Download - Annexure II Tech Data Sheet
-
Sr.
NoSpeicification IOCL Requirement Vendor Reply/ Confirm
1 Maximum ambient temperature 40 Deg C
2 Minimum ambient temperature 9 Deg C
3 Design ambient temperature 40.0 Deg C
4 Relative humidity max/min 96 % / 50%
5 Altitude above MSL 54 m
6 Environment Humid & corrosive
7 Location 03 Bldg. (Inside refinery -
Terrace of EWS , CSB &
Outside refinery-Admn building
of Block A & B
* Vendor to make site survey
before submitting the tender to
analyze the scope.
1 Rated Output To be mentioned by Vendor (To
meet total 200KW = (100 +100)
KW
2 No. of PV Modules To be mentioned by Vendor
3 No. of series module in one array To be mentioned by Vendor
4 No. of arrays in parallel
combination
To be mentioned by Vendor
1 PV cell type To be mentioned by Vendor
2 Make of SPV cell To be mentioned by Vendor
3 Make of SPV Module To be mentioned by Vendor
4 Maximum Power Rating of one
module
To be mentioned by Vendor
5 Rated Current of module To be mentioned by Vendor
6 Rated Voltage of module To be mentioned by Vendor
7 Short Circuit Current of module To be mentioned by Vendor
8 Open Circuit Voltage of module To be mentioned by Vendor
9 Sample I-V curve Submitted (Yes
/ No)
To be mentioned by Vendor
1 Mounting type Roof-mounted
2 Surface azimuth angle of PV
Module
To be mentioned by Vendor
Annexure-II
Technical Data Sheet to be compulsorily filled by Vendor
- 200KW Solar Panel, Roof top Grid Tie
A. Site Condition
B. SPV power plant
D. Mounting Arrangement
C. SPV Module
Page 1 of 4
-
3 Tilt angle(slope) of PV Module To be mentioned by Vendor
1 Enclosure To be mentioned by Vendor
2 Necessary Fuse Protection &
Surge Protection.
Yes
3 Fire Protection IEC 60 695-2-11- UL Subject 94
(Glow wire test )
4 Degree of protection against
mechanical load
IK 08 (5 Joule)
5 Rated Insulated Voltage DC 1000V
6 Dielectric strength 4.65 KV DC
7 Type Test In accordance to IEC 60364-712
1 Nomianl output power at site
based on the site conditions
Total 200 KW = 2*100KW
(Note: To be Installed on the
terrace of 3 no. Bldg to meet total
200KW output power overall)
2 Nominal Output array voltage
*shall be suitable for the MPPT
range of PCU
To be mentioned by Vendor
3 DC Array Input Operating
Voltage
(-20% to +15%) of the DC Array
input voltage
4 Type of solar charge controller MPPT Based Solar Charge
Controller
5 Switching device MOSFET/IGBT based
6 Continuous inverter Output
Rating (KVA)
7 Output Wave Form Pure Sine Wave Output
8 Total Harmonic distortion < 3% @ nominal power
9 Output Voltage 3 ph, 415 10 %
10 Output Frequency 50Hz 3%
11 Power Factor > 0.9
12 PCU Efficiency > 90% at nominal voltage &
power
13 Inverter efficiency 94% to 98% at full load
14 No. of Inverters with
Configuration
To be provided by Vendor
(8*25KW, to meet nominal
output power 4*50KW, at 3 nos.
bldgs with each having N+1
configuration or better)
Each 50KW solar system
will consist of 3 no. inverter
modules of min. 25 KW
each. (* all the inverters
provided shall be of similar
rating)
15 Inverter Type To be mentioned by Vendor
F. Power Conditioning Unit (PCU) / Inverter
E. DC Combiner Box / Array Junction Box
Page 2 of 4
-
16 Spare Inverter Module 2 no.
17 Idle Current < 4% of rated capacity
18 Regulation 2% for DC I/p variation & o/p
load variation
19 Overload Features 150% for 1 minute
20 Cooling Forced Air cooling, with
temperature controlled
cooling fan
21 Operating Temperature 0 to 50 C
22 Relative Humidity 95% Maximum
23 LED/LCD Display :
Indications
Display shall indicate system
functional parameters and
protection functional indicator
24 Data monitor and display controls RS485, Ethernet OR RS232
connectivity
25 Protections
26 a. Input over voltage
b. Low/high frequency
c. Short circuit
d. Under/over output voltage
e. Over Temperature
f. Grid Input under voltage / over
voltage with auto recovery
g. DC disconnect device
h. DC reverse polarity
i. Anti Islanding Protection as per
the standard
27 Enclosure Protection IP 21(for indoor) as per IEC 529
28 Safety 1. IEC 62103
2. IEC 62109 Part 1 & 2
3. Galvanic Isolation at input &
output through
transformer
29 Audible Noise < 45dB at 1 Meter
30 Power Control MPPT suitable for hybrid
operation.
31 Communication peripherals for
DATA analysis
LAPTOP (preferably Apple
make)
G. Catalogue
To be submitted along with the
bid
H. Drawings(To be submitted compulsorily along with the
Tender)
SPV Modules drawings, Solar
array layout,
Site & plant layout,
Page 3 of 4
-
Note: No cell to be kept blank.Vendor to give comments(compliance or non compliance) against each point