domestic fire sprinkler pump boost8n data...

10
BOOST8 BOOST8 BOOST8 BOOST8n n n Domestic fire sprinkler pump system complying with and significantly surpassing BS9251 2014 Technical Data Sheet Industry leading fire sprinkler pump system with plc control and simple LCD screen with product and system information Automatic weekly testing is carried out on the fire pump and the starting pressure switches (as EN12845). Any failure is reported via a fault output and displayed on screen providing reliability and resilience Our innovative flow control system shows our understanding of domestic fire sprinkler installations and problems contractors need to overcome. Flow controlled pumps can reduce tank size, saving valuable space and upfront costs (for town main boosting see page 4) The pump acts as a jockey pump and then a fire pump if required, with an automatic cooling line (as EN12845) Engineers know what's happening with the system at all times GRIFEN sprinkler solutions Tel: +44 (0)1625 575514 [email protected] www.grifen.co.uk GRIFEN sprinkler solutions NEW PRODUCT FEATURES The flow switch gives a fault signal when the pump is latched then a 20 second flow counter displays on screen until the fire alarm signal is given, reducing false alarms as the British standard demands PRODUCT FEATURES Two pressure switches giving switch backup (as EN12845) Failsafe wiring the pressure switch circuits will operate the pump if they go open circuit (as EN12845) Jockey pump the pump will operate for 8 seconds to remake pressure loss Fire pump the pump will operate if pressure is not maintained after a jockey run, with LCD and fault indication Comprehensive Combined Alarms; Weekly test failed, jockey limit, fire pump on demand (EN12845), annual test due and power failure- available as open on fault, SPDT optional Auto Cooling, if the fire pump operates, the solenoid valve opens every 20 seconds for 2 seconds to cool the impeller ensuring functionality even when a property is unoccupied. Automotive technology, a black electrophoretic bonded paint finish is applied to the pipe work inside and out, giving better protection and an attractive finish LPCB approved fire rated power and alarm cables Screen showing the weekly test has passed P1 pressure switch 1 went low pressure P2 pressure switch 1 went low pressure P1H pressure switch 2 returned healthy P2H pressure switch 2 returned healthy

Upload: others

Post on 26-Jun-2020

34 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: domestic fire sprinkler pump BOOST8n data sheets296016944.initial-website.co.uk/app/download/5785069798/domest… · Domestic fire sprinkler pump system complying with and significantly

BOOST8BOOST8BOOST8BOOST8nnnn

Domestic fire sprinkler pump system complying with and significantly surpassing BS9251 2014

Technical Data Sheet

Industry leading fire sprinkler pump system with plc control and simple LCD screen with product and system information Automatic weekly testing is carried out on the fire pump and the starting pressure switches (as EN12845). Any failure is reported via a fault output and displayed on screen providing reliability and resilience

Our innovative flow control system shows our understanding of domestic fire sprinkler installations and problems contractors need to overcome. Flow controlled pumps can reduce tank size, saving valuable space and upfront costs (for town main boosting see page 4) The pump acts as a jockey pump and then a fire pump if required, with an automatic cooling line (as EN12845) Engineers know what's happening with the system at all times

GRIFEN sprinkler solutions Tel: +44 (0)1625 575514 [email protected] www.grifen.co.uk

GRIFEN sprinkler solutions

NEW PRODUCT FEATURES

The flow switch gives a fault signal when the pump is latched then a 20 second flow counter displays

on screen until the fire alarm signal is given, reducing false alarms as the British standard demands

PRODUCT FEATURES

• Two pressure switches giving switch backup (as EN12845)

• Failsafe wiring the pressure switch circuits will operate the pump if they go open circuit (as

EN12845)

• Jockey pump the pump will operate for 8 seconds to remake pressure loss

• Fire pump the pump will operate if pressure is not maintained after a jockey run, with LCD and

fault indication

• Comprehensive Combined Alarms; Weekly test failed, jockey limit, fire pump on demand (EN12845), annual test due and power failure- available as open on fault, SPDT optional

• Auto Cooling, if the fire pump operates, the solenoid valve opens every 20 seconds for 2 seconds to cool the impeller ensuring functionality even when a property is unoccupied.

• Automotive technology, a black electrophoretic bonded paint finish is applied to the pipe work inside and out, giving better protection and an attractive finish

• LPCB approved fire rated power and alarm cables

Screen showing the weekly test has passed P1 pressure switch 1 went low pressure P2 pressure switch 1 went low pressure P1H pressure switch 2 returned healthy P2H pressure switch 2 returned healthy

Page 2: domestic fire sprinkler pump BOOST8n data sheets296016944.initial-website.co.uk/app/download/5785069798/domest… · Domestic fire sprinkler pump system complying with and significantly

FLOW CONTROL SYSTEM GRIFEN sprinkler solutions are a fire sprinkler product designer and manufacturer, not a pump manufacturer and we understand the regulations of systems and the implications on site, as a result we are able to provide systems that work for you and the end user. Our two unique flow controlled pump sets (B230-21 and B230-25/85) give the following benefits; • Cavitation of the pump is not possible • Q max is limited allowing tank size to be more easily calculated and reduced in size The product is configured for tank fed systems and is designed to give better functionality than BS9251 2014 and excellent competitiveness.

NEW BOOST8n FEATURES

• Weekly test failed (updated), now remembered on screen after power down, if the householder

turns off the power a small black square remains on the screen until the next weekly test is passed, the

fault alarm will stay on during power fail and return when power is reapplied

• Solenoid activation displayed every time the solenoid operates SOL appears on screen

• Flow switch pre wired with plc controlled delay and visual LCD 20 second counter, when the

pump is latched and the flow counter reaches 20 seconds the fire alarm contact changes state,

This alarm operates when the fire pump is on demand reducing false alarms as required by BS9251

2014.

• FIRE ALARM silencing If filling/ refilling a system the fire alarm will trigger after 20 seconds of flow

but you can silence it very easily before it even operates, so no need to go off watch/ cause

disturbance), it can’t be silenced at any other time.

• ANNUUAL SERVICE force on the service facility can be forced on ahead of time allowing improved

planning of time

• ANNUAL SERVICE silencing, the annual service fault can be silenced for 2 weeks at a time

• Button depressed when the button is pressed an @ appears on screen allowing you to know for

certain the button is pressed and allowing accurate timing

TOWN MAIN BOOSTING BOOST8n can be configured for town main boosting. We need to know; • Flow rate from the main is higher than the pump can deliver • The static pressure of the main in order to set the pressure switch

correctly, please note if the main has a high static pressure we may have to fit a different pressure gauge and switch.

To use the town main you will need permission from the water board and fit a suitable non return valve on the incoming supply The solenoid will always dump water every week, as a responsible company we would recycle that waste water, we hope you will do the same The maximum pressure of the pump and main must be below 10 bars

OTHER CONSIDERATIONS Alarm obligations under BS9251:2014 Fault alarm required for:

• power failed (monitored by BOOST8n as standard) • automatic test failed (monitored by BOOST8n as standard) • Low water level (optional if you want us to monitor it, the fault will be

displayed on screen and transmitted on the fault signal) Must be heard or seen in occupied part of building. All electrically operated alarm devices should be capable of carrying out their function in the event of a complete failure of the mains electrical power supply.

Page 3: domestic fire sprinkler pump BOOST8n data sheets296016944.initial-website.co.uk/app/download/5785069798/domest… · Domestic fire sprinkler pump system complying with and significantly

STATUS INDICATORS AND ALARMS

Events are displayed on the LCD screen and the fault alarm covering the following conditions to

make fault finding simpler;

• Jockey stop/ start alarm - Check for possible leaks

• Weekly test failed pump, contactor, solenoid, pressure switch failure

• Weekly test passed— LCD only

• Fire pump latched (pump on demand EN12845)

• Annual service due/ failed– keeps the system in compliance annually, with your company name

and phone number

• Power supply warnings 230VAC failure (also 24VDC with optional tank low level

P U M P R U N &

F I L L I N G

P 1 P 2 F S L L

P U M P P U R G E D

P U M P

W I L L

S T A R T

P 1 P 2

A start up screen gives anyone the chance to switch off if not purged/ valves open etc

When the pump starts it displays this screen (right) during filling if any input device is unhealthy it will display in real time and extinguish when healthy. • P1 pressure switch number 1 • P2 Pressure switch number 2 • FS flow switch and its operational

time

SET – UP AND SELF COMMISSIONING

The pump will run until both pressures are healthy and there is no more flow. The filling sequence will stop after 2 minutes, enabling the system to go into auto mode, enabling the fault alarm to be active if needed

The product keeps a count of the number of times it starts as a jockey pump. This aims to give pre failure warnings due to any system or product leaks. The jockey counter resets every hour if less than 8 starts have occurred. The system will keep a count of the number of times jockey limit has been reached, shown in the bottom right of the screen, it can not be cleared

A U T O M O D E

S Y S T E M O K

1 8 / 0 5 / 2 0 1 5

A U T O M O D E

J O C K E Y N O 1

T I M E 5 / 8

The jockey pump function is operational for the first time this hour, it has run for 5 of its 8 second run time (centre below)

When the system is OK, the time and date flash intermittently. The product’s weekly test is time and date stamped by this clock.

NORMAL OPERATION

A U T O M O D E

J O C K E Y

L I M I T

1

If the jockey pump operates more than 8 times in an hour JOCKEY LIMIT appears on the screen and fault alarm and screen can be cleared

The fire signal will trigger after 20 seconds of continuous flow, the fire signal can be disabled for the fill period which is 2 minutes. A new feature brings the product out of fill mode ensuring the pump could latch and give the fault alarm if necessary.

Page 4: domestic fire sprinkler pump BOOST8n data sheets296016944.initial-website.co.uk/app/download/5785069798/domest… · Domestic fire sprinkler pump system complying with and significantly

GRIFEN sprinkler solutions Tel: +44 (0)1625 575514 [email protected] www.grifen.co.uk

The system is in automatic mode, but the last weekly test failed The cause of the failure was P1. The system can also indicate P2 failure or both. P1 or P2 will fail if they don’t go unhealthy during the solenoid drain, they must be healthy at the end of the pump run sequence, The black square in the corner indicates this weekly test has failed. If the power is cycled and this square is on the screen, the last test failed. The square will only extinguish and the alarm clear when a successful test is completed. A weekly test will always repeat the next week, whether it passed or failed

The pump can be tested manually at any time (by following a simple step, the auto test will then be repeated) NB If service is due on screen a 6 minute service run will take priority, the auto test will still take place. To perform a manual on demand weekly test a successful service must be performed first.

THE AUTOMATIC WEEKLY TEST SUPASSING BS 9251 2014 BASED ON EN12845 PRINCIPALS

• TESTED AUTOMATICALLY every Monday at 10am • PRESSURE DROP TEST PEFORMED (EN12845) • 2 NORMALLY CLOSED PRESSURE SWITCHES TESTED ON EACH PUMP (EN12845) • ALARM IN FAILURE OR POWER DOWN • SIMPLE RECORD KEPT IF ALL CONDITIONS ARE NOT HEALTHY • ON DEMAND WEEKLY TEST AT ANY TIME REQUIRED

A U T O M O D E

S E R V I C E D U E

1 9 / 0 5 / 2 0 1 5

When an annual service is due the screen will scroll with the purchasers name and phone number when this occurs the general alarm will change state. To reset the annual service (beyond silencing) screen and alarm a successful test must be carried out. The annual test must check the correct function of the pump and all the switches. If it passes the unit will warn again in 12 months, if fails it will alarm and must be repeated and pass to clear the fault

P U M P L A T C H E D

+ F I R E A L A R M

P 1 F A U L T S O L

P 1 F S 2 0

PUMP LATCHED (fault alarm condition changed state),(EN12845 - fire pump on demand) the pump will now run continually until switched off at the mains +FIRE ALARM indicates the flow switch has been flowing for 20 seconds, the fire alarm signal will now have changed state SOL The solenoid is cooling the pump P1 fault (could also indicate P2 or both) this indicates which pressure switch was unhealthy when the pump latched after the jockey sequence P1 (bottom row) indicates P1 is currently at low pressure (could also indicate P2)

A U T O M O D E

W E E K L Y T E S T

F A I L P 1

WEEKLY TEST

FIRE PUMP AND ALARMS

ANNUAL SERVICE

SERVICES to be carried out by fire sprinkler companies, ensuring ongoing compliance with BS9251 2014. If an

annual service is not carried out the system will still function as normal.

At any time when the annual test is carried out correctly the alarm will silence for one year. The pump system

can be forced to do an annual service before it is due, BOOST8n will call for a service in 1 year regardless of

whether it is forced on or not

• If the pump is switched off the power failed alarm will operate.

• When power is restored the device will remember its last annual status and operate the alarm if a test

remains due.

• The sprinkler system can remain pressurised at all building levels when maintenance is being carried out.

• The flow test can be carried out on the pump only ensuring the motor and impeller are capable of the duty at

the correct pressure, ignoring any hydrostatic head.

Page 5: domestic fire sprinkler pump BOOST8n data sheets296016944.initial-website.co.uk/app/download/5785069798/domest… · Domestic fire sprinkler pump system complying with and significantly

SPECIFIERS GUIDE TO UNIQUE FEATURES

• WEEKLY PRESSURE DROP TEST PEFORMED (as EN12845) • WEEKLY TEST FAILURE REPORTED with on screen indication as to the cause • BACKUP PRESSURE SWITCHES wired (as EN12845) • LCD SCREEN • PUMP ON DEMAND AUTO COOLING (this feature cools the pump in the case of people being

away from the house/ it has saved many pumps in the field over the years) • JOCKEY PUMP MONITORING • PLC WITH ELCTRONICALLY CONTROLLED FLOW SWITCH GENERATED FIRE ALARM AND

VISUAL TIME COUNTER, complete with silence facility on initial fill • ANNUAL SERVICE WARNING • ANTI TAMPER ALARMS, (remembers service due and weekly test failed after power down until

they are satisfied, also alarms when switched off)

GRIFEN sprinkler solutions Tel: +44 (0)1625 575514 [email protected] www.grifen.co.uk

P U M P L A T C H E D

+ F I R E A L A R M

P 1 F A U L T S O L

P 1 F S 2 0

Below: Screen showing FS20 with a PLC counter and super accurate electronic delay SOL shows the solenoid is active in cooling or weekly test

Below; Prewired flow switch with LPCB approved FP200 fire rated cable with super accurate PLC controlled time delay

PLC technology requires no input or intervention when monitoring your fire sprinkler system. Where alarms are referred to volt free contacts are provided, these must be connected to suitable battery backed up alarms on site. We reserve the right to make technical adjustments to the specifications, we are happy to discuss site specific modifications/ technical improvements. FLOWST8FLOWST8FLOWST8FLOWST8n n n n offers higher flow rates and pressures for

residential applications, local mist system protection, suction lift

capability. We also manufacture integrated duty/ backup pumps and

supply uninterruptable power systems.

DUPLIC8 offers either 2 x 1/2 or 2 x full duty fully integrated

intelligent pump package

We also manufacture low pressure water mist pump systems

PRODUCT OPTIONS

• Your scrolling service message with your telephone number

(included as a no cost option)

• Monitored valves

• Integrated battery backed up fault and fire alarm system, we can

manufacture this as a complete turnkey kit, please contact us if

you would like us to bring this to market

CHOOSING YOUR PUMP We are here to help, please feel free to call and ask for advice. We have laid out all the BOOST8n pumps on one easy read graph (page 7), the following pages give the three variations with finer detail including electrical data etc. Dont forget you now need to use a fuse of high rupturing capacity, MCBs are not permitted

Page 6: domestic fire sprinkler pump BOOST8n data sheets296016944.initial-website.co.uk/app/download/5785069798/domest… · Domestic fire sprinkler pump system complying with and significantly

BOOst8n series

Standard BOOST8n BOOST8n options BOOST8n high flow

B230-25/85 85 l/min @ 2.5 bar

B230-35 100 l/min @ 3.5 bar

BH230-26 120 l/min @ 2.6 bar

B230-21 100 l/min @ 2.1 bar

B230-36 100 l/min @ 3.6 bar

BH230-38 120 l/min @ 2.8 bar

B230-30 100 l/min @ 3 bar

B230-44 100 l/min @ 4.4 bar

BH230-47 120 l/min @ 4.7 bar

B230-38 100 l/min @ 3.8 bar

B230-51 100 l/min @ 5.1 bar

BH230-53 120 l/min @ 5.3 bar

Grifen sprinkler solutions

Page 7: domestic fire sprinkler pump BOOST8n data sheets296016944.initial-website.co.uk/app/download/5785069798/domest… · Domestic fire sprinkler pump system complying with and significantly

Pre

ssu

re (

bar)

Flow Rate (litres/min)

B230-25/85 85 l/min @ 2.5 bar

230V

B230-21 100 l/min @ 2.1 bar

230V

B230-30 100 l/min @ 3.0 bar

230V

B230-38 100 l/min @ 3.8 bar

230V

BOOST8n series

9.6

9.6

9.6

13.9

Model Duty Voltage Full load current

(amps)

Kw

1.5

1.5

1.5

2.2

Inlet

1.25”

1.25”

1.25”

1.5”

Outlet

1”

1”

1”

1”

Boost8n delivery data

GRIFEN sprinkler solutions

Page 8: domestic fire sprinkler pump BOOST8n data sheets296016944.initial-website.co.uk/app/download/5785069798/domest… · Domestic fire sprinkler pump system complying with and significantly

Pre

ssu

re (

bar)

Flow Rate (litres/min)

BH230-26 120 l/min @ 2.6 bar

230V

BH230-37 120 l/min @ 3.7 bar

230V

BH230-47 120 l/min @ 4.7 bar

230V

BH230-53 120 l/min @ 5.3bar

230V

BH series

7.8

8.7

13

13

Model Duty Voltage Full load current

(amps)

Kw

1.3

1.5

2.2

2.2

Inlet

1.25”

1.25”

1.25”

1.25”

Outlet

1”

1”

1”

1”

Boost8n BH pumps

GRIFEN sprinkler solutions

Page 9: domestic fire sprinkler pump BOOST8n data sheets296016944.initial-website.co.uk/app/download/5785069798/domest… · Domestic fire sprinkler pump system complying with and significantly

0.00

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

9.00

0 20 40 60 80 100 120 140

Pre

ssu

re (

bar)

Flow Rate (litres/min)

B230-35 100 l/min @ 3.5 bar

230V

B230-36 100 l/min @ 3.6 bar

230V

B230-44 100 l/min @ 4.4 bar

230V

B230-51 100 l/min @ 5.1 bar

230V

BOOST8n options

7.3

7.8

7.8

8.7

Model Duty Voltage Full load current

(amps)

Kw

1.1

1.3

1.3

1.5

Inlet

1.25”

1.25”

1.25”

1.25”

Outlet

1”

1”

1”

1”

Boost8n option pumps

GRIFEN sprinkler solutions

Page 10: domestic fire sprinkler pump BOOST8n data sheets296016944.initial-website.co.uk/app/download/5785069798/domest… · Domestic fire sprinkler pump system complying with and significantly

Technical Specifications

Model Flow at duty point Qmax H max VAC kW Full Load Current (Amps)

inlet outlet test Suction centre line (mm)

B230-21 100l/min @ 2.1 bar 112 l/min 5.0 bar 230 1.5 9.6 1.25” 1” 3/4” 115

B230-25/85 85 l/min @ 2.5 bar 102 l/min 5.0 bar 230 1.5 9.6 1.25” 1” 3/4” 115

B230-30 100l/min @ 3.0bar 130 l/min 5.0 bar 230 1.5 9.6 1.25” 1” 3/4” 115

B230-38 100 l/min @ 3.8 bar 150 l/min 5.4 bar 230 2.2 13.9 1.5” 1” 3/4” 140

B230-35 100l/min @ 3.5 bar 120l/min 6.3 bar 230 1.1 7.3 1.25” 1” 3/4” 166

B230-36 100 l/min @ 3.6 bar 130 l/min 5.8 bar 230 1.3 7.8 1.25” 1” 3/4” 90

B230-44 100l/min @ 4.4 bar 130l/min 6.9 bar 230 1.3 7.8 1.25” 1” 3/4” 90

B230-51 100 l/min @ 5.1 bar 130 l/min 8.1 bar 230 1.5 8.7 1.25” 1” 3/4” 90

BH230-26 120 l/min @ 2.6 bar 165 l/min 3.6 bar 230 1.3 7.8 1.5” 1” 1” 90

BH230-37 120 l/min @ 3.7 bar 205 l/min 4.8 bar 230 1.5 8.7 1.5” 1” 1” 90

BH230-47 120 l/min @ 4.7 bar 212 l/min 6.0 bar 230 2.2 13 1.5” 1” 1” 90

BH230-53 120 l/min @ 5.3 bar 220 l/min 7.2 bar 230 2.2 13 1.5” 1” 1” 90

WHO WE ARE

GRIFEN sprinkler solutions were started in 1999 as a sole trader, we became a limited company some 8 years later, we are an innovative provider of electro mechanical sprinkler products

We design all our own products and software and we are happy to make changes/ develop products which you may require, our in-house capabilities are all value added UK skills

Our ethos is “improve where possible” you will see from this new software package that this is action and not just words, we want to make things better.

The testing of our products at design stage is based on the principals of introducing failures and mitigating against them wherever possible, you may not be aware of those details, but they are there and are likely to be unique product features which give robustness and reliability for your system.

Example, we set out with the idea “what are we trying to do?” that has resulted in;

• backup pressure switches—not required but the rules could be critical one day

• Failsafe wiring of the pressure switches– not covered by rules but could be critical one day

• Uncommanded starts; we provide pump cooling, we know people leave houses unattended, if a faulty cable starts and runs the pump it could be destroyed on your return or worse, this feature has save countless pumps from burning out, and leaves the pump available for fire fighting if required

By calling us you will receive technical support to guide you through any problems you may have

Please give us a call and arrange to visit our demo room where you can try these features for yourself

GRIFEN sprinkler solutions Tel: +44 (0)1625 575514 [email protected] www.grifen.co.uk