | +JSR–––––––––––––––+ | || +–+JUMP TO SUBROUTINE+–+ || |SBR file number 5| || +––––––––––––––––––+ |
SLC-500 R I/ORung 2:0
Latch configuration mode andunlatch setpoint and run modes.Clear one-shot bits.
Rung 2:1
Initialize the sequencer forconfiguration mode. Thisincludes loading the sequencerinput file with the configurationblock transfer numbers, settingthe sequencer length, clearingthe sequencer position andmoving the reset word into thesequencer’s output file. Also,the sequencer’s output file donebit is unlatched to insure thatthe next rung is not activeimmediately and the blocktransfer preparation subroutineis called.
D–12 Sample Ladder Listing
Publication 1403-5.1
Rung 2:2 Begin setpoint mode once configuration is complete.| Config |Config |Status Status – Config || Mode |BTW |BTR Bad Table Mode || |Done |Done Check || B3 N55:0 N52:0 +EQU–––––––––––––––+ B3 ||––––] [––––––––] [––––––––] [–––––+EQUAL +–––––––––+––––(U)–––––+–|| 0 13 13 |Source A N82:36| | 0 | || | 0| | | || |Source B 0| | | || | | | | || +––––––––––––––––––+ | | || | Setpoint | || | Mode | || | B3 | || +––––(L)–––––+ || 1 |Rung 2:3 Initialize for appropriate mode.| Setpoint |One Shot 1 Initialize || Mode | Sequencer || Input File || B3 B3 +COP–––––––––––––––+ ||––––] [–––––––[OSR]––––––––––––––––––––––––––––––––––+–+COPY FILE +–+–|| 1 300 | |Source #N12:0| | || | |Dest #N10:0| | || | |Length 3| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Length | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || | |Source 2| | || | | | | || | |Dest R6:0.LEN| | || | | 1| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Position | || | +CLR–––––––––––––––+ | || +–+CLEAR +–+ || | |Dest R6:0.POS| | || | | 1| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Address | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || | |Source N10:0| | || | | 40| | || | |Dest N9:0| | || | | 40| | || | +––––––––––––––––––+ | || | Prepare | || | For BT | || | +JSR–––––––––––––––+ | || +–+JUMP TO SUBROUTINE+–+ || |SBR file number 5| || +––––––––––––––––––+ |Rung 2:4 Load number of setpoints into setpoint counter.| Setpoint |One Shot 2 Number Of || Mode | Setpoints || B3 B3 +MOV–––––––––––––––+ ||––––] [–––––––[OSR]––––––––––––––––––––––––––––––––––+–+MOVE +–+–|| 1 301 | |Source N20:0| | || | | 3| | || | |Dest C5:0.PRE| | || | | 3| | || | +––––––––––––––––––+ | || | C5:0 | || +––(RES)–––––––––––––––+ || |
Rung 2:2
If the configuration BTW anddiagnostic BTR are done, checkthat the diagnostic tableparameters indicate a successfulBTW (word 36 and 37 equal 0).If so, unlatch the configurationmode bit and latch the setpointmode bit.
Rung 2:3
Initialize the sequencer forsetpoint mode. Samefunctionality as Rung 2:0.
Rung 2:4
Move the number of setpointsinto the setpoint addresscounter. Reset the setpointcounter.
D–13Sample Ladder Listing
Publication 1403-5.1
Rung 2:5 Initialize for appropriate mode.| Run |One Shot 3 Initialize || Mode | Sequencer || Input File || B3 B3 +COP–––––––––––––––+ ||––––] [–––––––[OSR]––––––––––––––––––––––––––––––––––+–+COPY FILE +–+–|| 2 302 | |Source #N13:0| | || | |Dest #N10:0| | || | |Length 4| | || | +––––––––––––––––––+ | | | | | || | Initialize | || | Sequencer | || | Length | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || | |Source 3| | || | | | | || | |Dest R6:0.LEN| | || | | 1| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Position | || | +CLR–––––––––––––––+ | || +–+CLEAR +–+ || | |Dest R6:0.POS| | || | | 1| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Address | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || | |Source N10:0| | || | | 40| | || | |Dest N9:0| | || | | 40| | || | +––––––––––––––––––+ | || | Prepare | || | For BT | || | +JSR–––––––––––––––+ | || +–+JUMP TO SUBROUTINE+–+ || |SBR file number 5| || +––––––––––––––––––+ |Rung 2:6 Main block transfer sequencer.| BT Done || Bit || N[N9:0]:0 R6:0 +SQO–––––––––––––––+ ||–+––––] [–––––+––]/[––––––––––––––––––––––––––––+–+SEQUENCER OUTPUT +–(EN)–+–|| | 13 | EN | |File #N10:0+–(DN) | || | | | |Mask FFFF| | || | | | |Dest N9:0| | || | | | |Control R6:0| | || | | | |Length 3| | || | | | |Position 1| | || | | | +––––––––––––––––––+ | || | BT Error | | Prepare | || | Bit | | For BT | || | N[N9:0]:0 | | +JSR–––––––––––––––+ | || +––––] [–––––+ +–+JUMP TO SUBROUTINE+––––––+ || 12 |SBR file number 5| || +––––––––––––––––––+ |Rung 2:7 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 40| || | | || +––––––––––––––––––+ |
Rung 2:5
Initialize the sequencer for runmode. Same functionality asRungs 2:0 and 2:1.
Rung 2:6
This is the main block transfersequencer. The sequenceroutput word, N9:0, is updatedwhenever the previous blocktransfer is done or fails. Aftereach sequencer increment, theblock transfer preparationsubroutine is called.
Rung 2:7
Voltage/current BTR.
D–14 Sample Ladder Listing
Publication 1403-5.1
Rung 2:8 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 41| || | | || +––––––––––––––––––+ |Rung 2:9 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 42| || | | || +––––––––––––––––––+ |Rung 2:10 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 43| || | | || +––––––––––––––––––+ |Rung 2:11 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 44| || | | || +––––––––––––––––––+ |Rung 2:12 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 45| || | | || +––––––––––––––––––+ |Rung 2:13 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 46| || | | || +––––––––––––––––––+ |Rung 2:14 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 47| || | | || +––––––––––––––––––+ |Rung 2:15 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 48| || | | || +––––––––––––––––––+ |Rung 2:16 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 49| || | | || +––––––––––––––––––+ |
Rung 2:8
Real time power BTR.
Rung 2:9
Cumulative power BTR.
Rung 2:10
Device configuration BTR.
Rung 2:11
Communication configurationBTR.
Rung 2:12
Demand BTR.
Rung 2:13
Even harmonic distortion BTR.
Rung 2:14
Odd harmonic distortion BTR.
Rung 2:15
Even harmonic magnitudeBTR.
Rung 2:16
Odd harmonic magnitude BTR.
D–15Sample Ladder Listing
Publication 1403-5.1
Rung 2:17 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 50| || | | || +––––––––––––––––––+ |Rung 2:18 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 51| || | | || +––––––––––––––––––+ |Rung 2:19 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 52| || | | || +––––––––––––––––––+ |Rung 2:20 Perform appropriate block transfer read.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 3| || | 40| +––––––––––––––––––+ || |Source B 53| || | | || +––––––––––––––––––+ |Rung 2:21 Perform appropriate block transfer write.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 4| || | 40| +––––––––––––––––––+ || |Source B 54| || | | || +––––––––––––––––––+ |Rung 2:22 Perform appropriate block transfer write.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 4| || | 40| +––––––––––––––––––+ || |Source B 55| || | | || +––––––––––––––––––+ |Rung 2:23 Begin run mode once all setpoint block transfers are complete.| One Shot 4 Status – Setpoint Setpoint || Bad Table Counter Mode || Check Done Bit || +EQU–––––––––––––––+ B3 +EQU–––––––––––––––+ C5:0 B3 ||–+EQUAL +–––[OSR]––––+EQUAL +––––] [–––+––––(U)–––––+–|| |Source A N9:0| 303 |Source A N82:36| DN | 1 | || | 40| | 0| | | || |Source B 56| |Source B 0| | | || | | | | | | || +––––––––––––––––––+ +––––––––––––––––––+ | | || | Run | || | Mode | || | B3 | || +––––(L)–––––+ || 2 |
Rung 2:17
Even harmonic phase BTR.
Rung 2:18
Odd harmonic phase BTR.
Rung 2:19
Diagnostic BTR.
Rung 2:22
Configuration BTW.
Rung 2:20
Relay/setpoint BTR.
Rung 2:21
Command BTW.
Rung 2:23
If the setpoint counter done bitis set, the last setpoint BTW hasoccurred and was followed by adiagnostic BTR. If thediagnostic table indicates asuccessful setpoint BTW,setpoint mode is done. Thesetpoint mode bit is unlatched,and the run mode bit is latched.
D–16 Sample Ladder Listing
Publication 1403-5.1
Rung 2:24 Load next setpoint into setpoint write data location.| One Shot 5 Status – Setpoint Setpoint || Bad Table Counter Number || Check Done Bit || +EQU––––––––––+ B3 +EQU––––––––––––––+ C5:0 +CTU––––––––––––+ ||–+EQUAL +–[OSR]–+–+–+EQUAL +–+–]/[–+COUNT UP +–(CU)–+–|| |Source A N9:0| 304| | |Source A N82:36| | DN|Counter C5:0+–(DN) | || | 40| | | | 0| | |Preset 3| | || |Source B 56| | | |Source B 0| | |Accum 3| | || | | | | | | | +–––––––––––––––+ | || +–––––––––––––+ | | +–––––––––––––––––+ | | || | | Prepare | | || | | Initial | | || | | Setpoint | | || | | Write | | || | | +EQU––––––––––––––+ | | || | +–+EQUAL +–+ | || | |Source A C5:0.ACC| | || | | 3| | || | |Source B 0| | || | | | | || | +–––––––––––––––––+ | || | Setpoint | || | Data | || | Address | || | +ADD–––––––––––––––+ | || +––––––––––––––––––––––––––+ADD +––––––+ || | |Source A 21| | || | | | | || | |Source B C5:0.ACC| | || | | 3| | || | |Dest N20:1| | || | | 24| | || | +––––––––––––––––––+ | || | Move | || | Current | || | Setpoint | || | Data Into | || | BTW Table | || | +COP–––––––––––––––+ | || +––––––––––––––––––––––––––+COPY FILE +––––––+ || |Source #N[N20:1]:1| || |Dest #N86:1| || |Length 20| || +––––––––––––––––––+ |
Rung 2:25 Perform appropriate block transfer write.| +EQU–––––––––––––––+ +JSR–––––––––––––––+ ||–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|| |Source A N9:0| |SBR file number 4| || | 40| +––––––––––––––––––+ || |Source B 56| || | | || +––––––––––––––––––+ |Rung 2:26| ||–––––––––––––––––––––––––––––––––––––+END+––––––––––––––––––––––––––––––––––––|| |
Rung 2:26
End of file.
Rung 2:24
This rung is activated oncewhen the sequencer output filechanges to setpoint BTW. Itspurpose is to determine theaddress of the next setpoint dataand to copy the data residing atthis address into the setpointBTW data location. This isaccomplished by first adding anaddress offset to a base addressto determine the location of thenext setpoint data. The dataresiding at the resulting addressis then transferred to thesetpoint BTW data location. Acounter is used to determine theaddress offset. Prior to the firstsetpoint BTW, the counter isautomatically incremented. Forsubsequent setpoint BTWs, thecounter is incremented whenthe diagnostic table BTR for theprevious setpoint BTW issuccessful. For example, the3rd setpoint will reside at baseaddress 24. In this case, acounter value of 3 will be addedto the base address 21. Thedata residing at location 24 willthen be transferred into thesetpoint BTW data locationN86:1.
Rung 2:25
Setpoint BTW.
D–17Sample Ladder Listing
Publication 1403-5.1
BTR and BTW Subroutines
The SLC-500 R I/O BTR and BTW subroutines mimicthe read and write block transfer examples listed in theback of the Publication 1747–6.6, R I/O Scanner UserManual. The following rung descriptions and notespertain to modifications or additions to these examples.
1. The BTR and BTW subroutines use different files andbits than those given in the R I/O Scanner Manual.The substitutions are:
B3:0 – B3:5 are replaced by N15:0 – N15:4
B3:100 is replaced by the control word correspondingto the sequencer’s output file ( N[N9:0]:0 ).
2. The file M0.1 is used for the BTW while file M0.2 isused for the BTR routine.
3. The first rung of the block transfer examples in the Publication 1747–6.6, R I/O Scanner User Manual isnot used in the BTR and BTW subroutines. This isbecause the function performed by that rung,initializing the control flags for the M file blocktransfer, is done in the BTR or BTW subroutine at thetime the BTR and BTW block transfer are initiated.These control flags, which are moved into the M filecontrol buffers at the block transfer initiation, areinitialized for each control file associated with blocktransfer operations ( see Data Files Used section ).
BTR ( File 3 )
Rung 3:0| Service BT Status || The BT || Status/ || BT || Pending || +SBR–––––––––––––––+ N15:5 +COP–––––––––––––––+ ||–+SUBROUTINE +–+––––] [–––––+–––––––––––––––––––––+COPY FILE +–|| +––––––––––––––––––+ | 0 | |Source #M1:2.100| || | | |Dest #N15:0| || | | |Length 4| || | | +––––––––––––––––––+ || | Check BT | || | Status | || | Until DN | || | or ER Bit | || | Is Off | || | N15:5 | || +––––] [–––––+ || 1 |Rung 3:1| Virtual Check BT || BT Done Status || Bit Until DN || or ER Bit || Is Off || N15:0 N15:5 ||–+––––]/[–––––+–––––––––––––––––––––––––––––––––––––––––––––––––––––––(U)–––––|| | 13 | 1 || | Virtual | || | BT Err | || | Bit | || | N15:0 | || +––––]/[–––––+ || 12 |
Rung 3:0
Copy the BTR status area to afile which will be usedthroughout the program. Thisavoids addressing the M1 filemultiple times during eachprogram scan. Each time aninstruction containing an M1file bit, word or file is scannedby the processor, an immediatedata transfer to the moduleoccurs and therefore will impactthe overall processor time.
Rung 3:1
Unlatch the bit that continues tocheck the BTR status. When aBTR is complete, the done bit isset. The ladder program mustunlatch the enable bit, then waitfor the SN module to turn offthe done bit before another BTRto the same M-file location canbe initiated.
D–18 Sample Ladder Listing
Publication 1403-5.1
Rung 3:2| Virtual BT Data || BT Done || Bit || N15:0 +COP–––––––––––––––+ ||––––] [––––––––––––––––––––––––––––––––––––––––––––––+–+COPY FILE +–+–|| 13 | |Source #M1:2.110| | || | |Dest #N[N15:7]:1| | || | |Length 63| | || | +––––––––––––––––––+ | | | | | || | Service | || | The BT | || | Status/ | || | BT | || | Pending | || | N15:5 | || +––––(U)–––––––––––––––+ || | 0 | || | BT enable | || | bit | || | N[N9:0]:0 | || +––––(U)–––––––––––––––+ || | 15 | || | Check BT | || | Status | || | Until DN | || | or ER Bit | || | Is Off | || | N15:5 | || +––––(L)–––––––––––––––+ | Rung 3:3 1| Virtual BT Error || BT Err Code || Bit || N15:0 +MOV–––––––––––––––+ ||––––] [––––––––––––––––––––––––––––––––––––––––––––––+–+MOVE +–+–|| 12 | |Source N15:3| | || | | 0| | || | |Dest N15:4| | || | | 0| | || | +––––––––––––––––––+ | || | Service | || | The BT | || | Status/ | || | BT | || | Pending | || | N15:5 | || +––––(U)–––––––––––––––+ || | 0 | || | BT enable | || | bit | || | N[N9:0]:0 | || +––––(U)–––––––––––––––+ || | 15 | | | | | || | Check BT | || | Status | || | Until DN | || | or ER Bit | || | Is Off | || | N15:5 | || +––––(L)–––––––––––––––+ || | 1 | || | BT Error | || | Bit | || | N[N9:0]:0 | || +––––(L)–––––––––––––––+ || 12 |
Rung 3:2
When a BTR successfullycompletes, buffer the BT dataand unlatch the BT enable bit.As shown, 63 words are copiedto the BTR destination file,beginning at word 1, in order tomatch the Powermonitor II datatable layout. Also, unlatch theBTR pending bit and latch thebit that continues checking theBTR status until the SN moduleturns off the done bit.
Rung 3:3
If a BTR error occurs, unlatchthe enable bit and buffer the BTerror code. Also, unlatch theBTR pending bit, latch the bitthat continues checking theBTR status until the SN moduleturns off the error bit and latchthe control word error bit.
D–19Sample Ladder Listing
Publication 1403-5.1
Rung 3:4| BT |BT enable |Virtual |Virtual BT Done || Initiate |bit |BT Done |BT Err Bit || Bit | |Bit |Bit || N15:6 N[N9:0]:0 N15:0 N15:0 N[N9:0]:0 ||––––] [––––––––]/[––––––––]/[––––––––]/[–––––––––––––––––––––––+––––(U)–––––+–|| 0 15 13 12 | 13 | || | BT Error | || | Bit | || | N[N9:0]:0 | || +––––(U)–––––+ || | 12 | || | Service | || | The BT | || | Status/ | || | BT | || | Pending | || | N15:5 | || +––––(L)–––––+ || | 0 | || | BT enable | || | bit | || | N[N9:0]:0 | || +––––(L)–––––+ || | 15 | || | BT | || | Initiate | || | Bit | || | N15:6 | || +––––(U)–––––+ || 0 | Rung 3:5| BT enable || bit || N[N9:0]:0 +COP–––––––––––––––+ ||–+––––] [–––––+––––––––––––––––––––––––––––––––––––––––––+COPY FILE +–|| | 15 | |Source #N[N9:0]:0| || | | |Dest #M0:2.100| || | | |Length 3| || | | +––––––––––––––––––+ || | Virtual | || | BT Done | || | Bit | || | N15:0 | || +––––] [–––––+ || | 13 | || | Virtual | || | BT Err | || | Bit | || | N15:0 | || +––––] [–––––+ || 12 |Rung 3:6| BT enable |BT |Virtual |Virtual BT Error BT Done || bit |Initiate |BT Done |BT Err Code Bit || |Bit |Bit |Bit || N[N9:0]:0 N15:6 N15:0 N15:0 +EQU–––––––––––––––+ N[N9:0]:0 ||––––]/[––––––]/[––––––]/[–––––––]/[–––––+–+EQUAL +––––––(L)–––––+–|| 15 0 13 12 | |Source A N15:4| 13 | || | | 0| | || | |Source B 0| | || | | | | || | +––––––––––––––––––+ | || | BT Error BT Error | || | Code Bit | || | +NEQ–––––––––––––––+ N[N9:0]:0 | || +–+NOT EQUAL +––––––(L)–––––+ || |Source A N15:4| 12 || | 0| || |Source B 0| || | | || +––––––––––––––––––+ |Rung 3:7| +RET–––––––––––––––+ ||–––––––––––––––––––––––––––––––––––––––––––––––––––––––––+RETURN +–|| +––––––––––––––––––+ |Rung 3:8| ||–––––––––––––––––––––––––––––––––––––+END+––––––––––––––––––––––––––––––––––––|| |
Rung 3:4
When a new BTR is initiated,latch the enable bit, as long as aBTR is not in progress. Also,latch the BTR pending bit, sothe BTR status file will be BTRby the ladder program. Becausethis rung marks the beginningof the BTR, both the done anderror bits for the block transfercontrol word are unlatchedalong with the block transferinitiate bit.
Rung 3:5
Move the virtual control wordsto the M0 file for the SNmodule whenever a transition ofthe BTR enable bit occurs.
Rung 3:6
If all the conditions of this rungare true, the BTR cycle iscomplete. Latch the controlword done bit if the error wordat N15:4 is clear, or the controlword error bit if it is not.
Rung 3:7
Return from subroutine.
Rung 3:8
End of file.
D–20 Sample Ladder Listing
Publication 1403-5.1
BTW ( File 4 )Rung 4:0| Service BT Status || The BT || Status/ || BT || Pending || +SBR–––––––––––––––+ N15:5 +COP–––––––––––––––+ ||–+SUBROUTINE +–+––––] [–––––+–––––––––––––––––––––+COPY FILE +–|| +––––––––––––––––––+ | 0 | |Source #M1:2.200| || | | |Dest #N15:0| || | | |Length 4| || | | +––––––––––––––––––+ || | Check BT | || | Status | || | Until DN | || | or ER Bit | || | Is Off | || | N15:5 | || +––––] [–––––+ || 1 |Rung 4:1| Virtual Check BT || BT Done Status || Bit Until DN || or ER Bit || Is Off || N15:0 N15:5 ||–+––––]/[–––––+–––––––––––––––––––––––––––––––––––––––––––––––––––––––(U)–––––|| | 13 | 1 || | Virtual | || | BT Err | || | Bit | || | N15:0 | || +––––]/[–––––+ || 12 |Rung 4:2| Virtual Service || BT Done The BT || Bit Status/ || BT || Pending || N15:0 N15:5 ||––––] [––––––––––––––––––––––––––––––––––––––––––––––––––––––––+––––(U)–––––+–|| 13 | 0 | | | | | || | BT enable | || | bit | || | N[N9:0]:0 | || +––––(U)–––––+ || | 15 | || | Check BT | || | Status | || | Until DN | || | or ER Bit | || | Is Off | || | N15:5 | || +––––(L)–––––+ || 1 |
Rung 4:0
Copy the BTW status area to afile which will be usedthroughout the program, onlywhen a BTW is pending. Thisavoids accessing the M1 filemultiple times during each scan.Each time an instructioncontaining an M1 file bit, wordor file is scanned by theprocessor, an immediate datatransfer to the module occursand therefore will impact theprocessor scan time.
Rung 4:1
Unlatch the bit that continues tocheck the BTW status. When aBTW is complete, the done bitis set. The ladder must thenunlatch the enable bit, then waitfor the SN module to turn offthe done bit before anotherBTW to the same M-filelocation can be initialized.
Rung 4:2
When a BTW successfullycompletes, unlatch the BTWenable bit. Also, unlatch theBTW pending bit and unlatchthe bit that continues checkingthe BTW status until the SNmodule turns off the done bit.
D–21Sample Ladder Listing
Publication 1403-5.1
Rung 4:3| Virtual BT Error || BT Err Code || Bit || N15:0 +MOV–––––––––––––––+ ||––––] [––––––––––––––––––––––––––––––––––––––––––––––+–+MOVE +–+–|| 12 | |Source N15:3| | || | | 0| | || | |Dest N15:4| | || | | 0| | || | +––––––––––––––––––+ | || | Service | || | The BT | || | Status/ | || | BT | || | Pending | || | N15:5 | || +––––(U)–––––––––––––––+ || | 0 | || | BT enable | || | bit | || | N[N9:0]:0 | || +––––(U)–––––––––––––––+ || | 15 | || | Check BT | || | Status | || | Until DN | || | or ER Bit | || | Is Off | || | N15:5 | || +––––(L)–––––––––––––––+ || | 1 | | | | | || | BT Error | || | Bit | || | N[N9:0]:0 | || +––––(L)–––––––––––––––+ || 12 |Rung 4:4| BT |BT enable |Virtual |Virtual BT Done || Initiate |bit |BT Done |BT Err Bit || Bit | |Bit |Bit || N15:6 N[N9:0]:0 N15:0 N15:0 N[N9:0]:0 ||––––] [––––––––]/[––––––––]/[––––––––]/[–––––––––––––+––––(U)–––––––––––––––+–|| 0 15 13 12 | 13 | || | BT Error | || | Bit | || | N[N9:0]:0 | || +––––(U)–––––––––––––––+ || | 12 | || | +COP–––––––––––––––+ | || +–+COPY FILE +–+ || | |Source #N[N15:7]:1| | || | |Dest #M0:2.210| | || | |Length 63| | || | +––––––––––––––––––+ | || | Service | || | The BT | || | Status/ | || | BT | || | Pending | || | N15:5 | || +––––(L)–––––––––––––––+ || | 0 | || | BT enable | || | bit | || | N[N9:0]:0 | || +––––(L)–––––––––––––––+ || | 15 | || | BT | || | Initiate | || | Bit | || | N15:6 | || +––––(U)–––––––––––––––+ || 0 |
Rung 4:3
If a BTW errors, unlatch theenable bit, the BTW pending bitand buffer the BTW error code.Also, latch the bit that continueschecking the BTW status untilthe SN module turns off theerror bit and latch the controlword error bit.
Rung 4:4
When a new BTW is initiated,copy the data to the M0 file dataarea and latch the virtual BTWenable bit provided that a BTWis not in progress. As shown,only 63 words of the BTW datafile are copied to the M filebuffer, beginning at word 1, inorder to match thePowermonitor II data tablelayout. Also, latch the BTWpending bit, so the BT statusfile will be read by the ladderprogram. And because thisrung marks the beginning of theBTW, unlatch the control worddone and error bits and the BTinitiate bit.
D–22 Sample Ladder Listing
Publication 1403-5.1
Rung 4:5| BT enable || bit || N[N9:0]:0 +COP–––––––––––––––+ ||–+––––] [–––––+––––––––––––––––––––––––––––––––––––––––––+COPY FILE +–|| | 15 | |Source #N[N9:0]:0| || | | |Dest #M0:2.200| || | | |Length 3| || | | +––––––––––––––––––+ || | Virtual | || | BT Done | || | Bit | || | N15:0 | || +––––] [–––––+ || | 13 | || | Virtual | || | BT Err | || | Bit | || | N15:0 | || +––––] [–––––+ || 12 |Rung 4:6| BT enable |BT |Virtual |Virtual BT Error BT Done || bit |Initiate |BT Done |BT Err Code Bit || |Bit |Bit |Bit || N[N9:0]:0 N15:6 N15:0 N15:0 +EQU–––––––––––––––+ N[N9:0]:0 ||––––]/[–––––––]/[––––––]/[––––––]/[–––––+–+EQUAL +––––––(L)–––––+–|| 15 0 13 12 | |Source A N15:4| 13 | || | | 0| | || | |Source B 0| | || | | | | || | +––––––––––––––––––+ | || | BT Error BT Error | || | Code Bit | || | +NEQ–––––––––––––––+ N[N9:0]:0 | || +–+NOT EQUAL +––––––(L)–––––+ || |Source A N15:4| 12 || | 0| || |Source B 0| || | | || +––––––––––––––––––+ |Rung 4:7| +RET–––––––––––––––+ ||–––––––––––––––––––––––––––––––––––––––––––––––––––––––––+RETURN +–|| +––––––––––––––––––+ |Rung 4:8| ||–––––––––––––––––––––––––––––––––––––+END+––––––––––––––––––––––––––––––––––––|| |
Rung 4:5
Move the virtual control wordsto the M0 file for the SNmodule whenever a transition ofthe BTW enable bit occurs.
Rung 4:8
End of file.
Rung 4:7
Return from subroutine.
Rung 4:6
If all the conditions of this rungare true, the BTW cycle iscomplete. Latch the controlword done bit if the error wordat N15:4 is clear, or the controlword error bit if it is not.
D–23Sample Ladder Listing
Publication 1403-5.1
BT Preparation ( File 5 )Rung 5:0| Clear || BT || File || +SBR–––––––––––––––+ +FLL–––––––––––––––+ ||–+SUBROUTINE +––––––––––––––––––––––––––––––––+–+FILL FILE +–+–|| +––––––––––––––––––+ | |Source 0| | || | |Dest #N15:0| | || | |Length 7| | || | +––––––––––––––––––+ | || | Move | || | BT Data | || | Location | || | Into BT | || | File | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || | |Source N[N9:0]:3| | || | | | | || | |Dest N15:7| | || | | 70| | || | +––––––––––––––––––+ | || | BT | || | Initiate | || | Bit | || | N15:6 | || +––––(L)–––––––––––––––+ || | 0 | || | BT enable | || | bit | || | N[N9:0]:0 | || +––––(U)–––––––––––––––+ || 15 |Rung 5:1| +RET–––––––––––––––+ ||–––––––––––––––––––––––––––––––––––––––––––––––––––––––––+RETURN +–|| +––––––––––––––––––+ |Rung 5:2| ||–––––––––––––––––––––––––––––––––––––+END+––––––––––––––––––––––––––––––––––––|| |
Rung 5:0
In preparation for execution of ablock transfer, this rung clearsthe 8 words of file N15, movesthe BT data table location intoword N15:7, latches the BTinitiate bit and unlatches the BTenable bit.
Rung 5:1
Return from subroutine.
Rung 5:2
End of file.
D–24 Sample Ladder Listing
Publication 1403-5.1
SLC–500 RS-232Rung 2:0 Enable configuration mode and clear one shot bits.| First Config || Pass Mode || S:1 B3 ||––––] [––––––––––––––––––––––––––––––––––––––––––––––+––––(L)–––––––––––––––+–|| 15 | 0 | || | Setpoint | || | Mode | || | B3 | || +––––(U)–––––––––––––––+ || | 1 | || | Run | || | Mode | || | B3 | || +––––(U)–––––––––––––––+ || | 2 | || | Clear | || | One Shots | || | +CLR–––––––––––––––+ | || +–+CLEAR +–+ || | |Dest B3:18| | || | | 0100000000000000| | || | +––––––––––––––––––+ | || | +CLR–––––––––––––––+ | || +–+CLEAR +–+ || |Dest B3:19| || | 0000000000000000| || +––––––––––––––––––+ |Rung 2:1 Initialize for appropriate mode.| First Initialize || Pass Sequencer || Input File || S:1 +COP–––––––––––––––+ ||––––] [––––––––––––––––––––––––––––––––––––––––––––––+–+COPY FILE +–+–|| 15 | |Source #N11:0| | || | |Dest #N10:0| | || | |Length 3| | || | +––––––––––––––––––+ | | | || | Initialize | || | Sequencer | || | Length | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || | |Source 2| | || | | | | || | |Dest R6:0.LEN| | || | | 1| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Position | || | +CLR–––––––––––––––+ | || +–+CLEAR +–+ || | |Dest R6:0.POS| | || | | 1| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Address | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || |Source N10:0| || | 40| || |Dest N9:0| || | 40| || +––––––––––––––––––+ |
Rung 2:0
Latch configuration mode andunlatch setpoint and run modes.Clear one-shot bits.
Rung 2:1
Initialize the sequencer forconfiguration mode. Thisincludes loading the sequencerinput file with the configurationblock transfer numbers, settingthe sequencer length, clearingthe sequencer position andmoving the reset word into thesequencer’s output file.
D–25Sample Ladder Listing
Publication 1403-5.1
Rung 2:2 Begin setpoint mode once configuration is complete.| Config |Config |Status Status – Config || Mode |BTW |BTR Bad Table Mode || |Done |Done Check || B3 N55:0 N52:0 +EQU–––––––––––––––+ B3 ||––––] [––––––––] [––––––––] [–––––+EQUAL +–––––––––+––––(U)–––––+–|| 0 13 13 |Source A N82:36| | 0 | || | 0| | | || |Source B 0| | | || | | | | || +––––––––––––––––––+ | | || | Setpoint | || | Mode | || | B3 | || +––––(L)–––––+ || 1 |Rung 2:3 Initialize for appropriate mode.| Setpoint |One Shot 1 Initialize || Mode | Sequencer || Input File || B3 B3 +COP–––––––––––––––+ ||––––] [–––––––[OSR]––––––––––––––––––––––––––––––––––+–+COPY FILE +–+–|| 1 300 | |Source #N12:0| | || | |Dest #N10:0| | || | |Length 3| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Length | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || | |Source 2| | || | | | | || | |Dest R6:0.LEN| | || | | 1| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Position | || | +CLR–––––––––––––––+ | || +–+CLEAR +–+ || | |Dest R6:0.POS| | || | | 1| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Address | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || |Source N10:0| || | 40| || |Dest N9:0| || | 40| || +––––––––––––––––––+ |Rung 2:4 Load number of setpoints into setpoint counter.| Setpoint |One Shot 2 Number of || Mode | Setpoints || B3 B3 +MOV–––––––––––––––+ ||––––] [–––––––[OSR]––––––––––––––––––––––––––––––––––+–+MOVE +–+–|| 1 301 | |Source N20:0| | || | | 3| | || | |Dest C5:0.PRE| | || | | 3| | || | +––––––––––––––––––+ | || | C5:0 | || +––(RES)–––––––––––––––+ || |
Rung 2:2
If the configuration BTW anddiagnostic BTR are done, checkthat the diagnostic tableparameters indicate a successfulBTW (word 36 and 37 equal 0).If so, unlatch the configurationmode bit and latch the setpointmode bit.
Rung 2:3
Initialize the sequencer forsetpoint mode. Samefunctionality as Rung 2:0.
Rung 2:4
Move the number of setpointsinto the setpoint addresscounter. Reset the setpointcounter.
D–26 Sample Ladder Listing
Publication 1403-5.1
Rung 2:5 Initialize for appropriate mode.| Run |One Shot 3 Initialize || Mode | Sequencer || Input File || B3 B3 +COP–––––––––––––––+ ||––––] [–––––––[OSR]––––––––––––––––––––––––––––––––––+–+COPY FILE +–+–|| 2 302 | |Source #N13:0| | || | |Dest #N10:0| | || | |Length 3| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Length | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || | |Source 1| | || | | | | || | |Dest R6:0.LEN| | || | | 1| | || | +––––––––––––––––––+ | || | Initialize | || | Sequencer | || | Position | || | +CLR–––––––––––––––+ | || +–+CLEAR +–+ || | |Dest R6:0.POS| | || | | 1| | || | +––––––––––––––––––+ | | | | | || | Initialize | || | Sequencer | || | Address | || | +MOV–––––––––––––––+ | || +–+MOVE +–+ || |Source N10:0| || | 40| || |Dest N9:0| || | 40| || +––––––––––––––––––+ |Rung 2:6 Main block transfer sequencer.| BT || Done || Bit || N[N9:0]:0 R6:0 +SQO–––––––––––––––+ ||–+––––] [–––––+––]/[––––––––––––––––––––––––––––––––+SEQUENCER OUTPUT +–(EN)–|| | 13 | EN |File #N10:0+–(DN) || | | |Mask FFFF| || | | |Dest N9:0| || | | |Control R6:0| || | | |Length 1| || | | |Position 1| || | | +––––––––––––––––––+ || | BT | || | Error | || | Bit | || | N[N9:0]:0 | || +––––] [–––––+ || 12 |Rung 2:7| Voltage/ || Current || +EQU–––––––––––––––+ N40:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 40| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N40:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |
Rung 2:5
Initialize the sequencer for runmode. Same functionality asrungs 2:0 and 2:1.
Rung 2:6
This is the main block transfersequencer. The sequenceroutput word, N9:0, is updatedwhenever the previous blocktransfer is done or fails.
Rung 2:7
Voltage/current BTR.
D–27Sample Ladder Listing
Publication 1403-5.1
Rung 2:8| real time || Power || +EQU–––––––––––––––+ N41:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 41| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N41:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:9| Cumulative || Power || +EQU–––––––––––––––+ N42:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 42| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N42:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:10| Device || Config || +EQU–––––––––––––––+ N43:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 43| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N43:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:11| Comm. || Config || +EQU–––––––––––––––+ N44:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 44| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N44:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:12| Demand || +EQU–––––––––––––––+ N45:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 45| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N45:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:13| Even || Harmonic || Distortion || +EQU–––––––––––––––+ N46:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 46| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N46:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |
Rung 2:12
Demand BTR.
Rung 2:8
Real time power BTR.
Rung 2:9
Cumulative power BTR.
Rung 2:10
Device configuration BTR.
Rung 2:11
Communication configurationBTR.
Rung 2:13
Even harmonic distortion BTR.
D–28 Sample Ladder Listing
Publication 1403-5.1
Rung 2:14| Odd || Harmonic || Distortion || +EQU–––––––––––––––+ N47:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 47| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N47:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:15| Even || Harmonic || Magnitude || +EQU–––––––––––––––+ N48:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 48| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N48:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:16| Odd || Harmonic || Magnitude || +EQU–––––––––––––––+ N49:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 49| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N49:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:17| Even || Harmonic || Phase || +EQU–––––––––––––––+ N50:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 50| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N50:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:18| Odd || Harmonic || Phase || +EQU–––––––––––––––+ N51:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 51| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N51:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:19| Diagnostic || +EQU–––––––––––––––+ N52:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 52| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N52:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |
Rung 2:17
Even harmonic phase BTR.
Rung 2:14
Odd harmonic distortion BTR.
Rung 2:15
Even harmonic magnitudeBTR.
Rung 2:16
Odd harmonic magnitude BTR.
Rung 2:19
Diagnostic BTR.
Rung 2:18
Odd harmonic phase BTR.
D–29Sample Ladder Listing
Publication 1403-5.1
Rung 2:20| Relay/ || Setpoint || +EQU–––––––––––––––+ N53:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write READ+–(ER) || |Source B 53| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N53:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:21| Command || +EQU–––––––––––––––+ N54:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write WRITE+–(ER) || |Source B 54| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N54:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:22| Config || +EQU–––––––––––––––+ N55:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write WRITE+–(ER) || |Source B 55| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N55:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:23 Begin run mode once all setpoint block transfers are complete.| One Shot 4 Status – Setpoint Setpoint || Bad Table Counter Mode || Check Done Bit || +EQU––––––––––––––+ B3 +EQU–––––––––––––––+ C5:0 B3 ||–+EQUAL +–––[OSR]––––+EQUAL +––––] [––––+––––(U)–––––+–|| |Source A N9:0| 303 |Source A N82:36| DN | 1 | || | 40| | 0| | | || |Source B 56| |Source B 0| | | || | | | | | | || +–––––––––––––––––+ +––––––––––––––––––+ | | || | Run | || | Mode | || | B3 | || +––––(L)–––––+ || 2 |
Rung 2:22
Configuration BTW.
Rung 2:20
Relay/setpoint BTR.
Rung 2:21
Command BTW.
Rung 2:23
If the setpoint counter done bitis set, the last setpoint BTW hasoccurred and was followed by adiagnostic BTR. If thediagnostic table indicates asuccessful setpoint BTW,setpoint mode is done. Thesetpoint mode bit is unlatched,and the run mode bit is latched.
D–30 Sample Ladder Listing
Publication 1403-5.1
Rung 2:24 Load next setpoint into setpoint write data.| One Shot 5 Status – Setpoint Setpoint || Bad Table Counter Number || Check Done Bit || +EQU–––––––––––+ B3 +EQU–––––––––––––––+ C5:0 +CTU––––––––––+ ||–+EQUAL +–[OSR]–+–+–+EQUAL +–+–]/[–+COUNT UP +–(CU)–+–|| |Source A N9:0| 304| | |Source A N82:36| | DN |Counter C5:0+–(DN) | || | 40| | | | 0| | |Preset 3| | || |Source B 56| | | |Source B 0| | |Accum 3| | || | | | | | | | +–––––––––––––+ | || +––––––––––––––+ | | +––––––––––––––––––+ | | || | | Prepare | | || | | Initial | | || | | Setpoint | | || | | Write | | || | | +EQU–––––––––––––––+ | | || | +–+EQUAL +–+ | || | |Source A C5:0.ACC| | || | | 3| | || | |Source B 0| | || | | | | || | +––––––––––––––––––+ | || | Setpoint | || | Data | || | Address | || | +ADD–––––––––––––––+ | || +–––––––––––––––––––––––––+ADD +––––––+ || | |Source A 21| | || | | | | || | |Source B C5:0.ACC| | || | | 3| | || | |Dest N20:1| | || | | 24| | || | +––––––––––––––––––+ | || | Move | || | Current | || | Setpoint | || | Data into | || | BTW Table | || | +COP–––––––––––––––+ | || +–––––––––––––––––––––––––+COPY FILE +––––––+ || |Source #N[N20:1]:1| || |Dest #N86:1| || |Length 20| || +––––––––––––––––––+ |
Rung 2:25| Setpoint || +EQU–––––––––––––––+ N56:0 +MSG––––––––––––––––––––+ ||–+EQUAL +––]/[–––––––––––––––––––––+READ/WRITE MESSAGE +–(EN)–|| |Source A N9:0| 15 |Type PEER–TO–PEER+–(DN) || | 40| |Read/Write WRITE+–(ER) || |Source B 56| |Target Device 500CPU| || | | |Local/Remote LOCAL| || +––––––––––––––––––+ |Control Block N56:0| || |Control Block Length 14| || +–––––––––––––––––––––––+ |Rung 2:26| ||–––––––––––––––––––––––––––––––––––––+END+––––––––––––––––––––––––––––––––––––|| |
Rung 2:24
This rung is activated oncewhen the sequencer output filechanges to setpoint BTW. Itspurpose is to determine theaddress of the next setpoint dataand to copy the data residing atthis address into the setpointBTW data location. This isaccomplished by first adding anaddress offset to a base addressto determine the location of thenext setpoint data. The dataresiding at the resulting addressis then transferred to thesetpoint BTW data location. Acounter is used to determine theaddress offset. Prior to the firstsetpoint BTW, the counter isautomatically incremented. Forsubsequent setpoint BTWs, thecounter is incremented whenthe diagnostic table BTR for theprevious setpoint BTW issuccessful. For example, the3rd setpoint will reside at baseaddress 24. In this case, acounter value of 3 will be addedto the base address 21. Thedata residing at location 24 willthen be transferred into thesetpoint BTW data locationN86:1.
Rung 2:25
Setpoint BTW.
Rung 2:26
End of file.
Appendix E
Publication 1403-5.1
Technical Specifications
Product Approvals
UL 508 Component Recognized File E96956 andCSA C22.2 approval for Industrial Control Equipment.
Compliance to European Union Directives
If this product has the CE mark it is approved forinstallation within the European Union and EEA regions.It has been designed and tested to meet the followingdirectives.
EMC Directive
This product is tested to meet Council Directive89/336/EEC Electromagnetic Compatibility (EMC) andthe following standards, in whole or in part, documentedin a technical construction file:
• EN 50081-2 – Generic Emission Standard, Part 2 –Industrial Environment
• EN 50082-2 – Generic Immunity Standard, Part 2 –Industrial Environment
This product is intended for use in an industrialenvironment.
Low Voltage Directive
This product is tested to meet Council Directive73/23/EEC Low Voltage, by applying the safetyrequirements of IEC 1010-1.
This equipment is classified as open equipment and mustbe installed (mounted) in an enclosure during operationas a means of providing safety protection.
Screw Torque and W ire Size
Position Ratings
Mounting Screw TighteningTorque
0.9 to 1.1 Nm (8 to 10 lb-in.)
Communications Connector 0.6 to 0.8 Nm (8 to 10 lb-in.)
Terminal Screw TighteningTorque
0.2 to 2.5 mm2 (24-12 AWG),stranded or solid wire, Cu wireonly.
Terminal Block/Wire InsulationTemperature Index
75° C maximum
Environmental Specifications
Operating Temperature –40° C to +60° C
Storage Temperature –40° C to +85° C
Humidity5 to 95 percent,non-condensing
Vibration
Operational: 0.006 in. DA/1.0 GSine, 10 to 500 Hz, 3orthogonal axes.
VibrationNon-operational: 0.015 in.DA/2.5 G Sine, 10 to 500 Hz, 3orthogonal axes.
Shock
Operational: 15 G, Half Sine,11 ms duration, 3 orthogonalaxes, 3 (+) and 3 (–)pulses/axes, 18 pulses total.
ShockNon-operational: 30 G, HalfSine, 11 ms duration, 3orthogonal axes, 3 (+) and 3 (–)pulses/axes, 18 pulses total.
E–2 Technical Specifications
Publication 1403-5.1
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improveproductivity and quality for more than 90 years. We design, manufacture and support a broadrange of automation products worldwide. They include logic processors, power and motioncontrol devices, operator interfaces, sensors and a variety of software. Rockwell is one of theworld’s leading technology companies.
Worldwide representation.
Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic •Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru •Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain •Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1403-5.1 – January 1998Publication 1403-5.1 – January 1998Supersedes Publication 1403-5.1 October 1996
40055–162–01 (B)Copyright 1998. Rockwell International Corporation. All rights reserved. Printed in USA