Development of Premise Plumbing Hydraulics-Water Quality Models Juneseok Lee 1 and Andrew J. Whelton 2 1 Civil and Environmental Engineering, San José State University, San José, CA 95192 1 Lyles School of Civil Engineering, Purdue University, West Lafayette, IN 47907 6 TH Biennial Emerging Water Technology Symposium (EWTS) May 15-16, 2018 – Ontario, California

Upload: others

Post on 27-May-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Development of Premise Plumbing Hydraulics-Water

Quality Models Juneseok Lee1 and Andrew J. Whelton2

1Civil and Environmental Engineering, San José State University, San José, CA 951921Lyles School of Civil Engineering, Purdue University, West Lafayette, IN 47907

6TH Biennial Emerging Water Technology Symposium (EWTS)May 15-16, 2018 – Ontario, California

Page 2: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Building Plumbing Safety: Right Sizing Tomorrow's Water Systems for Efficiency, Sustainability, & Public Health

Andrew Whelton, Jade Mitchell, Janice Beecher, Joan Rose, Juneseok Lee, Pouyan Nejadhashemi, Erin Dreelin, Tiong Gim Aw, Amisha Shah, Matt Syal, Maryam Salehi

ACS Spring Meeting 2018

Page 3: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Corporation Stop

Water Main80 psig

Street

Curb Stop

Backflow preventer

Water meter

PREMISE

PLUMBING

SYSTEMS

WATER

DISTRIBUTION

SYSTEMS

Fire Hydrant

Service Line

Lee et al. J (2013) Water Supply AQUA 64(2)

Page 4: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Service Lines

Hot vs. ColdWater Pipes

Water Softener Whole House Filter

Habitat

POUDevices

CorrosionProducts

Water Heater

Fixtures and AeratorsMetals and Plastics

Page 5: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Domestic Hot Water

Some images courtesy of: Gordon & Rosenblatt, LLC

Cartridge FiltersHospital

Food Prep Facility

Premise plumbing is complex

Copper pipe to cPVC pipe

PEX pipe with copper manifold

Page 6: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Water Use Energy Policy Act of 1992

Pre-1994 (4+ gpm)

1994 (2.5 gpm)

2015 (0.5 gpm)

2016? (0.01 gpm)

WaterUse has

DecreasedFrom

Lower-FlowFaucets

Building Water Use has Been Declining

Page 7: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Residential plumbing is critical for the health and safety of populations worldwide.

5-10 million miles of plumbing Water saving & Low-flow devices

Increased water age

Enable contaminant leaching

Disinfectant residual loss

Microorganism proliferation

7

Page 8: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Integrative Hydraulic – WQ Modeling:

Page 9: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Goal: Elucidate the factors & their interactions that affectwater quality through integrative water distribution system-premise plumbing models.

Monitor

Water Quality&

Water Flowat

ReNEWW HouseNature Conservancy

Develop & calibrate plumbing

HydraulicWater quality

models

Developpredictive water quality models

Forresidence time,

plumbing materials,

temperature

9

Page 10: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Area: 266 m2, 4 bedroom, 2 bathConstructed in 1920s & renovated in 2014

10

Retrofitted Net-Zero Energy, Water and Waste

2015: PEX plumbing removed, new PEX plumbing installed, city and rainwater use; City water: Groundwater, treated with KMnO4, free chlorine residual, PVC and Iron water mains

http://www.ReNEWWhouse.com

Page 11: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Pipe Type

Diameter (ID),

cm

Length, m

Total Internal Surface Area,

m2

Cold1.2

41.9 0.3

Hot 40.9 0.3

Cold1.7

35.8 0.3

Hot 38.3 0.4

PEX-A pipe

11

Page 12: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Goal: To better understand link between water use & drinking water quality.Hypotheses:

1. Water quality inside the building influenced by chemical leached by PEX pipes. 2. Fixture usage pattern & water temperature influence organic & bacteria levels in

water.3. Less frequent used fixtures have lower water quality.

Page 13: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

During the 4 month building startup ….

How does cold and hot water quality change?

Water Softener

WaterHeater

Basement

Kitchen Sink

BathSink

TOCTOC

TOC PbCu

Zn

TOCTOC

TOC TOC

TOC

TOC

PbCu

Zn

Pb

Cu

Water Quality?

Water Quality?

MonitoringAfter softenerBasement (cold/hot)Kitchen sink (cold/hot)Bathroom sink (cold/hot)

Online flowOnline fixture tempGrab water sampling• Day 3, 15, 30, 60 & 90• Onsite: pH, chlorine residual,

temp• Lab: TOC, total metals, HPC,

gene copies

Salehi et al. (2018). Chemosphere.https://doi.org/10.1016/j.chemosphere.2017.11.070

Page 14: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Water Usage Monitoring & Analysis

Elapsed Time

Since Last Event

Event Duration

Time (s)

Water Flow (GPS)

4 months = 64,891,484 data points

14

Salehi et al. (2018). Chemosphere.https://doi.org/10.1016/j.chemosphere.2017.11.070

Page 15: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

ParameterTotal Volume

Used

(m3)

Number of

Events

Average

Elapsed Time

(hr)

Maximum

Elapsed Time

(hr)Fixture

Service Line 5.2 3535 0.1 72

Basement-Cold 0.4 60 0.5 72

Basement-Hot 0.04 21 0.7 72

1st Floor-Cold 0.3 619 0.6 72

1st Floor-Hot 0.2 389 0.9 72

2nd Floor-Cold 0.1 145 2.0 72

2nd Floor-Hot 1.0 825 0.5 72

Water Usage Patterns for a Few Fixtures Monitored in December 2015

Page 16: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

16

Water Usage Patterns

❑ During October to December the daily water usagevaried between 0.169-0.245 m3/d.

❑ Basement fixture was the least used (number of eventsat cold: 60-105, hot: 21-69) compared to the otherfixtures in the building (number of events at cold: 145-856, hot: 326-2,230).

❑ During October to December the most frequently usedfixture was the 2nd floor hot water (bathroom sink,number of events per month 2,230).

Page 17: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Pressure Results

Page 18: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72
Page 19: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72
Page 20: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Least

Frequent

Used Fixture

Greatest HPC

Greatest Gene

Copies

Greatest Fe, Zn and Pb

LevelsGreatest

TOC

Least Disinfectant

Residual

During the 4 month startup, bacteria levels increased with time and bacteria were more numerous in hot water vs. cold water

Salehi et al. (2018). Chemosphere.https://doi.org/10.1016/j.chemosphere.2017.11.070

Basement: Pb AL exceededBasement: Zn SMCL exceeded

All locations: Odor SMCL exceeded

Page 21: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

TOC Concentration Increased Inside the Building

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

Basement(Hot)

1st Floor (Hot) 2nd Floor (Hot) Basement(Cold)

1st Floor (Cold) 2nd Floor(Cold)

Diff

eren

ce b

etw

een

Wat

er

Softe

ner a

nd F

ixtu

re T

OC

C

once

ntra

tion

(∆ m

g/L)

Sampling Location

Day 3 Day 15

Day 30 Day 60

Day 90

TOC concentration was greater inside the building

across all fixtures.

0

5

10

15

20

25

WaterSoftener

Basement(Hot)

1st Floor (Hot) 2nd Floor(Hot)

Basement(Cold)

1st Floor(Cold)

2nd Floor(Cold)

Odo

r, TO

N

Sampling Location

Odor (TON) exceeded

US EPA SMCL of 3

21

Page 22: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Several Heavy Metals with Health & Aesthetic Limits were Detected

0

5

10

15

20

25

WaterSoftener

Basement(Hot)

1st Floor(Hot)

2nd Floor(Hot)

Basement(Cold)

1st Floor(Cold)

2nd Floor(Cold)

Pb (µ

g/L)

US EPA Action Level 15 µg/L

22

The basement fixture brass needle valve may have caused maximum Zn (5.9 mg/L), Fe (4.1 mg/L), and Pb (23 μg/L) levels compared to other fixture water samples.

Page 23: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Both HPC & Gene Copy Number Increased at 1st & 2nd Floor

Greatest HPC level (856.7 CFU/mL) at day 90 basement hot water.

Positive correlations between TOC levels & bacterial gene copynumbers at water softener, 1st floor (cold), 2nd floor (cold/hot).

23

Page 24: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Water Quality Summary

❑ The maximum water stagnation time was 72.0 hr.

❑ Bacteria & organic carbon levels increased inside the plumbing system compared to the municipal tap water entering the building.

❑ A greater amount of bacteria was detected in hot water samples compared to cold water samples.

❑ At the basement fixture, where the least amount of water use events occurred, greater organic carbon, bacteria, and heavy metal levels were detected.

Page 25: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Premise Plumbing Hybrid Model

Page 26: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

26

Pipe Inside Phenomenon

Water Flow (pH, Temp, )

(Stagnant / high velocity)

Particles

Biofilm

HOCl NOM DBP

Fe2+AOC

Page 27: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Integrative Hydraulics – WQ models

• Predict drinking water disinfectant residual and microbial quality at each fixture.

• framework of EPANET-MSX using the EPANET programmer’s toolkit• parameters: disinfectant concentrations, DBP, THMs, water age, temperature,

pH, TOC, heavy metal concentration, bulk decay rate constant, wall chlorine demand (wall reaction coefficients), microbiological quality, and turbidity.

• Stochastic nature of water demand: Poisson Rectangular Pulse models and SIMDEUM model.

Page 28: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

At time = t& Extended period• Hydraulic flow and Water quality

simulation which involve multi-species.

• Pressure at service line• Mostly steady state except extreme low/

high pressures• Stochastic demand at each fixture• Calibration of parameters for each

season’s dataWater Mains

Page 29: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Simulation for low flows

• Call EPANET Toolkit from MATLAB;

• Change water demand values based on low demand –Poisson Model Development

• This is iterated many times. • Produce distributions of WQ

parameters – Fe, AOC, Chlorine, etc.

MATLAB

EPANET Toolkit

Low Flow Poisson ModelWQ | Multi-Species

Distributions of WQ at each

fixture

Water Mains

Page 30: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Premise Plumbing Hybrid

Model with EPANET-MSX

1. Hydraulics -Water demand/

pressure

2. Water quality -pH, temp, NOM,

disinfectant, metal, etc.

3. Microbiology -pathogen,

legionella, etc.Plumbing systems Design (layouts,

sizes, fixtures, etc)

Low flowsimulations

AOC, Disinfectant, Pathogen, by -

product

AOC, Disinfectant, Pathogen, by -

product

AOC, Disinfectant, Pathogen, by -

product

AOC, Disinfectant, Pathogen, by -

product

AOC, Disinfectant, Pathogen, by -

product

Page 31: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72
Page 32: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

ACKNOWLEDGEMENT

Thanks to Environmental Protection Agency (grantR836890) for funding.

Special thanks to Whirlpool Corporation including EricBowler, Jason Schneemann and Ronald Vogelwede for providingtechnical assistance and hosting the test-site at the ReNEWWHouse Project.

Page 33: Development of Premise Plumbing Hydraulics-Water Quality ... · Service Line 5.2 3535 0.1 72 Basement-Cold 0.4 60 0.5 72 Basement-Hot 0.04 21 0.7 72 1st Floor-Cold 0.3 619 0.6 72

Building Plumbing Safety: Right Sizing Tomorrow's Water Systems for Efficiency, Sustainability, & Public Health

Andrew Whelton, Jade Mitchell, Janice Beecher, Joan Rose, Juneseok Lee, Pouyan Nejadhashemi,Erin Dreelin, Tiong Gim Aw, Amisha Shah, Matt Syal, Maryam Salehi

www.PlumbingSafety.org

Andrew Whelton, [email protected]