Low voltage control
M p % *
U s e r s m a n u a l
* r > #
Jinhua Huadong^^ironp^ital
Protection Equipm ntC., Ltd.
-
8/12/2019 Dien AP Thap
2/29
The inormation in this manual is protected by Copyright, no
p a r t of th is manual may be photo copied or copied by any means
w ithout p erm ission in w ritin g from Huadong Environmental
P ro te ct io n Company. The co nte nt o f th is manual is su b je ct to change
w ithout n o tic e. Huadong Environmental P ro te ct io n Company sh a ll n ot
responsible to anyone who may understand this manual wrongly or
fo r damages n p rin tin g .
-
8/12/2019 Dien AP Thap
3/29
Foreword
Thanks fo r usin g Huadong Envronmental p ro te c tio n E le ct ric
Appliance, we fe el highly f la t te re d by your usin g A de ta i ledUser' s manual is enclo sed with th is ap plian ce so th a t you can use
it masterly as soon as possible.
The co n ten t o f th is User s manual is de scrib ed com pletely andeasily, you can obtain some relevant knowledge for installation,op era tion and mantenance
We co ns ide r th a t the inform ation in th is manual is co rre ct andre lia b le , but the er ro r and the ca re les s omission th a t we couldn tco ntro l might not been fin d out or checked be ore p rn tin g , yourun derstand ng s h igh ly requ est!
Sometimes, we may make some change to hardware and softw are
in order to improve the components and the complete machine, sperform ance and r e l i a b i l i t y , and thus the softw are and hardw are
may d iff e re n c e from the manual, u se rs sh ould un de rstan d us.
Please dial our telephone (0579)2261886 to us if you find anym stak e o r any problems when u sin g
Thanks for your cooperation!
Huadong Environmental pr o te c tio n Co., Ltd
-
8/12/2019 Dien AP Thap
4/29
Contents
apterl G en era l.......................................................................................................1
apter2 Model and descriptions.........................................................................2
apter3 sa ge, Applicable Scope and fe a tu re ................................................3
apter4 Operating condit io ns............................................................................. 5
apter5 Setting method o f coritrol time o rd e r ................................................6
apter Debuggin g and o pe ra tion ....................................................................9
apter7 Testing, installation and m ain ten ance .............................................11
apter8 TO D 10 Op erator interface ..............................................................13
apter9 A whole set o f p ro d u c t......................................................................23
apterlO Ordering n o tic e ................................................................................24
-
8/12/2019 Dien AP Thap
5/29
User's manual for low voltage control P age 1 o f2 5
1 General
Electric dust collector low voltage auto-control system is an auto-controldevice for its cathode & anode vibrating motor, distribution plate vibrating^ wall
vibrating motor, constant temperature etc to ensure the electric dust collector has
a good reliability and security, it is a necessary device that could realize
automatization for working procedures o f electric dust collector.
As technical development and Computer popularization, PLC has be^n a
preferred control heart of electric dust collection low-voltage automatic
application with the low-voltage product changed from simple to set compiete,
from set complete to hgh, low voltage control system. Huadong Environmental
Protection Company owns its unique advantage in PLC applications, which can
master many kinds o f PLC program methods skillfully.
The key of electric dust collector PLC low voltage auto-control device relies ontheory design and program skill, WDK electric dust collector PLC low voltage
auto-control device collects many years experiences in designing and developing
electric dust collector povver-supply apparatus, integrates domestic and reign
advanced technology in industrial automatization application vvith the practicable
application of electric dust collector, resolves all kinds of problems during the whole
process of electric dust collector and dust bag automatic controlling and management,
meets the needs of users urthest, you can obtain the maximal technical support from
choosing the Products of Huadong Environmental Protection Company.
The series of WDK electric dust collector low voltage auto-control device are
more excellent than the same Products.
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682 26127 8^
-
8/12/2019 Dien AP Thap
6/29
User's manual for low voltage control Page 2 of25
2 Model and descriptions
Description : Static dust collector low-voltage automaticcontrol device
The meanings of model are as follows:
The device conrms to the relevant technical requirements of GB/T3797-89.
JinhuaHuadongEnvironmentalProtectionEquipmentCo..Ltd.0579-8226188682261278
-
8/12/2019 Dien AP Thap
7/29
-
8/12/2019 Dien AP Thap
8/29
User s manual for lovv vol tage c ontrol Page 4 of25
Features
WDK low voltage auto-control device is a low voltage power-supply apparatuswith vibrating, heating of electric dust collection that developed on the basis of
collecting the latest Products in the same industry both at home and abroad, it can also
detect material level and temperature etc switches and analog signals, which is a
comprehensive auto control device with program control, driving and signal treatment,
the technical features of a complete set of products include:
Programmable logical controller can control main control heart, it has developed
into a general industrial auto-control device based on microprocessor and integrated
modern Computer technology, automatic control technology and communication
technology, it is characterized by small volume, strong unction and convenient
maintenance, especially its ability to accommodate to horrible industrial
environment and high reliability.
The air leak phenomenon can be removed effciently for its dust removal and
wall vibrating linked together.
It prevents the dust carrying machine from load running for its dust removal
and dust carrying linked together.
Set the protective iinctions of short circuit and over current
It has a good Chinese Computer interface, convenient in operating, the
parameter and condition can be displayed and the control parameter can be set
hrough the keyboard on control panel, the salespeople neednt to know PLCprogrammable knowledge, the parameter owns memory unction ater modiying, no
need to reset ater disconnecting the power supply.
User can expand this equipment
The equipment can cormect with DCS,FCS system.( please carry on
negotiation with us when ordering.).
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682261278'^'-
-
8/12/2019 Dien AP Thap
9/29
Use^s manual for low voltage control Page 5 of25
Operating conditons
> The height above sea level shall not exceed 1000M> The ambience around the control box shall be -10~40c 0 ( t he r a t eo f
temperature change shall not exceed 10c/h)
> The maximal relative humidity shall not exceed 90%RH , no
condensation o ( relative temperature is 20 5 c )
> No electric dust, no gas or steam on the corrosive metal and insulated
materials around the equipments ambient gaSo
> No burst dangerous environment, no fiercely shock and impact in the
control room, the installation vertically gradient shall not exceed 5%.
> AC voltage shall conorms to the specications as belovv: sine wave ,
requency of 50Hz, within the range o f 2%, voltage of 380V,within the
range of+5% ~-7% .
> For special requirements, please carry on negotiation with us when
ordering.
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682261278
-
8/12/2019 Dien AP Thap
10/29
Use^s manual for low voltage control Page 6 o f 25
u Settng method of controllng tme order
Cathode & Anode vib ra tin g time o rde r
Vibrating control is an important link to improve dust collection efficiency and
reduce the second dust. In the same products, vibrating time can not be modied
optionally that is unscientifc.(only the people who knows PLC program could
modiy it). During the actual application, operate it by both hands when maintenance
or special conditions, when automatically vibrating in a certain time, it shall meet the
dust removal requirements of electric dust collector and reduce the second dust
irthest to set the vibrating cycleSo the principle o f vibrating control is:
Avoid operating cathode & anode vibrating in the same electric eld
synchronously.
The vibrating interval time is different;
Avoid operating anode vibrating and distribution board vibration
synchronously; Set the space rate in the electric field with the min. common multiple.
Dust removal and dust carrying motor time order
When controlling automatically, the dust removal motor time order should
interlock the working conditions of high > low material level and wall vibrator , and
thus to avoid short circuit in electric feld caused by the dust in dust funnel iirthest or
air eakage caused by idle running of dust removal machine, its general design
principle is :
It integrates active timing dust removal with passive dust removal:
1 Adopting initiative timing dust removal under no high, low material level
detection, the dust removal time shall be distributed according to the dust collection
proportion in every electric field: ls t electric field70%, 2nd electric field 20%, 3rd
electric fieldl0% , its actual time of dust removal equals to the addition of three
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682261278^
-
8/12/2019 Dien AP Thap
11/29
User's manual for low voltage control Page 7 o f25
electric felds;
2> High material level starts dust removal, low material level stops dust removal
if it is itted with material level measurer;
3 It integrates the timing with the material level control: High material levelstarts dust removal machine, after timing a certain time, please stop dust removal or
start timing dust removal, low material level stops dust removal.
Dust removal machine interlocks wall vibrator, the timing dust removal may not
alvvays same as the actual dust removal if is not itted with low material level
measurer, after stopping dust removal machine, please start the wall vibrator, the air
leakage phenomenon may be overcame by plugging the dust removal outlet with the
remnant dust on dust funnel wall. Dust removal machine interlocks dust carrying machine, please start the dust
removal machine after the dust carrying machine running for lmin, the capacity of
dust removal shall be less than the capacity of dust carrying, never removing dust
synchronously to cause dust carrying machines load running, adopting timing dust
removal and timing dust carrying if there is not a lot of dust.
Electric heater control The heater control is mainly a constant temperature control betvveen the range of
rossbeam(porcelain lining) and porcelain axis, in order to prevent insulated sleeve
ipe(quartz sleeve pipe) and porcelain axis from dewing to inAuence electric dust
ollectors normal running, please adopt low-voltage heating constant temperature
ontrol system to ensure that the insulated sleeve pipe and porcelain axis can run under
constant temperature of higher than dew point and the electric dust collector has a
igher working voltage to reach a better dust collection effciency. Start or stop electriceater with upper, lower limit temperature relay or control electric heater with PT100
latinum heating resistance temperature sensor signal, and thus the temperature in
nsulation can could be kept within a setting range and the temperature value can be
ndicated.
Chinese interface indicates running condition
The Chinese indicating on low voltage control box is a unique function of our
product, the Chinese display screen is installed on the panel of low control box ,
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682261278^
-
8/12/2019 Dien AP Thap
12/29
Use^s manual for low vo ltage control Page 8 of25
which can display the information, set value o f alarm to Service that promote the
debugging, operating and maintenances convenience.
During operating, if the loop fails, the text displayer would automatically tum to
the page of indicating faulty equipment with Chinese indicating, meanwhile raise
the alarm with PLC
JinhuaHuadongEnvironmentalProtectionEquipmentCo..Ltd.0579-82261886822 61278^-
-
8/12/2019 Dien AP Thap
13/29
Use^s manual for low voltage control Page 9 o f 25
Debugging and operatng
The control circuit in control box is restricted by operating cabinet, when the key
svvitch placed on long distance, control box can allowed to control, when the key
switch placed on machine side, the corresponding motor can be directly started.
Dust removal machines running is interlocked by dust carrying machine, dust
carrying machines running is interlocked by dust carrying signal.
Debugging Check each connection with instrument according to the dravving requirements to
ensure the wire can be connected correctly.
Tum off the supply switch in the cabinet, turn of f the total switch QF and PLC
supply switch QFA, then connecting door lock switch SP1, now PLC shall be
electriferous and salutatory shall be displayed.
Turn the major loop switch DQ F to the position of ON .
Hand debugging for every motor loop, turn the rotating switch on the control box
to the irst shit of machine side, then checking the phase order of motor to see if it
is correct or not.
After single machine debugging, tum the rotating switch on the control box to the
position o f long distance, debugging every loop through PLC. The dust removal
could be removed to the position o f long distance and Central control machine side.
When selecting the switch placed on the position of Central control, the preparedindicating lainp on low-voltage control box blinks. [The control box has DCS
interface]
Press ON/OFF key on the panel of low voltage cabinet to start the system.
During the period o f debugging, do make relevant debugging records and
modiying records o f equipments control requirements.
linhuaHuadongEnvironmental ProtectionEquipmentCo.,Ltd.0579-8226188682261278
-
8/12/2019 Dien AP Thap
14/29
User's manual for low voltage control Page 1 0 of 25
Operation
K Operating steps
Tum the key of operation case to long distance shit, every loop shall be
controlled by PLC. Tum plastic Shell breaker (QF) to the position of ON, and connect the major
loop.
Tum 2nd electric loop switch (QFA) to the position of ON.
Tum supply switch (SP1) to the position of ON.
Tum SP2 on the control box to the position of machine side(controlled by
machine side),dust removal motor may be prepared if tumed to the position of
Central control, and thus low voltage vvould send prepared signal to Central
control room. ( Controlled by upper level machine) [control box has DCS interface]
Press start key(SB01)or Central control key to transfer the signal to the lower
voltage cabinet.
See the instructions in text displayer manual to know TD200 operating method.
2^ Stopping steps
Press the stop key(SV02) or Central control key to cancel the driving signal. Tum supply svvitch(SPl) to the position of OFF.
If the equipment unused for a long time, please tum the plastic Shell (QF)to the
position o f OFF.
Points for attention
Never directly disconnect the power supply under working conditions to avoid
equipment malunction.
No power-supply signal for material level measurer etc switch contact. 0
The distance of testing temperature shall not exceed 100M.
linhuaHuadongEnvironmentalProtectionEquipmentCo.,ltd.0579-8226188682261278^*
-
8/12/2019 Dien AP Thap
15/29
Use^s manual for low voltage control Page 1 1 o f 25
, nstallaton, mantenance
Test ing After unpacking the equipment, check to see if its appearance and inner
components is damaged or not
Check to see if the components, accessories and technical documents is complete
or not.
Check to see if the instrument in control box is damaged and the astener, the
component is loosened or not after carrying, abnormal phenomenon should be
handled in time, please contact with our company directly if they cant be repaired
well.
I n s t a l l a t i o n
The control box shall be installed on a flat surface, V-iron is recommend, in this
way, it can be fastened easily and its outer shell can be grounded easily.
Connect the wire according to the dravving provided with the system, the inletconnection and the power outlet should adopt the lead vvire with sufficient section
according to the rated current. The temperature signal must adopt shield earth, switch
volume signal contact must be a closing contact.
The grounding must be in accordance with national relevant regulations about
high and low voltage connections (GB50168-92).
Control box shall has a reliable groundingo
Check all input and output vvire with instrument to ensure that the wire is correct
and reliable.
Maintenance
Read these instructions and complete dravving careiilly, know its construction,
performance, operating and maintenance methods etc.
Keep control box clean, dry and ventilated; all surfaces of components in the
JinhuaHuadongEnvironmentalProtectionEquipmentCo..Ltd.0579-8226188682261278
-
8/12/2019 Dien AP Thap
16/29
User's manual for low voltage control Page 12 of25
cabinet should be cleared away with dry compression air at the least of one month.
The equipment improperly running in any link is orbidden, when loop fails,
please repair it in time, the equipment can be used after removing the fault.
Turn the transfer switch of operation case to the position of long distance tokeep the equipment run automatically under normal condition.
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-82261886822 61 278 ^
-
8/12/2019 Dien AP Thap
17/29
Usei s manual for low voltage control Page 1 3 of25
8 Operation Instructions
TODllO Operator interface
Jinhua Huadong Environmental Protection Equipment Co., Ltd.
WDKPLC~04/S low voltage cabinet
System operation
In le t : 140'C 0u t let :135 c
(Figl. 1)
1. Funct iona l ins t ru c t io ns fo r keys
F1~F6 keys: page up/down, s e tt in g o f work mode et c.
D irec tion keys: page up/down, da ta ed it io n etc.
ESC key: re tu rn from p a rt ic u la r page (da ta inp ut page, password inpu t page,
alarra page and etc) to orginal page, or return to original page from present
page w ith g iv in g up th e d a ta m od if ic a to n .
ENT key: confirm the data, re tu rn from da ta input page to the o rig in a l page.
SET key: en te r n to the d ata ed it io n s ta tu s or en ter into d ata inp ut page.
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682261278^
-
8/12/2019 Dien AP Thap
18/29
2. Operation for user menu
It depends on actual user menu
Use^s manual for low voltage control Page 1 4 of2 5
:: i
r
l r a l r ' :' " ----------------------------------
WDKPLC-4/S low voltage cabinet
System operation
Inlet: 135"C outlet: 13CCC
' | | SQOnda r menui(b )Ma in menu
Run status
Help[F4]
Parameter
Esc [F6]
set
[Fl]
[F2]
Single unit control [F3]
Runstatus[Fl]
Anode vbrating in 1
electric field Run Menu F5
Anode vibrating in 2""
electric field Stop Esc F6
Anode vibratng in 3rt
electric field Stop
Anode vibrating in ltelectric field Stop _
Parameterset [F2]
liquipmont name StoplnAnode vibrating in 1electrc field 50S 150SAnode vbrating in 2*electric field 300S 150SAnode vbratng in 3rtelectric field 600S 150S
l
Single unitcontrol[F3]
Anode vibrating inelectric field ReadyRun status StopStop (Fl)Control status StopTimed(F2)
lsc F6Continous(F3)
Vi ew a 11secondarymenu be
pre ss in g
PgUp andPgDn keys
View allsecondarymenu bepressingPgUp andPgDn keys
View allsecondarymenu bepressingPgUp andPgDn keys
Help[F4]
Esc [F6]
lSIi/SHT/ENT Key :Data S c t Hl'l-F6 Kcy:!aRe/RelaycontrolIHrection key:PaR0 controi/Data sctJ
WDKPLC-4/S low voltagecabinet
System operationInlet 135X2 0utlet:130t:
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682 26 12 7 8^
-
8/12/2019 Dien AP Thap
19/29
User's manual for low voltage control Page 1 5 of25
When you press Fl- F5 keys and the direction keys on intal page (Fig 1.0),
then the pressing of F5 key on other pages (such as data input page, password input
page, but excludng the alarm page) will make the main menu page. By pressing Fl-F4
key, the main menu can be chosen, or the secondary menus will display. If one main
menu has been chosen, page down/up can make you to see the secondary-menus. It is
not available to skip to the secondary menus of other main menu. By pressing F5,
you return to the user s main menu and to other raains. By pressing ESC or F6, you
return to initial page.
Case
Once you enter the secondary menu page, page down/up w11 make page move. But
you can only view the secondary menu under the main menu.
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682 261278^
-
8/12/2019 Dien AP Thap
20/29
User's manual for low voltage control Page 1 6 O25
3*. * 1* 1 * 1 '* - PR -g
S t P t e * P 5 '# h ; t i F 6
g i p i i r # 4 : : i fS I i K i t m t : , < T
fI F2 F3 F4 .?5 f
A
SS c N?
. . . .ia.:,.
(Fig. 1. 2)
I-':z~
'i t
Jinhua Huadong Environmental Protection Equipment Co., Ltd.
Anode vibrating in 1 electric field Run Menu F5Anode vibrating in 2IK| electric field Stop Esc F6Anode vibrating in 3r
-
8/12/2019 Dien AP Thap
21/29
User's manual for low voltage control Page 1 7 of25
By pressng Fl-F4, choose the main menu. If you want to change the parameters,
press F2 to display the secondary menu page.
Jin hua Huadong Environmental Pro te ct io n Equipment Co., Ltd.Equipment Name StopAnode vib ratin g in 1 e le c tri c fie ld 150SAnode vibrating in 2"0 ele ct r ic f ie ld 300SAnode vib ratin g in 3rd e le c tri c fie ld 600S
Run150S150S150S
(Fig. 1. 5)
Pararaeter raodification
Press up/down keys to choose the page that contains the parameters to modify.
When cursor flashes, no page can be turned over. The ESC key is necessary to
cancel the edition.
Press SET key and enter the data edition status, then the cursor lashes at
the area of first changeable data Pressing ESC key can cancel the edition.
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682261278^ '
-
8/12/2019 Dien AP Thap
22/29
User's manual for low voltage control P ag e 1 8 of 2 5
Jin hu a Huadong Environmental P ro te ct io n Equipment Co. , Ltd.
Equipment Name Stop RunAnode v ib r at in g in 1" e l e c t r i c f ie ld 150S 150SAnode v ib ra tin g in 2"" e le c t r i c f ie ld 300S 150SAnode v ib ra t ing in 3rd e le c t r ic f ie ld 600S 150S
(Fig. 1.5)
Pressing the direction keys can move the cursor, and then you can choose the
data to edit.
Press SET key to enter the data input menu. If the data is protected by password,
enter the password. Once the password is correct, the data input page wil
automatically show up. If the password is incorrect, pause on the page of password
input.
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682261278^
-
8/12/2019 Dien AP Thap
23/29
User's manual for low voltage control Page 1 9 of 25
I- ** Wc 1'< * r PR S]r-ml $
M lpi-I
l f lI
' 99 9m M \ ' o o o c i p r ^ s
3150i
81K
F1 F2 '/F~3 -F4
-
8/12/2019 Dien AP Thap
24/29
Use^s manual for low voltage control Page 2 0 o f 25
Single unt operaton P re ss Up/Down keys to choose the page th a t shows the equipment used in the
s ing le un i t opera t ion .____________________________
- *3fL P i -Rj
|j| 52l(2E. S. n&l LLZI ^
F1
P\'T,'i
F2 c3 ?'l
(ffll7)Jin hu a Huadong Envronmental P ro te ct io n Equipment Co., Ltd.
Anode vib ratin g in lst e le c tr ic fie ld ReadyRun s ta tu s Stop Stop (Fl)Co ntrol s ta tu s Stop Timed(F2)Menu F5 Esc F6 Continuous(F3)
(Fig. 1.7)
For example, the sing le un i t operat ion for anode vib rat in g in r l e le c tric f ield
should be:
K Set the machine in timed mode, by p re ss in g F2 key. (F ig l.8 )
2s S et the machine in con tinuou s mode, by p re ss in g F3 key. (Fig. 1.9)
2- PUV 3
, ! l f 5 i i | i i H J & . 4 Si l p i i i p ; I :.(F 1) p
i B F2> i M t l i n i P i M ^ J ( F 3 ) 1
..Pl !2 F3 "4 i t
StT < T ENT *
1.8)
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682261278
-
8/12/2019 Dien AP Thap
25/29
Use^s manual for low voltage control Page 2 1 of25
Jinh ua Huadong Environmen tal P ro te ct io n Equipment Co ., Ltd.Anode vib ratin g in p l e le c tr i c f ie ld Ready
Run st a tu s Stop Stop (Fl)Con trol s ta tu s Stop Timed(F2)
Menu F5 Esc F6 Con tinuous(F3)
(Fig. 1.8)
-p tVr-it * * r Hi V }
m : a i r e w (Am ^ ..ru*! iU A l X - . I ttrhlmrlMMt? jii.v.
-
8/12/2019 Dien AP Thap
26/29
Use^s manual for low voltage control Page 2 2 of25
Alarming
When the alarm is a ctiva ted , the User ' s screen w ill sk ip into the alarm page
(Fig 1.1 0). With up/down keys, check a l l the alarm da ta. Pr es sin g ESC w i 11
make you quit the alarm page.
(H l 10)
Jinhua Huadong Environmental Protection Equipment Co., Ltd.Anode vi b ra tin g motor in lst e le c tr ic fie ld Fa ult
Po rce la in l in in g e l ec t rc h ea te r in r e l ec t r i c f i e ld Fau lt(Fig. 1.10)
Note: Pressing Mute button will relieve the alarm sound. After troubleshooting, the
pressing of Mute button will reset the fault.
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682261278^'-
-
8/12/2019 Dien AP Thap
27/29
User's manual for low voltage co ntrol Page 2 3 O 25
9 A whole set of Products
1. Low-voltage control box lse t2. Operating instructions lcopy
3. Product certicate lpcs
4 Complete drawing lcopy
5. Operation case is tted as technical requirements
6. Temperature sensor is fitted as technical requirem ents
JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682261278^
-
8/12/2019 Dien AP Thap
28/29
User's manual for low voltage control Page 2 4 of25
10 Ordering notice
Each electric dust collector low voltage auto-control system may be different
as the different situation. So detailed technical requirements (or dravving) should beprovided for users when ordering, the manufacturer shall do its best to meet the needs
of users according to the users requirements to produce.
The technical requirements made by users shall include:
Top electromagnetism vibrating:
Number of vibrator;
The annual arrangement o f vibrator and serial no. deined by users;
Vibrating c y c ^ vibrating height adustable range; Electromagnetism vibrator
parameter;
Other requirement.
Motor drive vibrating control:
Number of electric field;
Number of vibrating motoN description deined by users;Vibrating motor power> supply voltage> number of phase;
Vibrating time> vibrating interval adjustable range;
Whether operaton case(box)is itted with or not
Other requirements ( such as logic relation between each vibrating, whether shut-off
axis signal provided or not)
Heating control:
Number o f insulation can;
Number of heatei\ powe\ workingvolt;
Control method for users;
Model of temperature sensor;
Other requirements.JinhuaHuadongEnvironmentalProtectionEquipmentCo.,Ltd.0579-8226188682261278^
-
8/12/2019 Dien AP Thap
29/29
Use^s manual for low voltage control Page 2 5 o f25
Du stremovak dust carrying control:
Dust mnel quantity ^ vvhether fitted with wall vibrator and dust carrying control or
not ;
The power, phase number and work volt o f dust removal N dust carrying and wallvibrating motor;
Whether ltted with operation case(box) or not; Control mode;
Model of material level measurer, technical parameter;
Logical interlock relation between each electric ield dust removal;;
Other requirementSo
Cabinettype>. mode of inlet connection> color o f cabineto