displacement ventilation · 2013-04-26 · case study - conclusion displacement ventilation...

26
Displacement Ventilation Basics, Advantages, and Case Studies Barry J. Stamp, PE, LEED AP

Upload: others

Post on 08-Jul-2020

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Displacement Ventilation

Basics, Advantages, and Case Studies Barry J. Stamp, PE, LEED AP

Page 2: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Presentation Highlights:

Displacement Basics Design Basics Advantages Case Studies Q & A

Rocky Mountain ASHRAE Tech Conference

Page 3: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Displacement Basics

Ways to deliver conditioned air: Mixing – air delivery resulting in induction of

room air and mixing. Laminar – Directional air delivery at high

volume. Displacement – air delivery at the floor level

without mixing.

Rocky Mountain ASHRAE Tech Conference

Page 4: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Displacement Basics Air flow relies on

natural convective air movement caused by buoyancy forces.

Conditioned air is delivered to the space at floor level at a low temperature differential.

Rocky Mountain ASHRAE Tech Conference

Page 5: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Design Basics

Zone cooling load: Emphasis is on the occupied zone of the space.

Each component of the total space cooling load is addressed as a function of its impact on the occupied zone: Occupants, equipment, task lighting Solar / Envelope Overhead Lighting

Rocky Mountain ASHRAE Tech Conference

Page 6: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Design Basics From ASHRAE Research*:

The occupied zone heat gain contributions are: 13.2% of overhead

lighting 29.5% of occupants, task

lighting, equipment 18.5% of solar / envelope *Office, classroom and workshop applications

Rocky Mountain ASHRAE Tech Conference

Page 7: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Design Basics

Supply air temperature must be held within 10-degrees of set point.

HVAC equipment will still be sized for the total cooling load.

Air within the space will stratify, and the return air temperature may be several degrees higher than the set point temperature.

Rocky Mountain ASHRAE Tech Conference

Page 8: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Design Basics

Rocky Mountain ASHRAE Tech Conference

Room temperature stratification

Page 9: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Design Basics When is

Displacement not a good fit? Low ceiling heights High heating loads Applications that

require directional air flow

Rocky Mountain ASHRAE Tech Conference

Page 10: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Design Basics Heating with displacement

ventilation: Heating load must be sufficiently

low to be able to heat the space with low delta-T.

Morning warm-up can be a challenge.

Supplemental heating may be needed.

Special heating/cooling Dv diffusers are available.

Rocky Mountain ASHRAE Tech Conference

Page 11: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Advantages Displacement ventilation results in improved: Comfort Indoor air quality Acoustics Energy efficiency Reduced fan motor loads Refrigeration systems operate more

efficiently An expanded economizer window Reduction in OA delivered

Rocky Mountain ASHRAE Tech Conference

Page 12: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Case Study: Classroom Questions: What is the comfort condition in the seating

area? How does the T-stat temperature relate to the

seating area temperature? How much cooling capacity is lost through an

open door? What is the cause of a momentary temperature

bump seen in the afternoons?

Rocky Mountain ASHRAE Tech Conference

Page 13: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Case Study: Classroom South-facing classroom: Room equipped with view and daylight

windows. Student seating area for 25-30 students. Dv supplied at floor level along corridor wall and

along exterior wall (less than 35 FPM) Ceiling is sloped upward toward perimeter wall

and upward toward interior tubular skylights.

Rocky Mountain ASHRAE Tech Conference

Page 14: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Case Study: Classroom Data Logging Sensor Placement: Diffuser face Floor level near classroom door Student desktop in middle of room Room T-stat location Between exterior windows Under-side of pendant light At ceiling return air grille

Rocky Mountain ASHRAE Tech Conference

Page 15: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Case Study: Classroom

Rocky Mountain ASHRAE Tech Conference

Diffuser Floor Level

Room T-Stat

Light

Student Desktop

Ret. Grille

Ext. Wall

Page 16: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Case Study: Classroom Cooling Operation: Sunny weekday with full student population January day with low morning temperature of

24-degrees F and a high temperature of 63-degrees F

Near maximum solar gain – low solar angle

Rocky Mountain ASHRAE Tech Conference

Page 17: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Case Study: Classroom

6062646668707274767880

5:00

5:45

6:30

7:15

8:00

8:45

9:30

10:1

511

:00

11:4

512

:30

13:1

514

:00

14:4

515

:30

16:1

517

:00

Tem

pera

ture

, Deg

. F

Sensor Temperatures - Cooling

Diffuser

Floor

Desktop

T-Stat

Ext. Wall

Light

Ret. Grille

Rocky Mountain ASHRAE Tech Conference

Page 18: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Case Study: Classroom

Cooling Observations: Despite relatively high Delta-T, the MWU appears

to be effective. Room stratification approaches 10-degrees F. Student desktop temperatures are 1 to 3

degrees F lower than sensor temperature. Floor temperature is cool, and only dropped

slightly during cooling operation. Good SA penetration into the student seating

area.

Rocky Mountain ASHRAE Tech Conference

Page 19: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Case Study: Classroom

Rocky Mountain ASHRAE Tech Conference

Page 20: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Case Study: Classroom

Heating Operation: Overcast weekday with full student

population 68-degree set point January day with low morning temperature of

12-degrees F and a high temperature of 26-degrees F

Near zero solar gain

Rocky Mountain ASHRAE Tech Conference

Page 21: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Case Study: Classroom

6062646668707274767880

5:00

5:45

6:30

7:15

8:00

8:45

9:30

10:1

511

:00

11:4

512

:30

13:1

514

:00

14:4

515

:30

16:1

517

:00

Tem

pera

ture

, Deg

. F

Sensor Temperatures - Heating

Diffuser

Floor

Desktop

T-Stat

Ext. Wall

Light

Ret. Grille

Rocky Mountain ASHRAE Tech Conference

Page 22: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Case Study: Classroom

Heating Observations: MWU SAT is higher than desired, but effective.

Warm air does not immediately rise to the ceiling.

Room stratification is nearly non-existent. Exterior wall temperature is lowest reading,

reflecting room cooling from exterior. Good SA penetration into the seating area.

Rocky Mountain ASHRAE Tech Conference

Page 23: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Case Study - Conclusion

Displacement ventilation performance is as envisioned.

Room air stratification is close to the expected range in the cooling mode.

Heating mode operation is better than expected.

Airflow penetration into the seating area is very good.

Rocky Mountain ASHRAE Tech Conference

Page 24: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

References: System Performance Evaluation and Design

Guidelines for Displacement Ventilation, ASHRAE 2003

ASHRAE Fundamentals Volume, 2010 ANSI/ASHRAE Standard 62.1-2010, Ventilation for

Acceptable Indoor Air Quality Air Device Manufacturer Design Guidelines and

catalog data Thanks to Eaton Electrical Services Energy

Solutions Group

Rocky Mountain ASHRAE Tech Conference

Page 25: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Questions?

Rocky Mountain ASHRAE Tech Conference

Page 26: Displacement Ventilation · 2013-04-26 · Case Study - Conclusion Displacement ventilation performance is as envisioned. Room air stratification is close to the expected range in

Thank You!

Barry J, Stamp, P.E., LEED AP [email protected]

Rocky Mountain ASHRAE Tech Conference