dir oc + ef protn_apps

Upload: neelakandan-masilamani

Post on 02-Jun-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Dir OC + EF Protn_APPS

    1/72

    This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior

    written consent of Alstom Grid Technical Institute. All rights reserved.

    GRID

    Technical Institute

    App l icat ion o f Direct ion al

    Overcurrent

    and Earthfaul t Protect ion

  • 8/10/2019 Dir OC + EF Protn_APPS

    2/72

    > Directional Overcurrent and Earthfault Protection2 2

    Direct ional Protect ion

  • 8/10/2019 Dir OC + EF Protn_APPS

    3/72

    > Directional Overcurrent and Earthfault Protection3 3

    Need for Direct ion al Con trol

    Generally required if current can flow in both directions

    through a relay location

    e.g. Parallel feeder circuits

    Ring Main Circuits

    2.1 0.50.9 0.11.31.7

  • 8/10/2019 Dir OC + EF Protn_APPS

    4/72

    > Directional Overcurrent and Earthfault Protection4 4

    Need for Direct ion al Con trol

    Generally required if current can flow in both directions

    through a relay location

    e.g. Parallel feeder circuits

    Ring Main Circuits

    Grading has now been lost !

    2.1 0.50.9 0.11.31.7

  • 8/10/2019 Dir OC + EF Protn_APPS

    5/72

    > Directional Overcurrent and Earthfault Protection5 5

    Need for Direct ion al Con trol

    Generally required if current can flow in both directions

    through a relay location

    e.g. Parallel feeder circuits

    Ring Main Circuits

    Relays operate for current flow in direction indicated

    (Typical operating times shown)

    0.9 0.10.5 0.90.50.1

  • 8/10/2019 Dir OC + EF Protn_APPS

    6/72

    > Directional Overcurrent and Earthfault Protection6 6

    Ring Main Circui t

    With ring closed :

    Both load and fault current may flow in eitherdirection along feeder circuits

    Thus, directional relays are required

    Note: Directional relays look into the feeder

    Need to establish setting philosophy

    51 67

    51

    Load

    67 67

    Load

    67

    67 67

    Load

  • 8/10/2019 Dir OC + EF Protn_APPS

    7/72> Directional Overcurrent and Earthfault Protection7 7

    Ring Main Circui t

    Procedure :

    1. Open ring at A

    Grade : A'

    - E'

    - D'

    - C'

    - B'

    2. Open ring at A'

    Grade : A - B - C - D - E

    Typical operating times shown.

    Note : Relays B, C, D, E may be non-directional.

    1.30.1

    0.1 0.90.5

    0.9

    0.5

    B'

    A'

    B

    E E'

    A

    1.7

    D'

    D

    1.7

    1.3

    C' C

  • 8/10/2019 Dir OC + EF Protn_APPS

    8/72> Directional Overcurrent and Earthfault Protection8 8

    Ring System w ith Two Sources

    Discrimination between all relays is not possible due to differentrequirements under different ring operating conditions.

    For F1 :- B must operate before A

    For F2 :- B must operate after A

    Not

    Compatible

    B' B C' C

    D D'

    F1

    B

    F2

    A

    A'

  • 8/10/2019 Dir OC + EF Protn_APPS

    9/72> Directional Overcurrent and Earthfault Protection9 9

    Ring System w ith Two Sources

    Option 1

    Trip least important source instantaneously then treat as normal ringmain.

    Option 2

    Fit pilot wire protection to circuit A - B and consider as common sourcebusbar.

    A

    B

    Option 1Option 1Option 1

    Option 2 Option 2

    50

    PW PW

  • 8/10/2019 Dir OC + EF Protn_APPS

    10/72> Directional Overcurrent and Earthfault Protection10 10

    Parallel Feeders

    Non-Directional Relays :-

    Conventional Grading :-

    Grade A with C

    and Grade B with D

    Relays A and B have

    the same setting.

    51

    51

    A

    D

    Load

    51 B

    51 C

    A & B

    C & D

    Fault levelat F

    Operat

    ingTime

  • 8/10/2019 Dir OC + EF Protn_APPS

    11/72> Directional Overcurrent and Earthfault Protection11 11

    Parallel Feeders

    Consider fault on one feeder :-

    Relays C and D see the same fault current (I2). As C and

    D have similar settings both feeders will be tripped.

    51 A 51C

    51 B 51D

    LOAD

    I1

    + I2

    I1

    I2

  • 8/10/2019 Dir OC + EF Protn_APPS

    12/72> Directional Overcurrent and Earthfault Protection12 12

    Parallel Feeders

    Solution:- Directional Control at C and D

    Relay D does not operate due to current flow in the reverse

    direction.

    51 A 67C

    51 B 67D

    LOAD

    I1

    + I2

    I1

    I2

  • 8/10/2019 Dir OC + EF Protn_APPS

    13/72> Directional Overcurrent and Earthfault Protection13 13

    Parallel Feeders

    Setting philosophy for directional relays

    Load current always flows in non-operate direction.

    Any current flow in operate direction is indicative of a fault

    condition.

    51A 67

    E

    51 B 67

    C

    D

    Load

    51

  • 8/10/2019 Dir OC + EF Protn_APPS

    14/72> Directional Overcurrent and Earthfault Protection14 14

    Parallel Feeders

    Usually, relays are set :-

    - 50% of full load current (note thermal rating)

    - IDMT rather than DT

    - Minimum T.M.S. (0.1)

  • 8/10/2019 Dir OC + EF Protn_APPS

    15/72> Directional Overcurrent and Earthfault Protection15 15

    Paral lel Feeder Applicat ion

    P

    B

    B

    D

    D

    Load

    Load

    If3

    A C

    If1If2/2 If2

    BC

    D

    Ifmax

    A

    Grade A with B with C at If1

    (single feeder in service)

    GradeBwithDatIf3=If1

    (upper feeder open at P)

    Grade A with B at If2

    (both feeders in service)

    - check that sufficient margin existsfor bus fault at Q when relay A seestotal fault current If2, but relay Bsees only If2/2.

    If1

    If2

    M

    M = MarginM

    M

    Q

  • 8/10/2019 Dir OC + EF Protn_APPS

    16/72> Directional Overcurrent and Earthfault Protection16 16

    Advantage : Reduced number of grading

    stages

    6767

    51

    51

    5151

    P1

    P1

    S1

    S1

    S2

    S2

    P2

    P2

    Grid supply

    Part ial Different ial Scheme

  • 8/10/2019 Dir OC + EF Protn_APPS

    17/72> Directional Overcurrent and Earthfault Protection17 17

    Establ ish ing Direct ion

  • 8/10/2019 Dir OC + EF Protn_APPS

    18/72> Directional Overcurrent and Earthfault Protection18 18

    Establ ishing Direct ion :- Polar ising Quant i ty

    The DIRECTIONof Alternating Current may only bedetermined with respect to a COMMONREFERENCE.

    In relaying terms, the REFERENCEis called the POLARISING

    QUANTITY.

    The most convenient reference quantity is POLARISINGVOLTAGEtaken from the Power System Voltages.

  • 8/10/2019 Dir OC + EF Protn_APPS

    19/72

  • 8/10/2019 Dir OC + EF Protn_APPS

    20/72> Directional Overcurrent and Earthfault Protection20 20

    Direct ional Decision by Phase Comparison (2)

    RESTRAINT when S2lags S1by between 90 and 270 :-

    S2

    S1

    S2

    S2

    S2

    S2S2

    S2

  • 8/10/2019 Dir OC + EF Protn_APPS

    21/72> Directional Overcurrent and Earthfault Protection21 21

    Polarising Voltage for A Phase Overcurrent Relay

    OPERATE SIGNAL = IA

    POLARISING SIGNAL :- Which voltage to use ?

    Selectable from

    VA

    VB

    VC

    VA-B

    VB-C

    VC-A

  • 8/10/2019 Dir OC + EF Protn_APPS

    22/72> Directional Overcurrent and Earthfault Protection22 22

    Directional Relay

    Applied Voltage : VA

    Applied Current : IA

    Question :

    - is this connection suitable for a typical power system ?

    IA

    VA

    Operate

    Restrain

    VAF

    IAF

  • 8/10/2019 Dir OC + EF Protn_APPS

    23/72

    > Directional Overcurrent and Earthfault Protection23 23

    Polar ising Voltage

    Applied Voltage : VBC

    Applied Current : IA

    Polarising voltage remainshealthy

    Fault current is near centreof characteristic

    IA

    VBC

    ZERO SENSITIVITYLINE

    VA

    IAF

    IVBC

    VBC

    MAXIMUM SENSITIVITY LINE

    C

  • 8/10/2019 Dir OC + EF Protn_APPS

    24/72

    > Directional Overcurrent and Earthfault Protection24 24

    Relay Connect ion Angle

    The angle between the current applied to the relay and thevoltage applied to the relay at system unity power factor

    e.g. 90 (Quadrature) Connection : IA and VBC

    The 90 connection is now used for all overcurrent relays.30 and 60 connections were also used in the past, but nolonger, as the 90 connection gives better performance.

    IA

    VA

    90

    VBC

    VC VB

    Relay Characteris tic A ng le (R C A )

  • 8/10/2019 Dir OC + EF Protn_APPS

    25/72

    > Directional Overcurrent and Earthfault Protection25 25

    Relay Characteris tic Ang le (R.C.A .)

    for Electronic Relays

    The angle by which the current applied to the relay must be

    displaced from the voltage applied to the relay to produce maximumoperational sensitivity

    e.g. 45

    OPERATE

    IAFOR MAXIMUM OPERATESENSITIVITYRESTRAIN

    45

    VA

    RCA

    VBC

    90 C ti 45 R C A

  • 8/10/2019 Dir OC + EF Protn_APPS

    26/72

    > Directional Overcurrent and Earthfault Protection26 26

    90Connec tion - 45R.C.A .

    RELAY CURRENT VOLTAGEA IA VBC

    B IB VCA

    C IC V

    AB

    IA

    VA

    90

    VBVC

    MAX SENSITIVITY

    LINEOPERATE

    IAFOR MAXSENSITIVITYRESTRAIN 45

    45

    135

    VA

    VBC VBC

    90 C ti 30 R C A

  • 8/10/2019 Dir OC + EF Protn_APPS

    27/72

    > Directional Overcurrent and Earthfault Protection27 27

    90Connec tion - 30R.C.A .

    RELAY CURRENT VOLTAGEA IA VBC

    B IB VCA

    C IC V

    AB

    IA

    VA

    90

    VBVC

    VBC30

    30

    OPERATE

    MAXSENSITIVITYLINERESTRAIN

    IAFOR MAXSENSITIVITY

    150

    VA

    VBC

    S l t i f R C A (1)

  • 8/10/2019 Dir OC + EF Protn_APPS

    28/72

    > Directional Overcurrent and Earthfault Protection28 28

    Select ion o f R.C.A . (1)

    90 connection 30 RCA (lead)

    Plain feeder, zero sequence source behind relay

    Overcurrent Relays

  • 8/10/2019 Dir OC + EF Protn_APPS

    29/72

    > Directional Overcurrent and Earthfault Protection29 29

    Select ion o f R.C.A . (2)

    Plain Feeder

    900Connection

    RCA = 300

    Zero seq sourcebehind relay

    rom

    onnemans paper

    S l t i f R C A (3)

  • 8/10/2019 Dir OC + EF Protn_APPS

    30/72

    > Directional Overcurrent and Earthfault Protection30 30

    Select ion o f R.C.A . (3)

    90 connection 45 RCA (lead)

    Plain or Transformer Feeder :- Only Zero Sequence Source is inFront of Relay

    Transformer Feeder :- Delta/Star Transformer in Front of Relay

  • 8/10/2019 Dir OC + EF Protn_APPS

    31/72

    > Directional Overcurrent and Earthfault Protection31 31

    Select ion o f R.C.A . (4)

    Plain Or

    TransformerFeeder

    900Connection

    RCA = 450

    Zero seq sourceIn front of relay

    From

    Sonnemans paper

  • 8/10/2019 Dir OC + EF Protn_APPS

    32/72

    > Directional Overcurrent and Earthfault Protection32 32

    Select ion o f R.C.A . (5)

    Transformer

    Feeder

    900Connection

    RCA = 450

    /Y transformer

    in front of relay

    From

    Sonnemans paper

  • 8/10/2019 Dir OC + EF Protn_APPS

    33/72

    > Directional Overcurrent and Earthfault Protection33 33

    Direct ional Earth faul t Pro tect ion

    Directional Earth Fault

  • 8/10/2019 Dir OC + EF Protn_APPS

    34/72

    > Directional Overcurrent and Earthfault Protection34 34

    Directional Earth Fault

    Requirements are similar to directional overcurrent

    i.e. need operating signaland polarising signal

    Operating Signal

    obtained from residual connection of line CT's

    i.e. Iop = 3Io

    Polarising Signal

    The use of either phase-neutral or phase-phase voltage as

    the reference becomes inappropriate for the comparison withresidual current.

    Most appropriate polarising signal is the residual voltage.

    Residual Voltage (1)

  • 8/10/2019 Dir OC + EF Protn_APPS

    35/72

    > Directional Overcurrent and Earthfault Protection35 35

    Residual Voltage (1)

    May be obtained from broken delta V.T. secondary.

    Notes :

    1. VT primary must be earthed.

    2. VT must be of the '5 limb' construction (or 3 x single phase units)

    VRES= VA-G + VB-G+ VC-G = 3V0

    A

    BC

    VRES

    VC-GVB-GVA-G

    Residual Voltage (2)

  • 8/10/2019 Dir OC + EF Protn_APPS

    36/72

    > Directional Overcurrent and Earthfault Protection36 36

    Residual Voltage (2)

    Solidly Earthed System

    Residual Voltage at R (relaying point) is dependant upon ZS/ ZL ratio.

    3ExZ2ZZ2Z

    ZV

    L0L1S0S1

    S0

    RES

    E S R FZLZS

    A-G

    VCVC VC

    VB VBVB

    V

    RES

    VAVA

    V

    RES

    VBVCVCVC VBVB

    VAVA

    Residual Voltage (3)

  • 8/10/2019 Dir OC + EF Protn_APPS

    37/72

    > Directional Overcurrent and Earthfault Protection37 37

    Residual Voltage (3)

    Resistance Earthed System

    3Ex3ZZ2ZZ2Z

    3ZZV

    EL0L1S0S1

    ES0

    RES

    VA-G

    VA-GVA-G

    VA-G

    VB-GVC-G

    G.FG.F

    VB-G

    V

    RES

    V

    RES

    RES

    VC-GVC-GVC-G

    VC-G VB-GVC-G

    VB-G VB-G VB-G

    E

    N

    G

    S R FZLZ

    S

    ZE A-G

    G.F

    Relay Characteris tic A ng le (R C A )

  • 8/10/2019 Dir OC + EF Protn_APPS

    38/72

    > Directional Overcurrent and Earthfault Protection38 38

    Relay Characteris tic Ang le (R.C.A .)

    Voltage Polarising Signal

    Rotate VRESby 180O

    to obtain voltage polarisation signal0O, -45Oor -60OR.C.A. applied for maximum sensitivity

    e.g. -45V

    A

    V

    C

    V

    B

    VF

    VRES

    Rotate V

    RES

    by 180

    MAX SENSITIVITYLINE

    IRESFOR MAXSENSITIVITY-45

    OPERATE

    RESTRAIN

    Residual Voltage Polarisat ion

  • 8/10/2019 Dir OC + EF Protn_APPS

    39/72

    > Directional Overcurrent and Earthfault Protection39 39

    Residual Voltage Polarisat ion

    Relay Characteristic Angle

    0 - Resistance/Petersen Coil earthed systems

    -45 (Ilags V) - Distribution systems (solidly earthed)

    -60 (Ilags V) - Transmission systems (solidly earthed)

    +90 (Ileads V) - Insulated systems

    Zero Sequence Network :-

    V0 = 0 - I0 (ZS0+ 3R)

    (Relay Point)

    ZL0ZS0 I0

    V03R

  • 8/10/2019 Dir OC + EF Protn_APPS

    40/72

    App lication (1/11)

  • 8/10/2019 Dir OC + EF Protn_APPS

    41/72

    > Directional Overcurrent and Earthfault Protection41 41

    App lication (1/11)

    Typ ical UK Sub-Transm ission Protect ion System

    Distance protection (21), without signalling, is commonly used at

    sub-transmission levels

    Intertripping is used to supplement the distance protection by

    opening the LV breaker

    F1

    LV Load

    67

    Sub Transmission Network

    LV Network

    Intertripping

    Channel

    IT

    21

    CB1 CB2

    CB4

    Embedded

    generation

    CB3

    Faults at F1 cleared by:

    Distance protection at CB1and CB2

    Intertripping to CB4

    DOC (67) provides back-up in theevent of intertripping failure

    App lication (2/11)

  • 8/10/2019 Dir OC + EF Protn_APPS

    42/72

    > Directional Overcurrent and Earthfault Protection42 42

    App lication (2/11)

    Direct ional Protect ion

    Protection is naturally insensitive to load current (IA-LOAD), by virtue of itsdirection

    Since load current resides in the restraining region, a setting of 0.5In isoften selected

    DOC protection without embedded generation :-

    Operate

    Restrain

    VA

    VBVC

    RCA

    VBC

    (VPOL)

    45

    IA-LOAD

    IAF

    F1(A-B)

    67

    Sub Transmission NetworkCB1 CB2

    CB4CB3

    Normal

    LoadDirection

    (IA-LOAD)

    IAF

    IAF

    App lication (3/11)

  • 8/10/2019 Dir OC + EF Protn_APPS

    43/72

    > Directional Overcurrent and Earthfault Protection43 43

    App lication (3/11)

    Impact of Embedded Generat ion

    Excess generation is exported back on to the sub-transmission network

    Exported current (IA-EXP) resides in the operate region

    Unless measures are taken, the DOC relay mal-operates during peakexport conditions

    Increase threshold?

    Operate

    Restrain

    VA

    VBVC

    RCA

    VBC

    (VPOL)

    45

    IA-LOAD

    IA-EXP

    67

    Sub Transmission NetworkCB1 CB2

    CB4CB3

    Normal

    LoadDirection

    (IA-LOAD) IA-EXPEmbedded

    Generation

    IA-EXP

    App lication (4/11)

  • 8/10/2019 Dir OC + EF Protn_APPS

    44/72

    > Directional Overcurrent and Earthfault Protection44 44

    App lication (4/11)

    Problem.

    Increasing the current setting (IS

    ) to, say, 1.2In ensures stability of theDOC protection during peak export conditions. But.

    Reducing the sensitivity creates a potential blind spot for the DOC

    protection. This is a problem if :-

    67

    Sub Transmission NetworkCB1 CB2

    CB4CB3

    Embedded

    Generation

    F

    Potential

    Blind Spot

    IS> (IF1+IF2)

    The intertripping scheme fails

    to function and we are reliant

    of the DOC relay to clear the

    fault

    The embedded generation isminimal or none existent

    during the fault condition

    IF1+

    IF2

    IF1

    IF2

    IF1

    App lication (5/11)

  • 8/10/2019 Dir OC + EF Protn_APPS

    45/72

    > Directional Overcurrent and Earthfault Protection45 45

    App lication (5/11)

    Solut ionDOC w ith Load Bl inding

    Relay determines the difference between fault and load conditions bythe change in system impedance

    DOC protection is:

    Inhibited during load conditions, thus permitting export of excess generation

    Allowed to operate for faults providing the correct direction

    67

    CB1 CB2

    CB4CB3

    Embedded

    Generation

    F

    Potential

    Blind Spot

    IS> (IF1+IF2)

    IF1+IF2

    IF1

    IF1

    Load blinding originates from distance protection relays:

    jX

    R

    Fault Impedance

    (F)

    Load Locus

    (lagging VARs)

    Load Locus

    (leading VARs)

    Load Blinder

    Z behind

    relay

    Z in front

    of relayVS

    VS

    App lication (6/11)

  • 8/10/2019 Dir OC + EF Protn_APPS

    46/72

    > Directional Overcurrent and Earthfault Protection46 46

    App lication (6/11)

    Load Bl inder Character ist ic

    4 main settings denote the shape and behaviour of the blindercharacteristic:-

    ZMIN Minimum impedance threshold

    Load angle setting

    V< Voltage threshold to disable load blinder

    I2

    > Negative sequence threshold to disable load blinder

    How to set?jX

    R

    Load Locus

    (Import)

    Load Locus

    (Export)

    1

    2

    3

    4

    ZMIN1ZMIN2

    Application(7/11)

  • 8/10/2019 Dir OC + EF Protn_APPS

    47/72

    > Directional Overcurrent and Earthfault Protection47 47

    Application(7/11)

    Load Bl inder Sett ings

    ZMIN1 Minimum impedance threshold (Export)

    Set below the minimum load impedance

    Based upon rated current and rated voltage

    Include safety margin if required

    Example: for a 33kV system with a 600/5 CT (no margin):

    ZMIN2 Not required as imported load is naturally in the restrainingregion of the DOC relay

    inargmRatingPrimaryCT3

    ph)-(phltagePrimary VoRated(primary)ZMIN

    7.310063

    1033(primary)Z

    3

    MIN

    App lication (8/11)

  • 8/10/2019 Dir OC + EF Protn_APPS

    48/72

    > Directional Overcurrent and Earthfault Protection48 48

    App lication (8/11)

    Load Bl inder Sett ing

    Load angle setting

    Set above worst case power factor angle

    Include safety margin of typically 15

    Equal in inductive and capacitive reactance regions ( 1 = 2)

    Hence :-

    Example: lowest power factor = 0.85:

    15FactorPowerOSC -121

    471585.0OSC -121

    App lication (9/11)

  • 8/10/2019 Dir OC + EF Protn_APPS

    49/72

    > Directional Overcurrent and Earthfault Protection49 49

    App lication (9/11)

    Load Bl inder Sett ing

    V< Undervoltage threshold

    Designed to disable the load blinder during fault conditions

    Must disable load blinder for faults with minimum embedded generation(VFAULT 0.5VN)

    Disabling load blinder for faults with maximum embedded generationless important due to increase in fault current

    Recommended setting = 0.7VN

    Hence :-

    Example: For 33kV system:

    i.e. Operates if any ph-nvoltage falls below 13.3kV

    kV3.1331033.70V

    3

    jX

    47

    ZMIN=

    31.7Restraining

    region

    47

    Import region

    naturally

    blocked by

    DOC blindercharacteristic.

    Fault Impedance

    (HV fault)

    Restraining

    region

    R

    App lication (10/11)

  • 8/10/2019 Dir OC + EF Protn_APPS

    50/72

    > Directional Overcurrent and Earthfault Protection50 50

    App lication (10/11)

    Load Bl inder Character ist ic Setting Criteria (I2>)

    I2> Negative sequence current threshold

    Designed to disable the load blinder during unbalanced fault conditions where thephase to neutral voltage collapse is insufficient (common with delta / startransformers)

    Phase to Phase to Ground being the worst case

    Calculation assumes zero arc resistance to ground resulting in lowest possible I2component

    Sequence analysis gives the following setting guideline :-

    Example: Assuming IS= 0.5 IFLC

    i.e. Load blinder turns off ifI2component is above 0.166A sec

    secA..

    0.38I 1660600

    52450

    2

    S0.38II2

    67

    30MVA

    132kV

    33kV

    600/1 Full load current (IFLC)

    = 524A at 33kV

    App lication (11/11)

  • 8/10/2019 Dir OC + EF Protn_APPS

    51/72

    > Directional Overcurrent and Earthfault Protection51 51

    pp ( )

    Hyb rid Load B l inder / DOC Character ist ic

    (A -Phase Element)

    Import / Export LoadConditions

    Fault Condition

  • 8/10/2019 Dir OC + EF Protn_APPS

    52/72

    Insulated Sys tems (2)

  • 8/10/2019 Dir OC + EF Protn_APPS

    53/72

    > Directional Overcurrent and Earthfault Protection53 53

    y ( )

    Faulty Feeder

    VRES

    a b

    cIca

    Icb

    Ic-3I

    c

    Healthy Feeders

    VRES

    Ic = Ica + IcbRCA

    OperateRestrain

    VPOL

    -2IcRCA

    OperateRestrain

    VRES

    VPOL

    Peterson Co il Earthed Sys tems (1)

  • 8/10/2019 Dir OC + EF Protn_APPS

    54/72

    > Directional Overcurrent and Earthfault Protection54 54

    IL

    y ( )

    a b c

    Source

    IcbIca

    Ic

    IcbIca

    Ic

    IcbIca

    2Ic

    Location of CT's

    3IcIc

    IL

    IL

    Peterson Co il Earthed Sys tems (2)

  • 8/10/2019 Dir OC + EF Protn_APPS

    55/72

    > Directional Overcurrent and Earthfault Protection55 55

    y ( )

    Peterson Co il Earthed Sys tems (3)

  • 8/10/2019 Dir OC + EF Protn_APPS

    56/72

    > Directional Overcurrent and Earthfault Protection56 56

    Negative Phase Sequence Voltage Polarisat ion

  • 8/10/2019 Dir OC + EF Protn_APPS

    57/72

    > Directional Overcurrent and Earthfault Protection58 58

    Transmission Systems

    Directional earth fault used as back-up protection

    Can form part of a directional scheme

    VRESmight be unreliable due to mutual coupling

    Unsuitable VT for VRESmeasurement (i.e. open delta, 3-limb)

    Negative Sequence Network :-

    V2 = 0I2 (ZS2)

    ZL2ZS2 I2

    V2

    (Relay Point)

    ZS1=ZS2

    ZL1=ZL2

    Current Polar ising

  • 8/10/2019 Dir OC + EF Protn_APPS

    58/72

    > Directional Overcurrent and Earthfault Protection59 59

    A solidly earthed, high fault level (low source impedance) system

    may result in a small value of residual voltage at the relaying point. If

    residual voltage is too low to provide a reliable polarising signal thena current polarising signal may be used as an alternative.

    The current polarising signal may be derived from a CT located in a

    suitable system neutral to earth connection.

    e.g.

    POL

    OP

    DEF Relay

    Current Polarising (1)

  • 8/10/2019 Dir OC + EF Protn_APPS

    59/72

    > Directional Overcurrent and Earthfault Protection60 60

    POLDEF RELAY

    INCORRECTOP

    Direction of current depends on fault

    position

    Current Polarising (2)

  • 8/10/2019 Dir OC + EF Protn_APPS

    60/72

    > Directional Overcurrent and Earthfault Protection61 61

    POLDEF RELAY

    CORRECTOP

    Current Polarising (3)

  • 8/10/2019 Dir OC + EF Protn_APPS

    61/72

    > Directional Overcurrent and Earthfault Protection62 62

    POLDEF RELAY

    CORRECT IFZLO+ ZSOISPOSITIVE

    S

    OP

    Current Polarising (4)

  • 8/10/2019 Dir OC + EF Protn_APPS

    62/72

    > Directional Overcurrent and Earthfault Protection63 63

    POL DEF RELAY

    OP

    CORRECT

    Virtual Curren t Polarising (1)

  • 8/10/2019 Dir OC + EF Protn_APPS

    63/72

    > Directional Overcurrent and Earthfault Protection64 64

    The faulted phase is not considered in the residual

    voltage calculation.

    The polarising quantity is in the same direction as

    Vres.Applicable even where solid earthing immediately behind

    the IED prevents residual voltage from being developed.

    Faulted Phase Polarising

    A VB + VC

    B VA + VCC VA + VC

    Au to Transfo rmers (1)

  • 8/10/2019 Dir OC + EF Protn_APPS

    64/72

    > Directional Overcurrent and Earthfault Protection65 65

    ZT

    ZLZHSOURCE

    ZSSOURCE

    DEFRELAY

    Neutral connection is suitable for currentpolarising if earthfault current flows up the

    neutral for faults on H.V. & L.V. sides.

    For LV Faults

  • 8/10/2019 Dir OC + EF Protn_APPS

    65/72

    > Directional Overcurrent and Earthfault Protection67 67

    T

    H L

    IN= 3 (ILO- IHO)

    IH I

    L

    For HV Faults

  • 8/10/2019 Dir OC + EF Protn_APPS

    66/72

    > Directional Overcurrent and Earthfault Protection68 68

    T

    H L

    IN = 3 (IHO- ILO)

    IH IL

    Au to-Transform er Examp le

  • 8/10/2019 Dir OC + EF Protn_APPS

    67/72

    > Directional Overcurrent and Earthfault Protection69 69

    T

    H L

    IN = 3 (IHO- ILO)

    ZS

    ZS0ZL0ZH0IH0 IL0

    I0

    ZT0

    Au to-Transform er Examp le

  • 8/10/2019 Dir OC + EF Protn_APPS

    68/72

    > Directional Overcurrent and Earthfault Protection70 70

    kAn

    kV

    MVA

    x

    p.u.n

    H

    base

    0

    00

    kAn

    kV

    MVA

    x

    Z

    Z

    p.u.n

    Z

    Z

    L

    base

    0

    L000

    T0

    0

    L000

    T0

    L0

    Au to-Transform er Examp le

  • 8/10/2019 Dir OC + EF Protn_APPS

    69/72

    > Directional Overcurrent and Earthfault Protection71 71

    1

    Z

    Z

    kV

    kV

    r

    Z

    Z

    kV

    1

    kV

    1

    fes

    Z

    Z

    kV

    1

    kV

    1

    3

    .MVA

    L000

    T0

    L

    H

    L000

    T0

    L

    N

    L000

    T0

    L

    base

    N

    Au to-Transform er Examp le

  • 8/10/2019 Dir OC + EF Protn_APPS

    70/72

    > Directional Overcurrent and Earthfault Protection72 72

    T

    H L

    IN= 3 (ILO- IHO)

    ZS

    ZS0ZL0ZH0IH0 IL0

    I0

    ZT0

    IH0 = 0

    IN = 3IL0 which is +ve.

    Direct ional Contro l

  • 8/10/2019 Dir OC + EF Protn_APPS

    71/72

    > Directional Overcurrent and Earthfault Protection73 73

    Static Relay(MCGG + METI)

    Characteristic Selectable

    51 I

    Overcurrent Unit(Static)

    67

    V

    I

    M.T.A. Selectable

    Directional Unit(Static)

    Numerical Relay Direct ional Characterist ic

  • 8/10/2019 Dir OC + EF Protn_APPS

    72/72

    Characteristic angle cc = -95 0 95

    in 1 steps

    Polarising thresholdsVp 2V to 320V

    in 2V steps

    VT supervisionselectively block operation

    Zone of

    forward start

    forward operation

    Reverse start

    c - 90) c + 90)

    c

    +Is

    -Is