NFPA 13 – 2013 EditionUpdate
Session Agenda
2
• A2012 Code Cycle•NFPA 13 Code Development•Changes to NFPA 13 (NFPA 24)•What Didn’t Happen •Next Steps
A2012 Code Cycle
800+ Proposal
500+ Comments
TCC Meeting 12/6/11
NFPA Annual Meeting 2012 (Las Vegas)
3
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 2/24
Code Development
5 TC’s
1 TCC
Staff’s Role in Development
4
Who Does What?
SSI – All Installation Related Items
SSD – Discharge Criteria
RSS – NFPA 13R and 13D
PRI – NFPA 2 and NFPA 13 CH 10 (Extracted)
HBS – Chapter 9
TCC (Now CC) - Correlation
5
6
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 3/24
More Training on Changes
Venue Name
Start
Date
End
Date Days
Houston, TX
9/13/20
12
9/13/20
12 TH
Nashville, TN
9/27/20
12
9/27/20
12 TH
Holiday Inn Baltimore Inner
Harbor
10/19/2
012
10/19/2
012 F
Cincinnati, OH
10/25/2
012
10/25/2
012 TH
Phoenix, AZ
11/2/20
12
11/2/20
12 F
Atlantic City, NJ
11/30/2
012
11/30/2
012 F
Orlando, FL
12/14/2
012
12/14/2
012 F
7
Changes to NFPA 13, 13D, & 13R - 2013 Edition - 1 Day Seminar
Chapter 3 - Definitions
8
Control valve
Draft Curtain
Dwelling Unit
High Volume Low Speed Fan
Continuous Obstruction
Non-Continuous Obstruction
Clearance to Ceiling
Raw Water Source
Sprinkler System
Small Room
Antifreeze System
Combined Dry Pipe/Pre Action
Cross Main
System Riser
Clearance to Storage
General Sprinkler Characteristics
Open Top Container
Four-Way Bracing
Hanger
Net Vertical Force
Seismic Separation Assembly
Clearance to Storage
3.9.1.6 Clearance to Ceiling. Thedistance from the top of storage to
the ceiling above.
9
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 4/24
Four-Way Brace
Four-Way Brace. A sway brace or swaybrace assembly intended to resist
differential movement of the piping systemin all horizontal directions.
10
3.3.8/A.3.3.8 - Draft Curtain
A continuous material protrudingdownward from the ceiling to create areservoir for collecting smoke and heat.
Additional information about the size andinstallation of draft curtains can be found inNFPA 204.
11
3.3.18.2 Non-continuousObstruction
Continuous Obstruction. Anobstruction located at or below the level of
sprinkler deflectors which affect thedischarge pattern of two or more adjacentsprinklers
Non-continuous Obstruction . Anobstruction at or below the level of thesprinkler deflector which affects thedischarge pattern of a single sprinkler.
12
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 5/24
3.3.22 – Small Room
A compartment of light hazardoccupancy classification having
unobstructed construction, and a floor areanot exceeding 800 ft2 (74.3 m2).
13
3.4.1 - Antifreeze Sprinkler System
A wet pipe system using automaticsprinklers that contains a liquid solution toprevent freezing of the system, intended todischarge the solution upon sprinkleroperation, followed immediately by waterfrom a water supply.
14
3.4.1.1 - Premixed AntifreezeSolution
A mixture of an antifreeze material withwater that is prepared and factory mixed
by the manufacturer with a quality controlprocedure in place that ensures that theantifreeze solution remains homogeneousand that the concentration is as specified.
15
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 6/24
3.3.23* Sprinkler System
An integrated network of piping designed inaccordance with fire protection engineeringstandards that includes a water supply source,
a water control valve, a water flow alarm, anda drain. The portion of the sprinkler systemabove ground is a network of specifically sizedor hydraulically designed piping installed in abuilding, structure, or area, generallyoverhead, and to which sprinklers areattached in a systematic pattern. The systemis commonly activated by heat from a fire anddischarges water over the fire area.
16
Nitrogen and Other Gases
Air, nitrogen or other approved gas- Where airis used to charge, maintain or supervisesprinkler systems, nitrogen or other approvedgas shall also be permitted to be used.
17
FDC Pressure
The pressurepotential from a fire
departmentconnection shall notbe considered indetermining ratedpressure per Section6.1.3.
18
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 7/24
Re-use of Sprinklers
When a sprinkler has been removed forany reason it shall not be reinstalled.
19
CPVC Compatibility
Nonmetallic pipe and fittings included
in table 6.3.1.1 and table 6.4.1 shall be
listed.
Manufacturers installation
instructions shall include it’s listing
limitations.
20
CPVC Compatibility
When CPVC pipe is used in
combination systems utilizing steel
pipe, cutting oils and lubricants used
for fabrication of the steel piping shall
be compatible with CPVC materials.
21
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 8/24
CPVC Compatibility
Other construction materials such as
paint, electrical and communication
wiring, thread sealants, gasketlubricant shall not come in contact
with CPVC unless they have been
evaluated as compatible with CPVC
materials by a testing lab.
22
Escutcheon/Cover Plate Assembly
The use of caulking or glue to seal thepenetration or to affix the components of arecessed escutcheon or concealed coverplate shall not be permitted.
23
6.2.6.2.2/6.2.6.2.3Painting Sprinklers
Where sprinklers have had paint applied byother than the sprinkler manufacturer, they
shall be replaced with new listed sprinklers ofthe same characteristics, including K-factor,thermal response, and water distribution.
Where cover plates on concealed sprinklershave been painted by other than the sprinklermanufacturer, the cover plate shall bereplaced.
24
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 9/24
6.2.9.1Stock of Spare Sprinklers
A supply of at least six spare sprinklersshall be maintained on the premises so thatany sprinklers that have operated or beendamaged in any way can be promptlyreplaced.
25
6.3.1.1.1 - Above Ground Pipe
Underground pipe shall be permitted toextend into the building through the slab orwall not more than 24 inches.
26
Relief Valves at Each Floor
7.1.2.3 A relief valve per Section 7.1.2.1shall be required downstream of check
valves required by Section 8.17.5.2.2(1).
Each connection from a standpipe that ispart of a combined system to a sprinklersystem shall have an individual controlvalve and check valve of the same size asthe connection.
27
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 10/24
6.10 - Signs
28
7.1.1 - Pressure Gauges
An approved pressure gauge conforming to
8.17.3 shall be installed in each system riser.
29
Antifreeze Systems
Premixed Solution
Glycerine 48%
PG 38%
More than 38% PG for ESFR
Manufacturers Certificate
New Solutions
30
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 11/24
NEW FPRF DATA
TC TIA
• Only Listed Solutions
• Listing Must Show It Doesn’t Ignite Public TIA
Ban All Antifreeze
31
What Can Happen
32
Backflow Testing
A means shall be provided to perform a fullforward flow test in accordance with
8.17.4.6
33
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 12/24
Sprinklers in Mechanical Equip
Sprinklers shall not be required to beinstalled within electrical equipment,mechanical equipment, or air handlingunits.
34
Water Mist Systems
NFPA 13 does notcontemplate WaterMist Systems. UseNFPA 750.
35
High Temp Heads – Storage
High-temperature sprinklers shall bepermitted to be used throughout ordinary
extra hazard occupancies, storageoccupancies and as allowed in thisstandard and other NFPA codes andstandards.
36
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 13/24
Attic Sprinkler Temp ratings
Attics should be conditioned or useintermediate temperature heads.
37
CMSA in O/L Hazard Occupancies
Quick response CMSA sprinklers designedto meet any criteria in Chapter 12 throughChapter 20 shall be permitted to protectlight and ordinary hazard occupancies.
Standard response CMSA sprinklersdesigned to meet any criteria in Chapter 12through Chapter 20 shall be permitted to
protect ordinary hazard occupancies.
38
Exposed Barrel Lengths
39
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 14/24
Exposed Barrel Lengths
40
Attached Insulation
For insulation that is installed attacheddirectly to against the ceiling or roofstructure and is installed flat and parallel tothe ceiling or roof structure, the deflectordistance shall be measured to theunderside of the insulation.
41
Small Closets
In all closets andcompartments, including
those closets housingmechanical equipment,that are not larger than400 ft3in size, a singlesprinkler at the highestceiling space shall besufficient without regard toobstructions or minimumdistance to the wall.
42
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 15/24
Dry Area Concept
Notwithstanding the obstruction rulesprovided in Chapter 8, it is not intended orexpected that water will fall on the entirefloor space of the occupancy.
43
Back-to-Back Sidewalls
The maximum width of the lintel or soffitshall not exceed 16inches.
The maximum width of the lintel or soffit canexceed 16 inches when a pendent sprinkler isinstalled under the lintel or soffit.
44
Sprinkler Spacing <6 FeetStandard and EC Sprinklers
(1) Baffles are arranged to protect theactuating elements.
(2) Baffles shall be of solid and rigid materialthat will stay in place before and duringsprinkler operation.
(3) Baffles shall be not less than 8 in. longand 6 in. (152 mm) high.
45
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 16/24
Sprinkler Spacing <6 FeetStandard and EC Sprinklers
(4) The tops of baffles shall extend between2 in. and 3 in. (51 mm and 76 mm) abovethe deflectors of upright sprinklers.
(5) The bottoms of baffles shall extenddownward to a level at least even with thedeflectors of pendent sprinklers.
46
8.3.3.4 – Use of Sprinklers
When existing light hazard systems areconverted to use quick-response orresidential sprinklers, all sprinklers in acompartment shall be changed.
8.3.4.1 Sprinklers shall have a minimumnominal K-factor of 5.6 unless permitted by8.3.4.
47
8.4.5.3 - Residential Sprinklers
Where residential sprinklers are installed in
a compartment as defined in 3.3.6, all
sprinklers within the compartment shall be
residential sprinklers.
48
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 17/24
Sidewall Obstructions Rule
Obstructions on the wall opposite from thesidewall sprinkler shall be permitted wherethe obstruction is up to 2 ft deep and 2 ftwide
49
8.5.5.3.1.1
Open Grate Flooring
• Open grate flooring over 4 feet in width shall
require sprinkler protection below thegrating.
50
Residential Sidewall Sprinklers
Residential horizontal sidewall sprinklerdeflectors shall be located no more than 6
in. from the wall on which they aremounted unless listed for greaterdistances.
51
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 18/24
Insulated Concealed Spaces
2 Inch Air Gap Permitted at Top
Entirely Not Practical
52
Elevator Requirements
Automatic fire sprinklers shall not berequired in elevator machine rooms andelevator machine machinery spaces,control spaces or hoistways of tractionelevators where the following are met:
1) The elevator machine room, machineryspace, control room, control space or
hoistway of traction elevator is and spacesare dedicated to elevator equipment only
53
Elevator Requirements
2) Spaces are protected by smokedetectors, or other automatic fire
detection, installed in accordance withNFPA72.
Spaces are separated from the remainderof the building by walls and floor/ceiling orroof/ceiling assemblies having a fireresistive resistance rating of not less thanthat specified by the applicable buildingcode
54
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 19/24
Elevator Requirements
4) Spaces are protected by smokedetectors, or other automatic fire
detection, installed in accordance withNFPA72.
5) The elevator machinery is not of thehydraulic type
55
Backflow as Required Control Valve
A listed backflow prevention device shall beconsidered a control valve, and anadditional control valve shall not berequired.
56
8.15.3.1 Stairways ofCombustible Construction
Sprinklers shall be installed beneath all
stairways of combustible construction.
8.15.3.1.1 Sprinklers shall be installed atthe top of combustible stair shafts.
8.15.3.1.2* Sprinklers shall be installedunder the landings at each floor level.
8.15.3.1.3 Sprinklers shall be installedbeneath the lowest intermediate landing.
57
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 20/24
8.15.9* - Hospital Clothes Closets
Sprinklers shall not be required in clothes
closets of patient sleeping rooms in
hospitals where the area of the closet doesnot exceed 6 ft² (0.55 m²) provided the
distance from the sprinkler in the patient
sleeping room to the back wall of the closet
does not exceed the maximum distance
permitted by 8.5.3.2.
58
8.17.2.5.1
Check Valve for FDC
A listed check valve shall be installed in
each fire department connection and shall
be located in an accessible location.
59
Heat Loss Calculation
Water filled piping shall be permitted to beinstalled in areas where the temperature is
less than 40°F (4°C) when heat losscalculation performed by a ProfessionalEngineer are performed to verify that thesystem will not freeze
60
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 21/24
Heat Tracing
Where used to protectbranch lines, the heat
tracing system shall bespecifically listed foruse on branchlines.
Electric supervision ofthe heat tracing systemshall provide positiveconfirmation that thecircuit is energized.
61
Concealed Space Calculations
Unless the requirements of Section
11.2.3.1.4(4) are met for buildings having
unsprinklered combustible concealed
spaces, as described in Sections
8.15.1.2 and 8.15.6, the minimum design
area of sprinkler operation for that portion
of the building shall be eight sprinklers
3000 ft2 (279 m2).
62
ESFR and CMSA Applications
ESFR and CMSA
sprinklers meeting
any criteria in
Chapters 12-20
shall be permitted
to protect light and
ordinary hazard
occupancies.
63
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 22/24
Pressure Balancing
22.4.2.4.3 Pressure balancing shall bepermitted through the use of a K-factor
developed for branch lines or portions ofsystems using the formula in 22.4.2.5.
22.4.2.5 K-factor Formula. K-factors, flowfrom an orifice or pressure from an orificeshall be determined on the basis of thefollowing formula:
64
Chapter 23Plans & Calculations
23.2.1.1* Where a water flow test is used forthe purposes of system design, the test shall beconducted no more than 12 months prior toworking plan submittal unless otherwiseapproved by the AHJ.
Water Supply Capacity
23.1.2 Capacity. Water supplies shall becapable of providing the required flow and
pressure for the remote design areadetermined using the procedures inChapters 11 through 22.
66
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 23/24
67
K =Q
√P
K=Q/(p)0.5
K Factor Equation
What’s Not Happening
Re-use of Sprinklers Heads
Cloud Ceilings
Shadow Areas
Specially Listed
Exposed Expanded Plastics
68
Stay informed about innovation atNFPA, visit: www.nfpa.org/innovation
8/12/2019 ÷ºÎ 3. NFPA13 2013 Edition Update
http://slidepdf.com/reader/full/aoi-3-nfpa13-2013-edition-update 24/24
NFPA 13 – 2013 EditionUpdate