diesel generator set mtu 16v4000 ds2250
TRANSCRIPT
Optionalequipmentandfinishingshown.Standardmayvary.Optionalequipmentandfinishingshown.Standardmayvary.
mtu 16V4000 DS2250DieselGeneratorSet
Producthighlights
380V–11kV/50Hz/standbypower/NEA(ORDE)optimized16V4000G74F/waterchargeaircooling
Bene� ts— Lowfuelconsumption— Optimizedsystemintegrationability— Highreliability— Highavailabilityofpower— Longmaintenanceintervals
Support— Globalproductsupportoffered
Standards— Engine-generatorsetisdesignedandmanufacturedinfacilitiescertifiedtostandardsISO2008:9001andISO2004:14001
— GeneratorsetcompliestoISO8528— GeneratormeetsNEMAMG1,BS5000,ISO,DINENandIECstandards
— NFPA110
Power rating— Systemratings:2230kVA-2350kVA— AcceptsratedloadinonestepperNFPA110*— GeneratorsetcompliestoG3accordingtoISO8528-5— GeneratorsetexceedsloadstepsaccordingtoISO8528-5*
Performance assurance certi� cation (PAC)— Engine-generatorsettestedtoISO8528-5fortransientresponse— 85%loadfactor— Verifiedproductdesign,qualityandperformanceintegrity— Allenginesystemsareprototypeandfactorytested
Complete range of accessories available— Controlpanel— Powerpanel— Circuitbreaker/powerdistribution— Fuelsystem— Fuelconnectionswithshut-offvalvemountedtobaseframe— Starting/chargingsystem— Exhaustsystem— Mechanicalandelectricaldrivenradiators— Mediumandoversizedvoltagealternators
Emissions— NEA(ORDE)optimized
Certi� cations— CEcertificationoption— Unitcertificateacc.toVDE-AR-N4110
* Changestothestandardparametersets(alternator-regulatorand
genset-controller)arenecessary
Application data 1)
EngineManufacturer mtuModel 16V4000G74FType 4-cycleArrangement 16VDisplacement:l 76.3Bore:mm 170Stroke:mm 210Compressionratio 16.4Ratedspeed:rpm 1500Enginegovernor ECU9Maxpower:kWm 1965Aircleaner dry
Fuel systemMaximumfuellift:m 5Totalfuelflow:l/min 20
Fuel consumption 2) l/hr g/kwhAt100%ofpowerrating: 471.1 199At75%ofpowerrating: 358.7 202At50%ofpowerrating: 247.4 209
Liquid capacity (lubrication)Totaloilsystemcapacity:l 300Enginejacketwatercapacity:l 175Intercoolercoolantcapacity:l 50
Combustion air requirementsCombustionairvolume:m3/s 2.5Max.airintakerestriction:mbar 50
Cooling/radiator systemCoolantflowrate(HTcircuit):m3/hr 68.5Coolantflowrate(LTcircuit):m3/hr 30Heatrejectiontocoolant:kW 660Heatradiatedtochargeaircooling:kW 430Heatradiatedtoambient:kW 90Fanpowerforelectr.radiator(40°C):kW 70
Exhaust systemExhaustgastemp.(afterturbocharger):°C 480Exhaustgasvolume:m3/s 6.6Maximumallowablebackpressure:mbar 85Minimumallowablebackpressure:mbar 30
Standardandoptionalfeatures
System ratings (kW/kVA)
Generator model Voltage NEA (ORDE) optimized
without radiator with mechanical radiator
kWel kVA* AMPS kWel kVA* AMPS
LeroySomerLSA52.3S7(LowvoltageLeroySomerstandard)
380V 1864 2330 3540 1808 2260 3434
400V 1864 2330 3363 1808 2260 3262
415V 1864 2330 3242 1808 2260 3144
LeroySomerLSA52.3L12(LowvoltageLeroySomeroversized)
380V 1864 2330 3540 1808 2260 3434
400V 1864 2330 3363 1808 2260 3262
415V 1864 2330 3242 1808 2260 3144
Marathon744RSL7092(LowvoltageMarathon)
380V 1848 2310 3510 1784 2230 3388
400V 1848 2310 3334 1784 2230 3219
415V 1808 2260 3144 1784 2230 3102
Marathon1020FDL7093(LowvoltageMarathonoversized)
380V 1848 2310 3510 1784 2230 3388
400V 1848 2310 3334 1784 2230 3219
415V 1808 2260 3144 1784 2230 3102
Marathon1020FDH7097(Mediumvolt.marathon)
11kV 1864 2330 122 1800 2250 118
LeroySomerLSA53.2XL9(Mediumvolt.LeroySomer)
11kV 1880 2350 123 1808 2260 119
*cosphi=0.8
1 AlldatarefersonlytotheengineandisbasedonISOstandardconditions(25°Cand100mabovesealevel).
2 ValuesreferencedareinaccordancewithISO3046-1.Conversioncalculatedwithfueldensityof0.83g/ml.Allfuelconsumptionvaluesrefertoratedenginepower.
Standard and optional features
Representsstandardfeatures
Representsoptionalfeatures
Cooling system
Jacketwaterpump Thermostat(s) Waterchargeaircooling
Mechanicalradiator Electricaldrivenfront-endcooler Jacketwaterheater
Control panel
Unitcablingwithcodedplugsforeasyconnectionofcustomer-specificcontrols(V0) Pre-wiredcontrolcabinetforeasyapplicationofcustomizedcontroller(V1+) Islandoperation(V2) AutomaticmainsfailureoperationwithATS(V3a) Automaticmainsfailureoperationincl.controlofgeneratorandmainsbreaker(V3b) Islandparalleloperationofmultiplegensets(V4) Automaticmainsfailureoperationwithshort(<10s)mainsparalleloverlapsynchronization(V5)
Mainsparalleloperationofasinglegenset(V6) Mainsparalleloperationofmultiplegensets(V7) Baslercontroller Deifcontroller Completesystemmetering Digitalmetering Engineparameters Generatorprotectionfunctions Engineprotection SAEJ1939engineECUcommunications Parametrizationsoftware Multilingualcapability Multipleprogrammablecontactinputs Multiplecontactoutputs
Eventrecording IP54frontpanelratingwithintegratedgasket Differentexpansionmodules Remoteannunciator Daytankcontrol Generatorwindingtemperaturemonitoring Generatorbearingtemperaturemonitoring ModbusTCP-IP
Generator
4polethree-phasesynchronousgenerator Brushless,self-excited,self-regulating,self-ventilated Digitalvoltageregulator Anticondensationheater StatorwindingY-connected,accessibleneutral(broughtout) ProtectionIP23
InsulationclassH,utilizationacc.toH RadiosuppressionEN55011,group1,cl.B Shortcircuitcapability3xInfor10sec WindingandbearingRTDs(withoutmonitoring) ExcitationbyAREP MountingofCT´s:2coreCT´s Windingpitch:2/3winding Voltagesetpointadjustment±10%
MeetsNEMAMG-1,BS5000,IEC60034-1,VDE0530,DINEN12601,AS1359andISO8528-3requirements LeroySomerlowvoltagegenerator Marathonlowvoltagegenerator Oversizedgenerator Mediumvoltagegenerator
Engine
4-cycle Standardsinglestageairfilter Oildrainextension&shut-offvalve
Closedcrankcaseventilation Governor-electronicisochronous Commonrailfuelinjection
NEA(ORDE)optimizedengine
Connectivity
Theenginesystemautomaticallycollectsandtransfersenginedatatothemanufacturerfromtimetotime.Thedataisusedbythemanufacturerforthepurposesofproduct
developmentandimprovementaswellasserviceoptimization.Userscanloginorregisterviahttps://mtu-go.comandalsogaininsightintothedata.
Standard and optional features
Representsstandardfeatures
Representsoptionalfeatures
Circuit breaker/power distribution
3-polecircuitbreaker 4-polecircuitbreaker
Electrical-actuatedcircuitbreaker BaseframemountedGCB,pre-wiredwithgenerator,readyforcommissioning
Fuel system
Flexiblefuelconnectorsmountedtobaseframe Fuelfilterwithwaterseparator Fuelfilterwithwaterseparatorheavy-duty
Switchablefuelfilterwithwaterseparator Switchablefuelfilterwithwaterseparatorheavy-duty Seperatefuelcooler
Fuelcoolerintegratedintocoolingequipment
Starting/charging system
24Vstarter Redundantstartingsystem
Starterbatteries,cables,rack,disconnectswitch(lockable)
Batterycharger Alternator
Mounting system
Weldedbaseframe Resilientengineandgeneratormounting Modularbaseframedesign
Baseframemountingonfoundation/baseplatewithusingclampingbrackets
Exhaust system
Exhaustbellowswithconnectionflange Exhaustsilencerwith10dB(A)soundattenuation
Exhaustsilencerwith30dB(A)soundattenuation
Exhaustsilencerwith40dB(A)soundattenuation Y-connection-pipe
Power panel
Supplyelectricaldrivenradiatorfrom45kW–75kW
Rolls-Royce Groupwww.mtu-solutions.com/powergen
Weights and dimensions
Drawing above for illustration purposes only, based on a standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design. See website for unit specific template drawings.
Emissionsdata
— Consultyourlocalmtu distributorforemissionsdata.
Sounddata
— Consultyourlocalmtudistributorforsounddata.
Weightsanddimensionsarebasedonopenpowerunitsandareestimatesonly.Consultthefactoryforaccurateweightsanddimensionsforyourspecificengine-generatorset.
System Dimensions (LxWxH) Weight (dry/less tank)
Openpowerunit(OPU) 4766x1810x2330mm 12428kg
Ratingdefinitionsandconditions
— Standbyratingsapplytoinstallationsservedbyareliableutilitysource.Thestandbyratingisapplicabletovaryingloadsforthedurationofapoweroutage.Nooverloadcapabilityforthisrating.RatingsareinaccordancewithISO8528-1,ISO-3046-1,BS5514andAS2789.Averageloadfactor:≤85%.Operatinghours/year:max.500.— Consultyourlocalmtudistributorforderatinginformation.
Subjecttochange.|3237831|Edition01/22|BMC2021-12.