diesel powered generating set mbh1900dm - spp | power ·  · 2015-01-21630a, vacuum or sf6...

4
Standard Generating set Features Engine Specifications Alternator Specifications Compliance Standards Engine - GE8V228, EFI diesel engine, heavy duty, 1000rpm / 900rpm. Alternator - Double bearing, Class F insulation, Different voltage range is available. Air filter. Cooling system - Tropical remote radiator, heavy duty, 50°C with no derating. Air Starting System Base Frame - Heavy duty steel base frame, with Spring type anti-vibration mounts. Exhaust - Residential type muffler, flexible stainless steel bellows, Noise Attenua- tion, Exhaust Temperature Monitoring and Protection Automatic Control Panel - Control, moni- toring, protection, synchronizing. Genset Configuration Type: Open set Enclosed set - Sound & weather proof, ventilation, Air filtration. Switchgear - Metalclad withdrawable 3.3/6.6/11KV, 630A, vacuum or SF6 Switchgear - Air Circuit Breaker (ACB) 2500/3200A for Low Voltage: 0.38/0.4/0.415 kV(for single units only). Compliance Standards - ISO9001 / ISO3046 / ISO8528 GE 8V228 V-Type Direct Injection 8-cylinder Diesel Engine Idle Speed 440 rpm Rated Speed 50 Hz: 1000 rpm Rated Speed 60 Hz: 900 rpm Brushless double bearing, revolving field 6-poles for 50Hz 1000rpm 8-pole for 60Hz 900rpm Winding Pitch: ca.5/6 Cooling: IC01-Open Circuit Ventilation Enclosure: IP23 Heavy Duty Bearing Class F Insulation (Stator and Rotor) The generating set complies with ISO 3046, ISO 8528. Bearing Temperature Detectors (2xPT100 per phase) monitoring and protection Teminal Box for connection Alternator Sand Filter Alternator meets IEC 60034 Voltage: 0.4, 3.3, 6.6, 6.9, 11, 13.8 KV 50 Hz/60 Hz Elastic Coupling used for a perfect alignment between Engine/Alternator 4 Terminals Star point connected in terminal box Stator Temperature Detectors(2xPT100 per phase) monitoring and protection EFI controller: (Governor) Engine Governor Unit (EC2+) Engine Inputs Outputs Construction 4 Valves per Cylinder Forged Steel Type 4 Stroke, Electronic Fuel Injection Prime Rating (PRP) Continuous Rating (Cont) 50Hz/1000 rpm 60Hz/900 rpm 1917 kVA 1534 kWe 1725 kVA 1380 kWe 1744 kVA 1395 kwe 1569 kVA 1255 kwe Diesel Powered Generating Set MBH1900DM www.MBH.de

Upload: hoangnguyet

Post on 05-Apr-2018

213 views

Category:

Documents


1 download

TRANSCRIPT

Standard Generating set Features

Engine Specifi cations

Alternator Specifi cations

Compliance Standards

Engine - GE8V228, EFI diesel engine, heavy duty, 1000rpm / 900rpm.Alternator - Double bearing, Class F insulation, Different voltage range is available.Air fi lter.Cooling system - Tropical remote radiator, heavy duty, 50°C with no derating.Air Starting System

Base Frame - Heavy duty steel base frame, with Spring type anti-vibration mounts.Exhaust - Residential type muffl er, fl exible stainless steel bellows, Noise Attenua-tion, Exhaust Temperature Monitoring and ProtectionAutomatic Control Panel - Control, moni-toring, protection, synchronizing.

Genset Confi guration Type:Open set Enclosed set - Sound & weather proof, ventilation, Air fi ltration.Switchgear - Metalclad withdrawable 3.3/6.6/11KV, 630A, vacuum or SF6 Switchgear - Air Circuit Breaker (ACB) 2500/3200A for Low Voltage: 0.38/0.4/0.415 kV(for single units only).Compliance Standards - ISO9001 / ISO3046 / ISO8528

GE 8V228

V-Type Direct Injection8-cylinder Diesel EngineIdle Speed 440 rpmRated Speed 50 Hz: 1000 rpmRated Speed 60 Hz: 900 rpm

Brushless double bearing, revolving fi eld6-poles for 50Hz 1000rpm8-pole for 60Hz 900rpmWinding Pitch: ca.5/6Cooling: IC01-Open Circuit Ventilation Enclosure: IP23Heavy Duty BearingClass F Insulation (Stator and Rotor)

The generating set complies with ISO 3046, ISO 8528.

Bearing Temperature Detectors (2xPT100 per phase) monitoring and protectionTeminal Box for connectionAlternator Sand FilterAlternator meets IEC 60034Voltage: 0.4, 3.3, 6.6, 6.9, 11, 13.8 KV50 Hz/60 Hz

Elastic Coupling used for a perfect alignment between Engine/Alternator4 Terminals Star point connected in terminal boxStator Temperature Detectors(2xPT100 per phase) monitoring and protection

EFI controller: (Governor)

Engine Governor Unit (EC2+)Engine Inputs Outputs

Construction

4 Valves per Cylinder Forged Steel

Type

4 Stroke, Electronic Fuel Injection

Prime Rating (PRP) Continuous Rating (Cont)

50Hz/1000 rpm

60Hz/900 rpm

1917 kVA1534 kWe1725 kVA1380 kWe

1744 kVA1395 kwe1569 kVA1255 kwe

Diesel Powered Generating Set

MBH1900DMwww.MBH.de

Intake Air System

Heavy Duty Intake Air FilterDuct for distribution air inletMechanical Gauge for Air Differential Pressure with Alarming Contact

Auxiliaries’ Transformer (In case of MV Output)

Designed and rated based on the Gen-set auxiliaries:- Dry type or Oil type- Equipped with Buchholz Relay- Temperature Monitor Control Panel for alarm and trip - Connection: Yno-yn

Exhaust System

Silencer Residential TypeStainless Steel BellowExhaust pipe Jacketing (In case of enclosed set)

Auxiliaries

Electrical System

Air Starting System

Base Mounted Air Compressors (qty=1)Vertical Air Tank Receiver of 500Lt capac-ity (1000 Liters Optional)Mechanical gauge for starting air pressure indicator with alarming contact.Pressure gauge indicator installed on the air tank receiver.Air motor starter solenoid (24VDC)Compressors Control Panel (Compressors Redundancy)Pressure Switches:- Low Pressure Alarm- Start 1st Compressor- High Pressure Alarm

Voltage Regulation

The voltage Regulator provides ±0.25% regulationThree protection functions: fi eld overvoltage, and loss of sensingProgrammable stability settings to optimize transient performance

Fuel System Specifi cation

Fuel Water SeparatorManual and/or automatic fuel pumpDuplex fuel oil fi lterMechanical Gauge for Fuel oil pressure with alarming contact

Oil System

Lube Oil FilterLube Oil/HT water preheating systemPre-lube oil pumpCentrifugal-Self Cleaning Oil Filter with alarming contact to control panelMechanical Gauge for Engine Lube Oil Inlet Temperature with alarming contactMechanical Gauge Lube Oil pressure with alarming contact

Water System

LT/HT table radiator with electrical cooling fans.Engine driven water pumpDrain Cooling fansThermostatic ValvesHT Water Pre-Heating System Mechanical Gauge for Water Pressure Inlet with alarming contactMechanical Gauge for Water Temperature with alarming contactExpansion Tank

Frequency Regulation

Isochronous under varying loads from no load to 100% full load

Random Frequency Variation

Will not exceed ±0.25 of its mean value for constant load

MBH1900DM

LV Distribution Panel-Motor Control Center

To supply and sense all the generating auxiliaries such as: Radiator Fans, Engine Air Inlet Fans, Air Compressors, Pre-lube Pump, DC Charger, Swg Power Supply.Auxiliaries Auto/off/manual selectorFault/run LEDSpare circuit for future useSupply Available LEDs (R,S,T)Fixed Type, total coordination

Start-up Generator (Optional)

In case of a mains power supply, the Start-up Generator can be started either manually by the operator or automatically following a mains failure to supply the Gen-set auxiliaries:- Pre-heater- Pre-lube- Air CompressorsThe BOG is rated accordingly.Medium Voltage Switchgear

(In case of MV Output)

Rated Voltage: 11KV or 6.6KV (for other voltages please refer to company)IP 4XMV Circuit Breaker3 PolesGenerator Management and protection Outgoing with fuse protection for Genset auxiliaries transformer (Optional)

Low Voltage Breaker (In case of LV Output)

ACB from GE or Mitsubishi or equivalent

Control System

DC Panel

2x100AH Batteries with a suitable battery charger (24VDC/20A) sized to suit all DC components: - Generator Control Panel - Auxiliaries; transformer control panel - MCC PanelNote: In case of 110VDC additional set of batteries with suitable battery charger are available

Genset Controller

Operation Mode- Automatic Mains Failure- Island Operation- Fixed Power/Base load- Peak Shaving- Load Take Over- Mains Power Export

Protection (ANSI) - Over Current- Reversed Power- Oil Pressure / Temperature- Cooling Water Pressure / Temperature- Fuel Level

Engine Control- Start/Stop/Pre-lube sequence- Generator breaker Closing/Opening/ Synchronizing sequence.- Run and Stop Coil.- Relay output for Governor Control- Relay output for AVR Control- Different Operation Mode- Modbus (TCP/IP) Communication Port

Genset Local Display

Controlling and Monitoring of the System via Touch ScreenTouch Buttons for Generator Set Operation Modes and Start/Stop SequenceTouch Buttons for Generator Breaker Open/Close OperationsAlarm List DisplayData Monitoring Window and TrendingConnection to AGC Display Port using Ethernet

EFI Controller: (EC2+)

- Variable Fuel Injection Timing- Finer Control of Fuel Volume- Higher Injection Pressure- Reduced Maintenance of Mechanical Components

Human Machine Interface Lube Oil Pump Control System Fuel Control SystemHigh Fuel Level WarningLow Fuel Level WarningLow Fuel Level Shutdown

MBH1900DM

Set Output VoltageContinuous Rating (kWe)Continuous Rating (KVA)Prime Rating (kWe)Prime Rating (KVA)Engine MakeEngine ModelCylindersEngine BuildStandard Governor/ClassAspiration and CoolingBore and StrokeCompression RatioCubic CapacityStartingMininmum Ambient Temp.Engine Coolant Capacity

Direction of Rotation (Flywheel)Gross Engine Output (Prime)Gross Engine Input (LTP) Alternator Voltage Regulation Set Output Frequency Speed Alternator Insulation ClassFuel consumption Prime (LTP)Recommended FuelLubrication System Oil CapacityCoolant CapacityExhaust Temperature @ rated loadExhaust Gas pressure (max) Exhaust Gas FlowRadiator*Fan Temperature (IN/OUT)Lubrication Oil Consumption

50 Hz

* Based on site ambient condition

60 Hz 50 Hz 60 Hz 0.4, 3.3, 6.6, 6.9, 11, 13.8

1395

1744

1534

1917

GE

8 V228

8

V-Type

EFI-Electronic

Turbocharged-intercooled

228.6mmx266.7mm

15.7 : 1

87.6 Liters

Air Starter

5ºC

151 Liters

1255

1569

1380

1725

GE

8 V228

8

V-Type

EFI-Electronic

228.6mmx266.7mm

15.7 : 1

87.6 Liters

Air Starter

5ºC

151 Liters

CCW

1598 KWm

1743 kWm

±0.25 %

50 Hz

1000 RPM

Class F

371 Liters/Hr

#2 Diesel

606 Liters

TBD

427 °C

24.9 mbar

6 m3/s

TBD

50/70ºC

1.0 Liter/Hr

CCW

1438 KWm

1569 kWm

±0.25 %

60 Hz

900 RPM

Class F

319 Liters/Hr

#2 Diesel

606 liters

TBD

427°C

24.9 mbar

5.4 m3/s

TBD

50/70ºC

0.9 Liters/Hr

TECHNICAL DATA

Generating Set Options

Fire Alarm SystemManual Synchronizing FeatureRemote Monitoring Station (Up to 4 Gen-Sets)

Extended Air Tank Receiver Capacity (1000 Liters)Additional Air Compressor for Redun-dancy OperationSpace Heater single Phase for Alternator

Black Start and/or Emergency Application Features:- Black Start Control System (Auto Black Start and Manual Black Start)- Emergency Diesel Generator- Mimic panel

Dimensions and Weight-OPEN SET

Dimensions and Weight-ENCLOSED SET

Dimensions and Weight-ELECTRICAL ROOM (OPTIONAL)

ModelMBH1900DM

Open

Air Tank Receiver Rack

ModelMBH1900DM

Electrical Room (Optional)ISO Radiator

ModelMBH1900DM

Enclosed

Length(mm)8824

3500

Length(mm)5940

Length(mm)12000

Width(mm)2700

1380

Width(mm)2360

Width(mm)3500

Height(mm)3250

2430

Height(mm)2390

Height(mm)3450

Set Weight(kg)

33000

2000

Set Weight(kg)7000

Enclosed Weight(kg)

42000

DS-MBH۱۹۰۰DM-۰۱-C

Maschinenbau Halberstadt GmbH, Rudolf-Diesel-Strasse ۳۸۸۲۰ ,٥۰ Halberstadt, GermanyT. ۳۲۰ ۳۹٤۱ ٤۹+, F. ۲٤۰۳٦ ۳۹٤۱ ٤۹[email protected] - www.MBH.de

Specifi cations may change without notice. Check with your distributor for more information.

Depends on project