distributed amplifier unit (dau) (eesdau100) emergency ... mr1... · distributed amplifier unit...

42
Emergency Evacuation System Distributed Amplifier Unit (DAU) (EESDAU100) Emergency Microphone All Call (EMA) (EESEMA) Installation and Commissioning Manual Complies with EN54-16:2008 EN54-4:1997 & A1:2002 &A2:2006 Power ON System FAULT General FAULT Emergency Emergency Microphone Emergency Evacuation System Distributed Amplifier Unit 0832-CPR-F0111 714N/01 Complies with EN54-16:2008 EN54-4:1997 & A1:2002 &A2:2006 Emergency Evacuation System Distributed Amplifier Unit 0832-CPR-F0111 714N/01

Upload: doankien

Post on 09-Mar-2018

219 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

Emergency Evacuation System

Distributed Amplifier Unit (DAU) (EESDAU100) Emergency Microphone All Call (EMA) (EESEMA)Installation and Commissioning Manual

Complies with EN54-16:2008EN54-4:1997 & A1:2002 &A2:2006

Power ON

System FAULT

General FAULT

Emergency

Emergency Microphone

Emergency Evacuation SystemDistributed Amplifier Unit

0832-CPR-F0111 714N/01

Complies with EN54-16:2008EN54-4:1997 & A1:2002 &A2:2006

Emergency Evacuation SystemDistributed Amplifier Unit

0832-CPR-F0111 714N/01

Page 2: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com 2

Contents

1. INTRODUCTION....................................................................................................................................................................................................................... 4

1.1 System Description........................................................................................................................................................................................................ 4

2. VoCALL EMERGENCY EVACUATION SYSTEM (EES) DAU.................................................................................................................................. 5

3. VoCALL EMERGENCY EVACUATION SYSTEM (EES) EMA................................................................................................................................. 6

4. SUITABILITY............................................................................................................................................................................................................... 7

5. PRIORITIES.................................................................................................................................................................................................................. 8

6. OPERATION................................................................................................................................................................................................................. 8

7. INDICATION AND CONTROLS................................................................................................................................................................................... 9

7.1 Vocall Emergency Evacuation System (EES) DAU Operation ........................................................................................................................ 9 7.2 Vocall Emergency Evacuation System (EES) EMA Operation ........................................................................................................................ 9 7.3 Controls............................................................................................................................................................................................................................ 9 7.4 Indications............................................................................................................................................................................................................... 10

7.5 Maintenance.................................................................................................................................................................................................................. 10

8. IMPORTANT SAFETY INFORMATION.................................................................................................................................................................. 118.1 Anti-Static Handling Guidelines.............................................................................................................................................................................. 11

9. UNPACKING THE UNIT........................................................................................................................................................................................... 129.1 Preperation..................................................................................................................................................................................................................... 129.2 Siting Vocall Emergency Evacuation System (EES) DAU And Emergency Evacuation System EMA.............................................. 139.3 Mounting Vocall Emergency Evacuation System (EES) DAU........................................................................................................................ 13

10. CONNECTING VoCALL EMERGENCY EVACUATION SYSTEM (EES) DAU..................................................................................................... 13

10.1 Planning The Wiring ..................................................................................................................................................................................................1410.2 Mains Connection ......................................................................................................................................................................................................1410.3 Batteries ..............................................................................................................................................................................................................................1410.4 Safety Information...........................................................................................................................................................................................................1510.5 Battery Conection.........................................................................................................................................................................................................1510.6 Earth Fault Monitoring.............................................................................................................................................................................................1510.7 EMA Address and Priority Setting........................................................................................................................................................................15

11. VoCALL EMERGENCY EVACUATION SYSTEM (EES) DAU CONNECTIONS ................................................. .................................................15

11.1 Speaker Circuits .........................................................................................................................................................................................................1611.2 Safety Information .....................................................................................................................................................................................................1611.3 Wiring The Speakers .................................................................................................................................................................................................1611.4 Cable Length Chart.....................................................................................................................................................................................................17

12. NETWORK.................................................................................................................................................................................................................18

13. FIRE ALARM INTERFACE.............................................................................................................................. ..........................................................19

14. MOMENTARY OPERATION....................................................................................................................................................................................20

15. FAULT OUTPUT RELAY............................................................................................................................................................................................20

16. PAGE INPUT................................................................................................................................................. .............................................................20

17. USING THIRD PARTY MICROPHONES.......................................................................................................... .......................................................20

18. MUSIC INPUT............................................................................................................................................... ............................................................20

Page 3: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

Contents

Contents

19. MENUS.................................................................................................................................................................................................................2119.1 Navigating The Vocall Emergency Evacuation System (EES) DAU Menu............................................................. ..................................2119.2 Access Level Menu List Format..............................................................................................................................................................................21

19.3 Menu Actions..............................................................................................................................................................................................................22

19.4 Inputting Text.............................................................................................................................................................................................................22

19.5 Status Display.........................................................................................................................................................................................................22

19.6 User Menu List......................................................................................................................................................................................................23

19.7 Accept Faults Menu............................................................................................................................................................................................2319.8 Current Fault Menus..................................................................................................................................................................................................2319.9 Panel Version Menu......................................................................................................................................................................................................2319.10 Panel Test Menu...........................................................................................................................................................................................................2419.11 Log In Menu...................................................................................................................................................................................................................2419.12 Back Menu..................................................................................................................................................................................................................2419.13 Manager Menu List..................................................................................................................................................................................................2519.14 Log Out........................................................................................................................................................................................................................2519.15 Music Volume Menu...................................................................................................................................... .........................................................2519.16 Page Volume Menu ................................................................................................................................................................................................2619.17 Silence Message Menu...........................................................................................................................................................................................2619.18 Manager Pin Menu..................................................................................................................................................................................................2619.19 Panel Reboot Menu........................................................................................................................................ .........................................................2719.20 Engineer Menu List..................................................................................................................................................................................................2719.21 Engineer Pin Menu........................................................................................................................................ ..........................................................2819.22 Message Test Menu....................................................................................................................................... ..........................................................2819.23 Panel Name Menu........................................................................................................................................... .........................................................2819.24 Messages Menu List....................................................................................................................................... ..........................................................2919.25 Message Latch................................................................................................................................................ ...........................................................2919.26 Message Name............................................................................................................................................... ...........................................................29

19.27 Menu Buzzer.................................................................................................................................................... ...........................................................3019.28 Device Setting Menu....................................................................................................................................... ........................................................3019.29 Emergency Volume Menu.............................................................................................................................. .......................................................3119.30 Network Menu List.......................................................................................................................................... .........................................................3119.31 Settings............................................................................................................................................................. ............................................................3219.32 DAU Preset Menu............................................................................................................................................ ..........................................................3319.33 Audio Input Preset Menu................................................................................................................................ .......................................................33

20. FAULT CODE AND DESCRIPTIONS..................................................................................................................................................................34-39

21. TECHNICAL SPECIFICATION............................................................................................................................................................................ 40-41

3

Page 4: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

Important Instructions

4

1. IntroductionVoice Alarm (VA) systems are the quickest way to evacuate the public and staff from a building.

Following fire detection, automated messages control the flow of people in stairwells and corridors allowing an orderly evacuation without panic. These messages are supplemented by spoken announcements from the fire service or management suite confirming the validity and need to leave the building.

This positive confirmation speeds evacuation and avoids the “false alarm” mentality reducing the risk of death from fire.

1.1 System DescriptionThe Emergency Evacuation System DAU (Distributed Ampli-fier Unit) and the Emergency Evacuation System EMA (Emergency Microphone All-call) form a simple distrib-uted Voice Alarm system. Each Emergency Evacuation Sys-tem DAU is a single zone Voice Alarm unit. A maximum of 32 Emergency Evacuation System DAUs and a maximum of 8 control microphones, which includes the Emergency Evacuation System EMA, can be connected via an audio and dual data bus network to form a distributed Voice Alarm system.

The network is dual redundant, with isolators on each device for both the audio and data, so a single short circuit or open circuit will not affect system operation. Failure of any node will only affect the zone that node serves.

The BS EN54-16:2013 optional functions with require-ments for the Emergency Evacuation System DAU that were assessed by LPCB are:

• Clause 7.6.2: A manual option to silence the Voice Alarm unit.

• Clause 7.7.2: A manual option to reset the Voice Alarm unit.

• Clause 8.3: Indication of faults related to the transmission path to the Cooper loop fire interface unit, which sits on the Cooper analogue addressable fire panel loop.

• Clause 12: Emergency Evacuation System EMA emergency microphone.

Page 5: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com 5

2. Emergency Evacuation System DAUEach Emergency Evacuation System (EES) DAU is a self- contained unit. It can be operated by any FACIE system via local opto-isolated inputs designed to be connected to sounder circuits.

Each Emergency Evacuation System DAU can be remotely operated through the network ports. A Emergency Evacuation System emergency microphone can be used for emergency paging, and manual operation of the three on-board emergency messages Evacuate, Alert, and Test.

Each Emergency Evacuation System DAU has a unique network address between one and thirty two.

In addition to the emergency functions, each Emergency Evacuation System DAU has a local paging input and a local background music input, both of which are over-ridden in emergency mode. A microphone used for non-emergency purposes can be attached to the local paging input for local paging.

The Emergency Evacuation System DAU has four LED indicators on the front panel: Power On (Green), System Fault (Yellow), General Fault (Yellow), and Emergency (Red). These are complimented with a two - line twenty character, backlit LCD module.

Menus on the Emergency Evacuation System DAU are accessed using four navigation buttons. The menu structures have three levels of access: User (access level 1 - no PIN), Manager (access level 2 - PIN protected), and Engineer (access level 3 - PIN protected).

The Emergency Evacuation System DAU network connections provide power to remote devices such as the Emergency Evacuation System EMA microphone. Each network port reports faults occurring on any of the network cable cores. The audio short and audio earth faults cause the operation of the associated audio isolator, preventing these faults affecting other nodes.

Resetting the Emergency Evacuation System DAU can be per-formed by a reset command issued by activating the external fire interface reset opto-isolated input, or manually via menu at Manager or Engineer access level.

Any fault on the Emergency Evacuation System (EES) DAU will cause the fault relay to activate. It is the responsibility of the FACIE to react to the fault triggered.

Important Instructions

Page 6: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com 6

Important Instructions

3. Emergency Evacuation System EMAThe Emergency Evacuation System EMA is an All Call emergency microphone designed to section 12 of EN54-16 designed to be used with the Emergency Evacuation System DAU only.

Each Emergency Evacuation System EMA has a unique network address between one and eight.If two units are of the same priority, a first come, first served operation is observed. The winning microphone illuminates the Speak LED, and the losing one illuminates the Busy LED. If the system is in use by a lower priority microphone, the Busy LED on the high priority will illuminate, and pulse at 1Hz to indicate that it can over-ride the currently used microphone, if required. If over-ridden, the Busy LED will illuminate on the lower priority unit, and the Speak LED will illuminate on the high priority microphone.

A pre-announcement chime is available on each Emergency Evacuation System EMA The chime can be selected as one, two or three notes, allowing different control points to identify themselves. This chime, if selected, is operated when the Speak LED illuminates and can be seen on the articulation meter. To help keep the speech level constant, a compressor limiter is provided in the audio signal processing. The bass level, treble level, output level, and chime level are adjustable for optimum balance.

The audio processing, address, priority and chime settings are restricted from user access with a hinged plate requiring a hex key to gain access, and access to the microphone is via a key lock door.

The Emergency Evacuation System EMA has four manual controls in addition to the PTT. These are buttons that trigger the Evacuate, Alert, and Test messages, and the Cancel message button. Beside each message button there is an LED to show operation of that message on one or more Emergency Evacuation System DAUs.

The Cancel message button will manually silence the VACIE and stop all messages until another fire condition is indicated, or the manual control buttons re-initiate a message.

The microphone contains a close-coupled, noise-cancelling capsule, which is fully monitored for open and short circuit. The audio chain has short circuit isolators that activate to isolate the line, and allow operation in the redundant direction. The data network is protected for open, short and stuck data, so a single network fault will not affect operation.

The Emergency Evacuation System EMA all call emergency microphone is housed in the same enclosure type as the Emergency Evacuation System DAU, with a clear front window and fire key lock preventing unauthorised access to the microphone and controls.

Page 7: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com 7

Important Instructions

4. SuitabilityVoice Alarm systems are recommended for all public buildings and multi-story buildings over four floors by BS9999 and Building Regulations Document B allows smaller evacuation stairwells in buildings with Voice Alarm fitted.

In public buildings it is not possible to fire drill the public, as they visit the premises infrequently, so systems such as Voice Alarms save valuable time in evacuating the building.

The use of phased messages in multi-story buildings prevents over-crowding in stairwells and at exits, thus preventing secondary injuries. In phased evacuation, the floor in fire receives the evacuate message. The floor above and the floor below receive an Alert message preparing them for evacuation.

In more complex scenarios the use of multiple Alert and Evacuate messages can be beneficial, with messages telling the evacuees that they are going the right way, and messages asking people to make way for people leaving evacuated areas. These additional messages can dramatically speed up the evacuation process, especially in malls and large airport environments.

Emergency Evacuation System DAU has been developed to replace talking sounders in many Voice Alarm applications, and is available in several forms. The Emergency Evacuation System DAU is a complete Voice Alarm system in a single wall mount box which is complete with messages, fire interface, dual 50W monitored amplifiers, EN54-4 compliant power supply, monitored battery charger and the ability to connect non-monitored paging and music directly.

The Emergency Evacuation System DAU has been developed to draw the minimum of current in standby conditions and mutes the music and low priority paging when the AC supply fails, reducing quiescent current to 60mAH, and thus allowing the use of 5AH commodity SLA batteries for full compliance with BS 5839-8.

Connection to fire alarm systems could not be simpler. The Emergency Evacuation System DAU has a built in independent Alert and Evacuate inputs that can be connected to reverse monitored sounder circuits directly. Once activated, the fire signals need to be de-latched by the Reset (Silence) input. For retrofit to systems with relays, a protected 24V auxiliary supply is available on the page port connector.

The speaker lines are monitored using a continuous low current DC system that works with the audio playing. Speaker faults reported are open, short and earth faults. Each speaker fitted to Emergency Evacuation System DAU must have a DC blocking capacitor fitted. The use of DC monitoring allows all cable types (MICC and soft skin) to be used with the system.

Music sources can be plugged directly into the Emergency Evacuation System DAU. The music level can be set using the menu system. When used with a paging microphone, the music mutes instantly and restores gently after paging.

Page 8: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com 8

Important Instructions

5. PrioritiesThe Emergency Evacuation System DAU has fixed priorities for the audio and control inputs.

Emergency Evacuation System EMA Emergency Microphone in Priority Mode has the highest priority input on the system, designed to be used by the controlling officer.

Emergency Evacuation System EMA Emergency Microphone in Secondary Mode has the second highest priority input on the system, designed to be used by a secondary control point such as the security office.

External Paging Microphone in Emergency Mode has the third highest priority input on the system, designed to be used by other responsible staff.

Message Generator has three messages. All messages latch until reset. Messages are reset from the Emergency Evacuation System DAU Manager/Engineer menus, from the Cancel message button on the Emergency Evacuation System EMA microphone, or by the RESET input from the Fire Alarm input. Messages are prioritised in the following order:

EVACUATE: Triggered from the fire alarm interface or from the Emergency Evacuation System EMA, highest priority message.

ALERT: Triggered from the fire alarm interface or from the Emergency Evacuation System EMA, second highest priority message.

TEST: Triggered from the front panel or from the Emergency Evacuation System EMA, lowest priority message.

Page Input in Page Mode is designed for non-emergency functions such as reception paging. This input has a higher priority than the test message, and other non-emergency messages, but has a lower priority than any emergency input.

Music Input is the lowest priority input and is automatically selected when no other input is exerting a priority. If music is not used, set the level control in the music volume menu to mute.

6. OperationThe Emergency Evacuation System DAU is fully automatic in operation. Manual control can be accomplished via the Manager menu or the Engineer menu.

The Emergency Evacuation System DAU has fully compliant fault monitoring when correctly installed and commissioned. Contact Service if any status indicators are illuminated YELLOW. This is also indicated by a Sounder or Voice Alarm fault on the Fire Alarm Panel if properly commissioned.

Page 9: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com 9

Operating Instructions

7. Indications and Controls

7.1 DAU OperationThe Emergency Evacuation System DAU has four indicators, a four button navigation system and a two-line, twenty character backlit LCD for all configuration functions and status display.

Power On Illuminates when a power source is available and the unit is energised.

System Fault Illuminates when a watchdog or checksum event occurs at the local unit.

General fault Illuminates when any fault is detected by the local unit.

Emergency Illuminates when any emergency message is being broadcast on any unit on the network system, including the local unit.

7.2. EMA OperationThe Emergency Evacuation System EMA has three push buttons with associated LEDs to initiate messages, and a push button to cancel messages and a fist microphone with push to talk button which addresses all Emergency Evacuation System DAU units present (as an ALL CALL). The status LEDs indicates the Fault and Audio state of the unit.

7.3 ControlsPTT: Push to Talk (located on the side of the Microphone) Pressing this button will cause the microphone audio to go live to all Emergency Evacuation System DAU units on the network.

Evacuate: Pressing this button broadcasts the Evacuate message to all Emergency Evacuation System DAU units on the network. If the Evacuate message is playing on any Emergency Evacuation System DAU, the red LED will be illuminated if a message has been cancelled and is on its last cycle, the red LED will flash.

Alert: As Evacuate, but the message broadcast is the Alert message, and the yellow LED is illuminated.

Test: As Evacuate, but the message broadcast is the Test message, and the green LED is illuminated.

Cancel: Pressing this silences all messages on the system, causing the associated message LEDs to start flashing till cycle ends.

Complies with EN54-16:2008

EmergencyEvacuationSystem

Emergency Microphone

Complies with EN54-16:2008

EmergencyEvacuationSystem

Emergency Microphone

Complies with EN54-16:2008EN54-4:1997 & A1:2002 &A2:2006

Power ON

System FAULT

General FAULT

Emergency

Emergency Evacuation SystemDistributed Amplifier Unit

0832-CPR-F0111 714N/01

VoCALLVoice Alarm

System

Evacuate

Alert

Test

Cancel

PowerFault

SpeakBusy

Page 10: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

Operating Instructions

10

7.4 IndicationsPower: The unit is receiving power from the network.

Fault: A fault condition exists on this unit that is relayed to all Emergency Evacuation System

DAUs on the network.

Speak: The PTT switch has been activated, and speech can now take place.

Busy: The PTT has been activated, and the system is busy with someone of equal or higher priority.

VU Meter: Indicates the volume of the announcement.

7.5 MaintenanceIt is the manufacturers recommendation that this system be maintained in accordance with the current version of BS5839-8. There may be other recommendations from you insurer or accreditation body; please check these before agreeing to a maintenance plan

Page 11: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

Installation Instructions

11

8. Important Safety InformationThis Equipment must only be installed and maintained by suitably skilled and competent person. This Equipment is defined as Class 1 in EN60065 (Low Voltage Directive) and must be EARTHED.

Each DAU requires a 3A spur, returning to a breaker clearly marked Voice Alarm DO NOT TURN OFF. If the units are distributed around a site, it is essential all units are on the same mains phase, as they are classified TEN 230V, powering from different phases can mean a 440V potential can be present in a unit during a major fault incident.

CAUTION

WARNING

INDOOR USE ONLY

NO USER SERVICEABLE PARTS

THIS UNIT MUST BE EARTHED

TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS UNIT IN RAIN OR MOISTURE

SHOCK HAZARD- ISOLATE BEFORE OPENING

WARNING

WARNING

WARNING

8.1. Anti-static Handling Guidelines

MAKE SURE THAT ELECTRO-STATIC HANDLING PRECAUTIONS ARE TAKEN IMMEDIATELY BEFORE HANDLING PCBS AND OTHER STATIC SENSITIVE COMPONENTS.

BEFORE HANDLING ANY STATIC-SENSITIVE ITEMS, OPERATORS SHOULD GET RID OF ANY ELECTROSTATIC CHARGE BY TOUCHING A SOUND SAFETY EARTH, SUCH AS A RADIATOR. ALWAYS HANDLE PCBS BY THEIR SIDES AND AVOID TOUCHING ANY COMPONENTS. PCBS SHOULD BE STORED IN A CLEAN, DRY PLACE THAT IS FREE FROM VIBRATION, DUST AND EXCESSIVE HEAT.

STORING THE PCBS IN A SUITABLE BOX WILL ALSO GUARD THEM AGAINST MECHANICAL DAMAGE.

CAUTION

Page 12: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

Installation Instructions

12

9. Unpacking the UnitRemove the Emergency Evacuation System DAU from its packing, and check the contents against the following list: Emergency Evacuation System DAU control Unit

Emergency Evacuation System DAU & EMA Installation and Maintenance manual (this document) Emergency Evacuation System DAU & EMA User Guide & logbook

Accessory pack with the following contents:-

2 off 9KΩ 1W end-of-line Resistors

Crimped Battery Link Lead

Inside the unit, there should be:

1 off 3 way music connector

4 off 4 way network connectors

1 off 5 way page microphone connector

1 off 6 way fire interface connector

1 off 2 way fault relay connector

2 off 2 way inverted speaker connectors

If there are any Items missing please contact your supplier, quoting the unit serial number and the name on the packing list enclosed so the situation can be rectified.

9.1 PreparationBefore mounting the Emergency Evacuation System DAU on the wall it is advisable to remove the cable knockouts. Decide how the wiring will be brought into the unit and remove the required knockouts for cable entry. If a knockout is removed, fill the hole with a fire rated gland compliant with BS5839-8.

There are 18 knockouts on the top face available for use. 17 of these knockouts are used for speaker network A, speaker network B, fault relay, fire alarm interface, paging microphone, music input, network in, and network out. The 18th knockout on the top face is used for mains only. Mains SHOULD NOT enter the box by any other hole.

Unused knockouts must be left unopened to comply with the LVD. Accidentally knocked out holes should be blanked off.

Page 13: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

9.2 Siting Emergency Evacuation System DAU and VoCALL Voice EMATo comply with standards, the Emergency Evacuation System DAU should be sited in areas of low fire hazard, so that the equipment is unlikely to be involved in a fire before adequate warning has been given. It needs to be located in a readily accessible location. The ambient light level in the vicinity should be such that the visual indications can be clearly seen, controls easily operated, and the instructions and legends easily read. The ambient noise level in the vicinity should not prevent the audible indications from being heard. The ambient temperature should not fall below -5˚C, and should not exceed 40˚C. The ambient humidity should not exceed 93%.

The Emergency Evacuation System EMA should be sited in an appropriate location where both staff and fire-fighters can manage an emergency situation. The Emergency Evacuation System EMA should be sited where the audible indication from third party equipment will not interfere with the use of the microphone. The Emergency Evacuation System EMA should be sited within the same fire zone as a Emergency Evacuation System DAU, at a distance of no more than 3m. The ambient temperature should not fall below -5˚C, and should not exceed 40˚C. The ambient humidity should not exceed 93%.

9.3 Mounting Emergency Evacuation System DAUBefore mounting the DAU on the wall it is advisable to remove the cable knockouts.

The Emergency Evacuation System DAU weighs 10kg with batteries, so care should be taken to securely mount the unit on stud walling.

10. Connecting Emergency Evacuation System DAUTo comply with Electro-Magnetic Compatibility (EMC) regulations and to reduce the risk of electrical interference in the system wiring, the use of fire-resistant screened cables is recommended throughout the installation.

All wiring should come into the enclosure via the knockouts provided and be fixed tidily to the relevant terminals. For an overview of the connections required for the fire alarm interface, loudspeakers, network, and paging/background music equipment, please refer to the relevant sections later in this manual.

Note that correct cable glanding is essential and due regard should be paid to any system specifications which demand a certain cable type, providing it meets the appropriate national wiring regulations.

Installation Instructions

13

Page 14: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

Installation Instructions

14

10.3 BatteriesThe Emergency Evacuation System DAU requires two number 12V 5Ah sealed lead acid batteries to provide backup power in the event of mains failure as defined in BS5839-8 for 24 hours standby and 30 minutes operation.

For 72 hour standby and 1 hour operation, two number 12V 17Ah batteries are required. These will need to be fitted in an external battery enclosure. The monitored charger in the Emergency Evacuation System DAU is capable of charging and monitoring these batteries. NOTE: This option has NOT been assessed by LPCB, and thus is NOT certified for use.

Main Distribution

Board

VoCALLVoice DAU

3A

>3mm

>0.75mm2 <2.5mm2

10.1. Planning the WiringAll System wiring should be installed to meet the appropriate parts of BS 5839-8(2013), BS EN 60849(1998) and BS 7671(Wiring Regulations). Other national standards of installation should be adhered to where applicable.

Do not test wiring using an insulation tester with any equipment or speakers connected, as the 500 Volt test voltage will destroy these devices totally.

You must observe local wiring regulations. Do not run SELV and LV cables in the same enclosure without adequate insulation between them.

10.2 Mains ConnectionEach Emergency Evacuation System Voice DAU requires a 3A spur, returning to a breaker clearly marked “Voice Alarm DO NOT TURN OFF”. If the units are distributed around a site, it is essential all units are on the same mains phase, as they are classified TEN 230V, powering from different phases can mean a 440V potential can be present in a unit during a major fault incident.

Page 15: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

Installation Instructions

15

10.4. Safety Information

BATTERIES

SEALED LEAD ACID BATTERIES CONTAIN SULPHURIC ACID WHICH CAN CAUSE BURNS IF EXPOSED TO THE SKIN, THE LOW INTERNAL RESISTANCE OF THESE BATTERIES MEANS LARGE CURRENTS WILL FLOW IF THEY ARE ACCIDENTALLY SHORT CIRCUITED, CAUSING BURNS AND A RISK OF FIRE- EXERCISE CAUTION WHEN HANDLING BATTER-IES.

POWER UP PROCEDURE

ALWAYS APPLY MAINS POWER BEFORE CONNECTING BATTERIES, DO NOT COMMISSION VoCALL COMPACT ON BATTERIES, AS THE HIGH INRUSH CURRENT REQUIRED BY THE POWER SUPPLY MAY RUPTURE THE BAT-TERY FUSE.

ALWAYS CONNECT THE POSITIVE (RED +) TERMINAL FIRST.

POWER DOWN PROCEDURE

DISCONNECT THE BATTERIES BEFORE REMOVING THE MAINS POWER; ALWAYS REMOVE THE NEGATIVE (BLACK – TERMINAL) FIRST.

CAUTION

OV

R L Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Au

dio

--

Au

dio

+

Pag

e

GN

D

Au

x 24

V

Res

et --

Res

et +

Ale

rt --

Ale

rt +

EV

AC

--

EV

AC

+

Co

m

NO

0V 100V

0V 100V

RX

--

RX

+

TX

--

TX

+

TX

-

TX

+

RX

--

RX

+

12V 5AHVRSLA Battery

12V 5AHVRSLA Battery

To PSULink Supplied

Music NetworkOut

NetworkIn

PagingInput

FireContacts

FaultRelay

SpeakersCct A Cct B

10.5. Battery Connections

10.6. Earth Fault Monitoring

Every DAU has an internal jumper located below the PSU connector (bottom right of the PCB) which controls the earth fault monitoring of the network. This jumper should only be left in place on one of the DAUs on the network. The DAU with the monitoring enabled should be the unit that will be visited in the event of a system fault being reported on the EMA or Fire Detection and Alarm System (FDAS).

10.7. EMA Address and Priority SettingThe EMA will arrive set as microphone address 1. If this is the only EMA on the network, then you do not need to change any settings. If there is more than 1 EMA on the network, then each will have to be set up with a unique address. This is done using the 4-switch block located on the left-hand side of the termination PCB inside the EMA.

The 4-switch block has 2 functions; setting the address of the EMA and setting the priority of the EMA.

Each EMA will need to have a different address set for the fault monitoring process.

The EMA with high priority will be able to take control of the audio announcement from any EMA set to low priority. We recommend that only 1 EMA on the network is set to “high priority” and that this EMA is located at the main CIE that will be visited in the event of a fire.

Please see the tables below for the addressing and priority settings. Please note that the when the switch is set in the left hand position, this is counted as OFF; the right hand position is counted as ON.

Switch 3 Switch 2 Switch 1 Address

OFF OFF OFF 1

OFF OFF ON 2

OFF ON OFF 3

OFF ON ON 4

ON OFF OFF 5

ON OFF ON 6

ON ON OFF 7

ON ON ON 8

Switch 4 Priority

OFF Low priority

ON High priority

The fourth switch is used to set the EMAs priority.

Page 16: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

11.1 Speaker CircuitsEach Emergency Evacuation System DAU has two speaker Circuits, A & B. Each output of the Emergency Evacuation System DAU can support 50W of speakers. This is typically five 10W speakers, twelve 4W speakers or thirty-three 1.5W speakers, or one hundred ½ W speakers.

4W speakers are generally fitted in noisy offices or reception areas, 1.5W speakers are usually used in corridors, and ½W speakers in small rooms or open plan offices.

11.2 Safety Information

SPEAKERS

SPEAKER CIRCUITS CARRY 100V AC.

POWER

DISCONNECT BEFORE SERVICING TO PREVENT SHOCK HAZ-ARD.

CIRCUITS

SPEAKER CIRCUITS ON EMERGENCY EVACUATION SYSTEM ARE DC MONITORED.

SUITABILITY

SUITABLE SPEAKERS FOR EMERGENCY EVACUATION SYSTEM DAU MUST HAVE A THERMAL FUSE TO DISCONNECT THE SPEAKER IF IT IS IN THE AREA IN FIRE, AND A DC BLOCKING CAPACITOR FITTED. TYPICALLY THE CAPACITOR IS 2.2UF 250V DC.

11.3 Wiring the SpeakersThe wiring goes through each speaker, with the last speaker having the 9KΩ end-of-line resistor.

CAUTION

Before connecting the speaker lines to Emergency Evacuation System DAU, count the number of speakers and note the tapping at which they are set. Most manufacturers will supply speakers at the maximum tapping, or at the half power tapping. This value should not exceed the 50W rating of the Emergency Evacuation System DAU for a single circuit.

It is desirable to have an impedance meter available to measure the AC load of the speaker circuit which will be connected to the Emergency Evacuation System DAU. The measurement on the impedance meter should not be lower than 200 Ohms at 1KHz.

To work out the load from the impedance meter reading use the following equation:

P=10,000/Z

Where

P is the power of the amplifier load

Z is the impedance in Ohms

Note: Once the speaker lines are tested, record the results and the location of the end-of-line devices in the User Log book supplied.

The lines should now be checked for the DC resistance between cores. This should read 9K Ohms if the wires from the Emergency Evacuation System DAU to the end-of-lines are complete.

The speaker lines should also be tested between each core and earth. This should be in excess of 100KΩ. If not, check the cabling. Record the results in the user logbook.

Speaker cables must be earthed to the safety earth connection point. Preferred types are screened soft skin cables such as FP200, although MICC can be used.

16

Installation InstructionsO

V

R L Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Au

dio

--

Au

dio

+

Pag

e

GN

D

Au

x 24

V

Res

et --

Res

et +

Ale

rt --

Ale

rt +

EV

AC

--

EV

AC

+

Co

m

NO

0V 100V

0V 100V

RX

--

RX

+

TX

--

TX

+

TX

-

TX

+

RX

--

RX

+

12V 5AHVRSLA Battery

12V 5AHVRSLA Battery

To PSULink Supplied

Music NetworkOut

NetworkIn

PagingInput

FireContacts

FaultRelay

SpeakersCct A Cct B

11. Emergency Evacuation System DAU Connections

Page 17: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

11.4 Cable Length ChartThe following table shows the maximum cable run to achieve a drop of no more than 1dB as required by BS5839-8. The table also takes into account high frequency losses which prevent systems performing to the requirements of BS EN 60849. This means the system needs to achieve a common intelligibility scale value equivalent to 0.5 STI (speech transmission index). This requires a bandwidth of 200Hz to 7kHz.

Note: MICC has shorter runs for the same cross section area due to the higher load capacitance of the cable and the effect this has on high frequency signals.

12. NetworkThe Emergency Evacuation System DAU is designed to network with the Emergency Evacuation System EMA fire microphone and other Emergency Evacuation System units to form a multi-zone Voice Alarm System, which is connected pin for pin as described below:

Network Out connects to Network In on the next device, and so on until the ring is complete.

Cable Type & Gauge Maximum Cable Length

10W 20W 50W Load Load Load

1mm Soft Skin 1500M 750M 300M

1.5mm Soft Skin 2000M 1000M 400M

2.5mm Soft Skin 4000M 2000M 900M

1mm MICC 300M 200M 100M

1.5mm MIC 500M 250M 150M

2.5mm MICC 700M 300M 200M

Emergency Evacuation System DAU Connections Emergency Evacuation System EMA Connections

17

Installation Instructions

Network Out

Network In

Net

Aud

io -

Net

Aud

io +

GN

D24

V O

ut

Net

Aud

io -

Net

Aud

io +

GN

D24

V O

ut

RX

- R

X +

TX +

TX +

TX -

TX -

RX

- R

X +

Network Out

Network In

Net

Aud

io -

Net

Aud

io +

GN

D24

V O

ut

Net

Aud

io -

Net

Aud

io +

GN

D24

V O

ut

RX

- R

X +

TX +

TX +

TX -

TX -

RX

- R

X +

Page 18: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

2 core FP200

2 core FP200

2 core FP200

2 core FP200

2 core FP200

2 core FP200

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

RX

--

RX

+

TX

--

TX

+

TX

--

TX

+

RX

--

RX

+

NetworkOut

NetworkIn

RX

--

RX

+

TX

--

TX

+

TX

--

TX

+

RX

--

RX

+

NetworkOut

NetworkIn

NetworkOut

NetworkIn

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

NetworkOut

NetworkIn

VoCALL Voice Device No1 VoCALL Voice Device No1

As shown in the diagram above, 2-core cables are used. The 2-core cables are:

• Power (24V Out, GND)

• Audio (Net Audio-, Net Audio+)

• Transmit device #1 (Tx+, Tx-) which connects to Receive device #2 (Rx+, Rx-)

• Receive device #1 (Rx+, Rx-) which connects to Transmit device #2 (Tx+, Tx-)

18

Installation Instructions

VoCALL Voice Device No 2VoCALL Voice Device No 1

2-core PH120

2-core PH120

2-core PH120

2-core PH120

2-core PH120

2-core PH120

Page 19: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

13. Fire Alarm InterfaceThe Emergency Evacuation System DAU has been designed to connect to virtually any fire alarm system from simple conventional systems, to complex analogue addressable loop systems.

The minimum fire alarm interface, as defined by BS 5839-8, is a monitored signal from the fire panel for Evacuate, a de-latch signal on reset or silence, and a signal from the Voice Alarm to the Fire Alarm Control and Indicating Equipment signalling a fault. The interface monitoring is the responsibility of the Fire Alarm system, and this is usually achieved by using sounder driver outputs from a conventional panel, or monitored sounder interfaces on an addressable loop.

The inputs to Emergency Evacuation System DAU are opto-isolated, and are designed for direct connection to polarised sounder drive outputs. In the normal monitored state, Emergency Evacuation System DAU expects to see between 0V and -33V on the inputs, and between +8V and +33V to trigger a message. To measure the voltage, use the meter black (-) lead on Alert- or Evac- and the meter red (+) lead on Alert+ or Evac+.

Once triggered, the inputs latch. Evacuate always overrides Alert. Since the Fire Alarm monitors this link and not the Voice Alarm, the Voice Alarm will not report a fault if the Alert contact is not used.

To silence messages, the reset connection must have +10 to +33V applied. This can be done from a relay which closes on fire panel reset or silence as shown below. The Alert or Evacuate fire trigger must be removed for Reset to work.

The fault output relay must be connected to the Fire Alarm Control and Indicating Equipment to provide a fault sounder in the event of a fault with the Emergency Evacuation System DAU, otherwise an external fault sounder must be provided to comply with BS5839-8.

NOTE: Messages will always play to the end of the current cycle when RESET. This is a requirement, not a fault.

In this scheme, Alert and Evac require a sounder circuit drive to trigger the message, and the Evac signal end-of-line is in series with the fault relay of Emergency Evacuation System DAU. If the Emergency Evacuation System DAU detects a fault, the fault output relay opens, removing the sounder circuit end-of-line, consequently indicating a sounder fault on the fire alarm system. Alternatively the fault output relay can be wired via a monitored input module to the fire alarm panel.

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

RX

--

RX

+

TX

--

TX

+

TX

-

TX

+

RX

--

RX

+

NetworkOut

NetworkIn

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

RX

--

RX

+

TX

--

TX

+

TX

-

TX

+

RX

--

RX

+

NetworkOut

NetworkIn

Res

et --

Res

et +

Ale

rt --

Ale

rt +

EV

AC

--

EV

AC

+

FireContacts

OV

R L Au

dio

--

Au

dio

+

Pag

e

GN

D

Au

x 24

V

Co

m

NO

Music PagingInput

FaultRelay

19

Installation Instructions

Page 20: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

14. Momentary OperationIf no reset output is available, and you have permission from the authorities or consultant, the Emergency Evacuation System DAU can be set for momentary operation. However this will not comply with the word of BS 5839-8. In this mode the messages will sound when there is a positive voltage across the Alert or Evac terminals. This is configured from the Messages settings menu.

15. Fault Output RelayThe Normally Open and Common contacts of the fault output relay are brought out on this connector. If the contacts are shorted together, this unit is HEALTHY.

16. Page InputThe paging input is an unmonitored line level input. Connect the PTT line to GND to operate. Once operated, paging will mute the music input. Once paging is complete, the music will return gently.

17. Using Third Party MicrophonesThird party microphones can be used with Emergency Evacuation System DAU as long as they can provide a volt free PTT contact, and a balanced line level (0dBV) audio output. A 24V 100mA feed is available on the page connector to provide power to an external microphone pre-amplifier to boost signals from microphone to line level.

Note: the Emergency Evacuation System DAU does not contain a chime generator. The microphone used must provide this if required.

The level of the paging microphone can be independently adjusted using the Page Volume menu.

NOTE: Use of a third party microphone for any emergency purpose is not permitted in LPCB approved installations.

18. Music InputThe music input is connected via a stereo pair. The Emergency Evacuation System DAU is mono in operation. The Left and Right signals are mixed together in the Emergency Evacuation System DAU. If a mono line signal is required, this can be provided to either input.

Music is automatically muted when mains fails in line with BS5839-8 to preserve battery life. The level of the Music can be independently adjusted using the music volume menu.

NOTE: If music is to be broadcast on the Emergency Evacuation System DAU, an appropriate PRS Licence should be obtained within the UK.

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

RX

--

RX

+

TX

--

TX

+

TX

-

TX

+

RX

--

RX

+

NetworkOut

NetworkIn

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

RX

--

RX

+

TX

--

TX

+

TX

-

TX

+

RX

--

RX

+

NetworkOut

NetworkIn

Res

et --

Res

et +

Ale

rt --

Ale

rt +

EV

AC

--

EV

AC

+

FireContacts

OV

R L Au

dio

--

Au

dio

+

Pag

e

GN

D

Au

x 24

V

Co

m

NO

Music PagingInput

FaultRelay

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

RX

--

RX

+

TX

--

TX

+

TX

-

TX

+

RX

--

RX

+

NetworkOut

NetworkIn

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

RX

--

RX

+

TX

--

TX

+

TX

-

TX

+

RX

--

RX

+

NetworkOut

NetworkIn

Res

et --

Res

et +

Ale

rt --

Ale

rt +

EV

AC

--

EV

AC

+

FireContacts

OV

R L Au

dio

--

Au

dio

+

Pag

e

GN

D

Au

x 24

V

Co

m

NO

Music PagingInput

FaultRelay

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

RX

--

RX

+

TX

--

TX

+

TX

-

TX

+

RX

--

RX

+

NetworkOut

NetworkIn

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

Net

Au

dio

--

Net

Au

dio

+

GN

D

24V

Ou

t

RX

--

RX

+

TX

--

TX

+

TX

-

TX

+

RX

--

RX

+

NetworkOut

NetworkIn

Res

et --

Res

et +

Ale

rt --

Ale

rt +

EV

AC

--

EV

AC

+

FireContacts

OV

R L Au

dio

--

Au

dio

+

Pag

e

GN

D

Au

x 24

V

Co

m

NO

Music PagingInput

FaultRelay

20

Installation Instructions

Page 21: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19. Menus

19.1 Navigating the Emergency EvacuationSystem DAU MenusAll functions of the Emergency Evacuation System DAU can be configured using the front panel LCD and the four navigation buttons (UP, DOWN, TICK and CROSS (x)).

The currently selected menu item is denoted by “>”, whether this be a menu from the menu list, or a menu item in a specific menu. In the case of text entry, the currently selected character will be underlined.

The UP button will scroll up through all possible options of the currently selected menu item.

The DOWN button will scroll down through all possible options of the currently selected menu item. The TICK button behavior depends upon item currently selected.

If the current item is an item in a menu list, it will show that selected menu.

If this is a item within a selected menu, it will move the cursor to the next menu item.

If this is menu action within a selected menu, it will execute the shown menu action. Menu actions are usually Next, Save, and Quit.

The CROSS button behavior depends upon the item currently selected.

If the current item is an item in the User menu list, it will return the operator to the status display.

If the current item is an item in the Manager or Engineer menu list, it will return the user to the Log out menu item.

If the current item is within a menu, it will exit that menu, returning the operator back to the menu list. If this menu is a configuration menu, it will discard all changes made.

When the Emergency Evacuation System DAU is powered up, it will always revert to the status display.

19.2 Access Level Menu List FormatThe menus have 3 access levels: User, Manager, and Engineer. The access levels determine which menus are accessible to the operator. Inaccessible menus are hidden from the operator. Each access level has the same format.

The top line shows the unit type, the current software version number, and the number of faults (!0 in this case showing there are no faults).

The bottom line shows the currently selected menu item.

Use the UP button to scroll up through all available menus for this access level.

Use the DOWN button to scroll down through all available menus for this access level.

Use the TICK button to show the currently selected menu.

DAU v1.11 0>Log In

21

Operating Instructions

Page 22: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19.3 Menu ActionsIn all configuration menus, the menu actions are displayed in the top right corner of the LCD. The menu actions are Next, Save, and Quit. If the cursor “>” is by a menu action, it can be changed by using the UP and DOWN buttons.

Pressing the TICK button will execute the selected menu action:

Next: moves cursor back to first menu item, or to next page, depending upon menu Save: stores data in working memory and configuration memory, then exits the menu Quit: exits the menu without storing the data

Pressing the CROSS button will exit the menu without storing the data.

19.4 Inputting TextAll text input on the Emergency Evacuation System DAU uses the same technique. The text to be edited is bracketed by “>” and “<”. This gives a visual key to the length of the text allowed. This length varies depending upon the menu.

When text entry is used, the current text for the entry is displayed. The first character is highlighted using an underscore. Use the UP and DOWN buttons to change this character, by scrolling the list of acceptable characters, as shown below.

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z 0 1 2 3 4 5 6 7 8 9 ~ Abcdefghijklmnopqrstuvwxyz’@?<>&#()+-=ÿ

Press the TICK button to move to the next character, or to move to the next menu item if on the last character.

Press the CROSS button to exit this menu, discarding any changes.

19.5 Status DisplayThe status display shows the panel name, the current fault status, and the current audio status.

The panel name is editable via menu accessible as an Engineer. This is usually location, installer, or area served.

The current faults status relates to the number of faults that have occurred on this unit and any network microphone, e.g. Emergency Evacuation System EMA.

If there are no faults, then a healthy banner is shown.

If there are any faults, then the number of faults is shown.

Press the tick key to show the User menu.

Eaton*Healthy* Music

EatonFaults:2 Music

22

Operating Instructions

Page 23: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19.6 User Menu ListThe User menu list allows the operator access to all menus available at access level 1.

The User menu list includes status menus and action menus. Accept faults may not be visible if so configured (see Accept faults menu).

19.7 Accept Faults MenuThis menu is only visible if there a fault has occurred that has not been accepted.

This menu is an action menu. It is used to accept faults that have occurred.

If a fault is present on the system, or a fault has appeared and gone when buzzer is set to latching, the fault buzzer will sound.

Pressing the TICK button will silence the buzzer. As long as a fault is present, the fault buzzer will beep once every 15 seconds. If the fault remains present for 8 hours, the fault buzzer will resound in accordance with BS 5839-8. Press the TICK or CROSS button to exit this menu.

If the Emergency Evacuation System DAU is in an access level 1 area, then it is recommended that this menu is not shown in the User menu by setting the User option in the Buzzer Settings menu to NO. This is to prevent an unauthorised user silencing the fault buzzer.

19.8 Current Faults MenuThis menu is a status menu. It displays one fault entry from the list of all current faults.

The top line shows the number of the current fault entry and the total number of faults. The bottom line shows the fault text for the current fault entry.

Use the UP and DOWN buttons to scroll through all fault entries. See Appendix A for a list of all faults.

Press TICK or CROSS to exit this menu.

19.9 Panel Version MenuThis menu displays the software version number and release date.

Press TICK or CROSS to exit this menu.

DAU v1.11>Log in

Accept FaultsCurrent FaultsPanel VersionPanel TestBack

Faults:6>Accept Faults

Faults:6*Faults Accepted*

Fault 6 of 23Amplifier A OC

V1.7.11Date: DD.MM.YY

23

Operating Instructions

Page 24: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19.10 Panel Test MenuThis menu is an action menu. It performs a panel indicator test.

Press the TICK button to execute the action selected.

START will start the panel indicator test. This will illuminate the general fault LED, the system fault LED, and the emergency LED in sequence. The buzzer will sound. The LCD is tested by filling the screen with block characters, and then deleting these block characters.

QUIT will exit this menu, stopping the panel indicator test if necessary.

19.11 Log in MenuThis menu is an action menu. It allows the operator to enter the PIN to gain access to either the Manager or Engineer menus.

The PIN is a 4 digit number. The current digit is shown, with the other digits hidden behind an asterisk. The UP and DOWN buttons are used to change the currently selected digit.

The TICK button is used to move to the next digit. If on the last digit, the TICK button will accept the 4 digit number entered.

The Manager menu is shown if the PIN matches the Manager PIN.

The Engineer menu is shown if the PIN matches the Engineer PIN.

If an invalid PIN is entered, a warning is displayed. Press TICK or CROSS button to return to the User menu.

Press the CROSS button at any time to return to the User menu.

Default Manager PIN is 3333. Default Engineer PIN is 0000.

Once commissioned, it is recommended that the Manager PIN and Engineer PIN are changed to something memorable.

19.12 Back MenuThis action menu will return the operator back to the status display. This is the same as pressing the CROSS button in the User menu list.

Panel Test>Start

Enter PIN_0***_

*Invalid User*

24

Operating Instructions

Page 25: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19.13 Manager Menu ListThe Manager menu list allows the operator access to all menus available at access level 2. This incorporates the User menu list.

The Manager menu list includes status menus, action menus, and configuration menus. The configuration menus are for non-emergency items only.

Accept faults, Current faults, Panel version, and Panel test menus are the same as described above in the User menu list. See above for details on these menus.

Press the CROSS button on any menu item to select the Log Out menu item.

19.14 Log OutThe Log out menu is an action menu. It returns the operator to the status display, and changes the access level back to User level (access level 1).

19.15 Music Volume MenuThis menu is a non-emergency configuration menu. It is used to change the volume of the music input.

Press the UP button to increase the music volume. Press the DOWN button to decrease the music volume.

The music volume change will wrap round from 0 to Mute, or Mute to 0. The music volume value displayed is the attenuation level in dB.

The music volume is changed in real time, so increasing or decreasing the music volume will automatically adjust the audio volume of the music input. This is the only configuration menu that does not require a menu action to save any changes.

To disable the music input, set the music volume to Mute.

Press the TICK or CROSS key to exit this menu, keeping the music volume chosen.

Music : NextVolume>-6 Mute : No

25

Operating Instructions

DAU v1.11 0>Log Out

Accept faults Current faults Panel version Music volume Page volume Manager PIN Panel reboot Panel test Silence message

Page 26: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19.16 Page Volume MenuThis menu is a non-emergency configuration menu. It is used to change the volume of non-emergency, or page level, audio.

Page volume is defined as all non-emergency, non-music audio. This includes the Test message, the local audio input port set to Page level, and a network microphone set for PA use.

If page volume is selected, Press the UP button to increase the page volume.

Press the DOWN button to decrease the page volume.

The page volume will wrap around from 0 to Mute, or Mute to 0. The page volume value is the attenuation level in dB.

If the menu actions are selected, use the UP and DOWN buttons to change the action, and the TICK button to execute the chosen action.

Press the CROSS button to exit this menu.

19.17 Silence Message MenuThis menu is an action menu. This menu silences or resets the message currently playing.

If a message is silenced or reset, it will always continue playing until the end of the message then stop. It will not repeat.

If the message is playing in response to an active fire contact, the message will be silenced. The silence message menu will be hidden, and it will be replaced by the Resound message.

If the message is playing in response to a manual request, the message will be reset.

Press the TICK or CROSS button to exit this menu.

19.18 Manager PIN MenuTo change the Manager PIN, enter the 4 digit PIN by the new entry. Use the UP and DOWN buttons to change the digit, and the TICK button to move to the next digit or onto the menu actions if on the last digit.

Re-enter the new Manager PIN on the Repeat line.

To save the new Manager PIN, use the UP or DOWN button to change the menu action to Save then press the TICK button.

If the New and Repeat PINs do not match, a warning is displayed. Press the TICK or CROSS button to clear the warning and to return the operator to the menu list. The new Manager PIN will not be saved.

If the new Manager PIN is the same as Engineer PIN, a warning is displayed. Press the TICK or CROSS button to clear the warning and to return the operator to the menu list. The new Manager PIN will not be saved.

Press the CROSS button at any time to exit this menu.

Page :NextVolume>-6

New:**** >Next Repeat:****

Message silenced

26

Operating Instructions

Page 27: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19.19 Panel Reboot MenuThis menu is an action menu. This menu will perform a software reboot.

To reboot the panel, use the UP or DOWN buttons to change the menu item to Yes, then press the TICK

button to confirm the reboot request.

If the menu item is No, and the TICK button is pressed, this will exit the menu. Press the CROSS key to exit the menu.

19.20 Engineer Menu ListThe Engineer menu list allows the operator access to all menus available at access level 3. This incorporates the User menu list and the Manager menu list.

The Engineer menu list includes status menus, action menus, and configuration menus.

Accept faults, Current faults, Panel version, and Panel test menus are the same as described above in the User menu list. See above for details on these menus.

Log out, Music volume, Page volume, Silence message, Resound message, and Manager PIN are the same as described above in the Manager menu list. See above for details on these menus.

Press the CROSS button on any menu item to select the Log Out menu item.

Reboot Panel>No

DAU v1.11>Log Out

Accept faults Current faults Panel version Music volume Page volume Manager PIN Engineer PIN Panel reboot Panel test Message test Panel nameMessagesBuzzerDevice settings Emergency Volume NetworkSilence message

27

Operating Instructions

Page 28: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19.21 Engineer PIN MenuThis menu is a configuration menu. This menu allows the operator to change the Engineer PIN.

To change the Engineer PIN, enter the 4 digit PIN by the new entry. Use the UP and DOWN buttons to change the digit, and the TICK button to move to the next digit or onto the menu actions if on the last digit.

Re-enter the new Engineer PIN on the Repeat line.

To save the new Engineer PIN, use the UP or DOWN button to change the menu action to Save, and then press the TICK button.

If the New and Repeat PINs do not match, a warning is displayed. Press the TICK or CROSS button to clear the warning and to return the operator to the menu list. The new Engineer PIN will not be saved.

If the new Manager PIN is the same as Engineer PIN, a warning is displayed. Press the TICK or CROSS button to clear the warning and to return the operator to the menu list. The new Engineer PIN will not be saved.

Press the CROSS button at any time to exit this menu.

19.22 Message Test MenuThis menu is an action menu. It is used to test the audio quality of the chosen message, and to test the speakers.

With Test message selected, use the UP and DOWN buttons to scroll through all three messages available. Press the TICK key to move the cursor to the menu action on the bottom line.

With the cursor on the second line, use the UP and DOWN buttons to toggle this action between Start and Quit.

If the menu action is start, this will start the selected message playing. This message will repeat until the message test has finished.

If the menu action is quit, it will stop any message currently playing at the end of its current cycle. It also exits the menu.

Press the CROSS button to stop any message current at the end of its current cycle. It also exits the menu.

19.23 Panel Name MenuThis menu is a configuration menu. It sets the panel name that is shown on the status display.

The name can be anything up to 18 characters in length, such as installer, location or area served. Press the UP and DOWN buttons to change the character selected, or the menu actions.

Press the TICK button to move the cursor to the next character, or to execute the selected menu action. Press the CROSS button to exit the menu, discarding any changes.

Test Message>Test:Start

Panel Name >Next>Eaton<

New:**** >Next Rpt:****

28

Operating Instructions

Page 29: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19.24 Messages Menu ListThe Messages menu list is used to select the menus to configure messages 1, 2 or 3. The operator can also move back to the Engineer menu list if the TICK button is pressed on Back.

Press the UP or DOWN button to scroll through all entries of the Messages menu list. Press the TICK button to enter the menu selected.

Press the CROSS button to exit this menu list.

19.25 Message LatchThis menu is a configuration menu. It sets the latched state for each message once they’ve been triggered .

Message 1 is the lowest priority message. It is usually assigned as the Test message. The message audio priority can be defined as Test, Alert or Evac.

Test is a non-emergency state that has a lower priority than normal PA paging, but a higher priority than music.

Alert is the lowest priority level defined as Emergency. This level overrides all non-emergency inputs, but is itself overridden by all other emergency inputs.

Evacuate is higher priority than the Alert message. It overrides all inputs except for Emergency pages, either by the Emergency Evacuation System EMA, or another emergency microphone.

If Latch is set to Y, the message will continuously repeat until reset by an external source, or via the silence message menu.

If Latch is set to N, the message will repeat until the triggering source is removed. Once removed, the message will play to the end, and then stops.

Press the UP and DOWN buttons to cycle between the options for the selected menu item. Press the TICK key to move to the next menu item, or to execute the selected menu action. Press the CROSS key to exit the menu, discarding any changes.

19.26 Message NameThe message name can be set and assigned in this menu. As with before, Msg 1 has been set the lowest priority so we’ll call it test and so on for Alert and Evac.

Press the UP and DOWN buttons to cycle between the options for the selected menu item.

Press the TICK key to move to the next menu item, or to execute the selected menu action.

Press the CROSS key to exit the menu, discarding any changes.

Select Message>Message

LatchMessage nameBack

Message Latch :Next1>No 2:Yes 3:Yes

Message Name :NextMsg>1 Name:>Test

29

Operating Instructions

Page 30: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19.27 Buzzer MenuThis menu is a configuration menu. It defines how the buzzer is to operate, the visibility of the Accept faults menu, and if the alarm buzzer is implemented. This menu has two pages. To move between the pages, press the TICK button when the menu action Next is selected.

Page 1

The first page sets the buzzer mode, and the visibility of the Accept faults menu.

Mode has three options: Mute- No local fault sounder

Mom- the fault sounder only plays when faults are present and have not been accepted

Ltch- the fault sounder plays when a fault occurs, and will continue playing until faults have been accepted.

If the Alarm buzzer is enabled, then the buzzer will sound a 2-tone warning when playing an emergency message. This alarm buzzer is non-compliant as it fails to reach the requisite volume as described in EN54-16 Clause 13.10.2.

If Alarm is selected, press the UP or DOWN button to enable or disable the alarm buzzer. Press the TICK button to select the menu actions.

Press the UP or DOWN button to change the option for the menu item selected.

Press the TICK button to move to the next menu item, or to execute the menu action selected. Press the CROSS button to exit the menu, discarding any changes.

If the menu action is selected, press the UP or DOWN button to change the action. Press the TICK button to execute the action selected.

Press the CROSS button to exit the menu, discarding any changes.

19.28 Device Settings MenuThis menu is a configuration menu. It sets if optional devices are present.

There are two optional devices: a second amplifier module designated Amplifier B, and a Cooper Fire analogue loop interface device.

Amplifier module B is monitored only if Amp B is set to “Y”.

The Cooper Fire loop interface is monitored only if Loop i/f is set to “Y”.

If Amp B or LOOP i/f is selected, press the UP or DOWN button to change the monitoring status for the selected device. Press the TICK button to move to the next menu item.

If the menu action is selected, press the UP or DOWN button to change the menu action. Press the TICK button to execute the menu action selected.

Press the CROSS button to exit the menu, discarding any changes.

Buzzer :NextMode>Ltch Alarm:Y

Devices Used :Next Amp B>N Loop i/f:N

30

Operating Instructions

Page 31: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19.29 Emergency Volume MenuThis menu is a configuration menu. It is used to change the volume of - emergency level, audio.

Emergency volume is defined as all emergency audio. This includes the Alert and Evacuate messages, the local audio input set to Emergency level, and a network microphone in Emergency mode.

If Emergency volume is selected,

Press the UP button to increase the emergency volume. Press the DOWN button to decrease the emergency volume.

The emergency volume will wrap around from 0 to Mute, or Mute to 0. The emergency volume value is the attenuation level in dB.

If the menu actions are selected, use the UP and DOWN buttons to change the action, and the TICK button to execute the chosen action.

Press the CROSS button to exit this menu.

19.30 Network Menu ListThe network menu list has menus to configure the network settings for this unit, to define which Emergency Evacuation System DAUs are present on the network, and to define which network audio inputs are present.

Press the UP or DOWN button to scroll through the menus.

Press the TICK button to enter the menu chosen, or to move back to the Engineer menu list if Back is chosen.

Press the CROSS button to move back to the Engineer menu list.

Emergency :Next Volume>0

Network>Settings

DAUAudio InputBack

31

Operating Instructions

Page 32: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19.31 SettingsThis menu is a configuration menu. It has two pages. It allows the operator to assign a network address to his unit, and to specify what type of unit is connected to the network in port and the network out port.

To move between pages, press the TICK button with the menu action Next selected.

Page 1

The first page sets the network address of this unit.

If address is selected, press the UP or DOWN button to change the network address. Valid addresses lie in the range 1 to 32. Press the TICK button to select the menu action.

Note: the network address must be unique. If 2 or more units share the same address, this will cause a major conflict with the network communication.

If the menu action is selected, press the UP or DOWN button to change the menu action. Press the TICK button to execute the menu action selected.

Page 2

The second page sets the network port monitoring options.

Each network port is independently monitored. The operator specifies the unit that is connected to the

Network In port and the unit that is connected to the Network Out port.

If the unit is a Emergency Evacuation System EMA or another network microphone, then set that port to Mic. If the unit is a Emergency Evacuation System DAU, then set that port to DAU.

To disable the monitoring for the port, then set that port to None.

If the In or Out port is selected, press the UP or DOWN button to change the unit type for that port. Press the TICK button to move to the next menu item.

If the Emergency Evacuation System DAU is a stand-alone unit, i.e. not connected to the Emergency Evacuation System network, then

Set the network address to 1

Set monitor port In to None

Set monitor port Out to None

If the menu action is selected, press the UP or DOWN button to change the menu action. Press the TICK button to execute the action selected.

Network :NextAddress>1

Monitor port :NextIn>Mic Out>Mic

32

Operating Instructions

Page 33: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

19.32 DAU Present MenuThis menu is a configuration menu. This defines which DAU ad-dresses are present on the network.

This menu is used to inform the unit which Emergency Evacuation System DAUs should be present on the network. It is used primarily to ensure that two Emergency Evacuation System DAUs do not broadcast their status to the network at the same time, thus causing a conflict.

Each page has four network addresses. The first page has ad-dresses 1 to 4. The second page has addresses 5 to 8. The last page has addresses to 32. Press the TICK button with the menu action Next selected to show the next page.

For each Emergency Evacuation System DAU present on the network, set its address to “Y”. Press the UP or DOWN button

to change the address option between “Y” and “N”.

If an address is selected, press the TICK button to move to the next address. If a menu action is selected, press the TICK button to execute that menu action.

Press the CROSS button to exit the menu, discarding any changes.

19.33 Audio Input Present MenuThis menu is a configuration menu. This defines which network audio inputs are present on the network.

A network audio input is defined as a device used to input audio onto the system. This is a network microphone, e.g. Emergency Evacuation System EMA.

This menu is used to determine which audio inputs are present on the network. This menu has 2 pages. Page 1 configures addresses 1 to 4. Page 2 configures addresses 5 to 8. Press the TICK button with the menu action Next selected to move to the other page.

For each network audio input present, set its address to “Y”. Press the UP or DOWN button to change the address option between “Y” and “N”.

If an address is selected, press the TICK button to move to the next address. If a menu action is selected, press the TICK button to execute that menu action.

Press the CROSS button to exit the menu, discarding any changes.

DAU Present :Next1>Y 2:Y 3:Y 4:N

Audio Input :Next1>Y 2:Y 3:N 4:N

33

Operating Instructions

Page 34: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

20. Fault Codes and descriptionsFault Description

Mic 1 missing Network has been defined with a microphone, e.g. fire microphone or paging panel, with network address 1. This microphone is not present on the network.

Check microphone has the correct address.

Check microphone has power.

Mic 2 missing Network has been defined with a microphone, e.g. fire microphone or paging panel, with network address 2. This microphone is not present on the network.

Check microphone has the correct address.

Check microphone has power.

Mic 3 missing Network has been defined with a microphone, e.g. fire microphone or paging panel, with network address 3. This microphone is not present on the network.

Check microphone has the correct address.

Check microphone has power.

Mic 4 missing Network has been defined with a microphone, e.g. fire microphone or paging panel, with network address 4. This microphone is not present on the network.

Check microphone has the correct address.

Check microphone has power.

Mic 5 missing Network has been defined with a microphone, e.g. fire microphone or paging panel, with network address 5. This microphone is not present on the network.

Check microphone has the correct address.

Check microphone has power.

Mic 6 missing Network has been defined with a microphone, e.g. fire microphone or paging panel, with network address 6. This microphone is not present on the network.

Check microphone has the correct address.

Check microphone has power.

Mic 7 missing Network has been defined with a microphone, e.g. fire microphone or paging panel, with network address 7. This microphone is not present on the network.

Check microphone has the correct address.

Check microphone has power.

Mic 8 missing Network has been defined with a microphone, e.g. fire microphone or paging panel, with network address 8. This microphone is not present on the network.

Check microphone has the correct address.

Check microphone has power.

Msg module fault The audio safe message module is either missing, it has failed, or the message store has been corrupted.

Using the Audio Safe Downloader utility, connect the Audio Safe Message Player lead to the Message Upload socket.

Using the utility, perform a hardware check on the module to determine if messages have been corrupted, or the message module has failed.

Speaker A open Speaker line A has an open circuit.

Check if end-of-line resistor is present. Check if any speakers are connected.

Speaker A short Speaker line A has a short circuit.

Check if speaker cable has a short.

Check if any attached speakers are shorted.

34

Operating Instructions

Page 35: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

Fault Description

Speaker A earth Speaker line A has an earth fault.

Check if speaker cable is shorted to earth.

Amp A protect Amplifier A has entered protect mode to protect the amplifier. This occurs during a short circuit or an earth fault

Amp A hot fault Amplifier module A is critically overheating. The volume will be reduced in attempt to cool the amplifier by reducing the amount of energy used.

Amp A shutdown Amplifier module A has shut down. This is to protect the amplifier from fatal damage. Once the condition that causes the shutdown has passed, the amplifier will attempt to restart.

If the amplifier cannot restart, then the amplifier has failed.

Amp A fuse Amplifier module A fuse is either missing or has blown.

Replace fuse.

Speaker B open Speaker line B has an open circuit.

Check if end-of-line resistor is present. Check if any speakers are connected.

Speaker B short Speaker line B has a short circuit.

Check if speaker cable has a short.

Check if any attached speakers are shorted.

Speaker B earth Speaker line B has an earth fault.

Check if speaker cable is shorted to earth.

Amp B protect Amplifier B has entered protect mode to protect the amplifier. This occurs during a short circuit or an earth fault

Amp B hot fault Amplifier module B is critically overheating. The volume will be reduced in attempt to cool the amplifier by reducing the amount of energy used.

Amp B shutdown Amplifier module B has shut down. This is to protect the amplifier from fatal damage. Once the condition that causes the shutdown has passed, the amplifier will attempt to restart.

If the amplifier cannot restart, then the amplifier has failed.

Amp B fuse Amplifier module A fuse is either missing or has blown.

Replace fuse.

Net in comms There is no network communication from the network in port.

This fault occurs if there is a problem with the cable transmit pair, the cable receive pair, or it has not received any data from the network in port.

If this fault does not have a corresponding Rx or Tx fault, then the unit connected to the other end of the network in cable is not transmitting. Check this unit.

Net in Rx There is a fault with the network in cable receive pair.

Check cable.

Net in Tx There is a fault with the network in transmit pair.

Check cable.

Net in audio SC There is a short circuit on the network in cable audio pair.

Check cable.

Net in audio OC There is an open circuit on the network in cable audio pair.

Check cable.

35

Operating Instructions

Page 36: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

Fault Description

Net in power + flt There is a fault on the network in positive power cable (24V).

Check cable.

Net in power 0V flt There is a fault on the network in ground power cable (0V).

Check cable.

Net out comms There is no network communication from the network out port.

This fault occurs if there is a problem with the cable transmit pair, the cable receive pair, or it has not received any data from the network out port.

If this fault does not have a corresponding Rx or Tx fault, then the unit connected to the other end of the network out cable is not transmitting. Check this unit.

Net out Rx There is a fault with the network out cable receive pair.

Check cable.

Net out Tx There is a fault with the network out transmit pair.

Check cable.

Net out audio SC There is a short circuit on the network in cable audio pair.

Check cable.

Net out audio OC There is an open circuit on the network in cable audio pair.

Check cable.

Net out power + flt There is a fault on the network out positive power cable (24V).

Check cable.

Net out power 0V flt There is a fault on the network out ground power cable (0V).

Check cable.

Invalid net comms Data is received but is corrupted.

Check network transmit and receive cables.

Battery fault Battery is connected, but has a fault.

Charger fault Battery charger is in fault.

Check if battery is connected.

Mains fault Mains failed.

Check mains fuse.

Earth cable fault A cable has been shorted to earth.

Check all cables.

Amp i/f fault Amplifier module has failed to initialise.

Invalid net index Corrupted network address that lies outside valid range.

Set network address in network settings when logged on as engineer.

Mic 1 audio in flt Network microphone at address 1 has a fault on the network in cable audio pair.

Check network in audio cable on microphone 1.

Mic 2 audio in flt Network microphone at address 2 has a fault on the network in cable audio pair.

Check network in audio cable on microphone 2.

Mic 3 audio in flt Network microphone at address 3 has a fault on the network in cable audio pair.

Check network in audio cable on microphone 3.

36

Operating Instructions

Page 37: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

Fault Description

Mic 4 audio in flt Network microphone at address 4 has a fault on the network in cable audio pair.

Check network in audio cable on microphone 4.

Mic 5 audio in flt Network microphone at address 5 has a fault on the network in cable audio pair.

Check network in audio cable on microphone 5.

Mic 6 audio in flt Network microphone at address 6 has a fault on the network in cable audio pair.

Check network in audio cable on microphone 6.

Mic 7 audio in flt Network microphone at address 7 has a fault on the network in cable audio pair.

Check network in audio cable on microphone 7.

Mic 8 audio in flt Network microphone at address 8 has a fault on the network in cable audio pair.

Check network in audio cable on microphone 8.

Mic 1 audio out flt Network microphone at address 1 has a fault on the network out cable audio pair.

Check network out audio cable.

Mic 2 audio out flt Network microphone at address 2 has a fault on the network out cable audio pair.

Check network out audio cable.

Mic 3 audio out flt Network microphone at address 3 has a fault on the network out cable audio pair.

Check network out audio cable.

Mic 4 audio out flt Network microphone at address 4 has a fault on the network out cable audio pair.

Check network out audio cable.

Mic 5 audio out flt Network microphone at address 5 has a fault on the network out cable audio pair.

Check network out audio cable.

Mic 6 audio out flt Network microphone at address 6 has a fault on the network out cable audio pair.

Check network out audio cable.

Mic 7 audio out flt Network microphone at address 7 has a fault on the network out cable audio pair.

Check network out audio cable.

Mic 8 audio out flt Network microphone at address 8 has a fault on the network out cable audio pair.

Check network out audio cable.

Mic 1 comms in flt Network microphone at address 1 has a network serial data communications fault on network in.

Check network in cable transmit pair. Check network in cable receive pair.

Check microphone 1 is powered on and working.

Mic 2 comms in flt Network microphone at address 2 has a network serial data communications fault on network in.

Check network in cable transmit pair. Check network in cable receive pair.

Check microphone 2 is powered on and working.

Mic 3 comms in flt Network microphone at address 3 has a network serial data communications fault on network in.

Check network in cable transmit pair. Check network in cable receive pair.

Check microphone 3 is powered on and working.

Mic 4 comms in flt Network microphone at address 4 has a network serial data communications fault on network in.

Check network in cable transmit pair. Check network in cable receive pair.

Check microphone 4 is powered on and working.

37

Operating Instructions

Page 38: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

Fault Description

Mic 5 comms in flt Network microphone at address 5 has a network serial data communications fault on network in.

Check network in cable transmit pair. Check network in cable receive pair.

Check microphone 5 is powered on and working.

Mic 6 comms in flt Network microphone at address 6 has a network serial data communications fault on network in.

Check network in cable transmit pair. Check network in cable receive pair.

Check microphone 6 is powered on and working.

Mic 7 comms in flt Network microphone at address 7 has a network serial data communications fault on network in.

Check network in cable transmit pair. Check network in cable receive pair.

Check microphone 7 is powered on and working.

Mic 8 comms in flt Network microphone at address 8 has a network serial data communications fault on network in.

Check network in cable transmit pair. Check network in cable receive pair.

Check microphone 8 is powered on and working.

Mic 1 comms out flt Network microphone at address 1 has a network serial data communications fault on network out

Check network out cable transmit pair.

Check network out cable receive pair.

Check microphone 1 is powered on and working.

Mic 2 comms out flt Network microphone at address 2 has a network serial data communications fault on network out.

Check network out cable transmit pair. Check network out cable receive pair.

Check microphone 2 is powered on and working.

Mic 3 comms out flt Network microphone at address 3 has a network serial data communications fault on network out.

Check network out cable transmit pair. Check network out cable receive pair.

Check microphone 3 is powered on and working.

Mic 4 comms out flt Network microphone at address 4 has a network serial data communications fault on network out.

Check network out cable transmit pair. Check network out cable receive pair.

Check microphone 4 is powered on and working.

Mic 5 comms out flt Network microphone at address 5 has a network serial data communications fault on network out.

Check network out cable transmit pair. Check network out cable receive pair.

Check microphone 5 is powered on and working.

Mic 6 comms out flt Network microphone at address 6 has a network serial data communications fault on network out.

Check network out cable transmit pair. Check network out cable receive pair.

Check microphone 6 is powered on and working.

Mic 7 comms out flt Network microphone at address 7 has a network serial data communications fault on network out.

Check network out cable transmit pair. Check network out cable receive pair.

Check microphone 7 is powered on and working.

Mic 8 comms out flt Network microphone at address 8 has a network serial data communications fault on network out.

Check network out cable transmit pair. Check network out cable receive pair.

Check microphone 8 is powered on and working.

Mic 1 mic fault Network microphone at address 1 has a faulty microphone.

Check if microphone is attached.

Mic 2 mic fault Network microphone at address 2 has a faulty microphone.

Check if microphone is attached.

38

Operating Instructions

Page 39: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

Fault Description

Mic 3 mic fault Network microphone at address 3 has a faulty microphone.

Check if microphone is attached.

Mic 4 mic fault Network microphone at address 4 has a faulty microphone.

Check if microphone is attached.

Mic 5 mic fault Network microphone at address 5 has a faulty microphone.

Check if microphone is attached.

Mic 6 mic fault Network microphone at address 6 has a faulty microphone.

Check if microphone is attached.

Mic 7 mic fault Network microphone at address 7 has a faulty microphone.

Check if microphone is attached.

Mic 8 mic fault Network microphone at address 8 has a faulty microphone.

Check if microphone is attached.

Net not configured Network has not been configured.

Log in as engineer and set all network settings, including DAU & audio input addresses under the Network menu.

Flash chksum fail Code checksum has failed. Software is corrupted.

EEPROM chksum fail Configuration data checksum has failed. Configuration is corrupted.

Fire loop i/f fault Internal Cooper Fire loop interface board fault.

Check if Cooper Fire loop interface board is attached. Check if Cooper Fire panel is attached to interface board.

If not used with a Cooper Fire loop interface board, disable fire loop interface in Device Settings menu.

Watchdog reset An error has occurred in the software causing the panel to reset.

Will remain permanently in fault until faults are accepted.

Mic 1 watchdog reset Network microphone 1 has had an error in the software causing the microphone to reset.

Will remain permanently in fault until the fault has been accepted at any panel.

Mic 2 watchdog reset Network microphone 2 has had an error in the software causing the microphone to reset.

Will remain permanently in fault until the fault has been accepted at any panel.

Mic 3 watchdog reset Network microphone 3 has had an error in the software causing the microphone to reset.

Will remain permanently in fault until the fault has been accepted at any panel.

Mic 4 watchdog reset Network microphone 4 has had an error in the software causing the microphone to reset.

Will remain permanently in fault until the fault has been accepted at any panel.

Mic 5 watchdog reset Network microphone 5 has had an error in the software causing the microphone to reset.

Will remain permanently in fault until the fault has been accepted at any panel.

Mic 6 watchdog reset Network microphone 6 has had an error in the software causing the microphone to reset.

Will remain permanently in fault until the fault has been accepted at any panel.

Mic 7 watchdog reset Network microphone 7 has had an error in the software causing the microphone to reset.

Will remain permanently in fault until the fault has been accepted at any panel.

Mic 8 watchdog reset Network microphone 8 has had an error in the software causing the microphone to reset.

Will remain permanently in fault until the fault has been accepted at any panel.

39

Operating Instructions

Page 40: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

21. Technical Specification

POWER SUPPLY (Approved EN54-4)Mains

Nominal Voltage 230V AC -15%, +10%

Nominal Current 75mA

Maximum Current 750mA

Input fuse R1s NTC SG39 Imax 4A

Output Voltage including tolerances

26V output 27V -10%, +10%

26Vraw 20.6V to 29.5V

5V output 4.6V to 5.5V

Ripple voltages

26V output 800mV

26Vraw 800mV

5V output 430mV

Maximum loadings

26V output 1.5A

Vraw 2.0A

Vbat (battery) 0.970A

5V 3A

Output current

Min output current 75mA

I Max.a 2 40mA

I Max.b 690mA

Emergency Evacuation System DAU is protected by an internal thermal device. This requires no maintenance.

BATTERIESNumber of batteries 2 connected in series

Manufacturer YUCEL Y5-12L

Capacity 5Ah

Battery fuse 6.3A Anti-Surge (F4)

Maximum battery current 3.5A

Standby current 56mA

Maximum charging current to the batteries 1.0A

Float Voltage 27.4V

Final Voltage 21.0V

Charging characteristics Constant Voltage with 0.970A limit with temperature compensation

Maximum current drawn from batteries when mains 3.5Ais not available

Deep discharge protection 20.6V

Maximum internal resistance of battery and associated 0.6Ωcircuitry

40

Specification

Page 41: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

EATON EMA & DAU Installation and Commissioning Manual (PR211-181-510-10, PINSTDAUINST) January 2016 www.eaton.com

INPUTSNetwork

Ports Network In, Network Out

Monitoring Data, Audio and Power. Audio isolated on Fault

Audio Sensitivity 0dBV Balanced Line -10dBV to + 4dBV

Control Data Balanced RS422 stream 200mV to 5V

Power +24V nominal 500mA self-resetting fuse

BGM

Sensitivity -6dBV to +2dBV

Page

Sensitivity -6dBV to +4dBV

PTT Type 0V to access

Power +24V nominal 100mA self-resetting fuse

Fire Interface

Inputs 3 off isolated +12V to +33V (Alert, Evacuate, Reset)

Outputs 1 Relay (open on fault) 30V 1A Max

Power +24V nominal 100mA self-resetting fuse

SPEAKERSCircuits 2 off 50W RMS each

Level 100V RMS (+40dBV)

Bandwidth 80Hz to 18 KHz (-3dB full power)

Distortion 0.1% 50W @ 27.6V

1% 50W @ 23V

Monitoring DC end-of-line (9K expected)

Fault indication Open, Short, Earth

Protection Short, Open, Thermal, DC offset

Amplifier module fuse 3.15AT

41

Specification

Page 42: Distributed Amplifier Unit (DAU) (EESDAU100) Emergency ... MR1... · Distributed Amplifier Unit (DAU) (EESDAU100) ... (EMA) (EESEMA) Installation and Commissioning Manual ... malls

Eaton Industries ManufacturingGmbH Electrical Sector EMEARoute de la Longeraie 71110 Morges, SwitzerlandEaton.eu

Eaton Cooper Lighting and Safety Ltd.Wheatley Hall RoadDoncaster, South YorkshireDN2 4NBTel: +44 (0) 1302 303 999E-mail: [email protected]: www.cooperfire.com

© 2016 EatonAll Rights ReservedPrinted in UKJanuary 2016

Eaton is a registered trademark.

All other trademarks are propertyof their respective owners.